Vector Group defines the relationship between the
Primary Voltage Vectors and the Secondary Voltage
Vectors. The Primary or Secondary Voltage Vectors may
Star or Delta.
 It is necessary to ensure that transformers to be
connected in parallel have the same vector group to
avoid circulating currents in the paralleled transformers
among other including same voltage level, same
percentage impedance and the same frequency.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
The concept of vector groups was adopted for transformers in the Generation,
Transmission and Distribution Networks in a manner so as to avoid the transfer
of Zero Sequence Current from each of the networks into the other. Delta Blocks
the flow of Zero Sequence Current.
The vector groups was also chosen in manner so as to enable the Earthing or
grounding of the various networks to facilitate the control of earth fault current
by the use of Neutral Ground Resistor(NGR). Where the Network is solidly
earthed, the earthing system is designed based on the exact short circuit level of
the Network, be it Generation, Transmission and Distribution.
Resonant Grounding (Peterson Coil) is also used in countries like Germany,
where the Reactance of the Peterson coil is tuned to match the Fictitious
Capacitance of the network. This way the earth fault current is reduced to
approximately Zero at the instant of fault (Inductive Current minus (-) Capacitive
Current). By this means countries with these scheme do not normally trip on
earth fault.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
The concept of vector groups was adopted for
transformers in the Generation, Transmission and
Distribution Networks in a manner so as to make
the overall phase shift Zero (0) at the Distribution
end close to the Customer.
The following slides analysis the various vector
group of the Generation, Transmission and
Distribution Network of the Ghana Power System.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Generation (Ynd1) Transmission (Ynd11)
Shifts Star ahead Delta Nullifies the Phase shift
by 30° by 30° by shifting Delta at 30 °
ahead Star
Distribution (MV) (Dyn1) Distribution (LV) (Dyn11)
Shifts Delta ahead Star Nullifies the Phase shift
by 30° by 30° by shifting Star at 30 °
ahead Delta
•RESULTANT PHASE SHIFT = ZERO (0)
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
It can be seen clearly that the Resultant Phase Shift in the
overall Vector Group of the Ghana Power System from
Generation through to the Distribution (LV) Network is
Zero (0). This way Customer end power is not affected by the
overall vector group of the power system.
The following slides show the various vector groups
available for Star-Delta, Star-Star, Delta-Star and Delta-Delta
Transformers.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Delta – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
11 3 7
Delta – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
5 9 1
As clearly shown above, there are six vector group options available for Delta –
Star Transformer Configuration. These are;
Dy1 Dy3 Dy5 Dyn1 Dyn3 Dyn5
Or
Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Star – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
1 9 5
Star – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a a a
11 3 7
As clearly shown above, there are six vector group options available for Star –
Delta Transformer Configuration. These are;
Yd1 Yd3 Yd5 Ynd1 Ynd3 Ynd5
Or
Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
 Yd1 or Ynd1 is the same as Dy11 or Dyn11 as in both cases Star (Y) leads
Delta (D) by 30°.
 Yd11 or Ynd11 is the same as Dy1 or Dyn1 as in both cases Delta (D) leads
Star (Y) by 30°.
Note: By Inspection
Delta – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
0 8 4
Delta – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
6 2 10
As clearly shown above, there are six vector group options available for Delta –
Delta Transformer Configuration. These are;
Dd0 Dd2 Dd4
Dd6 Dd8 Dd10
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Star – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
0 8 4
Star – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
6 2 10
As clearly shown above, there are six vector group options available for Star – Star
Transformer Configuration. These are;
Yy0 Yy2 Yy4 Yyn0 Yyn2 Yyn4
Or
Yy6 Yy8 Yy10 Yyn6 Yyn8 Yyn10
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
As clearly shown in the previous slides, there are Twenty-Four (24) vector groups
for Star Delta Transformers. Below is the reiteration of these vector groups;
Dy1 Dy3 Dy5 Or Dyn1 Dyn3 Dyn5
Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11
Dd0 Dd2 Dd4
Dd6 Dd8 Dd10
Yd1 Yd3 Yd5 Or Ynd1 Ynd3 Ynd5
Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11
Yy0 Yy2 Yy4 Or Ynyn0 Ynyn2 Ynyn4
Yy6 Yy8 Yy10 Ynyn6 Ynyn8 Ynyn10
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Dyn1
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
A
C B
c
b
a
30°
30°
30°
The Primary Voltage Vectors (Delta) leads the Secondary Voltage Vectors
(Star) by 30°. This is also known as lag in Aspen DistriView
Dyn11
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
A
C B
c
b
a
30°
30°
30°
The Primary Voltage Vectors (Delta) lags the Secondary Voltage Vectors
(Star) by 30°. This is also known as lead in Aspen DistriView
Thank You Very Much For
Your Kind Attention
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana

More Related Content

PDF
Testing of Transformers.
PPTX
STUDY OF ELECTRICAL POWER GENERATION, TRANSMISSION AND DISTRIBUTION IN BANG...
PPTX
Testing of transformer
PPT
Understanding transformer vector group
PPTX
Multilevel inverter
PDF
Full transformer
PPT
Sc and oc test on transformer
PPTX
industrial training on 132 kv substation
Testing of Transformers.
STUDY OF ELECTRICAL POWER GENERATION, TRANSMISSION AND DISTRIBUTION IN BANG...
Testing of transformer
Understanding transformer vector group
Multilevel inverter
Full transformer
Sc and oc test on transformer
industrial training on 132 kv substation

What's hot (20)

PPTX
Tap changer
PPSX
Substations
PPT
Power systems symmetrical components
PPT
3phase circuits
PPT
kvl kcl- nodal analysis
PPT
Transformer basic
PPT
Testing and Condition Monitoring of Substation Equipments
PPTX
Classification of transmission lines
PPTX
Presentation on substations
PPTX
Three Phase Transformer Connections.pptx
PPT
1.1 three phase power supply
PPT
Transformer design by s u khaparkar
PPTX
PPTX
Sub station training ppt
PPTX
Multi level inverter
PDF
PERFORMANCE OF TRANSMISSION LINES:
PPTX
Circuit theory basics
PPTX
Types of wires, three phase system earthing
PPTX
Sequence impedances of transformers 
PPT
Electrical Measurements
Tap changer
Substations
Power systems symmetrical components
3phase circuits
kvl kcl- nodal analysis
Transformer basic
Testing and Condition Monitoring of Substation Equipments
Classification of transmission lines
Presentation on substations
Three Phase Transformer Connections.pptx
1.1 three phase power supply
Transformer design by s u khaparkar
Sub station training ppt
Multi level inverter
PERFORMANCE OF TRANSMISSION LINES:
Circuit theory basics
Types of wires, three phase system earthing
Sequence impedances of transformers 
Electrical Measurements
Ad

Viewers also liked (10)

PDF
Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
PDF
Three phase vector groups
PPTX
Test vector compression
PDF
Guide to transformer resistance testing
PDF
PP10 startup manual (Unofficial as Requested)
PPT
Installation, Testing and Troubleshooting of Transformers
PDF
Best transformer-test-procedures-en
PDF
Optical Current Transformer (OCT)
PDF
Transformer testing
PPTX
Startup Ideas and Validation
Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
Three phase vector groups
Test vector compression
Guide to transformer resistance testing
PP10 startup manual (Unofficial as Requested)
Installation, Testing and Troubleshooting of Transformers
Best transformer-test-procedures-en
Optical Current Transformer (OCT)
Transformer testing
Startup Ideas and Validation
Ad

Similar to Presentation on Vector Groups by Armstrong (20)

PDF
IRJET- Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
PPT
332038674-Vector-Group-of-Transformers.ppt
PDF
A novel four wire inverter system using SVPWM technique for ups applications
PDF
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
PDF
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
PDF
T-09_SFRA_Experience_Locarno.pdf sweep frequency response
PPT
FAULT Analysis presentation Armstrong
PDF
A044040108
PDF
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
PDF
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
PPTX
Question bank Electrical Engineering
PDF
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
PDF
Two-level inverter and three-level neutral point diode clamped inverter for t...
PDF
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
PDF
Cascaded Open-End Winding Transformer based DVR
PDF
Topological Advancement in DVR; A review
PDF
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
PDF
11.modeling, analysis and control of hexagram inverter for three phase induc...
PDF
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
PDF
Cascade Protection with Transient Voltage copy
IRJET- Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
332038674-Vector-Group-of-Transformers.ppt
A novel four wire inverter system using SVPWM technique for ups applications
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
T-09_SFRA_Experience_Locarno.pdf sweep frequency response
FAULT Analysis presentation Armstrong
A044040108
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
Question bank Electrical Engineering
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Two-level inverter and three-level neutral point diode clamped inverter for t...
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
Cascaded Open-End Winding Transformer based DVR
Topological Advancement in DVR; A review
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
11.modeling, analysis and control of hexagram inverter for three phase induc...
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
Cascade Protection with Transient Voltage copy

Presentation on Vector Groups by Armstrong

  • 1. Vector Group defines the relationship between the Primary Voltage Vectors and the Secondary Voltage Vectors. The Primary or Secondary Voltage Vectors may Star or Delta.  It is necessary to ensure that transformers to be connected in parallel have the same vector group to avoid circulating currents in the paralleled transformers among other including same voltage level, same percentage impedance and the same frequency. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 2. The concept of vector groups was adopted for transformers in the Generation, Transmission and Distribution Networks in a manner so as to avoid the transfer of Zero Sequence Current from each of the networks into the other. Delta Blocks the flow of Zero Sequence Current. The vector groups was also chosen in manner so as to enable the Earthing or grounding of the various networks to facilitate the control of earth fault current by the use of Neutral Ground Resistor(NGR). Where the Network is solidly earthed, the earthing system is designed based on the exact short circuit level of the Network, be it Generation, Transmission and Distribution. Resonant Grounding (Peterson Coil) is also used in countries like Germany, where the Reactance of the Peterson coil is tuned to match the Fictitious Capacitance of the network. This way the earth fault current is reduced to approximately Zero at the instant of fault (Inductive Current minus (-) Capacitive Current). By this means countries with these scheme do not normally trip on earth fault. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 3. The concept of vector groups was adopted for transformers in the Generation, Transmission and Distribution Networks in a manner so as to make the overall phase shift Zero (0) at the Distribution end close to the Customer. The following slides analysis the various vector group of the Generation, Transmission and Distribution Network of the Ghana Power System. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 4. Generation (Ynd1) Transmission (Ynd11) Shifts Star ahead Delta Nullifies the Phase shift by 30° by 30° by shifting Delta at 30 ° ahead Star Distribution (MV) (Dyn1) Distribution (LV) (Dyn11) Shifts Delta ahead Star Nullifies the Phase shift by 30° by 30° by shifting Star at 30 ° ahead Delta •RESULTANT PHASE SHIFT = ZERO (0) 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 5. It can be seen clearly that the Resultant Phase Shift in the overall Vector Group of the Ghana Power System from Generation through to the Distribution (LV) Network is Zero (0). This way Customer end power is not affected by the overall vector group of the power system. The following slides show the various vector groups available for Star-Delta, Star-Star, Delta-Star and Delta-Delta Transformers. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 6. Delta – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 11 3 7
  • 7. Delta – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 5 9 1
  • 8. As clearly shown above, there are six vector group options available for Delta – Star Transformer Configuration. These are; Dy1 Dy3 Dy5 Dyn1 Dyn3 Dyn5 Or Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 9. Star – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 1 9 5
  • 10. Star – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 11 3 7
  • 11. As clearly shown above, there are six vector group options available for Star – Delta Transformer Configuration. These are; Yd1 Yd3 Yd5 Ynd1 Ynd3 Ynd5 Or Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana  Yd1 or Ynd1 is the same as Dy11 or Dyn11 as in both cases Star (Y) leads Delta (D) by 30°.  Yd11 or Ynd11 is the same as Dy1 or Dyn1 as in both cases Delta (D) leads Star (Y) by 30°. Note: By Inspection
  • 12. Delta – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 0 8 4
  • 13. Delta – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 6 2 10
  • 14. As clearly shown above, there are six vector group options available for Delta – Delta Transformer Configuration. These are; Dd0 Dd2 Dd4 Dd6 Dd8 Dd10 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 15. Star – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 0 8 4
  • 16. Star – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 6 2 10
  • 17. As clearly shown above, there are six vector group options available for Star – Star Transformer Configuration. These are; Yy0 Yy2 Yy4 Yyn0 Yyn2 Yyn4 Or Yy6 Yy8 Yy10 Yyn6 Yyn8 Yyn10 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 18. As clearly shown in the previous slides, there are Twenty-Four (24) vector groups for Star Delta Transformers. Below is the reiteration of these vector groups; Dy1 Dy3 Dy5 Or Dyn1 Dyn3 Dyn5 Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11 Dd0 Dd2 Dd4 Dd6 Dd8 Dd10 Yd1 Yd3 Yd5 Or Ynd1 Ynd3 Ynd5 Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11 Yy0 Yy2 Yy4 Or Ynyn0 Ynyn2 Ynyn4 Yy6 Yy8 Yy10 Ynyn6 Ynyn8 Ynyn10 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 19. Dyn1 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana A C B c b a 30° 30° 30° The Primary Voltage Vectors (Delta) leads the Secondary Voltage Vectors (Star) by 30°. This is also known as lag in Aspen DistriView
  • 20. Dyn11 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana A C B c b a 30° 30° 30° The Primary Voltage Vectors (Delta) lags the Secondary Voltage Vectors (Star) by 30°. This is also known as lead in Aspen DistriView
  • 21. Thank You Very Much For Your Kind Attention 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana