National Workshop on
“Efficient Operation and Maintenance of Boilers”
organized by National Productivity Council
at Visakhapatnam(AP)
Presented By:
Vikas shrivastava & Akhilesh Tiwari
under guidance of Mr. R N Yadav and Mr. A K Saxena
From JAYPEE SIDHI CEMENT PLANT
, SIDHI,MP
EFFICIENT AND SAFE OPERATION
OF BOILERS AND PREVENTION
OF BOILER EXPLOSION
BY JAYPEE SIDHI CEMENT PLANT, SIDHI (M.P.)
PARAMETERS REQUIRED TO BE MAINTAINED STRICTLY
FOR EFFICIENT OPERATION OF AFBC BOILERS
 Bed Height/FD Air Pressure
 Primary Air Pressure
 Bed Temp./Furnace Temperature
 Fuel Size
 Bed Material size & Specifications
 Air & Fuel ratio
BED HEIGHT/FD AIR PRESSURE
 Static height for AFBC Boiler is to be maintained 300
to 325 mm during initial light up of boiler.
 Expand bed height for AFBC boiler is to be maintained
500 mmwc to 600 mmwc.
 FD Air discharge Pressure 600 to 650 mmwc.
 Wind box or Air Box pressure 500 to 600 mmwc.
 NOTE: High W.B. pressure increases the erosion
of bed coils & low W.B. stops fluidization.
PRIMARY AIR PRESSURE
 P.A. fan air header pressure for AFBC boiler is to be
maintained 1000 to 1150 mmwc.
 Difference of primary air pressure & F.D. wind box
pressure is to be maintained approximately 500
mmwc.
 NOTE: High P.A. pressure increases the bed coil
erosion and carryover to enhance secondary
combustion.
BED TEMPERATURE/FURNACE
TEMPERATURE FOR AFBC/CFBC
 Depends upon the type of fuel & firing method.
Indian coal 850 to 900 Deg.C.
Imported coal 875 to 925 Deg.C.
Lignite fuel 800 to 850 Deg.C.
Pet coke 875 to 950 Deg.C.
 Rice husk and other biomass fuel 850 to 900 Deg.C.
 Stoker firing 1100 to 1200 Deg.C.
 Pulverized fuel firing 1100 to 1300 Deg.C.
 For oil & gas firing 1100 to 1500 Deg.C.
FUEL SIZE
 When firing with Indian/Imported coal following sizes are
to strictly maintained as it will affect on performance of
boiler.
 For AFBC/CFBC Size : 0 to 8 mm
Less than 1 mm not allowed more than 20%.
Distribution: 1 to 5 mm – 70%
5 to 8 mm -20%
0 to 1 mm – 10%
NOTE: Lower the size of coal, higher the unburnt in fly
ash, higher the size of coal, higher the erosion of bed
coils and blockage of fuel air pipe & clinkerization in
boiler.
FUEL SIZE CONT’D
 For STOKER FIRED BOILERS Size: 5 to 25 mm
Less than 5 mm not allowed more than 5%
Distribution: 5 mm to 15 mm-25%
15 mm to 25 mm-70%
0 mm to 5 mm -5%
NOTE: Lower the size of coal higher unburnt in
flyash & carryover through boiler.
FUEL SIZE CONT’D
 PULVARIZED FIRED BOILERS
Pulverized coal size: mesh powder
 (μm) and, for a bituminous coal
Size Distribution: 2% is +300 micro metre (μm)
70-75% is below 75 microns
20% is about 75-100 microns
NOTE: Higher the size of pulverized coal below 100 mesh
results unburnt in bottom ash.
BED MATERIAL SIZE &
SPECIFICATION
 Bed Material Size: 0.85 mm to 2.36 mm
Distribution : 0.85 mm to 1.00 mm – 10%
1.00 mm to 1.50 mm - 50%
1.5 mm to 2.36 mm - 40 %
BED MATERIAL SIZE &
SPECIFICATION CONT’D
 Bed Material Specifications:
Crushed fire bricks castables IS8 grade bricks or river
silica sand
Fusion Temp. 1300 Deg.C Shape: Spherical Angular
Bulk Density 1050 Kg/M3 Silica : 65%
Al2O3 28% Fe2O3: 1.05%
PbO2 1.67 % MnO : Trace
MgO 0.23 % P2O5 : 0.08 %
V2O 0.22 % K2O : 0.45 %
AIR TO FUEL RATIO
 Theoretical Air for combustion:
Theoretical Air Required:
4.31(8/3C+8(H-O/8)+S) Kg/Kg of fuel burnt.
 To Understand the basics of efficient boiler Operation, the
combustion process must be understood. Stable combustion
condition requires the right amount of fuels and Oxygen,
combustion products are heat energy,CO2,water vapour,
N2,Sox,Nox and O2. In theory there is a specific amount of
O2 needed to completely burn a given amount of fuel. In
practice , burning conditions are never ideal, Therefore excess
air must be supplied to burn the fuel completely depending
upon the type of fuel.
TYPICAL EXCESS AIR TO ACHIEVE HIGHEST
EFFICIENCY FOR DIFFERENT FUELS
 Captive Power plant(Coal) boilers normally run about
15 to 20 %.
 Fuel oil fired boilers may run as low as 5 to 10 %.
 Natural gas fired boilers may run as low 5 to 8%.
 Pulverized coal fired boilers may run about 10 to 15%.
OXYGEN AT BOILER OUTLET
 To Ensure complete combustion of the fuel used,
combustion chambers are supplied with excess air.
 Excess air increase the amount of oxygen and the
probability of combustion of all fuels.
 EA= (O2% /21- O2% )x100
 Stoichiometric Combustion
 fuel + Oxygen in the air are in perfect balance-.
 CO2% or O2% in flue gas is an important indication
of the combustion efficiency.
BOILER EMERGENCIES
 Various Emergencies situations during Operation with
a special emphasis on the safety aspect like boiler
protection systems controls and interlocks.
Drum level low and low-low.
Drum level high and high-high.
Furnace draught high and high-high.
Bed Temp. high.
Bed Temp low.
Water wall/screen tube/Evaporator tube failure.
BOILER EMERGENCIES CONT’D
Super heater tube failure.
High Super heater Temp.
Low Super heater Temp.
Flame failure.
Furnace Explosion.
Boiler pressure high.
Coal feeder failure.
PAH/SAH tube failure.
Boiler feed pump failure.
Fan Failure.
DRUM LEVEL LOW AND LOW-LOW
 (A) CAUSES:
 Failure of BFP.
 Failure of drum level controllers.
 Excess opening of CBD/IBD.
 Sudden change in load(sudden red’n in load)
 Water tube failure
 (B) EFFECT:
 Boiler pressure parts may damage badly.
 (C) ACTIONS:
 Run the boiler if drum level is within safe limit otherwise
allow boiler to trip when the water level goes low-low limit
to protect the boiler pressure parts.
DRUM LEVEL HIGH AND HIGH HIGH
 (A) CAUSES:
 Failure of drum level controller.
 Sudden increase in load.
 Sudden increase in firing rate.
 (B) EFFECT:
 Water may enter in to the turbine and serious damage of turbine blades and
thrust pads.
 Carry over in Super heater and sharp fall in S.H. temp.
 Flange gasket may be failure.
 (C) ACTIONS:
 Run the boiler if drum level within safe limit and control the FCV.
 Open the CBD to maintain drum level in safe limit.
 Open the TG side main steam & Turbine drains to avoid the water entering into
TG.
 Trip the TG when steam temp gets below the safe limit.
FURNACE DRAUGHT HIGH AND
HIGH HIGH
 (A) CAUSE:
 Due to faulty operation of fan control.
 Disturbed combustion .
 Uncontrolled fuel entry.
 (B) EFFECT:
 Boiler may damage due to high furnace pressure.
 Weak part of furnace(ducting & Enclosure)may explode high
furnace pressure.
 (C) ACTION:
 If it is due to faulty operation of ID/FD/PA/SA fan control , take
it on manual mode and maintain furnace in suction.
 If furnace pressure has increased beyond limit allow boiler to
trip on furnace draught high-high.
BED TEMP. HIGH
 (A) CAUSE:
 High CV & low ash coal
 Low PA/FD/SA flow
 Sudden change in load
 Ash recirculation system trouble.
 Faulty bed thermocouple
 (B) EFFECT:
 Chances of clinker formation
 Chances of refractory failure.
 Chances of Screen tube failure.
 (C) ACTION:
 Control bed temp. by recirculation of ash.
 Increased PA & SA flow and reduce the load by cutting coal feeder.
 Coal feeder should be trip if bed temp increases beyond 975 deg.c
 If bed temp. exceeds further then allow boiler to trip to avoid clinker formation.
 Check the bed thermocouple.
BED TEMP. LOW
 (A) CAUSE:
 High PA/FD/SA flow w.r.to load.
 Low CV & high Ash content coal used.
 Coal feeder trips or overfeeding of coal in to furnace.
 Faulty bed thermocouples.
 Water /screen/evaporator tube leakage.
 (B) EFFECT:
 Boiler steam flow reduce.
 Super heater temp. drops.
 Furnace draught fluctuates.
 (C)ACTIONS:
 Boiler PA/FD/SA flow reduced if excessive.
 Check bed thermocouple.
 Stop bed material supply, if running.
 Check any leakage sound from furnace.
WATER WALL/SCREEN
TUBE/EVAPORATOR TUBE FAILURE
 (A) CAUSE:
 Starved water wall.
 Block tube ,erode tube, pitted tube, salt deposits.
 (B) EFFECT:
 Hissing steam leakage noise from boilers.
 Unstable flame fluctuating draught.
 Bed temp. drops sharply.
 Increase ID fan loading.
 Flue gas outlet temp. decreased.
 (ACTIONS):
 Take shut down the boiler when boiler tube leakage
noticed and maintain the drum level.
SUPER HEATER TUBE FAILURE
 (A) CAUSE:
 Inadequate steam flow and high gas temp. during hot start-up.
 Erosion of tube due to high excess air.
 Blocked tube.
 Starvation of tube.
 Salt deposition due to high water level in drum.
 (B) EFFECT:
 Hissing noise noticed.
 Flue gas temp drops & high FW consumption than steam..
 Overloading of ID fan.
 (C) ACTIONS:
 As soon as leakage noticed start reducing the load and trip the boiler.
 Try to locate leakage through manholes before the boiler depressurized.
 Boiler is to be forced cooled when S.H. leakage noticed.
HIGH SUPER HEATER TEMP.
 (A) CAUSE:
 High Excess air.
 Low feed water temp or HP heater not in service at constant firing
/load.
 Sudden increase in firing rate to increase steam pressure.
 Inadequate spray water.
 (B) EFFECT:
 +ve turbine expansion.
 Creep rate increase in tube metal ,turbine parts & steam piping.
 (C) ACTIONS:
 Always keep HP heaters in line when optimum loading of TG.
 Slow down firing rate to limit the S.H. Temp.
 Reduce excess air if more.
 Check Spray control.
LOW SUPER HEATER TEMP
 (A) CAUSE:
 Soot deposit on super heater tube.
 Inadequate air flow.
 High spray.
 Sudden increase in load and pressure drops.
 High Drum level.
 (B) EFFECT:
 Turbine expansion may be –ve.
 May induce thermal stresses in S.H.
 (C) ACTIONS:
 Check air flow, increase, if necessary.
 Reduce spray, if more.
 Avoid sudden rise in load to boiler pressure drop.
 Check feed water temp.
FLAME FAILURE
 (A) CAUSE:
 Dirty Oil/gas burner.
 Faulty flame sensor.
 Furnace pressure high.
 Low combustion Air.
 (B) EFFECT:
 Boiler will trip on flame failure.
 Chances of furnace explosion if unburnt oil/gas/coal moisture entered in furnace.
 Steam pressure & temp. may fall.
 Variation in drum level.
 (ACTIONS):
 Purge the boiler putting burner back and purge burner as per cycle time( minimum 5
minutes).
 Check the flame sensor & clean the photocell if found dirty.
 Check the igniter circuit & H.V. transformer .
 Clean the burner tip & nozzles regularly.
 Ensure the healthiness of explosion vent & door.
FURNACE EXPLOSIONS
 (A) CAUSE:
 Accumulation of unburnt fuel during lit up /start up of
boiler.
 Improper burning.
 Inadequate air.
 Secondary combustion.
 (B) EFFECT:
 Furnace explosion can cause extensive damage.
 (C) ACTION:
 Always purge the boiler with min 40% full load air for
about 5 minutes. No cut short in purging allowed.
 Adjust fuel air ratio.
BOILER PRESSURE HIGH
 (A) CAUSE:
 Sudden drop in load/steam flow.
 Uncontrolled fuel entry.
 Turbine/prime mover trips.
 (B) EFFECT:
 Disturbance in drum water level.
 Safety valve may disturbed if pressure rise in frequent way.
 Boiler may trip at high high pressure.
 (C) ACTIONS:
 Open start up vent to control the pressure.
 Control fuel ,air input & drum level.
 If TG /prime mover has tripped first, allow boiler to trip but safety valve may
lift.
 TG warm up vent put in auto, if pressure exceeds then it will open accordingly.
 Use Electromagnetic safety valve to limit the frequent operation of spring
loaded safety valve.
PAH/SAH TUBE FAILURE
 (A) CAUSE:
 Erosion of Air heater tubes.
 Corrosion of Air heater tubes.
 (B) EFFECT:
 Flue gas temp. after APH will fall down.
 Increase in O2% in at Air heater I/L.
 Air heater completely in line during initial start up.
 (C) ACTIONS:
 Control flue gas temp. bypasses PAH.
 Reduce coal feeding /air to maintain O2%.
 If leakages of tubes are more then stop the boiler and plug
that tubes.
COAL FEEDER FAILURE
 (A) CAUSE:
 Electrical supply failed.
 VFD faulty.
 Bed temp.high.
 Furnace draught low.
 Drum level low.
 (B) EFFECT:
 Boiler pressure may fall down.
 Steam temp. fall sharply.
 Bed temp.will decrease.
 Variation in furnace pressure.
 Variation in drum level.
 (C)ACTION:
 Control boiler pressure by reducing the TG load & control S.H. steam temp. by closing
the spray CV.
 Reduce PA/SA air to control bed temp.
 Control furnace draught & drum level.
 Check the electrical fault or emergency stop button.
 Check the VFD fault, if any.
 Restart the coal feeder after detecting the cause of failure.
BOILER FEED PUMP FAILURE
 (A) CAUSE:
 Motor protection relay operates.
 Lube oil temp. high.
 Discharge flow less.
 Motor bearing temp. high
 Deaerator level low.
 BFP Suction DP high.
 (B) EFFECT:
 Stand by pump will start in Auto/manual.
 (C)ACTIONS:
 Start the stand by pump ,if it does not start on auto ,adjust the load to
maintain the drum.
 Analyze and rectify the fault in the main feed pump & put it in auto.
 Check the BFP suction strainer & clean it ,if found chocked.
LOSS OF FANS
 (A)CAUSE:
 Electrical motor protection relay operated.
 Fan bearing temp. becomes high-high.
 Motor bearing temp. becomes very high.
 Drive fault.
 Boiler trip.
 ID fan trips.
 SA trip.
 (B) EFFECT:
 Boiler will trip on.
 Furnace draft either low or high.
 (C)ACTIONS:
 Rectify electrical fault, if any.
 Check cause for boiler trip and normalize it.
 Check fan/motor bearing RTD.
 Restart the fan(ID/FD/SA) after checking the cause of tripping and
taking corrective actions.
EXPLOSIVE POWER OF BOILER
 It will not be false to state that power librated by the
explosion of Lancashire boiler 7.5’ dia x 30’ length,
working at 7 Kg/CM^2 is sufficient to project it to a
height of 3.29 KMS. Therefore hazards of boiler
explosion may well be imagined.
 As a thumb rule, it could be stated that destruction
hazards of 28.3 liters of water at 4.23 Kg/CM2 and
sat.temp in a steam boiler is equivalent to 0.45 Kg of
gun powder.
Introduction to furnace explosions
In CFBC Boilers
 Many CFBC Boilers have suffered/reported furnace
explosion in the past, Apart from causing severe losses to
the business concerned , the occurrences have shaken the
confidence of CPP professionals , however PF boilers are
more prone to the such type explosions than CFBC boiler
but the Operation philosophy of PF boiler is clearly
understood and established due to history of centuries.
 As regards of CFBC boilers, these are completely newer
generation of technology and explosions avoidance
measures are not clearly understood by the operating
Engineers.
TYPE OF EXPLOSIONS IN CFBC
BOILERS
 Most of the explosions faced in CFBC boilers are dust
explosions caused by small particles of coal in the bed
and in the free board kept under suspension by
fluidizing air fans.
 Explosions due to FO/HSD/LDO used in duct burners
and /or load carrying burners has also been reported.
DUST EXPLOSIONS
 A dust explosions is the rapid combustion of a dust cloud .
In a confined or nearly confined space, the explosions is
characterized by relatively rapid development of pressure
with flame propagation and the evolution of large
quantities of heat(coal) and reaction products. The
required oxygen for this combustion is mostly supplied by
the combustion air.
 The condition necessary for a dust explosions is a
simultaneous presence of a dust cloud of proper
concentration in air that will support combustion and
suitable ignition source.(Coal/HSD/LDO/FO).
 Minor flue gas explosions are called puffs or blow backs.
FIRE TRIANGLE AND EXPLOSION
PENTAGON
 There are three necessary elements which must occur simultaneously to cause a fire
FIRE TRIANGLE EXPLOTION PENTAGON
Ignition Source(Coal/LDO/HSD/FO) Coal/LDO/HSD/FO
,Suspension Confinement
Air or Oxygen Heat (Temp.) Air or Oxygen Heat (Temp.)
 On the other hand, for an explosions to occur,5 elements Fuel, heat, Oxygen,
Suspension and confinement must occur simultaneously :.
 These form the five sides of the explosions pentagon like fire triangle, removing any
ignition source one of these requirements would prevent an explosions.
 Remembering the three sides of the fire triangle (Fuel, heat & Oxygen) and five sides of
the explosion pentagon(Fuel, heat, Oxygen, Suspension & Confinement) is important in
preventing fires and explosions at any facility.
 By eliminating the possibility of either suspension or confinement , an explosion can not
occur, but a fire may occur. By eliminating the fuel, the heat ,or the Oxygen
requirements , neither a fire nor an explosion can occur.
BASIC PHILOSPHY OF EXPLOSIONS
PREVENTION
 Basic Principles of avoidance of explosions are:
 Fuel should never fed in to the furnace continuously for than 12
seconds when there is no fire and coal should be added in a small
quantity at ignition temp of coal.
 Furnace is completely purged of the explosive mixture and then
fired.
 Fuel supply should be stopped immediately if fire/flame is not
established and repurging is surely done before restart.
 Correct air fuel ratio is to be maintained so that dust
concentration with explosive limits is never achieved.
 Explosion doors/vents/bleed valve (IN AFBC) must be perfectly
operational and all protections and interlocks and fan drives
sequence to be check in each shutdown as per OEM
schedule/recommendations.
BOILER EXPLOSIONS PICTURES
EXPLOSIONS PICTURES CONT’D
BOILER FURNACE EXPLODED
BOILER STRUCTURES,BUILDINGS, &
CABLE GALLRIES COLLAPSED
THE END

More Related Content

PPTX
Boiler safety protection
PPT
Boiler Operation
PDF
PPTX
Turbine safety protection
PDF
AFBC BOILERS PERFORMANCE IMPROVEMENT
PPTX
Guidelines for storage Handling and Dispensing of CNG.pptx
PPTX
Deaerator
PDF
INSPECTION OF PRESSURE VESSELS TO ASME Section VIII Div. 1.pdf
Boiler safety protection
Boiler Operation
Turbine safety protection
AFBC BOILERS PERFORMANCE IMPROVEMENT
Guidelines for storage Handling and Dispensing of CNG.pptx
Deaerator
INSPECTION OF PRESSURE VESSELS TO ASME Section VIII Div. 1.pdf

What's hot (20)

PPT
Boiler -Emergency Handling
PPT
Boiler efficiency by loss Method
PPTX
Combustion in a CFBC Boiler
PPT
Pre commissioning steam turbines load trial
PDF
CFBC Boiler vs Pulverized Fired Boiler
PDF
Handling of turbine side emergencies
PPTX
Boiler Introduction
PPT
Heat rate audit in thermal power plant
PPTX
Boiler Loss of Flame Protection- MFT
PPT
Energy adudit methodology for boiler
PPT
Unit lightup synchronisation & shutdown
PPT
Factors Affecting Boiler Performance
PPTX
Pulverized coal fired boiler startup procedure
PPT
Boiler commissioning procedure
PDF
Unit shutdown procedure operation
PDF
Training material for air preheater
DOC
Heat rate of coal fired power plant
PPTX
CFBC boiler operation
PPTX
Thermal power plant efficiency
PPTX
Boiler Purging-Logic, Importance & Working
Boiler -Emergency Handling
Boiler efficiency by loss Method
Combustion in a CFBC Boiler
Pre commissioning steam turbines load trial
CFBC Boiler vs Pulverized Fired Boiler
Handling of turbine side emergencies
Boiler Introduction
Heat rate audit in thermal power plant
Boiler Loss of Flame Protection- MFT
Energy adudit methodology for boiler
Unit lightup synchronisation & shutdown
Factors Affecting Boiler Performance
Pulverized coal fired boiler startup procedure
Boiler commissioning procedure
Unit shutdown procedure operation
Training material for air preheater
Heat rate of coal fired power plant
CFBC boiler operation
Thermal power plant efficiency
Boiler Purging-Logic, Importance & Working
Ad

Viewers also liked (12)

PPS
PPS
107 basic instrumentation
PDF
Matematica slides tx2
PPT
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
PPS
Boiler explosion at exxon mobil singapore
PDF
Caldeiras
PPT
Practical Distributed Control Systems (DCS) for Engineers and Technicians
PDF
Dcs course
PPS
Basics Of Instrumentation
PDF
Distributed Control System Basics
107 basic instrumentation
Matematica slides tx2
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
Boiler explosion at exxon mobil singapore
Caldeiras
Practical Distributed Control Systems (DCS) for Engineers and Technicians
Dcs course
Basics Of Instrumentation
Distributed Control System Basics
Ad

Similar to Safe Operation and Explosions in Boilers (20)

PDF
BOILER PRESENTATION ON 21.10.14 1.pdf
PDF
Steam_Boiler_Basics_tim_powell_hughes.pdf
PPT
660 mw supercritical boiler
PDF
Ntpc (national thermal power corporation) sipat boiler haxxo24 i~i
PPTX
steam boilers.pptx
PPT
Thermal Power Plants
PPTX
boilers
PPTX
Boiler thermalpowerplants 12898051220529-phpapp02
PPTX
sugar mill ss.pptx
PPTX
Boiler & co generation presentation finished not yet
PPTX
Boiler & co generation presentation finished not yet
PPTX
Boiler & co generation presentation finished not yet
PPT
PPT on APH BHEL.ppt for power plant personnel
PPT
Thermal Power plant familarisation & its Auxillaries
PPTX
COAL BASED THERMAL POWER PLANTS (UNIT-1).pptx
PPT
Unit II boiloers and its mountings
PPTX
Basic Concepts of a Boiler in powerplant.pptx
PPTX
Unit-II- Steam Generators.pptx
PDF
typesofboilers-140421031520-phpapp01.pdf
BOILER PRESENTATION ON 21.10.14 1.pdf
Steam_Boiler_Basics_tim_powell_hughes.pdf
660 mw supercritical boiler
Ntpc (national thermal power corporation) sipat boiler haxxo24 i~i
steam boilers.pptx
Thermal Power Plants
boilers
Boiler thermalpowerplants 12898051220529-phpapp02
sugar mill ss.pptx
Boiler & co generation presentation finished not yet
Boiler & co generation presentation finished not yet
Boiler & co generation presentation finished not yet
PPT on APH BHEL.ppt for power plant personnel
Thermal Power plant familarisation & its Auxillaries
COAL BASED THERMAL POWER PLANTS (UNIT-1).pptx
Unit II boiloers and its mountings
Basic Concepts of a Boiler in powerplant.pptx
Unit-II- Steam Generators.pptx
typesofboilers-140421031520-phpapp01.pdf

More from National Productivity Council, Hyderabad, India (15)

PDF
New Technologies in Process Heating
PDF
Boiler Water Treatment for LP,MP and HP Boiler
PDF
Efficient steam systems - Generation to WHR
PDF
PDF
PDF
Boiler Superheater Design Modification
PDF
Developments in Industrial Boilers, WHR and Power Boilers
PDF
Indigenization of Russian Make WHR by Vizag Steel
PDF
Online Efficiency Monitoring and Diagnostics in Coal Fired Boiler
PDF
Optimizing Combustion using a Flue Gas Analyser
PDF
PDF
Boiler Operation and Maintenance Experiences
PDF
Minimum Energy Performance Standards for Boilers in India
New Technologies in Process Heating
Boiler Water Treatment for LP,MP and HP Boiler
Efficient steam systems - Generation to WHR
Boiler Superheater Design Modification
Developments in Industrial Boilers, WHR and Power Boilers
Indigenization of Russian Make WHR by Vizag Steel
Online Efficiency Monitoring and Diagnostics in Coal Fired Boiler
Optimizing Combustion using a Flue Gas Analyser
Boiler Operation and Maintenance Experiences
Minimum Energy Performance Standards for Boilers in India

Recently uploaded (20)

PDF
20250617 - IR - Global Guide for HR - 51 pages.pdf
PPTX
Amdahl’s law is explained in the above power point presentations
PPTX
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
PPTX
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
PDF
August 2025 - Top 10 Read Articles in Network Security & Its Applications
PPTX
A Brief Introduction to IoT- Smart Objects: The "Things" in IoT
PDF
Exploratory_Data_Analysis_Fundamentals.pdf
PDF
Unit1 - AIML Chapter 1 concept and ethics
PPTX
Management Information system : MIS-e-Business Systems.pptx
PDF
August -2025_Top10 Read_Articles_ijait.pdf
PDF
Applications of Equal_Area_Criterion.pdf
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PDF
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
PPTX
mechattonicsand iotwith sensor and actuator
PDF
UEFA_Embodied_Carbon_Emissions_Football_Infrastructure.pdf
PDF
distributed database system" (DDBS) is often used to refer to both the distri...
PPTX
ai_satellite_crop_management_20250815030350.pptx
PDF
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
PDF
Implantable Drug Delivery System_NDDS_BPHARMACY__SEM VII_PCI .pdf
PPTX
wireless networks, mobile computing.pptx
20250617 - IR - Global Guide for HR - 51 pages.pdf
Amdahl’s law is explained in the above power point presentations
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
August 2025 - Top 10 Read Articles in Network Security & Its Applications
A Brief Introduction to IoT- Smart Objects: The "Things" in IoT
Exploratory_Data_Analysis_Fundamentals.pdf
Unit1 - AIML Chapter 1 concept and ethics
Management Information system : MIS-e-Business Systems.pptx
August -2025_Top10 Read_Articles_ijait.pdf
Applications of Equal_Area_Criterion.pdf
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
mechattonicsand iotwith sensor and actuator
UEFA_Embodied_Carbon_Emissions_Football_Infrastructure.pdf
distributed database system" (DDBS) is often used to refer to both the distri...
ai_satellite_crop_management_20250815030350.pptx
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
Implantable Drug Delivery System_NDDS_BPHARMACY__SEM VII_PCI .pdf
wireless networks, mobile computing.pptx

Safe Operation and Explosions in Boilers

  • 1. National Workshop on “Efficient Operation and Maintenance of Boilers” organized by National Productivity Council at Visakhapatnam(AP) Presented By: Vikas shrivastava & Akhilesh Tiwari under guidance of Mr. R N Yadav and Mr. A K Saxena From JAYPEE SIDHI CEMENT PLANT , SIDHI,MP
  • 2. EFFICIENT AND SAFE OPERATION OF BOILERS AND PREVENTION OF BOILER EXPLOSION BY JAYPEE SIDHI CEMENT PLANT, SIDHI (M.P.)
  • 3. PARAMETERS REQUIRED TO BE MAINTAINED STRICTLY FOR EFFICIENT OPERATION OF AFBC BOILERS  Bed Height/FD Air Pressure  Primary Air Pressure  Bed Temp./Furnace Temperature  Fuel Size  Bed Material size & Specifications  Air & Fuel ratio
  • 4. BED HEIGHT/FD AIR PRESSURE  Static height for AFBC Boiler is to be maintained 300 to 325 mm during initial light up of boiler.  Expand bed height for AFBC boiler is to be maintained 500 mmwc to 600 mmwc.  FD Air discharge Pressure 600 to 650 mmwc.  Wind box or Air Box pressure 500 to 600 mmwc.  NOTE: High W.B. pressure increases the erosion of bed coils & low W.B. stops fluidization.
  • 5. PRIMARY AIR PRESSURE  P.A. fan air header pressure for AFBC boiler is to be maintained 1000 to 1150 mmwc.  Difference of primary air pressure & F.D. wind box pressure is to be maintained approximately 500 mmwc.  NOTE: High P.A. pressure increases the bed coil erosion and carryover to enhance secondary combustion.
  • 6. BED TEMPERATURE/FURNACE TEMPERATURE FOR AFBC/CFBC  Depends upon the type of fuel & firing method. Indian coal 850 to 900 Deg.C. Imported coal 875 to 925 Deg.C. Lignite fuel 800 to 850 Deg.C. Pet coke 875 to 950 Deg.C.  Rice husk and other biomass fuel 850 to 900 Deg.C.  Stoker firing 1100 to 1200 Deg.C.  Pulverized fuel firing 1100 to 1300 Deg.C.  For oil & gas firing 1100 to 1500 Deg.C.
  • 7. FUEL SIZE  When firing with Indian/Imported coal following sizes are to strictly maintained as it will affect on performance of boiler.  For AFBC/CFBC Size : 0 to 8 mm Less than 1 mm not allowed more than 20%. Distribution: 1 to 5 mm – 70% 5 to 8 mm -20% 0 to 1 mm – 10% NOTE: Lower the size of coal, higher the unburnt in fly ash, higher the size of coal, higher the erosion of bed coils and blockage of fuel air pipe & clinkerization in boiler.
  • 8. FUEL SIZE CONT’D  For STOKER FIRED BOILERS Size: 5 to 25 mm Less than 5 mm not allowed more than 5% Distribution: 5 mm to 15 mm-25% 15 mm to 25 mm-70% 0 mm to 5 mm -5% NOTE: Lower the size of coal higher unburnt in flyash & carryover through boiler.
  • 9. FUEL SIZE CONT’D  PULVARIZED FIRED BOILERS Pulverized coal size: mesh powder  (μm) and, for a bituminous coal Size Distribution: 2% is +300 micro metre (μm) 70-75% is below 75 microns 20% is about 75-100 microns NOTE: Higher the size of pulverized coal below 100 mesh results unburnt in bottom ash.
  • 10. BED MATERIAL SIZE & SPECIFICATION  Bed Material Size: 0.85 mm to 2.36 mm Distribution : 0.85 mm to 1.00 mm – 10% 1.00 mm to 1.50 mm - 50% 1.5 mm to 2.36 mm - 40 %
  • 11. BED MATERIAL SIZE & SPECIFICATION CONT’D  Bed Material Specifications: Crushed fire bricks castables IS8 grade bricks or river silica sand Fusion Temp. 1300 Deg.C Shape: Spherical Angular Bulk Density 1050 Kg/M3 Silica : 65% Al2O3 28% Fe2O3: 1.05% PbO2 1.67 % MnO : Trace MgO 0.23 % P2O5 : 0.08 % V2O 0.22 % K2O : 0.45 %
  • 12. AIR TO FUEL RATIO  Theoretical Air for combustion: Theoretical Air Required: 4.31(8/3C+8(H-O/8)+S) Kg/Kg of fuel burnt.  To Understand the basics of efficient boiler Operation, the combustion process must be understood. Stable combustion condition requires the right amount of fuels and Oxygen, combustion products are heat energy,CO2,water vapour, N2,Sox,Nox and O2. In theory there is a specific amount of O2 needed to completely burn a given amount of fuel. In practice , burning conditions are never ideal, Therefore excess air must be supplied to burn the fuel completely depending upon the type of fuel.
  • 13. TYPICAL EXCESS AIR TO ACHIEVE HIGHEST EFFICIENCY FOR DIFFERENT FUELS  Captive Power plant(Coal) boilers normally run about 15 to 20 %.  Fuel oil fired boilers may run as low as 5 to 10 %.  Natural gas fired boilers may run as low 5 to 8%.  Pulverized coal fired boilers may run about 10 to 15%.
  • 14. OXYGEN AT BOILER OUTLET  To Ensure complete combustion of the fuel used, combustion chambers are supplied with excess air.  Excess air increase the amount of oxygen and the probability of combustion of all fuels.  EA= (O2% /21- O2% )x100  Stoichiometric Combustion  fuel + Oxygen in the air are in perfect balance-.  CO2% or O2% in flue gas is an important indication of the combustion efficiency.
  • 15. BOILER EMERGENCIES  Various Emergencies situations during Operation with a special emphasis on the safety aspect like boiler protection systems controls and interlocks. Drum level low and low-low. Drum level high and high-high. Furnace draught high and high-high. Bed Temp. high. Bed Temp low. Water wall/screen tube/Evaporator tube failure.
  • 16. BOILER EMERGENCIES CONT’D Super heater tube failure. High Super heater Temp. Low Super heater Temp. Flame failure. Furnace Explosion. Boiler pressure high. Coal feeder failure. PAH/SAH tube failure. Boiler feed pump failure. Fan Failure.
  • 17. DRUM LEVEL LOW AND LOW-LOW  (A) CAUSES:  Failure of BFP.  Failure of drum level controllers.  Excess opening of CBD/IBD.  Sudden change in load(sudden red’n in load)  Water tube failure  (B) EFFECT:  Boiler pressure parts may damage badly.  (C) ACTIONS:  Run the boiler if drum level is within safe limit otherwise allow boiler to trip when the water level goes low-low limit to protect the boiler pressure parts.
  • 18. DRUM LEVEL HIGH AND HIGH HIGH  (A) CAUSES:  Failure of drum level controller.  Sudden increase in load.  Sudden increase in firing rate.  (B) EFFECT:  Water may enter in to the turbine and serious damage of turbine blades and thrust pads.  Carry over in Super heater and sharp fall in S.H. temp.  Flange gasket may be failure.  (C) ACTIONS:  Run the boiler if drum level within safe limit and control the FCV.  Open the CBD to maintain drum level in safe limit.  Open the TG side main steam & Turbine drains to avoid the water entering into TG.  Trip the TG when steam temp gets below the safe limit.
  • 19. FURNACE DRAUGHT HIGH AND HIGH HIGH  (A) CAUSE:  Due to faulty operation of fan control.  Disturbed combustion .  Uncontrolled fuel entry.  (B) EFFECT:  Boiler may damage due to high furnace pressure.  Weak part of furnace(ducting & Enclosure)may explode high furnace pressure.  (C) ACTION:  If it is due to faulty operation of ID/FD/PA/SA fan control , take it on manual mode and maintain furnace in suction.  If furnace pressure has increased beyond limit allow boiler to trip on furnace draught high-high.
  • 20. BED TEMP. HIGH  (A) CAUSE:  High CV & low ash coal  Low PA/FD/SA flow  Sudden change in load  Ash recirculation system trouble.  Faulty bed thermocouple  (B) EFFECT:  Chances of clinker formation  Chances of refractory failure.  Chances of Screen tube failure.  (C) ACTION:  Control bed temp. by recirculation of ash.  Increased PA & SA flow and reduce the load by cutting coal feeder.  Coal feeder should be trip if bed temp increases beyond 975 deg.c  If bed temp. exceeds further then allow boiler to trip to avoid clinker formation.  Check the bed thermocouple.
  • 21. BED TEMP. LOW  (A) CAUSE:  High PA/FD/SA flow w.r.to load.  Low CV & high Ash content coal used.  Coal feeder trips or overfeeding of coal in to furnace.  Faulty bed thermocouples.  Water /screen/evaporator tube leakage.  (B) EFFECT:  Boiler steam flow reduce.  Super heater temp. drops.  Furnace draught fluctuates.  (C)ACTIONS:  Boiler PA/FD/SA flow reduced if excessive.  Check bed thermocouple.  Stop bed material supply, if running.  Check any leakage sound from furnace.
  • 22. WATER WALL/SCREEN TUBE/EVAPORATOR TUBE FAILURE  (A) CAUSE:  Starved water wall.  Block tube ,erode tube, pitted tube, salt deposits.  (B) EFFECT:  Hissing steam leakage noise from boilers.  Unstable flame fluctuating draught.  Bed temp. drops sharply.  Increase ID fan loading.  Flue gas outlet temp. decreased.  (ACTIONS):  Take shut down the boiler when boiler tube leakage noticed and maintain the drum level.
  • 23. SUPER HEATER TUBE FAILURE  (A) CAUSE:  Inadequate steam flow and high gas temp. during hot start-up.  Erosion of tube due to high excess air.  Blocked tube.  Starvation of tube.  Salt deposition due to high water level in drum.  (B) EFFECT:  Hissing noise noticed.  Flue gas temp drops & high FW consumption than steam..  Overloading of ID fan.  (C) ACTIONS:  As soon as leakage noticed start reducing the load and trip the boiler.  Try to locate leakage through manholes before the boiler depressurized.  Boiler is to be forced cooled when S.H. leakage noticed.
  • 24. HIGH SUPER HEATER TEMP.  (A) CAUSE:  High Excess air.  Low feed water temp or HP heater not in service at constant firing /load.  Sudden increase in firing rate to increase steam pressure.  Inadequate spray water.  (B) EFFECT:  +ve turbine expansion.  Creep rate increase in tube metal ,turbine parts & steam piping.  (C) ACTIONS:  Always keep HP heaters in line when optimum loading of TG.  Slow down firing rate to limit the S.H. Temp.  Reduce excess air if more.  Check Spray control.
  • 25. LOW SUPER HEATER TEMP  (A) CAUSE:  Soot deposit on super heater tube.  Inadequate air flow.  High spray.  Sudden increase in load and pressure drops.  High Drum level.  (B) EFFECT:  Turbine expansion may be –ve.  May induce thermal stresses in S.H.  (C) ACTIONS:  Check air flow, increase, if necessary.  Reduce spray, if more.  Avoid sudden rise in load to boiler pressure drop.  Check feed water temp.
  • 26. FLAME FAILURE  (A) CAUSE:  Dirty Oil/gas burner.  Faulty flame sensor.  Furnace pressure high.  Low combustion Air.  (B) EFFECT:  Boiler will trip on flame failure.  Chances of furnace explosion if unburnt oil/gas/coal moisture entered in furnace.  Steam pressure & temp. may fall.  Variation in drum level.  (ACTIONS):  Purge the boiler putting burner back and purge burner as per cycle time( minimum 5 minutes).  Check the flame sensor & clean the photocell if found dirty.  Check the igniter circuit & H.V. transformer .  Clean the burner tip & nozzles regularly.  Ensure the healthiness of explosion vent & door.
  • 27. FURNACE EXPLOSIONS  (A) CAUSE:  Accumulation of unburnt fuel during lit up /start up of boiler.  Improper burning.  Inadequate air.  Secondary combustion.  (B) EFFECT:  Furnace explosion can cause extensive damage.  (C) ACTION:  Always purge the boiler with min 40% full load air for about 5 minutes. No cut short in purging allowed.  Adjust fuel air ratio.
  • 28. BOILER PRESSURE HIGH  (A) CAUSE:  Sudden drop in load/steam flow.  Uncontrolled fuel entry.  Turbine/prime mover trips.  (B) EFFECT:  Disturbance in drum water level.  Safety valve may disturbed if pressure rise in frequent way.  Boiler may trip at high high pressure.  (C) ACTIONS:  Open start up vent to control the pressure.  Control fuel ,air input & drum level.  If TG /prime mover has tripped first, allow boiler to trip but safety valve may lift.  TG warm up vent put in auto, if pressure exceeds then it will open accordingly.  Use Electromagnetic safety valve to limit the frequent operation of spring loaded safety valve.
  • 29. PAH/SAH TUBE FAILURE  (A) CAUSE:  Erosion of Air heater tubes.  Corrosion of Air heater tubes.  (B) EFFECT:  Flue gas temp. after APH will fall down.  Increase in O2% in at Air heater I/L.  Air heater completely in line during initial start up.  (C) ACTIONS:  Control flue gas temp. bypasses PAH.  Reduce coal feeding /air to maintain O2%.  If leakages of tubes are more then stop the boiler and plug that tubes.
  • 30. COAL FEEDER FAILURE  (A) CAUSE:  Electrical supply failed.  VFD faulty.  Bed temp.high.  Furnace draught low.  Drum level low.  (B) EFFECT:  Boiler pressure may fall down.  Steam temp. fall sharply.  Bed temp.will decrease.  Variation in furnace pressure.  Variation in drum level.  (C)ACTION:  Control boiler pressure by reducing the TG load & control S.H. steam temp. by closing the spray CV.  Reduce PA/SA air to control bed temp.  Control furnace draught & drum level.  Check the electrical fault or emergency stop button.  Check the VFD fault, if any.  Restart the coal feeder after detecting the cause of failure.
  • 31. BOILER FEED PUMP FAILURE  (A) CAUSE:  Motor protection relay operates.  Lube oil temp. high.  Discharge flow less.  Motor bearing temp. high  Deaerator level low.  BFP Suction DP high.  (B) EFFECT:  Stand by pump will start in Auto/manual.  (C)ACTIONS:  Start the stand by pump ,if it does not start on auto ,adjust the load to maintain the drum.  Analyze and rectify the fault in the main feed pump & put it in auto.  Check the BFP suction strainer & clean it ,if found chocked.
  • 32. LOSS OF FANS  (A)CAUSE:  Electrical motor protection relay operated.  Fan bearing temp. becomes high-high.  Motor bearing temp. becomes very high.  Drive fault.  Boiler trip.  ID fan trips.  SA trip.  (B) EFFECT:  Boiler will trip on.  Furnace draft either low or high.  (C)ACTIONS:  Rectify electrical fault, if any.  Check cause for boiler trip and normalize it.  Check fan/motor bearing RTD.  Restart the fan(ID/FD/SA) after checking the cause of tripping and taking corrective actions.
  • 33. EXPLOSIVE POWER OF BOILER  It will not be false to state that power librated by the explosion of Lancashire boiler 7.5’ dia x 30’ length, working at 7 Kg/CM^2 is sufficient to project it to a height of 3.29 KMS. Therefore hazards of boiler explosion may well be imagined.  As a thumb rule, it could be stated that destruction hazards of 28.3 liters of water at 4.23 Kg/CM2 and sat.temp in a steam boiler is equivalent to 0.45 Kg of gun powder.
  • 34. Introduction to furnace explosions In CFBC Boilers  Many CFBC Boilers have suffered/reported furnace explosion in the past, Apart from causing severe losses to the business concerned , the occurrences have shaken the confidence of CPP professionals , however PF boilers are more prone to the such type explosions than CFBC boiler but the Operation philosophy of PF boiler is clearly understood and established due to history of centuries.  As regards of CFBC boilers, these are completely newer generation of technology and explosions avoidance measures are not clearly understood by the operating Engineers.
  • 35. TYPE OF EXPLOSIONS IN CFBC BOILERS  Most of the explosions faced in CFBC boilers are dust explosions caused by small particles of coal in the bed and in the free board kept under suspension by fluidizing air fans.  Explosions due to FO/HSD/LDO used in duct burners and /or load carrying burners has also been reported.
  • 36. DUST EXPLOSIONS  A dust explosions is the rapid combustion of a dust cloud . In a confined or nearly confined space, the explosions is characterized by relatively rapid development of pressure with flame propagation and the evolution of large quantities of heat(coal) and reaction products. The required oxygen for this combustion is mostly supplied by the combustion air.  The condition necessary for a dust explosions is a simultaneous presence of a dust cloud of proper concentration in air that will support combustion and suitable ignition source.(Coal/HSD/LDO/FO).  Minor flue gas explosions are called puffs or blow backs.
  • 37. FIRE TRIANGLE AND EXPLOSION PENTAGON  There are three necessary elements which must occur simultaneously to cause a fire FIRE TRIANGLE EXPLOTION PENTAGON Ignition Source(Coal/LDO/HSD/FO) Coal/LDO/HSD/FO ,Suspension Confinement Air or Oxygen Heat (Temp.) Air or Oxygen Heat (Temp.)  On the other hand, for an explosions to occur,5 elements Fuel, heat, Oxygen, Suspension and confinement must occur simultaneously :.  These form the five sides of the explosions pentagon like fire triangle, removing any ignition source one of these requirements would prevent an explosions.  Remembering the three sides of the fire triangle (Fuel, heat & Oxygen) and five sides of the explosion pentagon(Fuel, heat, Oxygen, Suspension & Confinement) is important in preventing fires and explosions at any facility.  By eliminating the possibility of either suspension or confinement , an explosion can not occur, but a fire may occur. By eliminating the fuel, the heat ,or the Oxygen requirements , neither a fire nor an explosion can occur.
  • 38. BASIC PHILOSPHY OF EXPLOSIONS PREVENTION  Basic Principles of avoidance of explosions are:  Fuel should never fed in to the furnace continuously for than 12 seconds when there is no fire and coal should be added in a small quantity at ignition temp of coal.  Furnace is completely purged of the explosive mixture and then fired.  Fuel supply should be stopped immediately if fire/flame is not established and repurging is surely done before restart.  Correct air fuel ratio is to be maintained so that dust concentration with explosive limits is never achieved.  Explosion doors/vents/bleed valve (IN AFBC) must be perfectly operational and all protections and interlocks and fan drives sequence to be check in each shutdown as per OEM schedule/recommendations.