        The IEC 61850 Standard an intelligent application in Substation &
                             Automation system
                   Mohan Vinayak Sawarkar 1.                    Mohini Mohan Sawarkar 2.
                       1.
                            Bharati Vidyapeeth Institute of Technology, Navi Mumbai.
                            Lecturer- Electrical                                mohansawarkar@gmail.com
                       2.
                            Bharati Vidyapeeth College of Engineering, Navi Mumbai.
                            Asst. Professor- Electrical            mohini1nov@yahoo.co.in

ABSTRACT
As industrial economies grow and become more efficient they also become more reliable on electricity as their main
source of energy. Hence, a blackout in electrical system causes massive damage to social and economic aspects of a
society. To prevent interruptions and to provide energy to electricity consumers reliably automation needs to take
place at each stage of the electrical system: generation, transmission, and distribution. As each stage is automated,
there has to be reliable, fast, and efficient communication amongst devices and the SCADA control center.
Communication lines need to carry information and data between substations and control centers at different parts of
the network so that monitoring and automation of the system can occur. Without adequate communication amongst
devices SCADA system will render itself useless and will not be able to provide the reliability and efficiency needed
in today‟s electricity markets. It is also important to note that automation in electrical systems allows for the system
control and operator to define specific performance and protection parameters, which will lead to consistency across
the electrical grid. Legacy substation automation protocols and architectures typically provided basic functionality
for power system automation and were designed to accommodate the technical limitations of the networking
technology available for implementation. IEC61850 is an important new international standard for substation
automation that will have a very significant impact on how electric power systems are designed and built for many
years to come.

COMMUNICATION SYSTEM NEEDS.

 Consequently, a key component of a communication system is the ability to describe themselves from both a data
and services (communication functions that an IED performs) perspective.     Other “key” requirements include:
· High-speed IED to IED communication
· Networkable throughout the utility enterprise
· High-availability
· Guaranteed delivery times
· Standards based
· Multi-vendor interoperability
· Support for Voltage and Current samples data
· Support for File Transfer
· Auto-configurable / configuration support
· Support for security

COMMUNICATION NETWORK

A network is an interconnected system of electronic devices which share information with each other. A network
provides the media in which the information is transferred from one location to another. It is also the vein or
bloodline of any SCADA system, so its speed, reliability, and efficiency are absolutely crucial. There are many
types of networks, but only two types apply to substation environments and power systems: Serial-based and
Ethernet-based. Ethernet-based systems in power systems are also referred to as Integrated Substation Control
Systems (iSCS). There are many standards for each type of networks; however, in substation automation RS-232
2


(point-to-point links) and RS-485 (multi-drop links) in serial networks and IEEE 802.3 in Ethernet systems are the
most common.

PROTOCOL

A protocol is a set of formal rules describing how to transmit data across a network. The rules could be low-level,
which define the electrical and physical standards to be observed, bit- and byte-ordering and the transmission and
error detection and correction of the bit stream. In this section the high-level protocols will be discussed which
describe the data formatting, including the syntax of messages, character sets, and sequencing of messages. In short,
a protocol is a predefined digital language. The need for a protocol is quite apparent. In any power system there are
many devices from different countries and made by different manufacturers which perform different tasks in
SCADA. In order to create a communication network a common „language‟ or protocol is needed.

GENERAL PROPERTIES OF PROTOCOL

a) Network compatibility – some protocols have only been defined to operate in serial networks such as
Conitel. On the other hand, some protocols have been defined to work both on Ethernet and Serial systems such as
DNP 3.0
b) Speed – the speed at which a protocol transfers information amongst multiple devices is a very important
measure of its performance.
c) Reliability – the transfer of information has to be reliable. Some protocols may have checks in place to ensure
proper communication of messages. The level of reliability is another important measure of a protocol‟s
performance.
d) Expandability – protocols need to be able to handle small, medium, and large systems in SCADA. For
example, DNP 3.0 is able to handle very large system with over 65,000 data objects, whereas, Conitel or
Cooper protocols will not handle such large amounts of information well.
e) Security – in today‟s information age the security of information has to be ensured or else information may be
hacked or hampered during its transfer through the network. The protocol‟s level of security and encryption of data
are important issues in power systems.
f) Acceptability – a protocol needs to be accepted in the power industry and by the equipment manufacturers.
Protocols that are unique to specific manufacturers and are proprietary cannot be the common „language‟ in a
SCADA system. When choosing a protocol one needs to determine
whether all the components of the power system are able to communicate in that specific protocol or not.
g) Simplicity – It is important for a protocol to be simple so that its users can configure and maintain SCADA
systems easily and without the need for special expertise. The number of features and functionalities should be
limited to provide an economic solution for manufacturers and consumers.
h) Consistency – a protocol has to be controlled and standardized by one committee in the world to provide
consistency.
i) Functionality – a protocol should have all the features and functions used in SCADA such as time
synchronization and file transfer.
j) Economics – a protocol should be economic as its costs will determine its future in power systems.

IEC 61850 MODELLING APPROACH

Legacy protocols have typically defined how bytes are transmitted on the wire. However, they did not specify how
data should be organized in devices in terms of the application. This approach requires power system engineers to
manually configure objects and map them to power system variables and low-level register numbers, index numbers,
I/O modules, etc. IEC 61850 is unique. In addition to the specification of the protocol elements (how bytes are
transmitted on the wire), IEC 61850 provides a comprehensive model for how power system devices should
organize data in a manner that is consistent across all types and brands of devices. This eliminates much of the
tedious non-power system configuration effort because the devices can configure themselves..
3


        The IEC 61850 device model begins with a physical device. A physical device is the device that connects
        to the network. The physical device is typically defined by its network address. Within each physical
        device, there may be one or more logical devices.
        Each logical device contains one or more logical nodes. A Logical node is a named grouping of data and
        associated services that is logically related to some power stem function. There are logical nodes for
        automatic control names of which all begin with the letter “A”. There are Logical nodes for metering and
        measurement the names of which all begin with the letter “M”. Likewise there are logical nodes for
        Supervisory Control (C), Generic Functions (G), Interfacing/Archiving (I), System logical nodes (L),
        Protection (P), Protection Related (R), Sensors (S), Instrument Transformers (T), Switchgear (X), Power
        Transformers (Y), and Other Equipment (Z).. The standard Name of the Logical node for a Measurement
        Unit for 3-phase power is MMXU.
        Each element of data within the logical node conforms to the specification of a common data class (CDC)
        per IEC 61850-7-3. Each CDC describes the type and structure of the data within the logical node. Each
        CDC has a defined name and a set of CDC attributes each with a defined name, defined type, and specific
        purpose.
        Each individual attribute of a CDC belongs to a set of functional constraints (FC) that groups the attributes
        into categories




                                        Fig.1 The object model of IEC 61850
PROCESS BUS:

When we are talking about a process bus in the context of IEC 61850, we are going one step further with the
introduction of communication technology in a substation automation system. In a traditional approach, a substation
automation system consists of multiple intelligent electronic devices (IED) like protection relays and bay control
devices. These devices are connected to each other and to the substation gateway and local HMI through a
communication network. Since that communication network connects all the devices of a substation, it is typically
called station bus. An example is shown in Figure




             Fig.2 Example of a substation automation system with a station bus
4




                   Fig.3 Example with process bus
With current and voltage transformers, the situation is similar. A typical interface here is what is called “Merging
Unit” as shown in Figure. A merging unit provides a set of samples of the analogue signal to the communication
network. Typically a merging unit will provide synchronized samples from the three phase currents and the three
phase voltages. If conventional CTs and VTs are used, the merging unit will do the analogue to digital conversion of
the conventional output of the CTs and VTs. If non conventional sensors like optical sensors are used, the merging
unit will be integrated in the electronics required to process the optical
signal.




               Fig. 4 Concept of a merging unit

Features are offered by the standard:
- The possibility to put a function or a functional element in test mode. IEC
61850 provides the possibility to put logical nodes or logical devices in a test
mode.
- The possibility to characterize a GOOSE message as a message being sent for
test purpose.
- The possibility to characterize a service of the control model as being sent for
test purpose.
- The possibility to flag any value sent from a server in the quality as a value for
test purpose.
- The possibility to substitute a value.
5


Conclusion

      A substation automation system including an IEC 61850 based Process bus offers several benefits to the
      user. As an overall consequence of the benefits, life cycle costs of a substation will be reduced
      The features of IEC 61850 show its power for introducing new intelligent applications being more complex
      and efficient for the power system management, system stability and asset management.
      IEC 61850 is a high-level communication standard with a lot of additional features regarding functions and
      engineering. It comprises the know-how of many engineers worldwide in the areas of communication,
      substations and substation automation including protection.

References

   1) Technical discussions with testing teams of MSETCL‟s 400 KV Kharghar substation.

   2) www.siemens.com

   3) www.abb.com

   4) www.areva-td.com

More Related Content

PPTX
Profibus
PPTX
IEC-61850
PPTX
315564438 hvdc-transmission-ppt
PPTX
HVDC presentation
PPTX
IEC61850 tutorial
PPT
Data Center Cooling Study on Liquid Cooling
PPTX
Underground cable
PPTX
Types of cables
Profibus
IEC-61850
315564438 hvdc-transmission-ppt
HVDC presentation
IEC61850 tutorial
Data Center Cooling Study on Liquid Cooling
Underground cable
Types of cables

What's hot (20)

PDF
Power cable - Installation methods
PDF
EPC Solutions - All About Substation
PPT
Measurement of high_voltage_and_high_currentunit_iv_full_version
PDF
Rectifiers and Back up Batteries at Telecom Sites
PPTX
Data Center Cooling Design - Datacenter-serverroom
PPTX
TCSC
PDF
BPMI TRANSFORMER PROTECTION.pptx.pdf
PDF
Metal-Enclosed Switchgear Load Interrupter Switches
PPT
Dimensioning Of Dc Power Systems
PPTX
Hvdc system.pptx
PDF
Selective Coordination
PDF
Integrated earthing systems
PPTX
Reactive power compensation using statcom
PPT
Model Predictive Control For Integrating Processes
PPTX
Control of hvdc system
PPTX
Power system protection
PPTX
Introduction to foundation fieldbus
PPTX
power factor correction soham+niraj
PPTX
PWM RECTIFIER
PPTX
A PPT ON 220 KV GSS HINDAUN CITY
Power cable - Installation methods
EPC Solutions - All About Substation
Measurement of high_voltage_and_high_currentunit_iv_full_version
Rectifiers and Back up Batteries at Telecom Sites
Data Center Cooling Design - Datacenter-serverroom
TCSC
BPMI TRANSFORMER PROTECTION.pptx.pdf
Metal-Enclosed Switchgear Load Interrupter Switches
Dimensioning Of Dc Power Systems
Hvdc system.pptx
Selective Coordination
Integrated earthing systems
Reactive power compensation using statcom
Model Predictive Control For Integrating Processes
Control of hvdc system
Power system protection
Introduction to foundation fieldbus
power factor correction soham+niraj
PWM RECTIFIER
A PPT ON 220 KV GSS HINDAUN CITY
Ad

Viewers also liked (10)

PDF
Practical IEC 61850 for Substation Automation for Engineers and Technicians
PDF
Nema standards publication mg 2 2001
PPTX
Power system automation
PPTX
Cyber Security in Substation Automation (IEC 61850)
DOCX
Scadasubstationautomation
PDF
Practical Distribution & Substation Automation (Incl. Communications) for Ele...
PPT
Practical Distribution and Substation Automation (incl. communications) for E...
PDF
substation automation
PDF
2010 11 18 Substation Automation Systems By Gin Quesada
PPTX
Scada substation automation prnsnt
Practical IEC 61850 for Substation Automation for Engineers and Technicians
Nema standards publication mg 2 2001
Power system automation
Cyber Security in Substation Automation (IEC 61850)
Scadasubstationautomation
Practical Distribution & Substation Automation (Incl. Communications) for Ele...
Practical Distribution and Substation Automation (incl. communications) for E...
substation automation
2010 11 18 Substation Automation Systems By Gin Quesada
Scada substation automation prnsnt
Ad

Similar to Paper on IEC 61850 (20)

DOCX
Main report
PDF
Final paperenhancing distribution system through the use of real time etherne...
PDF
Iec61850 overview and benefits paper general
PDF
IOT BASED POWER GRID MONITORING & CONTROL SYSTEM
PDF
Remote Monitoring L.V. Switchboard Power Status with 5G New Radio Network App...
PDF
REMOTE MONITORING L.V. SWITCHBOARD POWER STATUS WITH 5G NEW RADIO NETWORK APP...
PDF
Power system automation
PDF
Substation Automation in Smart Grid
PPTX
unit 4 smartsensors and application.pptx
PDF
Using Software Defined Networking to manage and control IEC 61850-based systems
PDF
1451synopsis 599 f-good nist
PDF
IRJET- Internet of Things (IoT) based Smart Grid
PPTX
smart grid
DOCX
The efficacy and challenges of scada and smart grid integration
PDF
IRJET - Smart Power Monitoring and Controlling through IoT
PDF
Modernization of Electrical Substation Automation Systems Using IEC61850
PPTX
Smart metering and control of transmission system
PDF
Electricity Theft: Reason and Solution
PPTX
Security Issues in SCADA based Industrial Control Systems
PDF
ANALYSIS OF POWER WIRE COMMUNICATION SYSTEM
Main report
Final paperenhancing distribution system through the use of real time etherne...
Iec61850 overview and benefits paper general
IOT BASED POWER GRID MONITORING & CONTROL SYSTEM
Remote Monitoring L.V. Switchboard Power Status with 5G New Radio Network App...
REMOTE MONITORING L.V. SWITCHBOARD POWER STATUS WITH 5G NEW RADIO NETWORK APP...
Power system automation
Substation Automation in Smart Grid
unit 4 smartsensors and application.pptx
Using Software Defined Networking to manage and control IEC 61850-based systems
1451synopsis 599 f-good nist
IRJET- Internet of Things (IoT) based Smart Grid
smart grid
The efficacy and challenges of scada and smart grid integration
IRJET - Smart Power Monitoring and Controlling through IoT
Modernization of Electrical Substation Automation Systems Using IEC61850
Smart metering and control of transmission system
Electricity Theft: Reason and Solution
Security Issues in SCADA based Industrial Control Systems
ANALYSIS OF POWER WIRE COMMUNICATION SYSTEM

Recently uploaded (20)

PDF
102 student loan defaulters named and shamed – Is someone you know on the list?
PDF
Anesthesia in Laparoscopic Surgery in India
PPTX
The Healthy Child – Unit II | Child Health Nursing I | B.Sc Nursing 5th Semester
PPTX
Introduction to Child Health Nursing – Unit I | Child Health Nursing I | B.Sc...
PDF
Insiders guide to clinical Medicine.pdf
PDF
Classroom Observation Tools for Teachers
PDF
Pre independence Education in Inndia.pdf
PPTX
Microbial diseases, their pathogenesis and prophylaxis
PPTX
Institutional Correction lecture only . . .
PPTX
Cell Structure & Organelles in detailed.
PPTX
human mycosis Human fungal infections are called human mycosis..pptx
PDF
VCE English Exam - Section C Student Revision Booklet
PDF
Business Ethics Teaching Materials for college
PDF
Chapter 2 Heredity, Prenatal Development, and Birth.pdf
PDF
BÀI TẬP BỔ TRỢ 4 KỸ NĂNG TIẾNG ANH 9 GLOBAL SUCCESS - CẢ NĂM - BÁM SÁT FORM Đ...
PPTX
school management -TNTEU- B.Ed., Semester II Unit 1.pptx
PDF
3rd Neelam Sanjeevareddy Memorial Lecture.pdf
PDF
Abdominal Access Techniques with Prof. Dr. R K Mishra
PDF
Basic Mud Logging Guide for educational purpose
PPTX
master seminar digital applications in india
102 student loan defaulters named and shamed – Is someone you know on the list?
Anesthesia in Laparoscopic Surgery in India
The Healthy Child – Unit II | Child Health Nursing I | B.Sc Nursing 5th Semester
Introduction to Child Health Nursing – Unit I | Child Health Nursing I | B.Sc...
Insiders guide to clinical Medicine.pdf
Classroom Observation Tools for Teachers
Pre independence Education in Inndia.pdf
Microbial diseases, their pathogenesis and prophylaxis
Institutional Correction lecture only . . .
Cell Structure & Organelles in detailed.
human mycosis Human fungal infections are called human mycosis..pptx
VCE English Exam - Section C Student Revision Booklet
Business Ethics Teaching Materials for college
Chapter 2 Heredity, Prenatal Development, and Birth.pdf
BÀI TẬP BỔ TRỢ 4 KỸ NĂNG TIẾNG ANH 9 GLOBAL SUCCESS - CẢ NĂM - BÁM SÁT FORM Đ...
school management -TNTEU- B.Ed., Semester II Unit 1.pptx
3rd Neelam Sanjeevareddy Memorial Lecture.pdf
Abdominal Access Techniques with Prof. Dr. R K Mishra
Basic Mud Logging Guide for educational purpose
master seminar digital applications in india

Paper on IEC 61850

  • 1. 1 The IEC 61850 Standard an intelligent application in Substation & Automation system Mohan Vinayak Sawarkar 1. Mohini Mohan Sawarkar 2. 1. Bharati Vidyapeeth Institute of Technology, Navi Mumbai. Lecturer- Electrical mohansawarkar@gmail.com 2. Bharati Vidyapeeth College of Engineering, Navi Mumbai. Asst. Professor- Electrical mohini1nov@yahoo.co.in ABSTRACT As industrial economies grow and become more efficient they also become more reliable on electricity as their main source of energy. Hence, a blackout in electrical system causes massive damage to social and economic aspects of a society. To prevent interruptions and to provide energy to electricity consumers reliably automation needs to take place at each stage of the electrical system: generation, transmission, and distribution. As each stage is automated, there has to be reliable, fast, and efficient communication amongst devices and the SCADA control center. Communication lines need to carry information and data between substations and control centers at different parts of the network so that monitoring and automation of the system can occur. Without adequate communication amongst devices SCADA system will render itself useless and will not be able to provide the reliability and efficiency needed in today‟s electricity markets. It is also important to note that automation in electrical systems allows for the system control and operator to define specific performance and protection parameters, which will lead to consistency across the electrical grid. Legacy substation automation protocols and architectures typically provided basic functionality for power system automation and were designed to accommodate the technical limitations of the networking technology available for implementation. IEC61850 is an important new international standard for substation automation that will have a very significant impact on how electric power systems are designed and built for many years to come. COMMUNICATION SYSTEM NEEDS. Consequently, a key component of a communication system is the ability to describe themselves from both a data and services (communication functions that an IED performs) perspective. Other “key” requirements include: · High-speed IED to IED communication · Networkable throughout the utility enterprise · High-availability · Guaranteed delivery times · Standards based · Multi-vendor interoperability · Support for Voltage and Current samples data · Support for File Transfer · Auto-configurable / configuration support · Support for security COMMUNICATION NETWORK A network is an interconnected system of electronic devices which share information with each other. A network provides the media in which the information is transferred from one location to another. It is also the vein or bloodline of any SCADA system, so its speed, reliability, and efficiency are absolutely crucial. There are many types of networks, but only two types apply to substation environments and power systems: Serial-based and Ethernet-based. Ethernet-based systems in power systems are also referred to as Integrated Substation Control Systems (iSCS). There are many standards for each type of networks; however, in substation automation RS-232
  • 2. 2 (point-to-point links) and RS-485 (multi-drop links) in serial networks and IEEE 802.3 in Ethernet systems are the most common. PROTOCOL A protocol is a set of formal rules describing how to transmit data across a network. The rules could be low-level, which define the electrical and physical standards to be observed, bit- and byte-ordering and the transmission and error detection and correction of the bit stream. In this section the high-level protocols will be discussed which describe the data formatting, including the syntax of messages, character sets, and sequencing of messages. In short, a protocol is a predefined digital language. The need for a protocol is quite apparent. In any power system there are many devices from different countries and made by different manufacturers which perform different tasks in SCADA. In order to create a communication network a common „language‟ or protocol is needed. GENERAL PROPERTIES OF PROTOCOL a) Network compatibility – some protocols have only been defined to operate in serial networks such as Conitel. On the other hand, some protocols have been defined to work both on Ethernet and Serial systems such as DNP 3.0 b) Speed – the speed at which a protocol transfers information amongst multiple devices is a very important measure of its performance. c) Reliability – the transfer of information has to be reliable. Some protocols may have checks in place to ensure proper communication of messages. The level of reliability is another important measure of a protocol‟s performance. d) Expandability – protocols need to be able to handle small, medium, and large systems in SCADA. For example, DNP 3.0 is able to handle very large system with over 65,000 data objects, whereas, Conitel or Cooper protocols will not handle such large amounts of information well. e) Security – in today‟s information age the security of information has to be ensured or else information may be hacked or hampered during its transfer through the network. The protocol‟s level of security and encryption of data are important issues in power systems. f) Acceptability – a protocol needs to be accepted in the power industry and by the equipment manufacturers. Protocols that are unique to specific manufacturers and are proprietary cannot be the common „language‟ in a SCADA system. When choosing a protocol one needs to determine whether all the components of the power system are able to communicate in that specific protocol or not. g) Simplicity – It is important for a protocol to be simple so that its users can configure and maintain SCADA systems easily and without the need for special expertise. The number of features and functionalities should be limited to provide an economic solution for manufacturers and consumers. h) Consistency – a protocol has to be controlled and standardized by one committee in the world to provide consistency. i) Functionality – a protocol should have all the features and functions used in SCADA such as time synchronization and file transfer. j) Economics – a protocol should be economic as its costs will determine its future in power systems. IEC 61850 MODELLING APPROACH Legacy protocols have typically defined how bytes are transmitted on the wire. However, they did not specify how data should be organized in devices in terms of the application. This approach requires power system engineers to manually configure objects and map them to power system variables and low-level register numbers, index numbers, I/O modules, etc. IEC 61850 is unique. In addition to the specification of the protocol elements (how bytes are transmitted on the wire), IEC 61850 provides a comprehensive model for how power system devices should organize data in a manner that is consistent across all types and brands of devices. This eliminates much of the tedious non-power system configuration effort because the devices can configure themselves..
  • 3. 3 The IEC 61850 device model begins with a physical device. A physical device is the device that connects to the network. The physical device is typically defined by its network address. Within each physical device, there may be one or more logical devices. Each logical device contains one or more logical nodes. A Logical node is a named grouping of data and associated services that is logically related to some power stem function. There are logical nodes for automatic control names of which all begin with the letter “A”. There are Logical nodes for metering and measurement the names of which all begin with the letter “M”. Likewise there are logical nodes for Supervisory Control (C), Generic Functions (G), Interfacing/Archiving (I), System logical nodes (L), Protection (P), Protection Related (R), Sensors (S), Instrument Transformers (T), Switchgear (X), Power Transformers (Y), and Other Equipment (Z).. The standard Name of the Logical node for a Measurement Unit for 3-phase power is MMXU. Each element of data within the logical node conforms to the specification of a common data class (CDC) per IEC 61850-7-3. Each CDC describes the type and structure of the data within the logical node. Each CDC has a defined name and a set of CDC attributes each with a defined name, defined type, and specific purpose. Each individual attribute of a CDC belongs to a set of functional constraints (FC) that groups the attributes into categories Fig.1 The object model of IEC 61850 PROCESS BUS: When we are talking about a process bus in the context of IEC 61850, we are going one step further with the introduction of communication technology in a substation automation system. In a traditional approach, a substation automation system consists of multiple intelligent electronic devices (IED) like protection relays and bay control devices. These devices are connected to each other and to the substation gateway and local HMI through a communication network. Since that communication network connects all the devices of a substation, it is typically called station bus. An example is shown in Figure Fig.2 Example of a substation automation system with a station bus
  • 4. 4 Fig.3 Example with process bus With current and voltage transformers, the situation is similar. A typical interface here is what is called “Merging Unit” as shown in Figure. A merging unit provides a set of samples of the analogue signal to the communication network. Typically a merging unit will provide synchronized samples from the three phase currents and the three phase voltages. If conventional CTs and VTs are used, the merging unit will do the analogue to digital conversion of the conventional output of the CTs and VTs. If non conventional sensors like optical sensors are used, the merging unit will be integrated in the electronics required to process the optical signal. Fig. 4 Concept of a merging unit Features are offered by the standard: - The possibility to put a function or a functional element in test mode. IEC 61850 provides the possibility to put logical nodes or logical devices in a test mode. - The possibility to characterize a GOOSE message as a message being sent for test purpose. - The possibility to characterize a service of the control model as being sent for test purpose. - The possibility to flag any value sent from a server in the quality as a value for test purpose. - The possibility to substitute a value.
  • 5. 5 Conclusion A substation automation system including an IEC 61850 based Process bus offers several benefits to the user. As an overall consequence of the benefits, life cycle costs of a substation will be reduced The features of IEC 61850 show its power for introducing new intelligent applications being more complex and efficient for the power system management, system stability and asset management. IEC 61850 is a high-level communication standard with a lot of additional features regarding functions and engineering. It comprises the know-how of many engineers worldwide in the areas of communication, substations and substation automation including protection. References 1) Technical discussions with testing teams of MSETCL‟s 400 KV Kharghar substation. 2) www.siemens.com 3) www.abb.com 4) www.areva-td.com