SlideShare a Scribd company logo
National Productivity Council 1
Pump and Fan system
Presented By
J.Nagesh Kumar
Sr.Dy.Director
National Productivity Council
AIP,Ambattur,Chennai-98
npcaip@vsnl.com
National Productivity Council 2
Centrifugal Pumps
National Productivity Council 3
Energy Balance for a Typical Pumping System
ELECTRICITY
100%
12% LOSS
MOTOR
2% LOSS
COUPLING
24% LOSS
PUMPS
9% LOSS
VALVES
11% LOSS
PIPES
WORK DONE ON WATER
National Productivity Council 4
Operating Point Defined
National Productivity Council 5
Unsafe Safety Allowance
System heads should be estimated as accurately as
possible
Do not add a “margin for safety” to the system
head
In trying to match the over specified head, a larger
pump will be recommended by the supplier
The larger pump will operate at a higher capacity
point (as required by the actual system head)
This can overload the pump motor and require
greater throttling
National Productivity Council 6
Efficiency Curves
28.6 kW
14.8 kW
National Productivity Council 7
Operation with Throttling
A
B
National Productivity Council 8
Typical pump characteristic
curves
National Productivity Council 9
The affinity law for a centrifugal pump
Flow:
Flow:
Q1 / Q2 = N1 / N2
Example:
100 / Q2 = 1750/3500
Q2 = 200 m3
/hr
Head:
Head:
H1/H2 = (N12
) / (N22
)
Example:
100 /H2 = 1750 2
/ 3500 2
H2 = 400 m
Kilowatts (kW):
Kilowatts (kW):
kW1 / kW2 = (N13
) / (N23
)
Example:
5/kW2 = 17503
/ 35003
kW2 = 40
National Productivity Council 10
Flow Control Strategies
 Bypass valve
 Zero savings
 Throttle output
 Increased system pressure drop
 Move system curve and reduces efficiency
 Effect less in flat H-Q curve
 Trim impeller
 Buy a new pump
 Variable speed drive
 Most efficient
 Power varies as cube of speed
 Different flow rates without affecting efficiency
National Productivity Council 11
Why Oversized Pump ?
Safety margins were added to the original calculations. Several people
are involved in the pump buying decision and each of them is afraid of
recommending a pump that proves to be to small for the job.
It was anticipated that a larger pump would be needed in the future,
so it was purchased now to save buying the larger pump later on.
It was the only pump the dealer had in stock and you needed one
badly. He might have offered you a "special deal" to take the larger
size.
You took the pump out of your spare parts inventory. Capital
equipment money is scarce so the larger pump appeared to be your
only choice.
You purchased the same size pump as the one that came out of the
application and that one was over sized also.
National Productivity Council 12
Energy conservation
measures
Conduct water balance minimise water consumption
Avoid idle cooling water circulation in DG sets,
compressors, refrigeration systems
In multiple pump operations, judiciously mix the
operation of pumps and avoid throttling
Have booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump, provide variable
speed drive, trim / replace impeller or replace with
correct sized pump
Remove few stages in multi-stage pump with over
designed head
National Productivity Council 13
Energy Savings Opportunities
 Give efficiency of the pump due consideration
while selecting a pump.
 Select pumps to match head flow requirements.
 Select a motor to match the load with high
efficiency.
 Optimize the piping design.
 Monitor all important system parameters like:
motor kW, pump head, flow temperature.
 Use pumps in series and parallel so that
mismatch in system design or variations in
operating conditions can be handled properly.
National Productivity Council 14
Energy Savings Opportunities
(Contd.)
 Use variable speed drives for variations of flow
due to process requirement.
 If the head flow is higher than needed by 5 to
15%, (i) The existing impeller should be
trimmed to a smaller diameter, (ii) or a new
impeller with a smaller diameter is to be put.
 In multistage pumps, add or remove stages to
the existing pump, allowing an increase /
decrease in delivered head of flow, if required.
National Productivity Council 15
Air conditioning System
Resinoid plant
Cold Well
Hot Well
Resinoid Moulding
Recirculated
cooled
air
Recirculated
cooled and
washed
air
46 TR x 2nos in operation
National Productivity Council 16
Avoid Cold well Pumps
Resinoid plant
Hot Well
Resinoid Moulding
Recirculated
cooled
air
Recirculated
cooled and
washed
air
46 TR x 2nos in operation
New line
Annual Savings – Rs.3
National Productivity Council 17
Open circuit pumping system (Existing)
Cold Well Hot Well
•Calibrator
•Piercing press
•Elongator
•Push Bench
•Reeler
•Stretch reducing mill
•Mandrel bar cooling
Scale
pit
Settling Tank
Settling Tank
Pressure
Sand Filter
350 m3
/hr
25 m
45 kw
195 m3
/hr
50 m
41 kw
175 m3
/hr
20 m
18 kw
5 kw x 2 no
National Productivity Council 18
Open circuit pumping system (Proposed)
Cold Well Hot Well
•Calibrator
•Piercing press
•Elongator
•Push Bench
•Reeler
•Stretch reducing mill
•Mandrel bar cooling
Scale
pit
Settling Tank
Settling Tank
Pressure
Sand Filter
350 m3
/hr
25 m
45 kw
195 m3
/hr
50 m
41 kw
175 m3
/hr
20 m
18 kw
5 kw x 2 no
National Productivity Council 19
Closed circuit pumping system
Cold Well
•Rotary hearth furnace
•Walking beam furnace
•Roll down furnace
•Spiral fin welding
•Nitrogen generator
•Normalising furnace
•Tempering Furnace
•Air compressors
•Hydraulic systems
Return
water
sump
600 m3
/hr
20 m
48 kw
60 m3
/hr
50 m
110 kw
Fans :30 kw x 3 no
Switch off during
6-9 AM & PM
National Productivity Council 20
Existing cooling water system for tube plant
Return water sump
Final
compounding
mill
Warming mill
Feeding mill
Extruder
8 m3
/hr
2.5 m3
/hr
0.4 m3
/hr
0.23 m3
/hr
Extruder
die cooling
3 m3
/hr
Extruder
conveyor cooling
9.4 m3
/hr
100 TR
10 HP
Actual - 6 kW
HP - 7.5
Actual - 4 kW
H - 22 m
Q - 16m3
/hr
HP - 20
Actual - 11 kW
H - 29 m
Q - 23 m3
/hr K4
1 4
2 3
HP - 10
Actual - 6 kW
H - 29 m
Q - 17m3
/hr
HP - 20
Actual - 16.2 kW
H - 56 m
Q - 15 m3
/hr
HP - 20
Actual - 12 kW
H - 39 m
Q - 23 m3
/hr
National Productivity Council 21
Modified cooling water system for tube
plant
Return water sump
Final
compounding
mill
Warming mill
Feeding mill
Extruder
8 m3
/hr
2.5 m3
/hr
0.4 m3
/hr
0.23 m3
/hr
Extruder
die cooling
3 m3
/hr
Extruder
conveyor cooling
9.4 m3
/hr
100 TR
10 HP
Actual - 6 kW
HP - 7.5
Actual - 4 kW
H - 22 m
Q - 16m3
/hr
HP - 20
Actual - 11 kW
H - 29 m
Q - 23 m3
/hr K4
1 4
HP - 10
Actual - 6 kW
H - 29 m
Q - 17m3
/hr
HP - 20
Actual - 16.2 kW
H - 56 m
Q - 15 m3
/hr
HP - 20
Actual - 12 kW
H - 39 m
Q - 23 m3
/hr Modified pumping system
HP - 3
Actual –1.4 kW
H - 22 m
Q - 17m3
/hr
National Productivity Council 22
Dump Chest to Belcore
(Existing Practice)
10 m
120 m3
/hr
Kw
10 m
120 m3
/hr
Kw
Dump
Chest
Belcore
HD Cleaner
Belcore
Feed Chest
National Productivity Council 23
Connect HD cleaner pump outlet to
Belcore feed pump
10 m
120 m3
/hr
Kw
10 m
120 m3
/hr
Kw
Dump
Chest
Belcore
HD Cleaner
National Productivity Council 24
Centrifugal fans
National Productivity Council 25
Difference between fans, blowers and
compressors
Equipment Specific Ratio Pressure rise (mmWg)
Fans Up to 1.11 1136
Blowers 1.11 to 1.20 1136 – 2066
Compressors more than 1.20 -
As per ASME the specific pressure, i.e, the ratio of the discharge
pressure over the suction pressure is used for defining the fans,
blowers and compressors as highlighted below :
National Productivity Council 26
Energy audit of fan
Collect fan and motor specifications with
ducting network
Measure motor power input
Measure fan and motor speed
Measure static pressure at various points in
the duct
Measure total and static pressure and
compute flow
Estimate the system efficiency and check fan
operating point
National Productivity Council 27
Fan and Blower Controls
The volume of air moved by fans and blowers is adjusted in four basic
ways:
Changing the rotational speed is the most efficient. If the volume
requirement is constant, it can be achieved by selecting appropriate
pulley sizes. If the volume varies with the process, adjustable-speed
drives can be used.
Changing the blade angle is a method used with some vane-axial fans.
Restricting the airflow is accomplished with dampers or valves which
close off the airflow at the inlet or outlet. Inlet vanes, which swirl the
air entering the centrifugal fan or blower, are more efficient than
dampers or butterfly valves.
Venting the high-pressure air, or recirculating it to the inlet, is often
used with positive-displacement blowers. It is sometimes used with
fan systems, but is the least efficient method as there is no reduction
in the air being moved.
National Productivity Council 28
What to Look for in the
Field
Overall system efficiency will be determined by the type of fan or blower,
its interaction with the air distribution system, and the method of control.
Determine whether the right type of fan or blower is used for an
application. Is your fan or blower is providing the best efficiency and
performance in a given application.
The efficiency of a system depends on the number and type of bends and
restrictions. Sharp bends, especially, increase the resistance the fan or
blower must overcome. Bends and restrictions near the inlet or outlet
seriously degrade capacity and efficiency.
With a properly selected fan or blower and well-designed air distribution
system, the method of control is the main thing determining energy
efficiency. In systems requiring constant air volume, the speed of a belt-
driven fan or blower should be adjusted by proper selection of pulley
sizes, and equipment should operate only when needed. In systems
requiring variable airflow, an adjustable-speed control is most efficient.
National Productivity Council 29
Energy conservation in fans
Match fan capacity to demand
 downsizing, pulley change, VSD..
Avoid unnecessary demand
 excess air reduction
 idling
Reduce pressure drops
 Remove redundant ducts
 Modify ducting with minimum bends
Drive system
 Provide direct drive where possible
 Replace V-belt by flat belt
Replace with energy efficient fans
Regular preventive maintenance
National Productivity Council 30
Checklist for energy savings in
Fans and Blowers
Use smooth, well-rounded air inlet cones for fan
air intakes.
Avoid poor flow distribution at the fan inlet.
Minimize fan inlet and outlet obstructions.
Clean screens, filters, and fan blades regularly.
Use airfoil-shaped fan blades.
Minimize fan speed.
Use low-slip or no-slip belts.
Check belt tension regularly.
National Productivity Council 31
Checklist for energy savings in
Fans and Blowers (contd.)
Use variable speed drives for large variable fan
loads.
Use energy-efficient motors for continuous or near-
continuous operation
Eliminate ductwork leaks.
Turn fans off when they are not needed.
Blowers
Use smooth, well-rounded air inlet ducts or cones
for air intakes.
Minimize blower inlet and outlet obstructions.
National Productivity Council 32
Checklist for energy savings in
Fans and Blowers (contd.)
Clean screens and filters regularly.
Minimize blower speed.
Use low-slip or no-slip belts.
Check belt tension regularly.
Eliminate variable pitch pulleys.
Use variable speed drives for large variable blower loads.
Use energy-efficient motors for continuous or near-
continuous operation.
Eliminate ductwork leaks.
Turn blowers off when they are not needed.
National Productivity Council 33
Flow control
Recirculation
Damper
VFC
VFD
Ideal
Flow
25 75
50 100
Power
100
75
50
25
National Productivity Council 34
Impact of speed reduction
National Productivity Council 35
Use of VSD: Boiler ID fan case
study
National Productivity Council 36
Use of VSD: Boiler ID fan case
study
(contd.)
National Productivity Council 37
Twin Benefits due to fan speed control
Thermax Boiler
6 TPH
10.75 Kg/cm2
Coconut shell
fired
Hopper
Coconut shell
crusher
Economiser
Dust
Collector
Primary Air
Fan
Secondary Air
Fan
Induced Draft
Fan
Damper
14 % O2
9 % O2
National Productivity Council 38
Energy saving in Boiler ID fan by speed
reduction through pulley change
8”
10”
1470 RPM 1181 RPM
26 kW
6”
10”
1470 RPM 882RPM
14 kW
National Productivity Council 39
Regulate with dampers in each
equipment
30 HP dust collector in Resinoid plant
Conical
Edger
Dry
disc
Blow
booth
22”
edger
22”
lathe
Existing:
•No dampers
•Suction remains
even when M/c
not operating
16 kW (all dampers open)
14.4 (3 dampers closed)
Proposed:
•Provide dampers
•Suction only in M/cs
operating
•Operate fan with
variable speed drive
Pneumatically
actuated dampers
Variable
Speed Drive
Conical
Edger
Dry
disc
Blow
booth
22”
edger
22”
lathe

More Related Content

PPT
Energy-Saving Designs for Existing Buildings
PPT
Energy efficiency in pumps and fans ppt
PPT
2010 Energy Audit Presentation
PPT
2010 Energy Presentation
PPT
2010 Energy Presentation
PPTX
Minimizing power requirment for pumps in dairy industry
PDF
Dyna pump spe paper saul tovar oxy permain
Energy-Saving Designs for Existing Buildings
Energy efficiency in pumps and fans ppt
2010 Energy Audit Presentation
2010 Energy Presentation
2010 Energy Presentation
Minimizing power requirment for pumps in dairy industry
Dyna pump spe paper saul tovar oxy permain

Similar to PUMPS and FANS - concept and explanation.ppt (20)

PPTX
Optimum overhaul of pumps 2014
PPTX
Energy Conservation Opportunities in industries at GCET
PDF
Handbook of mechanical engineering calculations
PDF
Increasing Pump Operating Life
PDF
Deabb 1904 13 en variable speed drive final
PDF
Handbook_of_Mechanical_Engineering_calcc
PPTX
Talk on energy efficiency by ajai arora
PPT
Refrigeration and air conditioning system
PPTX
Tips for energy conservation for industries
PPT
Pumps
PDF
An introduction to Energy Saving Opportunities in Pumping Systems
PDF
Energy Audit & Energy Conservation Opportunities in Electrical Equipments ...
PDF
Energy Savings with Variable Frequency Drives
PDF
Industrial Boiler Optimization Toolkit
PDF
Adm apn045-en 0912
PDF
3: Energy Management In Water Supply Systems - Pumping Operations
PDF
Why compressed air is so expensive and what to do about it
PPTX
Pumps and pumping system
PDF
APT Hydraulic Pump Investor Pres Saxon Tech
PDF
lec2_air_compressor.pdf
Optimum overhaul of pumps 2014
Energy Conservation Opportunities in industries at GCET
Handbook of mechanical engineering calculations
Increasing Pump Operating Life
Deabb 1904 13 en variable speed drive final
Handbook_of_Mechanical_Engineering_calcc
Talk on energy efficiency by ajai arora
Refrigeration and air conditioning system
Tips for energy conservation for industries
Pumps
An introduction to Energy Saving Opportunities in Pumping Systems
Energy Audit & Energy Conservation Opportunities in Electrical Equipments ...
Energy Savings with Variable Frequency Drives
Industrial Boiler Optimization Toolkit
Adm apn045-en 0912
3: Energy Management In Water Supply Systems - Pumping Operations
Why compressed air is so expensive and what to do about it
Pumps and pumping system
APT Hydraulic Pump Investor Pres Saxon Tech
lec2_air_compressor.pdf
Ad

Recently uploaded (20)

PDF
III.4.1.2_The_Space_Environment.p pdffdf
PPTX
Safety Seminar civil to be ensured for safe working.
PPTX
Fundamentals of Mechanical Engineering.pptx
PDF
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
PDF
Design Guidelines and solutions for Plastics parts
PPTX
Current and future trends in Computer Vision.pptx
PDF
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
PPT
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
PPTX
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
PPTX
Software Engineering and software moduleing
PDF
August 2025 - Top 10 Read Articles in Network Security & Its Applications
PPTX
Artificial Intelligence
PPTX
Module 8- Technological and Communication Skills.pptx
PDF
737-MAX_SRG.pdf student reference guides
PDF
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
PPTX
introduction to high performance computing
PDF
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
PDF
Level 2 – IBM Data and AI Fundamentals (1)_v1.1.PDF
PDF
BIO-INSPIRED ARCHITECTURE FOR PARSIMONIOUS CONVERSATIONAL INTELLIGENCE : THE ...
III.4.1.2_The_Space_Environment.p pdffdf
Safety Seminar civil to be ensured for safe working.
Fundamentals of Mechanical Engineering.pptx
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
Design Guidelines and solutions for Plastics parts
Current and future trends in Computer Vision.pptx
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
Software Engineering and software moduleing
August 2025 - Top 10 Read Articles in Network Security & Its Applications
Artificial Intelligence
Module 8- Technological and Communication Skills.pptx
737-MAX_SRG.pdf student reference guides
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
introduction to high performance computing
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
Level 2 – IBM Data and AI Fundamentals (1)_v1.1.PDF
BIO-INSPIRED ARCHITECTURE FOR PARSIMONIOUS CONVERSATIONAL INTELLIGENCE : THE ...
Ad

PUMPS and FANS - concept and explanation.ppt

  • 1. National Productivity Council 1 Pump and Fan system Presented By J.Nagesh Kumar Sr.Dy.Director National Productivity Council AIP,Ambattur,Chennai-98 npcaip@vsnl.com
  • 2. National Productivity Council 2 Centrifugal Pumps
  • 3. National Productivity Council 3 Energy Balance for a Typical Pumping System ELECTRICITY 100% 12% LOSS MOTOR 2% LOSS COUPLING 24% LOSS PUMPS 9% LOSS VALVES 11% LOSS PIPES WORK DONE ON WATER
  • 4. National Productivity Council 4 Operating Point Defined
  • 5. National Productivity Council 5 Unsafe Safety Allowance System heads should be estimated as accurately as possible Do not add a “margin for safety” to the system head In trying to match the over specified head, a larger pump will be recommended by the supplier The larger pump will operate at a higher capacity point (as required by the actual system head) This can overload the pump motor and require greater throttling
  • 6. National Productivity Council 6 Efficiency Curves 28.6 kW 14.8 kW
  • 7. National Productivity Council 7 Operation with Throttling A B
  • 8. National Productivity Council 8 Typical pump characteristic curves
  • 9. National Productivity Council 9 The affinity law for a centrifugal pump Flow: Flow: Q1 / Q2 = N1 / N2 Example: 100 / Q2 = 1750/3500 Q2 = 200 m3 /hr Head: Head: H1/H2 = (N12 ) / (N22 ) Example: 100 /H2 = 1750 2 / 3500 2 H2 = 400 m Kilowatts (kW): Kilowatts (kW): kW1 / kW2 = (N13 ) / (N23 ) Example: 5/kW2 = 17503 / 35003 kW2 = 40
  • 10. National Productivity Council 10 Flow Control Strategies  Bypass valve  Zero savings  Throttle output  Increased system pressure drop  Move system curve and reduces efficiency  Effect less in flat H-Q curve  Trim impeller  Buy a new pump  Variable speed drive  Most efficient  Power varies as cube of speed  Different flow rates without affecting efficiency
  • 11. National Productivity Council 11 Why Oversized Pump ? Safety margins were added to the original calculations. Several people are involved in the pump buying decision and each of them is afraid of recommending a pump that proves to be to small for the job. It was anticipated that a larger pump would be needed in the future, so it was purchased now to save buying the larger pump later on. It was the only pump the dealer had in stock and you needed one badly. He might have offered you a "special deal" to take the larger size. You took the pump out of your spare parts inventory. Capital equipment money is scarce so the larger pump appeared to be your only choice. You purchased the same size pump as the one that came out of the application and that one was over sized also.
  • 12. National Productivity Council 12 Energy conservation measures Conduct water balance minimise water consumption Avoid idle cooling water circulation in DG sets, compressors, refrigeration systems In multiple pump operations, judiciously mix the operation of pumps and avoid throttling Have booster pump for few areas of higher head Replace old pumps by energy efficient pumps In the case of over designed pump, provide variable speed drive, trim / replace impeller or replace with correct sized pump Remove few stages in multi-stage pump with over designed head
  • 13. National Productivity Council 13 Energy Savings Opportunities  Give efficiency of the pump due consideration while selecting a pump.  Select pumps to match head flow requirements.  Select a motor to match the load with high efficiency.  Optimize the piping design.  Monitor all important system parameters like: motor kW, pump head, flow temperature.  Use pumps in series and parallel so that mismatch in system design or variations in operating conditions can be handled properly.
  • 14. National Productivity Council 14 Energy Savings Opportunities (Contd.)  Use variable speed drives for variations of flow due to process requirement.  If the head flow is higher than needed by 5 to 15%, (i) The existing impeller should be trimmed to a smaller diameter, (ii) or a new impeller with a smaller diameter is to be put.  In multistage pumps, add or remove stages to the existing pump, allowing an increase / decrease in delivered head of flow, if required.
  • 15. National Productivity Council 15 Air conditioning System Resinoid plant Cold Well Hot Well Resinoid Moulding Recirculated cooled air Recirculated cooled and washed air 46 TR x 2nos in operation
  • 16. National Productivity Council 16 Avoid Cold well Pumps Resinoid plant Hot Well Resinoid Moulding Recirculated cooled air Recirculated cooled and washed air 46 TR x 2nos in operation New line Annual Savings – Rs.3
  • 17. National Productivity Council 17 Open circuit pumping system (Existing) Cold Well Hot Well •Calibrator •Piercing press •Elongator •Push Bench •Reeler •Stretch reducing mill •Mandrel bar cooling Scale pit Settling Tank Settling Tank Pressure Sand Filter 350 m3 /hr 25 m 45 kw 195 m3 /hr 50 m 41 kw 175 m3 /hr 20 m 18 kw 5 kw x 2 no
  • 18. National Productivity Council 18 Open circuit pumping system (Proposed) Cold Well Hot Well •Calibrator •Piercing press •Elongator •Push Bench •Reeler •Stretch reducing mill •Mandrel bar cooling Scale pit Settling Tank Settling Tank Pressure Sand Filter 350 m3 /hr 25 m 45 kw 195 m3 /hr 50 m 41 kw 175 m3 /hr 20 m 18 kw 5 kw x 2 no
  • 19. National Productivity Council 19 Closed circuit pumping system Cold Well •Rotary hearth furnace •Walking beam furnace •Roll down furnace •Spiral fin welding •Nitrogen generator •Normalising furnace •Tempering Furnace •Air compressors •Hydraulic systems Return water sump 600 m3 /hr 20 m 48 kw 60 m3 /hr 50 m 110 kw Fans :30 kw x 3 no Switch off during 6-9 AM & PM
  • 20. National Productivity Council 20 Existing cooling water system for tube plant Return water sump Final compounding mill Warming mill Feeding mill Extruder 8 m3 /hr 2.5 m3 /hr 0.4 m3 /hr 0.23 m3 /hr Extruder die cooling 3 m3 /hr Extruder conveyor cooling 9.4 m3 /hr 100 TR 10 HP Actual - 6 kW HP - 7.5 Actual - 4 kW H - 22 m Q - 16m3 /hr HP - 20 Actual - 11 kW H - 29 m Q - 23 m3 /hr K4 1 4 2 3 HP - 10 Actual - 6 kW H - 29 m Q - 17m3 /hr HP - 20 Actual - 16.2 kW H - 56 m Q - 15 m3 /hr HP - 20 Actual - 12 kW H - 39 m Q - 23 m3 /hr
  • 21. National Productivity Council 21 Modified cooling water system for tube plant Return water sump Final compounding mill Warming mill Feeding mill Extruder 8 m3 /hr 2.5 m3 /hr 0.4 m3 /hr 0.23 m3 /hr Extruder die cooling 3 m3 /hr Extruder conveyor cooling 9.4 m3 /hr 100 TR 10 HP Actual - 6 kW HP - 7.5 Actual - 4 kW H - 22 m Q - 16m3 /hr HP - 20 Actual - 11 kW H - 29 m Q - 23 m3 /hr K4 1 4 HP - 10 Actual - 6 kW H - 29 m Q - 17m3 /hr HP - 20 Actual - 16.2 kW H - 56 m Q - 15 m3 /hr HP - 20 Actual - 12 kW H - 39 m Q - 23 m3 /hr Modified pumping system HP - 3 Actual –1.4 kW H - 22 m Q - 17m3 /hr
  • 22. National Productivity Council 22 Dump Chest to Belcore (Existing Practice) 10 m 120 m3 /hr Kw 10 m 120 m3 /hr Kw Dump Chest Belcore HD Cleaner Belcore Feed Chest
  • 23. National Productivity Council 23 Connect HD cleaner pump outlet to Belcore feed pump 10 m 120 m3 /hr Kw 10 m 120 m3 /hr Kw Dump Chest Belcore HD Cleaner
  • 24. National Productivity Council 24 Centrifugal fans
  • 25. National Productivity Council 25 Difference between fans, blowers and compressors Equipment Specific Ratio Pressure rise (mmWg) Fans Up to 1.11 1136 Blowers 1.11 to 1.20 1136 – 2066 Compressors more than 1.20 - As per ASME the specific pressure, i.e, the ratio of the discharge pressure over the suction pressure is used for defining the fans, blowers and compressors as highlighted below :
  • 26. National Productivity Council 26 Energy audit of fan Collect fan and motor specifications with ducting network Measure motor power input Measure fan and motor speed Measure static pressure at various points in the duct Measure total and static pressure and compute flow Estimate the system efficiency and check fan operating point
  • 27. National Productivity Council 27 Fan and Blower Controls The volume of air moved by fans and blowers is adjusted in four basic ways: Changing the rotational speed is the most efficient. If the volume requirement is constant, it can be achieved by selecting appropriate pulley sizes. If the volume varies with the process, adjustable-speed drives can be used. Changing the blade angle is a method used with some vane-axial fans. Restricting the airflow is accomplished with dampers or valves which close off the airflow at the inlet or outlet. Inlet vanes, which swirl the air entering the centrifugal fan or blower, are more efficient than dampers or butterfly valves. Venting the high-pressure air, or recirculating it to the inlet, is often used with positive-displacement blowers. It is sometimes used with fan systems, but is the least efficient method as there is no reduction in the air being moved.
  • 28. National Productivity Council 28 What to Look for in the Field Overall system efficiency will be determined by the type of fan or blower, its interaction with the air distribution system, and the method of control. Determine whether the right type of fan or blower is used for an application. Is your fan or blower is providing the best efficiency and performance in a given application. The efficiency of a system depends on the number and type of bends and restrictions. Sharp bends, especially, increase the resistance the fan or blower must overcome. Bends and restrictions near the inlet or outlet seriously degrade capacity and efficiency. With a properly selected fan or blower and well-designed air distribution system, the method of control is the main thing determining energy efficiency. In systems requiring constant air volume, the speed of a belt- driven fan or blower should be adjusted by proper selection of pulley sizes, and equipment should operate only when needed. In systems requiring variable airflow, an adjustable-speed control is most efficient.
  • 29. National Productivity Council 29 Energy conservation in fans Match fan capacity to demand  downsizing, pulley change, VSD.. Avoid unnecessary demand  excess air reduction  idling Reduce pressure drops  Remove redundant ducts  Modify ducting with minimum bends Drive system  Provide direct drive where possible  Replace V-belt by flat belt Replace with energy efficient fans Regular preventive maintenance
  • 30. National Productivity Council 30 Checklist for energy savings in Fans and Blowers Use smooth, well-rounded air inlet cones for fan air intakes. Avoid poor flow distribution at the fan inlet. Minimize fan inlet and outlet obstructions. Clean screens, filters, and fan blades regularly. Use airfoil-shaped fan blades. Minimize fan speed. Use low-slip or no-slip belts. Check belt tension regularly.
  • 31. National Productivity Council 31 Checklist for energy savings in Fans and Blowers (contd.) Use variable speed drives for large variable fan loads. Use energy-efficient motors for continuous or near- continuous operation Eliminate ductwork leaks. Turn fans off when they are not needed. Blowers Use smooth, well-rounded air inlet ducts or cones for air intakes. Minimize blower inlet and outlet obstructions.
  • 32. National Productivity Council 32 Checklist for energy savings in Fans and Blowers (contd.) Clean screens and filters regularly. Minimize blower speed. Use low-slip or no-slip belts. Check belt tension regularly. Eliminate variable pitch pulleys. Use variable speed drives for large variable blower loads. Use energy-efficient motors for continuous or near- continuous operation. Eliminate ductwork leaks. Turn blowers off when they are not needed.
  • 33. National Productivity Council 33 Flow control Recirculation Damper VFC VFD Ideal Flow 25 75 50 100 Power 100 75 50 25
  • 34. National Productivity Council 34 Impact of speed reduction
  • 35. National Productivity Council 35 Use of VSD: Boiler ID fan case study
  • 36. National Productivity Council 36 Use of VSD: Boiler ID fan case study (contd.)
  • 37. National Productivity Council 37 Twin Benefits due to fan speed control Thermax Boiler 6 TPH 10.75 Kg/cm2 Coconut shell fired Hopper Coconut shell crusher Economiser Dust Collector Primary Air Fan Secondary Air Fan Induced Draft Fan Damper 14 % O2 9 % O2
  • 38. National Productivity Council 38 Energy saving in Boiler ID fan by speed reduction through pulley change 8” 10” 1470 RPM 1181 RPM 26 kW 6” 10” 1470 RPM 882RPM 14 kW
  • 39. National Productivity Council 39 Regulate with dampers in each equipment 30 HP dust collector in Resinoid plant Conical Edger Dry disc Blow booth 22” edger 22” lathe Existing: •No dampers •Suction remains even when M/c not operating 16 kW (all dampers open) 14.4 (3 dampers closed) Proposed: •Provide dampers •Suction only in M/cs operating •Operate fan with variable speed drive Pneumatically actuated dampers Variable Speed Drive Conical Edger Dry disc Blow booth 22” edger 22” lathe

Editor's Notes

  • #1: Ask the participants to list some pump applications.
  • #2: Centrifugal pumps account for the vast majority of pumps applications in industry. Centrifugal pumps give energy to the fluid by centrifugal action. They rely on the flow of fluid to create a seal to prevent fluid flowing backward through the pump. The volute is the most common centrifugal. The impeller vanes generally curve backwards, but radial and forward vanes are used.The velocity head of the fluid is converted into pressure head.
  • #3: Pumps are components of pumping systems, which also include motors, drives, piping and valves. Typically much less than half the electricity input to a pumping system is converted into useful movement of fluid. The rest is dissipated by the various components that make up the system. Energy losses are still greater when the system is not operating at its design point. Thus, there appears to be to be a considerable potential for saving electricity, both by improving component efficiencies and through better system design. 
  • #4: The system curve is a plot of system resistance vs flow. Once the operating point ie flow and pressure are determined, the pump has to be selected by superimposing the pump curve to intersect with the operating point on the system curve. The characteristic curve of a centrifugal pump is shown in the figure. The pump has to be selected so that it will operate at its best efficiency point. Oversizing of flow during initial selection creates can cause efficiency point to shift resulting reduced operational efficiency of the pump. Also the oversized pump needs to be throttled to meet the reduced flow condition.
  • #5: Selection of a pump is vital to energy efficiency in operations later. Allowances and liberal factors of safety enhances the capacity and head requirement. In actual operation the pump will be oversized leading to throttling.
  • #6: Use the white board and do the following Assume that we need to pump 68 m3/hr. to a 47 meter head with a pump that is 60% efficient at that point. Liquid Power - 68 x 47 / 360 = 8.9 Kw Where ‘360’ is a constant Shaft Power - 8.9 / 0.60 = 14.8 Kw Where 0.6 is the efficiency at that point Motor Power - 14.8 / 0.9 = 16.4 Kw Where 0.9 is the motor efficiency  As shown in the drawing, we should be using impeller "E" to do this, but we have an oversized pump so we are using the larger impeller "A" with the pump discharge valve throttled back to 68 cubic meters per hour, giving us an actual head of 76 meters. Now our Kilowatts look like this: 68 x 76 / 360 = 14.3 Kw being produced by the pump, and 14.3 / 0.50 = 28.6 Kw required to do this. Subtracting the amount of kilowatts we should have been using gives us: 28.6 - 14.8 = 13.8 extra kilowatts being used to pump against the throttled discharge valve. Extra energy used - 8760 hrs/yr x 13.8 = 120,880 kw. = $ 10,000/annum In this example the extra cost of the electricity could almost equal the cost of purchasing two or three pumps.
  • #7: This is just similar to fans that we have seen in the last session. The normal operating point A is what the pump had been designed for. But to accommodate lower flow, the flow is throttled leading to an incremental pressure drop. The flow at B is less than flow at A but has been achieved at the cost of additional head which involves waste of energy.
  • #9: For centrifugal pumps the laws that are applicable to fans are also applicable for pumps. Flow is proportional to speed, Head proportional to square of head and power to the cube of speed.
  • #10: Varying flow requirements can be met by conventional and low cost options such as by pass control or throttle control. But both these methods are highly energy inefficient. There are occasions when you might want to permanently change the amount of fluid you are pumping, or change the discharge head of a centrifugal pump. This can be economically achieved by trimming the impeller or replacing the pump with a reduced size of the impeller or at the worst replacing the pump itself. The most efficient way to deal with varying flows is by means of a variable speed drive. This ensures that the pump always operates at the best efficiency point and eliminates the need for any throttling. The virtue of this method is that it reduces the energy input to the system instead of dumping the excess. With decreasing costs in power electronics the variable speed drives are becoming more popular today.
  • #11: The normal mistakes done in selecting a pump is given above. Remember that the cost of operating an inefficient pump is many times more than the pump cost itself.
  • #12: As a first step, a water balance has to be made out quantifying requirements for various uses. Once this is done analysis needs to be made to reduce or recycle water. Reducing water consumption is the simplest way to save energy. Also look for standby equipment and equipment which are not in operation, but utilising water. For example a DG set which operates only during emergency might have water getting circulated for cooling. Such uses can be curtailed. Just to meet one or two applications where a higher pressure is required, the entire pumping system may be operating at a higher head. Reduce the pressure and provide booster pumps for such applications.
  • #13: First you should be sure of the flow and head requirements and then select the pump to operate in this point at maximum efficiency. The motor has to be selected so that the loading is maintained high. Energy efficient motor can be considered during new installations. Provide appropriate meters and log data so that analysis becomes easy. Where large variations are expected, multiple pumps have to be judiciously selected and operated for maximum efficiency.
  • #14: Variable speed drives can be considered only where continuous fluctuations are expected. Each pump casing has provision for replacement with lower or higher size impellers up to a certain limit and varies with manufacturer. Flow changes can be met by changing the impeller or trimming the existing impeller. In multistage pumps such as boiler feed pumps, too high a pressure than requirement can be dealt by removing a few stages of the pump.
  • #33: If fans rated for a higher flow rate, but a lesser flow is actually required: then flow reduction is effected by the following methods Recirculation: Venting the high-pressure air, or recirculating it to the inlet, is often used with positive-displacement blowers. It is sometimes used with fan systems, but is the least efficient method as there is no reduction in the air being moved. Damper: Restricting the airflow is accomplished with dampers or valves which close off the airflow at the inlet or outlet. Inlet vanes, which swirl the air entering the centrifugal fan or blower, are more efficient than dampers or butterfly valves. VFC: Variable speed fluid coupling. Motor speed is constant but the fluid coupling speed changes thus changing the speed of fan. VFD: Variable frequency drive which varies the speed of the motor itself Changing the blade angle is a method used with some vane-axial fans Changing the rotational speed is the most efficient. If the volume requirement is constant, it can be achieved by selecting appropriate pulley sizes. If the volume varies with the process, adjustable-speed drives can be used.
  • #37: Existing condition This is a coconut shell fired boiler. Boiler is operating with damper 100 % opening. Excess air is around 200 % with an oxygen level of 14 %. This means too much air is being supplied to the boiler. Improved Condition The excess air was reduced by closing the damper by 50 % and excess air was reduced to 75 %. Now the fuel consumption reduced by 5%.    Not only that. We have reduced the air by closing the damper which has incurred a unnecessary pressure loss. Now how can we reduce the power of the fan ?                    
  • #38: Existing condition   The ID fan is in oversized condition for the existing operating load.   So the minimum cost option is to reduce the motor pulley and reduce the fan speed. The motor pulley was reduced from 8” to 6”. Energy consumption in existing Condition (Damper control) 26 kW After reducing the motor pulley To 6” (damper fully open) 14 kW Annual saving 12 x 8000 96,000 kWH Speed reduction by pulley change can give only one fixed speed. Since the boiler is operating at constant load speed reduction through pulley change is the appropriate option. Where boiler load fluctuates a variable speed drive (inverter) may be installed. The speed can be varied according to load. The speed control can be effected in relation to fuel feeder RPM. The savings with variable speed drive will be marginally more because The motor and fan can be directly coupled thus eliminating the v-belt losses