PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT
USING DIFFERENTIAL RELAY
Prof.P.M.Khandare
Department of Technology, University of Pune
Dr.S.A.Deokar
Campus Director, ZES’s, DCOER, Pune
Abstract
As source of traditional energy is vanishes day by day, importance of microgrid increasing very
effectively. In traditional generation and transmission of electrical power we have to rely on frequency and
generation of power but in case of microgrid we have to depend on whether condition. Managing these
systems to change of atmospheric condition becomes challenging. All study going on all over world related
to microgrid protection of microgrid is one of them. Micro grids can either operate connected to the grid, or
in the case of a grid fault, in an islanded mode. Effect of high impedance fault is studied in this paper, by
taking help of Matlab-Simulink’s SimPower Systems. We model a microgrid containing mix of renewable
DG and one dispatch able source, we then simulate the HIF fault at one of the bus in both grid-connect and
island modes and analyze fault currents and voltage levels in order to determine how the protection scheme
of the distribution network would need to be changed to facilitate microgrid functionality. We show that
standard protection methods are insufficient and propose the use of digital relays which is different from
traditional system.
Keywords: Fault analysis, Microgrid, Protection
INTRODUCTION
From the United state report Investigator says “Microgrid has been proposed as way of integrating large
number of distributed renewable energy sources with distribution system, one problem with microgrid
implementation is designing proper protection scheme”. Relay protection of microgrid is different than
conventional power distribution grid in following ways (1) Current flow in microgrid in both direction while
in conventional grid support single end power supply.(2)Use of large power electronic converters cause
another problem.(3)Relay protection should be provided for islanding and normal mode, with high speed,
selectivity and reliability Which lead to great challenge for protection of Microgrid.
Domestic and foreign researchers have made extensive studies on the relay protection of MG. N-line
operation. Similarly, N. Schaefer et al. [4, 9] describe a scheme and the algorithm of an adaptive protection
relay, which comprises a real-time block and a non-real time block, both implemented in software and
hardware. Y. Han et al. [13] propose that, comparing the system’s impedance and the microgrid’s
impedance, over current instantaneous protections can be automatically adjusted to the new situation. Then,
K. Dang et al. [14] propose to use a way of comparison between the zero-sequence current and a threshold.
T. S. Ustun, et al [2] present an adaptive protection system based on an extensive communication system
that monitors the microgrid by means of a Central Protection Unit (CPU).
The main objective of this thesis is the modeling of a hybrid microgrid with its protection which will also
clear high impedance faults. A development of novel method for modeling high impedance faults is
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 9, Sept.-2015
2 | P a g e
important to demonstrate to show how the protection scheme can protect against them. This is important in
microgrid protection not only because as the percentage of high impedance faults on the distribution system
is not insignificant [7], but also because microgrids, in the islanded mode, typically have lower fault
currents. Hence modeling and complete protection of microgrid are the main part of this paper. The overall
system is simulated using MATLAB environment. In simulation work the renewable sources are modeled
using different equations.
SYSTEM TOPOLOGY AND DG MODELS
A. SYSTEM DESCRIPTION
A microgrid is group of controllable interconnected loads and distributed generation (DGs) with clearly
defined electrical boundaries that act as single controllable entity with respect to grid. Dynamic structure of
microgrid and its versatile operation will lead to alternative protection strategy. The system used in this
study is taken from [3] an 18-bus network with a load capacity of 3.03 MVA connected to a 10 MVA
transformer. The system with line parameters and feeder source impedance are given. The phase loads of
each bus were also given and are shown in Table 1. The system is protected using fuses and reclosers on the
overhead lines and breakers on the underground lines. To this system we added four solar arrays, two wind
turbines, and one diesel generator. The solar arrays are each connected to three-phase inverters and provide
a total of 2,256 kW. The wind generators provide an additional 500 kW to the grid. During islanded
operations, additional generation and load following is provided by a 300 kW diesel generator. System is
shown with solar arrays, wind turbine, disel generator is shown in fig 1
Table 1 bus loads for the microgrid in fig. 1
B. DISTRIBUTION SYSTEM WITH DG SOURCE
The given system in [3] is converted to microgrid by adding 4 solar arrays having capacity 564 Kw, 2 wind
turbines provides 500Kw to grid and 1 diesel generator which gives additional generation and load
following is provided by 300 kW. They are connected to three phase inverters to give total of 2256 kW.
Solar array are connected to node no. 3,6,16 and 18 and wind turbine is connected to 5th and 10th node of
system. Diesel generator is connected to node no.13
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 9, Sept.-2015
3 | P a g e
Fig1:- One line diagram of the microgrid with added DG sources
C. MODELING MICROGRID IN MATLAB SIMULINK
(i) PV arrays are built up with combined series/parallel combinations of PV solar cells, there are several
ways to model a PV cell, module, or array for simulation. A possible model of a photovoltaic array and
inverter [17] was researched. According to theory, its features were modeled in Simulink.
(ii)The diesel motor model used in this study is a modified version of matlab-simulink library demo
model [5] and is connected to a 300-kW/12.47-kV synchronous generator .The asynchronous motor is rated
150 HP, 12.47 kV and the synchronous machine is rated 375 KVA, 12.47kV.The diesel engine and
governor system are modeled by a Simulink block initially, the motor develops mechanical power of 150
HP (300 kW) and the diesel generator is in standby, providing no active power
(iii)Wind turbines are connected to a 100-kW and 400-kW squirrel-cage induction generators. According to
Wind turbine characteristics given wind speed is calculated which will give maximum power output.
Constant Wind Speed is fed to turbine to give required output.
Figure 2 shows grid connected system with DGs at various nodes; measurements are taken at each node as
shown.
Fig2:- MATLAB model of micro grid with different DG sources
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 9, Sept.-2015
4 | P a g e
SIMULATION OF HIGH IMPEDANCE FAULT
A. INTRODUCTION
When fault current is below pick up of conventional over current, If<100 Amps on grounded system, which
occurs because of Incipient insulator failures, Fallen conductors on concrete, tree, soil, gravel, sand, asphalt,
etc. this condition raises the electric potential of tangible objects around us and may result in death by
electrocution, severe electrical burns, or fires ignited by arcing and heating of materials. The occurrence of
such conditions also constitutes a loss of energy to the power companies as not all of the produced electrical
power is delivered to their appointed loads. Power is lost on the way of delivery and dissipated through
foreign objects which should not be in contact with the line. Conventional relaying schemes monitor short-
circuit conditions where a significant amount of the energy supplied by the power company flows directly
into the ground and never reaches its load. In this paper a new technique is proposed to model, locate, and
detect high-impedance faults. Patterns and characteristics in the line’s current provide for recognition and
are investigated to detect such faults. [21]
B. STATEMENT OF PROBLEM
Conventional detection schemes monitor only low-impedance faults (LIFs that result in instantaneous and
large increments of current due to a low-impedance path to ground ).A HIF seems invisible to such
detection methods because it presents only a small increment in line current and appears to be a normal load
increment. Following figure 6.1 depicts this scenario.
Fig3:- Distribution network with HIF
C. PURPOSE OF STUDY
HIF can occur in two cases. In one case, a conductor breaks and fall to ground and fallen phase current
decreases and protection relays cannot detect fault because current is not more than setting current of relays.
In other state conductor isn’t break but it touches a high impedance thing such as tree limbs. In this state
feeder current increase but it is not enough to detect by conventional protection relay. Therefore this type of
fault is very difficult to detect also it is very dangerous for human life and necessary to detect.
D. STATERGY OF HIF FAULT DETECTION
HIFs detection is very difficult by conventional techniques, various methods are proposed before [23]-[25]
but no effective solution. This paper proposed technique based on measurement of current sequence
component. One of the advantage is that it can easily incorporated with digital Relays .Based on
superposition theorem, cureent can be consist of two component (i) a normal-running component, and (2) a
fault-imposed component. The fault-imposed component can be calculated using superimposed networks
[26],[27]. Assuming that in(t) is the current of the normal system (normal-running current), if (t) is the
current of the faulted system (fault current), and ifi(t) is the current of the superimposed network (fault-
imposed current), one can write:
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 9, Sept.-2015
5 | P a g e
if (t) = in(t) + if i(t)
Typical HIF currents values of above type for a 12.5-kV distribution feeder are listed in Table 2[10].
TABLE 2 HIF currents values
Material Current(Amps)
Dry Asphalt 0
Concrete(non-reinforced) 0
Dry Sand 0
Wet Sand 15
Dry Sod 20
Dry Grass 25
Wet Sod 40
Wet Grass 50
Concrete Reinforced 75
To evaluate the method of HIF detection, a model based on Emanuel model for HIF is utilized, which is
depicted in Figure 4. HIF Current changes between 0 and 80 Amp as shown in above table 2 and it is
obtained with change of Emanuel parameters. A list of Emanuel parameter that is result from practical test
[18] is brought in Table 3.
TABLE 3 Value of Emanuel model parameter
Rp Rn
1 208 212
2 215 223
3 235 225
4 244 227
5 245 245
6 247 271
7 255 280
8 267 286
9 269 289
10 272 290
Data in Table 3 are used to simulate a HIF in a distribution feeder
Fig3:- Emanuel Model of HIF
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 9, Sept.-2015
6 | P a g e
SIMULATION OF HIGH IMPEDANCE FAULT
Emanuel model used to create Matlab Model which includes two DC sources, Vp and Vn. These represent the
arcing voltage of air in soil and/or between trees and the distribution line; two resistances, Rp and Rn,
between diodes which represent the resistance of trees and/or the earth resistance. When the line voltage is
greater than the positive DC voltage Vp, the fault current starts flowing towards the ground. The fault current
reverses backward from the ground when the line voltage is less than the negative DC voltage Vn.
Using above parameters of resistance from table 3 a variable resistance is modeled in matlab with controlled
voltage source. Resistance value is taken of 15% of constant resistance of 250ohm.Hence variable resistance
is obtained for which min and max values are from a table 3 To study a simulation of HIF, a sample
distribution system is considered with 12.47kVthree phase source and transmission line with two circuit
breakers on both sides. Figure 4 gives High impedance fault created on sample distribution system in
matlab.
Model of HIF thus discovered is used to simulate a fault on 18 bus distribution system. This fault is
simulated on various buses of Microgrid system.
Fig4:- HIF Fault on sample distribution System
MODELING OF NUMERICAL RELAY FOR COMPLETE PROTECTION OF MICROGRID
A.INTRODUCTION
There are different philosophies of protecting islanded microgrids. One is to simply trip the entire
microgrid offline once the fault is detected during islanding. For additional reliability, the faulted line will
need to be removed from service and the remaining connected loads and sources will operate as two smaller
islands. This will only work if the generation and load in each smaller system match. If higher reliability is
required, the feeders can be connected as a loop, so the loss of a feeder or a lateral will not result in service
disruption to customers. The higher reliability, however, comes at a higher cost.
B. PROPOSED PROTECTION SCHEME FOR MICROGRID
This proposed protection scheme uses a current differential relay with specified algorithm which considers
internal, external and high impedance faults. By using these relays on the end of each line segment, a very
robust protection scheme can be developed. During this simulation study, HIF current patterns are evaluated
by decomposing the line current into its spectral content and studying its harmonic content. It is observed
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 9, Sept.-2015
7 | P a g e
that HIF currents content different patterns than load switching and other system variation condition.
Specifically, it is noticed that phase shift for the 3rd
harmonics current with respect to the fundamental has
occurred. This phase shift of 3rd
harmonics current is used to distinguish the presence of high impedance
fault than load switching condition. This differentiating criterion is used to find out the algorithm for
numerical relay for HIF protection.
Acknowledgment (HEADING 5)
Fig 5:- algorithm for numerical relay for HIF protection
C. IMPLEMENTATION OF THE DIGITAL DIFFERENTIAL PROTECTION USING
MATLAB
Different protection functions are required to design an appropriate protection scheme for microgrids. “the
amplitude comparator module", “the harmonic comparator module" inside each comparator block. The
amplitude comparator module compares the magnitude of the fault currents at two end of protective device
and the output trip signal of the amplitude comparator module is used by the islanded-mode protection
module. Harmonic calculation module is generally comes in picture when high impedance faults exists in
system. Finally, the tripping module decides whether or not a trip signal should be issued to external
controlled circuit breaker.
Fig 6:- Tripping Module
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 9, Sept.-2015
8 | P a g e
SIMULATION RESULT
High impedance fault is simulated on sample distribution system. Results obtained for current waveform of
HIF is shown in figure 7
Fig7:- current waveform of HIF
Phasor shift in waveform detects the presence of HIF and distinguishes it from load switching conditions.
Load switching waveforms are shown in figure 8 below. It can be seen that there is no phase shift occur in
load switching case.
Fig 8:- Load switching waveforms
Numerical Differential relay deployed in system is used to protect against HIF types of fault.
Fig 9:- Clearance of HIF fault using differential relay
CONCLUSION
The economical and environmental merits of microgrids have motivated extensive researches and
development efforts toward resolving the technical challenges of this new and fast-growing technology. The
main objective of this study is to address some concerns related to the protection of microgrids. The issues
studied in the thesis are modeling of distribution generation and protection of the microgrid against different
fault scenarios in both modes of operation.
Microgrids can be protected using digital current differential relay deployed at each line end in system.
Relay structure thus proposed is able to protect all types of fault in medium voltage microgrid. In this way
complete protection of microgrid system can be achieved
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 9, Sept.-2015
9 | P a g e
REFERENCES
[1] "Fault Analysis and Protection of a Microgrid" E. Sortomme, Student Member, IEEE, G. J. Mapes, B.
A. Foster, S. S. Venkata, Fellow, IEEE
[2] T. S. Ustun, et al., "A microgrid protection system with central protection unit and extensive
communication", in Environment and Electrical Engineering (EEEIC), 2011 10th International Conference
on, 2011,
[3]G. Sybille Hydro-Quebec, Simulink: Emergency Diesel-Generator and Asynchronous Motor. [Matlab].
Natick, MA: MathWorks, Inc., 2007.
[4]R. Reid, B. Saulnier, R. Gagnon, Simulink: Wind-turbine asynchronous generator in isolated network,
[Matlab]. Natick, MA: MathWorks, Inc.,2007
[5]C. G. Wester, High Impedance Fault Detection on Distribution Systems, General Electric Company,
2008 [Online]. Available:http://pm.geindustrial.com/faq/documents/f60/ger3993.pdf
[6]S. R. Nam, J. K. Park, Y. C. Kang, and T. H. Kim, “A modeling method of a high impedance fault in a
distribution system using two series time varying resistances in EMTP,” in Proc. IEEE Power Eng.Soc.
Summer Meeting, Vancouver, BC, Canada, Jul. 2001, vol. 2, pp.1175–1180.
[7] N. Schaefer, et al., "Adaptive protection system for distribution networks with distributed energy
resources", in Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET
International Conference on, 2010, pp. 1-5
[8] “High Impedance Fault Detection of Distribution Network by Phasor Measurement Units” ,Mohsen
Ghalei Monfared Zanjani, Hossein Kazemi Karegar, Hasan Ashrafi Niaki, Mina Ghalei Monfared Zanjani,
Smart Grid and Renewable Energy, 2013, 4, 297-305
[9] “A New Approach to Current Differential Protection for Transmission Lines”, M. G. Adamiak,W.
Premerlani, ELECTRIC COUNCIL OF NEW ENGLAND Protective Relaying Committee Meeting October
22-23, 1998
[10] “Protection of Microgrids Using Differential Relays”, Manjula Dewadasa, Member, IEEE, Arindam
Ghosh, Fellow, IEEE and Gerard Ledwich, Senior Member, IEEE
[11] Y. Han, et al., "Study of adaptive fault current algorithm for microgrid dominated by inverter based
distributed generators", in Power Electronics for Distributed Generation Systems (PEDG), 2010 2nd IEEE
International Symposium on, 2010, pp. 852-854.
[12] D. Ke, et al., "An adaptive protection method for the inverter dominated microgrid", in Electrical
Machines and Systems (ICEMS), 2011 International Conference on, 2011, pp. 1-5.
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 9, Sept.-2015
10 | P a g e
[13] “Modeling and Simulation of Micro Grid System Based on Renewable Power Generation Units by
using Multilevel Converter”, K. Venkateswarlu, J. Krishna Kishore, QIS College of Engineering &
Technology, Prakasam dt (AP)
[14] “Study of Micro Grid Safety & Protection Strategies with Control System Infrastructures”, Md Razibul
Islam, Hossam A. Gabbar, Faculty of Energy System and Nuclear Science, University of Ontario Institute of
Technology, Oshawa, Canada.
[15] “A Photovoltaic Array Simulation Model for Matlab-Simulink GUI Environment” I. H. Altas1 and
A.M. Sharaf2
[18] “High-Impedance Fault Detection Using Discrete Wavelet Transform and Frequency Range and RMS
Conversion”, T. M. Lai, L. A. Snider, Senior Member, IEEE, E. Lo, Member, IEEE, and D. Sutanto, Senior
Member, IEEE
[16] “IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes,"
IEEE Std C37.110-2007), pp. C1-67, 2008.
[17] “Protection of micro-grids dominated by distributed generation using solid state converters”, by M. A.
Red fern and H. Al-Nasseri, in Proc. IET 9th Int. Conf. Develop. Power Syst. Protection, 2008, pp. 670–
674.
[18] “High Impedance Fault Detection on Distribution Systems”, by C. G. Wester, General Electric
Company, 2008 [Online].
[19] “Selection of current transformer and wire sizing in substations”, Sethuraman Ganesan ,ABB Inc.
,Allentown, PA
[20] “High impedance fault detection in low voltage networks” R. C. Christie, H. Zadehgol and M. M.
Habib, , IEEE Trans. on Power Delivery, vol. 8, no. 4, pp. 1829-1836, Oct. 1993.
[21] “Distribution high impedance fault detection utilizing high frequency current components” B. M.
Aucoin and B. D. Russell, IEEE Trans. on Power Apparatus and Systems, vol. 101, no. 6, pp. 1596-1606,
Jun. 1982.
[22] “Unique aspects of distribution system harmonics due to high impedance ground faults” D. I. Jeering
and J. R. Linders, , IEEE Trans. on Power Delivery, vol. 5, no. 2, pp. 1086-1094, Apr. 1990.
[23] “Research on no communication protection of distribution lines based on fault components” ,B.
Jianguang, D. Xinzhou, G. Yongji and B. Zhiqian, in Proc. intl. Conf.
[24]Power System Technology, pp. 1151-1155, Oct. 2002. J. D. Glover and M. S. Sarma, Power System
Analysis and Design, 3rd Edition, Pacific Grove, CA: Brooks/Cole, 2002.
[25] “Cooper Power Systems”, Ed. 3, Electrical Distribution-System Protection, Cooper Industries, 1990.

More Related Content

PDF
Microgrid Protection
PDF
Protection Strategies for Microgrids
PPTX
Microgrid Protection: Challenges and Solution
PPTX
A Review of Protection Schemes for Active Distribution Systems
PDF
Fault protection of a loop type low voltage dc bus based microgrids
PDF
Resume- EE
PPSX
Presentation o An Intelligent protection scheme for microgrid using data-mini...
PPTX
wireless fault protection and detection for dc microgrid
Microgrid Protection
Protection Strategies for Microgrids
Microgrid Protection: Challenges and Solution
A Review of Protection Schemes for Active Distribution Systems
Fault protection of a loop type low voltage dc bus based microgrids
Resume- EE
Presentation o An Intelligent protection scheme for microgrid using data-mini...
wireless fault protection and detection for dc microgrid

What's hot (18)

PDF
Voltage Support and Reactive Power Control in Micro-grid using DG
PPT
Mg protection 04022018
PDF
Frequency Scanning Techniques for Subsynchronous Resonance Screening Analysis
PDF
Microgrid Control Strategy
PPTX
DC_RING-BUS_MICROGRID_FAULT_PROTECTION
PDF
Final talk trident-05-10-2021- dr p k rout-converted
PPT
Transient stability analysis of inverter interfaced distributed generators in...
PDF
A transient current based micro grid connected power system protection scheme...
PDF
Control technique for single phase inverter photovoltaic system connected to ...
PPTX
Modelling and Control of a Microgrid with100kW PV System and Electrochemical ...
PPTX
Island Detection and Control Techniques
PPT
Islanding
PDF
Fi25986990
PPSX
Presentation, IEEE ENERGY CONVERSION CONGRESS & EXPO 2018
PPTX
Interconnection issue in microgrid
PDF
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
PPTX
UTILITY CONNECTED MICROGRID BASED DISTRIBUTION GENTRATION SYSTEM FOR POWER FL...
PDF
Anti-islanding
Voltage Support and Reactive Power Control in Micro-grid using DG
Mg protection 04022018
Frequency Scanning Techniques for Subsynchronous Resonance Screening Analysis
Microgrid Control Strategy
DC_RING-BUS_MICROGRID_FAULT_PROTECTION
Final talk trident-05-10-2021- dr p k rout-converted
Transient stability analysis of inverter interfaced distributed generators in...
A transient current based micro grid connected power system protection scheme...
Control technique for single phase inverter photovoltaic system connected to ...
Modelling and Control of a Microgrid with100kW PV System and Electrochemical ...
Island Detection and Control Techniques
Islanding
Fi25986990
Presentation, IEEE ENERGY CONVERSION CONGRESS & EXPO 2018
Interconnection issue in microgrid
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
UTILITY CONNECTED MICROGRID BASED DISTRIBUTION GENTRATION SYSTEM FOR POWER FL...
Anti-islanding
Ad

Similar to PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAY (20)

PDF
Dealing With Reactive Power in Islanded Micro Grid Corresponding Power Distri...
PDF
Korada2016
PDF
Optimal_Location_of_Distributed_Generation_and_its.pdf
PDF
Reactive Power Sharing Droop Control Strategy for DG Units in an Islanded Mic...
PDF
Application of crowbar protection on dfig based wind turbine connected to grid-2
PDF
Control for Grid Connected and Intentional Islanding of Distributed Power Gen...
PDF
New solutions for optimization of the electrical distribution system availabi...
PDF
Reactive Power Sharing in Islanded Microgrid by Droop Control Method
PDF
R.muthukumar, Analysis of Dynamic Stability of Microgrid
PDF
Optimal dg placement using multiobjective index and its effect on stability 2
PDF
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
PDF
D010622334
PDF
fault
PDF
Analysis and Implementation of Power Quality Enhancement Techniques in Hybrid...
PDF
Integration of renewable resources for dc micro grid applications
PDF
Overview: Simulation Analysis of low voltage DC micro grid - An investigation...
PDF
Renewable Energy Harvesting Using SuperCapacitor
PDF
L45016771
PDF
A Comprehensive Review of Protection Schemes for Distributed Generation
PDF
Frequency control in a microgrid including controllable load
Dealing With Reactive Power in Islanded Micro Grid Corresponding Power Distri...
Korada2016
Optimal_Location_of_Distributed_Generation_and_its.pdf
Reactive Power Sharing Droop Control Strategy for DG Units in an Islanded Mic...
Application of crowbar protection on dfig based wind turbine connected to grid-2
Control for Grid Connected and Intentional Islanding of Distributed Power Gen...
New solutions for optimization of the electrical distribution system availabi...
Reactive Power Sharing in Islanded Microgrid by Droop Control Method
R.muthukumar, Analysis of Dynamic Stability of Microgrid
Optimal dg placement using multiobjective index and its effect on stability 2
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
D010622334
fault
Analysis and Implementation of Power Quality Enhancement Techniques in Hybrid...
Integration of renewable resources for dc micro grid applications
Overview: Simulation Analysis of low voltage DC micro grid - An investigation...
Renewable Energy Harvesting Using SuperCapacitor
L45016771
A Comprehensive Review of Protection Schemes for Distributed Generation
Frequency control in a microgrid including controllable load
Ad

More from ijiert bestjournal (20)

PDF
CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP
PDF
A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...
PDF
COMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAF
PDF
POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE
PDF
FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY
PDF
REVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAIN
PDF
ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...
PDF
SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...
PDF
EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...
PDF
STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR
PDF
DESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFT
PDF
ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...
PDF
HEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENT
PDF
MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH
PDF
IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW
PDF
DESIGN OF WELDING FIXTURES AND POSITIONERS
PDF
ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...
PDF
REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...
PDF
PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...
PDF
MAGNETIC ABRASIVE FINISHING
CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP
A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...
COMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAF
POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE
FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY
REVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAIN
ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...
SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...
EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...
STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR
DESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFT
ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...
HEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENT
MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH
IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW
DESIGN OF WELDING FIXTURES AND POSITIONERS
ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...
REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...
PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...
MAGNETIC ABRASIVE FINISHING

Recently uploaded (20)

PPTX
Construction Project Organization Group 2.pptx
PDF
Digital Logic Computer Design lecture notes
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PPTX
Foundation to blockchain - A guide to Blockchain Tech
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
Lecture Notes Electrical Wiring System Components
PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PPT
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
PPTX
Internet of Things (IOT) - A guide to understanding
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PDF
Well-logging-methods_new................
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PPTX
Welding lecture in detail for understanding
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPTX
UNIT 4 Total Quality Management .pptx
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
DOCX
573137875-Attendance-Management-System-original
Construction Project Organization Group 2.pptx
Digital Logic Computer Design lecture notes
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Foundation to blockchain - A guide to Blockchain Tech
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
Lecture Notes Electrical Wiring System Components
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
Internet of Things (IOT) - A guide to understanding
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Operating System & Kernel Study Guide-1 - converted.pdf
Well-logging-methods_new................
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
Welding lecture in detail for understanding
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
UNIT 4 Total Quality Management .pptx
CYBER-CRIMES AND SECURITY A guide to understanding
573137875-Attendance-Management-System-original

PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAY

  • 1. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 9, Sept.-2015 1 | P a g e PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAY Prof.P.M.Khandare Department of Technology, University of Pune Dr.S.A.Deokar Campus Director, ZES’s, DCOER, Pune Abstract As source of traditional energy is vanishes day by day, importance of microgrid increasing very effectively. In traditional generation and transmission of electrical power we have to rely on frequency and generation of power but in case of microgrid we have to depend on whether condition. Managing these systems to change of atmospheric condition becomes challenging. All study going on all over world related to microgrid protection of microgrid is one of them. Micro grids can either operate connected to the grid, or in the case of a grid fault, in an islanded mode. Effect of high impedance fault is studied in this paper, by taking help of Matlab-Simulink’s SimPower Systems. We model a microgrid containing mix of renewable DG and one dispatch able source, we then simulate the HIF fault at one of the bus in both grid-connect and island modes and analyze fault currents and voltage levels in order to determine how the protection scheme of the distribution network would need to be changed to facilitate microgrid functionality. We show that standard protection methods are insufficient and propose the use of digital relays which is different from traditional system. Keywords: Fault analysis, Microgrid, Protection INTRODUCTION From the United state report Investigator says “Microgrid has been proposed as way of integrating large number of distributed renewable energy sources with distribution system, one problem with microgrid implementation is designing proper protection scheme”. Relay protection of microgrid is different than conventional power distribution grid in following ways (1) Current flow in microgrid in both direction while in conventional grid support single end power supply.(2)Use of large power electronic converters cause another problem.(3)Relay protection should be provided for islanding and normal mode, with high speed, selectivity and reliability Which lead to great challenge for protection of Microgrid. Domestic and foreign researchers have made extensive studies on the relay protection of MG. N-line operation. Similarly, N. Schaefer et al. [4, 9] describe a scheme and the algorithm of an adaptive protection relay, which comprises a real-time block and a non-real time block, both implemented in software and hardware. Y. Han et al. [13] propose that, comparing the system’s impedance and the microgrid’s impedance, over current instantaneous protections can be automatically adjusted to the new situation. Then, K. Dang et al. [14] propose to use a way of comparison between the zero-sequence current and a threshold. T. S. Ustun, et al [2] present an adaptive protection system based on an extensive communication system that monitors the microgrid by means of a Central Protection Unit (CPU). The main objective of this thesis is the modeling of a hybrid microgrid with its protection which will also clear high impedance faults. A development of novel method for modeling high impedance faults is
  • 2. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 9, Sept.-2015 2 | P a g e important to demonstrate to show how the protection scheme can protect against them. This is important in microgrid protection not only because as the percentage of high impedance faults on the distribution system is not insignificant [7], but also because microgrids, in the islanded mode, typically have lower fault currents. Hence modeling and complete protection of microgrid are the main part of this paper. The overall system is simulated using MATLAB environment. In simulation work the renewable sources are modeled using different equations. SYSTEM TOPOLOGY AND DG MODELS A. SYSTEM DESCRIPTION A microgrid is group of controllable interconnected loads and distributed generation (DGs) with clearly defined electrical boundaries that act as single controllable entity with respect to grid. Dynamic structure of microgrid and its versatile operation will lead to alternative protection strategy. The system used in this study is taken from [3] an 18-bus network with a load capacity of 3.03 MVA connected to a 10 MVA transformer. The system with line parameters and feeder source impedance are given. The phase loads of each bus were also given and are shown in Table 1. The system is protected using fuses and reclosers on the overhead lines and breakers on the underground lines. To this system we added four solar arrays, two wind turbines, and one diesel generator. The solar arrays are each connected to three-phase inverters and provide a total of 2,256 kW. The wind generators provide an additional 500 kW to the grid. During islanded operations, additional generation and load following is provided by a 300 kW diesel generator. System is shown with solar arrays, wind turbine, disel generator is shown in fig 1 Table 1 bus loads for the microgrid in fig. 1 B. DISTRIBUTION SYSTEM WITH DG SOURCE The given system in [3] is converted to microgrid by adding 4 solar arrays having capacity 564 Kw, 2 wind turbines provides 500Kw to grid and 1 diesel generator which gives additional generation and load following is provided by 300 kW. They are connected to three phase inverters to give total of 2256 kW. Solar array are connected to node no. 3,6,16 and 18 and wind turbine is connected to 5th and 10th node of system. Diesel generator is connected to node no.13
  • 3. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 9, Sept.-2015 3 | P a g e Fig1:- One line diagram of the microgrid with added DG sources C. MODELING MICROGRID IN MATLAB SIMULINK (i) PV arrays are built up with combined series/parallel combinations of PV solar cells, there are several ways to model a PV cell, module, or array for simulation. A possible model of a photovoltaic array and inverter [17] was researched. According to theory, its features were modeled in Simulink. (ii)The diesel motor model used in this study is a modified version of matlab-simulink library demo model [5] and is connected to a 300-kW/12.47-kV synchronous generator .The asynchronous motor is rated 150 HP, 12.47 kV and the synchronous machine is rated 375 KVA, 12.47kV.The diesel engine and governor system are modeled by a Simulink block initially, the motor develops mechanical power of 150 HP (300 kW) and the diesel generator is in standby, providing no active power (iii)Wind turbines are connected to a 100-kW and 400-kW squirrel-cage induction generators. According to Wind turbine characteristics given wind speed is calculated which will give maximum power output. Constant Wind Speed is fed to turbine to give required output. Figure 2 shows grid connected system with DGs at various nodes; measurements are taken at each node as shown. Fig2:- MATLAB model of micro grid with different DG sources
  • 4. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 9, Sept.-2015 4 | P a g e SIMULATION OF HIGH IMPEDANCE FAULT A. INTRODUCTION When fault current is below pick up of conventional over current, If<100 Amps on grounded system, which occurs because of Incipient insulator failures, Fallen conductors on concrete, tree, soil, gravel, sand, asphalt, etc. this condition raises the electric potential of tangible objects around us and may result in death by electrocution, severe electrical burns, or fires ignited by arcing and heating of materials. The occurrence of such conditions also constitutes a loss of energy to the power companies as not all of the produced electrical power is delivered to their appointed loads. Power is lost on the way of delivery and dissipated through foreign objects which should not be in contact with the line. Conventional relaying schemes monitor short- circuit conditions where a significant amount of the energy supplied by the power company flows directly into the ground and never reaches its load. In this paper a new technique is proposed to model, locate, and detect high-impedance faults. Patterns and characteristics in the line’s current provide for recognition and are investigated to detect such faults. [21] B. STATEMENT OF PROBLEM Conventional detection schemes monitor only low-impedance faults (LIFs that result in instantaneous and large increments of current due to a low-impedance path to ground ).A HIF seems invisible to such detection methods because it presents only a small increment in line current and appears to be a normal load increment. Following figure 6.1 depicts this scenario. Fig3:- Distribution network with HIF C. PURPOSE OF STUDY HIF can occur in two cases. In one case, a conductor breaks and fall to ground and fallen phase current decreases and protection relays cannot detect fault because current is not more than setting current of relays. In other state conductor isn’t break but it touches a high impedance thing such as tree limbs. In this state feeder current increase but it is not enough to detect by conventional protection relay. Therefore this type of fault is very difficult to detect also it is very dangerous for human life and necessary to detect. D. STATERGY OF HIF FAULT DETECTION HIFs detection is very difficult by conventional techniques, various methods are proposed before [23]-[25] but no effective solution. This paper proposed technique based on measurement of current sequence component. One of the advantage is that it can easily incorporated with digital Relays .Based on superposition theorem, cureent can be consist of two component (i) a normal-running component, and (2) a fault-imposed component. The fault-imposed component can be calculated using superimposed networks [26],[27]. Assuming that in(t) is the current of the normal system (normal-running current), if (t) is the current of the faulted system (fault current), and ifi(t) is the current of the superimposed network (fault- imposed current), one can write:
  • 5. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 9, Sept.-2015 5 | P a g e if (t) = in(t) + if i(t) Typical HIF currents values of above type for a 12.5-kV distribution feeder are listed in Table 2[10]. TABLE 2 HIF currents values Material Current(Amps) Dry Asphalt 0 Concrete(non-reinforced) 0 Dry Sand 0 Wet Sand 15 Dry Sod 20 Dry Grass 25 Wet Sod 40 Wet Grass 50 Concrete Reinforced 75 To evaluate the method of HIF detection, a model based on Emanuel model for HIF is utilized, which is depicted in Figure 4. HIF Current changes between 0 and 80 Amp as shown in above table 2 and it is obtained with change of Emanuel parameters. A list of Emanuel parameter that is result from practical test [18] is brought in Table 3. TABLE 3 Value of Emanuel model parameter Rp Rn 1 208 212 2 215 223 3 235 225 4 244 227 5 245 245 6 247 271 7 255 280 8 267 286 9 269 289 10 272 290 Data in Table 3 are used to simulate a HIF in a distribution feeder Fig3:- Emanuel Model of HIF
  • 6. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 9, Sept.-2015 6 | P a g e SIMULATION OF HIGH IMPEDANCE FAULT Emanuel model used to create Matlab Model which includes two DC sources, Vp and Vn. These represent the arcing voltage of air in soil and/or between trees and the distribution line; two resistances, Rp and Rn, between diodes which represent the resistance of trees and/or the earth resistance. When the line voltage is greater than the positive DC voltage Vp, the fault current starts flowing towards the ground. The fault current reverses backward from the ground when the line voltage is less than the negative DC voltage Vn. Using above parameters of resistance from table 3 a variable resistance is modeled in matlab with controlled voltage source. Resistance value is taken of 15% of constant resistance of 250ohm.Hence variable resistance is obtained for which min and max values are from a table 3 To study a simulation of HIF, a sample distribution system is considered with 12.47kVthree phase source and transmission line with two circuit breakers on both sides. Figure 4 gives High impedance fault created on sample distribution system in matlab. Model of HIF thus discovered is used to simulate a fault on 18 bus distribution system. This fault is simulated on various buses of Microgrid system. Fig4:- HIF Fault on sample distribution System MODELING OF NUMERICAL RELAY FOR COMPLETE PROTECTION OF MICROGRID A.INTRODUCTION There are different philosophies of protecting islanded microgrids. One is to simply trip the entire microgrid offline once the fault is detected during islanding. For additional reliability, the faulted line will need to be removed from service and the remaining connected loads and sources will operate as two smaller islands. This will only work if the generation and load in each smaller system match. If higher reliability is required, the feeders can be connected as a loop, so the loss of a feeder or a lateral will not result in service disruption to customers. The higher reliability, however, comes at a higher cost. B. PROPOSED PROTECTION SCHEME FOR MICROGRID This proposed protection scheme uses a current differential relay with specified algorithm which considers internal, external and high impedance faults. By using these relays on the end of each line segment, a very robust protection scheme can be developed. During this simulation study, HIF current patterns are evaluated by decomposing the line current into its spectral content and studying its harmonic content. It is observed
  • 7. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 9, Sept.-2015 7 | P a g e that HIF currents content different patterns than load switching and other system variation condition. Specifically, it is noticed that phase shift for the 3rd harmonics current with respect to the fundamental has occurred. This phase shift of 3rd harmonics current is used to distinguish the presence of high impedance fault than load switching condition. This differentiating criterion is used to find out the algorithm for numerical relay for HIF protection. Acknowledgment (HEADING 5) Fig 5:- algorithm for numerical relay for HIF protection C. IMPLEMENTATION OF THE DIGITAL DIFFERENTIAL PROTECTION USING MATLAB Different protection functions are required to design an appropriate protection scheme for microgrids. “the amplitude comparator module", “the harmonic comparator module" inside each comparator block. The amplitude comparator module compares the magnitude of the fault currents at two end of protective device and the output trip signal of the amplitude comparator module is used by the islanded-mode protection module. Harmonic calculation module is generally comes in picture when high impedance faults exists in system. Finally, the tripping module decides whether or not a trip signal should be issued to external controlled circuit breaker. Fig 6:- Tripping Module
  • 8. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 9, Sept.-2015 8 | P a g e SIMULATION RESULT High impedance fault is simulated on sample distribution system. Results obtained for current waveform of HIF is shown in figure 7 Fig7:- current waveform of HIF Phasor shift in waveform detects the presence of HIF and distinguishes it from load switching conditions. Load switching waveforms are shown in figure 8 below. It can be seen that there is no phase shift occur in load switching case. Fig 8:- Load switching waveforms Numerical Differential relay deployed in system is used to protect against HIF types of fault. Fig 9:- Clearance of HIF fault using differential relay CONCLUSION The economical and environmental merits of microgrids have motivated extensive researches and development efforts toward resolving the technical challenges of this new and fast-growing technology. The main objective of this study is to address some concerns related to the protection of microgrids. The issues studied in the thesis are modeling of distribution generation and protection of the microgrid against different fault scenarios in both modes of operation. Microgrids can be protected using digital current differential relay deployed at each line end in system. Relay structure thus proposed is able to protect all types of fault in medium voltage microgrid. In this way complete protection of microgrid system can be achieved
  • 9. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 9, Sept.-2015 9 | P a g e REFERENCES [1] "Fault Analysis and Protection of a Microgrid" E. Sortomme, Student Member, IEEE, G. J. Mapes, B. A. Foster, S. S. Venkata, Fellow, IEEE [2] T. S. Ustun, et al., "A microgrid protection system with central protection unit and extensive communication", in Environment and Electrical Engineering (EEEIC), 2011 10th International Conference on, 2011, [3]G. Sybille Hydro-Quebec, Simulink: Emergency Diesel-Generator and Asynchronous Motor. [Matlab]. Natick, MA: MathWorks, Inc., 2007. [4]R. Reid, B. Saulnier, R. Gagnon, Simulink: Wind-turbine asynchronous generator in isolated network, [Matlab]. Natick, MA: MathWorks, Inc.,2007 [5]C. G. Wester, High Impedance Fault Detection on Distribution Systems, General Electric Company, 2008 [Online]. Available:http://pm.geindustrial.com/faq/documents/f60/ger3993.pdf [6]S. R. Nam, J. K. Park, Y. C. Kang, and T. H. Kim, “A modeling method of a high impedance fault in a distribution system using two series time varying resistances in EMTP,” in Proc. IEEE Power Eng.Soc. Summer Meeting, Vancouver, BC, Canada, Jul. 2001, vol. 2, pp.1175–1180. [7] N. Schaefer, et al., "Adaptive protection system for distribution networks with distributed energy resources", in Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET International Conference on, 2010, pp. 1-5 [8] “High Impedance Fault Detection of Distribution Network by Phasor Measurement Units” ,Mohsen Ghalei Monfared Zanjani, Hossein Kazemi Karegar, Hasan Ashrafi Niaki, Mina Ghalei Monfared Zanjani, Smart Grid and Renewable Energy, 2013, 4, 297-305 [9] “A New Approach to Current Differential Protection for Transmission Lines”, M. G. Adamiak,W. Premerlani, ELECTRIC COUNCIL OF NEW ENGLAND Protective Relaying Committee Meeting October 22-23, 1998 [10] “Protection of Microgrids Using Differential Relays”, Manjula Dewadasa, Member, IEEE, Arindam Ghosh, Fellow, IEEE and Gerard Ledwich, Senior Member, IEEE [11] Y. Han, et al., "Study of adaptive fault current algorithm for microgrid dominated by inverter based distributed generators", in Power Electronics for Distributed Generation Systems (PEDG), 2010 2nd IEEE International Symposium on, 2010, pp. 852-854. [12] D. Ke, et al., "An adaptive protection method for the inverter dominated microgrid", in Electrical Machines and Systems (ICEMS), 2011 International Conference on, 2011, pp. 1-5.
  • 10. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 9, Sept.-2015 10 | P a g e [13] “Modeling and Simulation of Micro Grid System Based on Renewable Power Generation Units by using Multilevel Converter”, K. Venkateswarlu, J. Krishna Kishore, QIS College of Engineering & Technology, Prakasam dt (AP) [14] “Study of Micro Grid Safety & Protection Strategies with Control System Infrastructures”, Md Razibul Islam, Hossam A. Gabbar, Faculty of Energy System and Nuclear Science, University of Ontario Institute of Technology, Oshawa, Canada. [15] “A Photovoltaic Array Simulation Model for Matlab-Simulink GUI Environment” I. H. Altas1 and A.M. Sharaf2 [18] “High-Impedance Fault Detection Using Discrete Wavelet Transform and Frequency Range and RMS Conversion”, T. M. Lai, L. A. Snider, Senior Member, IEEE, E. Lo, Member, IEEE, and D. Sutanto, Senior Member, IEEE [16] “IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes," IEEE Std C37.110-2007), pp. C1-67, 2008. [17] “Protection of micro-grids dominated by distributed generation using solid state converters”, by M. A. Red fern and H. Al-Nasseri, in Proc. IET 9th Int. Conf. Develop. Power Syst. Protection, 2008, pp. 670– 674. [18] “High Impedance Fault Detection on Distribution Systems”, by C. G. Wester, General Electric Company, 2008 [Online]. [19] “Selection of current transformer and wire sizing in substations”, Sethuraman Ganesan ,ABB Inc. ,Allentown, PA [20] “High impedance fault detection in low voltage networks” R. C. Christie, H. Zadehgol and M. M. Habib, , IEEE Trans. on Power Delivery, vol. 8, no. 4, pp. 1829-1836, Oct. 1993. [21] “Distribution high impedance fault detection utilizing high frequency current components” B. M. Aucoin and B. D. Russell, IEEE Trans. on Power Apparatus and Systems, vol. 101, no. 6, pp. 1596-1606, Jun. 1982. [22] “Unique aspects of distribution system harmonics due to high impedance ground faults” D. I. Jeering and J. R. Linders, , IEEE Trans. on Power Delivery, vol. 5, no. 2, pp. 1086-1094, Apr. 1990. [23] “Research on no communication protection of distribution lines based on fault components” ,B. Jianguang, D. Xinzhou, G. Yongji and B. Zhiqian, in Proc. intl. Conf. [24]Power System Technology, pp. 1151-1155, Oct. 2002. J. D. Glover and M. S. Sarma, Power System Analysis and Design, 3rd Edition, Pacific Grove, CA: Brooks/Cole, 2002. [25] “Cooper Power Systems”, Ed. 3, Electrical Distribution-System Protection, Cooper Industries, 1990.