SIMATIC
S7 Graph for S7-300/400
Programming Sequential Control Systems
Getting Started Edition 04/2001
First Steps
www.dienhathe.vn
www.dienhathe.com
Copyright © Siemens AG 2001 All rights reserved
The reproduction, transmission or use of this document or its
contents is not permitted without express written authority.
Offenders will be liable for damages. All rights, including rights
created by patent grant or registration of a utility model or design,
are reserved.
Siemens AG
Bereich Automatisierungs- und Antriebstechnik
Geschaeftsgebiet Industrie-Automatisierungssysteme
Postfach 4848, D- 90327 Nuernberg
Disclaimer of Liability
We have checked the contents of this manual for agreement with
the hardware and software described. Since deviations cannot be
precluded entirely, we cannot guarantee full agreement. However,
the data in this manual are reviewed regularly and any necessary
corrections included in subsequent editions. Suggestions for
improvement are welcomed.
©Siemens AG 2001
Technical data subject to change.
Siemens Aktiengesellschaft 6ES7 811-0CC04-8XB0
Safety Guidelines
This manual contains notices intended to ensure personal safety, as well as to protect the products and
connected equipment against damage. These notices are highlighted by the symbols shown below and
graded according to severity by the following texts:
! Danger
indicates that death, severe personal injury or substantial property damage will result if proper
precautions are not taken.
! Warning
indicates that death, severe personal injury or substantial property damage can result if proper
precautions are not taken.
! Caution
indicates that minor personal injury can result if proper precautions are not taken.
Caution
indicates that property damage can result if proper precautions are not taken.
Notice
draws your attention to particularly important information on the product, handling the product, or to a
particular part of the documentation.
Qualified Personnel
Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are
defined as persons who are authorized to commission, to ground and to tag circuits, equipment, and
systems in accordance with established safety practices and standards.
Correct Usage
Note the following:
!
Warning
This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers
which have been approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed
correctly, and operated and maintained as recommended.
Trademarks
SIMATIC®, SIMATIC HMI® and SIMATIC NET® are registered trademarks of SIEMENS AG.
Third parties using for their own purposes any other names in this document which refer to trademarks might
infringe upon the rights of the trademark owners.
www.dienhathe.vn
www.dienhathe.com
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-1
3 Designing a Sequential Control System
Based on the Example of a Drill
Welcome to the S7 Graph Beginner’s Example
If you take an hour to work through the beginner’s example, you will learn how to
create a sequential control system for automating the drill as described below.
You first learn how to configure a sequential control system efficiently and will then
be guided step by step through the tasks you need to perform in the SIMATIC
Manager and in S7 Graph so that you can
• create the sequential control system,
• download it to the CPU and
• test it.
The correctly programmed sample is supplied with S7 Graph as a project called
"ZEn02_01_S7Graph_Drill".
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-2 A5E00105265-01
Requirements
To allow you to program and test the "drill" example, you require the following
hardware and software:
• Programming device/PC with
- STEP 7 standard package and the S7 Graph optional package
- MPI connection to the programmable logic controller
• A programmable logic controller (in our example an S7-300) consisting of the
following: standard rail, 24V power supply, CPU 314, and a digital input/output
module (8DI + 8DO)
• As an alternative to the PLC: The "PLC Simulation" S7 optional package
Procedure for Creating a Sequential Control System
The flow diagram illustrates the procedure for creating the sequential control
system for the drill example:
Create symbol table
Specify structure of sequencer
and define signals for system
Create drill project in the
SIMATIC Manager
Create sequencer:
• create and open S7 Graph FB1 in
the SIMATIC Manager
• Program sequencer
Program OB1 with FB1 call and
corresponding instance DB (DB1)
Download sample program (DB1, FB1,
OB1) to the CPU in the SIMATIC
Manager and test the sequencer
Symbolic
programming
yes
no
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-3
3.1 Technological Task and Functional Diagram
Task
You want to program a sequential control system to automate a drill. The setup of
the drill is shown by a technological drawing and the process sequence in the form
of a function diagram.
Technological Drawing - Set Up of the Drill
The drill consists of the following elements:
• Drill motor with feedback signals for drill running/stopped
• Start button and coolant switch
• Cooling pump with feedback signal for coolant pressure reached
• Clamping device with feedback signal for selected clamp pressure reached
• Carriage raise/lower drill with limit switches for drill up/down
Raise drill
Drill motor on
Feedback signal:
- Drill running
- Drill stopped
Cooling pump on
Feedback signal
Coolant pressure reached
Start button
Feedback signal:
Selected clamping pressure
reached
Limit switch:
Drill up
Limit switch:
Drill down
Coolant switch
Drill motor
Carriage
Clamp deviceCooling pump
Lower drill
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-4 A5E00105265-01
Initial State
The initial state of the drill is defined as follows:
• The drill motor and cooling pump are stopped
• The carriage/drill is in the upper position
• There is no work piece in the clamping device
Functional Diagram - Drilling Sequence
The entire drilling sequence can be divided into the following sections:
• Insert work piece (manual)
• If required, set switch for coolant (depending on the material)
• Start the machine with the start button (drill motor starts up)
• Clamp the work piece with the selected clamp pressure
• Start the cooling pump (if coolant selected)
• Lower drill and carriage to the bottom target position (drill)
• Wait 0.5 seconds at lower target position (drill)
• Raise drill with carriage to upper target position
• Remove work piece, turn off drill motor and cooling pump
• Remove work piece (manual)
Motor
running
stopped
Carriage
up
down
Element State
Clamping
device-
On
Off
Start
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-5
3.2 Selecting the Structure of the Sequencer
Before you create the program for the sequencer, you should include a concept
phase in which you break down the drilling operation into single steps. The basis of
the concept design is the technological drawing and the flowchart.
Dividing the Drilling Process into Individual Steps - Structure of the Sequencer
The drilling process is described by S7 Graph in the form of a sequencer. A
sequencer represents a sequence of single steps and conditions that control how
the process moves on to the next single step. To specify the structure of the
sequencer, follow the steps outlined below:
1. Break down the drilling process into steps and specify the order of the steps
(for example "step S2 follows S1" or "step S3 follows either step S4 or S7").
2. For each step, specify the actions that must be performed in the step (for
example in S1 the action "Drill ready" or in S3 the action "Turn on drill motor").
3. Then decide for every step which conditions must be met so that the process
can move on to the next step (for example for T1 the condition "Drill started -
start button pressed" or for T5 the condition "Drill in upper position").
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-6 A5E00105265-01
T2
S2
T8
T3
T7
S3
S1
T4
T1
T6
S7
S4
Drill ready (initial step)
Clamp work piece
Turn on drill motor
Turn on cooling pump
Lower drill (start drilling)
Drill program started (start button
pressed)
Work piece clamped with selected
pressure
Drill motor running at selected speed
(without coolant)
Coolant pressure reached
Drill in lower position
Drill motor running at selected speed
(with coolant)
S5
S6
T5
T6
S1
Raise drill
Release work piece, turn off drill motor
and cooling pump
Drill in upper position
Work piece is released, cooling
pump stopped, drill motor stopped
Waiting time 500 ms
S = step
T = transition
Monitor clamping
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-7
3.3 Defining the System Signals
Once you have broken down the drilling operation into individual steps, you should
then define the input and output parameters for each step. The basis of the
concept design is the technological drawing and the flowchart.
Defining Inputs and Outputs
List the inputs and outputs for the drill in the form of a table.
If you want to program symbolically, enter the required symbolic names (for
example input I 0.4 "Cl_press_ok") for the absolute inputs and outputs and any
comments that will make the program easier to understand (for example
"Workpiece clamping pressure reached").
In the drill example, it is assumed that the switches and contactors of the drill are
controlled via the inputs and outputs of the digital input/output module of the
S7-300 programmable controller. The input/output module has 8 inputs and 8
outputs. The default values of the input and output addresses of the module
inserted in slot 4 are as follows: I 0 to I 0.7 and Q =0.0 to Q 0.7.
Absolute
Addresses
Symbolic
addresses
Explanation
Inputs in the program (I)
I 0.0 Dr_mot_running Feedback signal for drill running at selected speed
I 0.1 Dr_mot_stopped Feedback signal for drill stopped
I 0.2 Drill_down Limit switch for drill in lower position
I 0.3 Drill_up Limit switch for drill in upper position
I 0.4 Cl_press_ok Feedback signal for work piece clamping pressure
reached
I 0.5 Coolant_sel Selector for coolant (dependent on work piece)
I 0.6 Cool_press_ok Feedback signal for coolant pressure reached
I 0.7 Start_button Start button of the drill
Outputs in the program (Q)
Q 0.0 Dr_mot_on Turn on drill motor
Q 0.1 Cool_pump_on Turn on cooling pump (dependent on work piece)
Q 0.2 Lower_drill Lower drill and carriage to bottom limit position
Q 0.3 Raise_drill Raise drill and carriage to the upper limit position
Q 0.4 Clamp_workp Clamp work piece at required pressure
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-8 A5E00105265-01
3.4 Creating the Drill Project in the SIMATIC Manager
Creating a Project
Projects for sequential control systems do not differ from other projects in STEP 7.
To create a new project in the SIMATIC Manager, follow the steps outlined below:
1. Select the menu command File > New.
2. Name the project "Drill".
Inserting an S7 Program
In this example, hardware configuration is unnecessary since the default
addressing of the input/output module in slot 4 is used. You can therefore
immediately insert an S7 program in the project folder in the SIMATIC Manager.
The S7 program serves as a folder for the blocks of the user program, the source
files and the symbols. Follow the steps below:
1. Select the "Drill" project.
2. Select the menu command Insert > Program > S7 Program.
3. Name the S7 program "Drill Program".
The folders for source files, blocks, and symbols are created automatically when
you insert an S7 program. An empty OB1 is also created in the Blocks folder.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-9
3.5 Creating a Symbol Table
When you program in STEP 7, you work with addresses such as I/O signals,
memory bits, counters, timers, data blocks, and function blocks. You can access
these addresses in your program in absolute format (for example I1.1, M2.0,
FB21).
You will find the program much clearer and easier to read if you use symbols (for
example Motor_A_on) instead of the absolute addresses. To allow the use of
symbols, you can enter a name, the absolute address, the data type and a
comment for every address used.
Once you have defined a symbol, it can be used throughout the entire user
program of a programmable module.
Creating a Symbol Table
If you want to write your program using symbolic addresses, it is advisable to
create the symbol table at this point.
1. Open the symbol table in the "Drill Program" folder by double-clicking
"Symbols".
2. Edit the table as shown below.
3. Save the symbol table using the menu command Table > Save.
The entries 1 to 14 are required for symbolic representation of the inputs and
outputs. The entries 15 to 18 allow symbolic representation of the blocks.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-10 A5E00105265-01
3.6 Creating an S7 Graph FB and Programming a Sequencer
Creating an S7 Graph FB
The S7 Graph FB will contain the sequencer. To create an S7 Graph FB, follow the
steps outlined below:
1. Open the "Blocks" folder in "Drill Program" in the SIMATIC Manager.
2. Select the menu command Insert > S7 Block > Function Block.
3. Set "S7 Graph" as the language in the "Properties" dialog box.
Result: The empty FB with the default number 1 is created in the "Blocks"
folder.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-11
Programming a Sequencer
After you have started the S7 Graph editor by double-clicking FB1 the system
inserts the first step (initial step) and the first transition. It is advisable to create the
structure at the "Sequencer" display level. To display conditions and actions,
activate the View > Display With > Conditions and Actions menu command.
Using the mouse and the "Sequencer" toolbar at the left-hand edge of the screen,
you can then position all the remaining steps and transitions, the alternative
branch and the jump from the end of the sequencer to the start of the sequencer.
There are two ways of doing this and both are illustrated here.
Method 1: "Direct" Mode
1. Select transition 1 and click with the mouse until the icon
insert step + transition
until you arrive at step/transition 6.
2. Select step 3 and then select the icon
open alternative branch.
This opens the alternative branch for supplying coolant. The branch begins
with transition 7.
3. With the mouse, select the icon
insert step + transition,
and insert step 7 (S7) and transition 8 (T8).
4. Select the icon
close alternative branch
and then select transition 3.
5. Now complete the sequencer structure by first selecting transition 6 and then
clicking on the icon
insert jump
and then selecting step 1.
Method 2: "Drag-and-Drop"
1. Return to the SIMATIC Manager and create function block FB2 in the "Blocks"
folder as described above. Once again select "GRAPH" as the source
language.
2. Start the S7 Graph editor by double-clicking FB2 in the "Blocks" folder.
3. Select the menu command Insert > Drag-and-Drop.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-12 A5E00105265-01
4. With the mouse, select the icon
insert step + transition
and then click on the last transition of the individual elements until you arrive at
step/transition 6.
5. Select the icon
open alternative branch
and open the alternative branch for the coolant by clicking on step 3. The
branch begins with transition 7.
6. With the mouse, select the icon
insert step + transition,
to insert step 7 (S7) and transition 8 (T8).
7. Select the icon
close alternative branch
and first select transition 8 and then transition 3.
8. Now complete the sequencer structure with
insert jump
by first selecting transition 6 and then step 1.
Note
Before you start to program step actions, close function block FB2. You only
created this FB to try out the second method of creating a sequencer structure.
When you close the FB, answer all prompts with "No". For the rest of the exercise,
you will be working in FB1.
3.7 Programming Step Actions
There are also two methods available for programming step actions and
transitions: Direct and Drag-and-Drop. The procedure described below assumes
you have selected the menu command Insert > Drag-and-Drop:
1. Select the menu command Insert > .
Result: The mouse pointer then appears as shown below:
2. Insert an empty action line by clicking the action box.
3. Enter the actions.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-13
An action consists of an instruction and an address. For the drill program, four
different instructions are necessary in the steps:
• S Set output
• R Reset output
• N Non holding: As long as the step is active, the signal state of the
address is 1.
• D Delay: The address is set to 1 after the defined time has elapsed
following activation of the step and is reset when the step is deactivated.
3.8 Programming Transitions
The bit logic instructions "normally open contact", "normally closed contact" and
"comparator" are used for the step enabling conditions in the transitions. To
program transitions:
1. Set the "LAD" view and select the appropriate icons in the "LAD/FBD" toolbar
insert normally-open contact
insert normally-closed contact
insert comparator
2. Position the symbols at the appropriate points by clicking the transition lines.
You can exit the insert mode at any time with the ESC key.
3. Enter the addresses. Click the placeholder "??.?" of the required text field.
Then enter an absolute or symbolic address (for example I 0.7, "Start_switch").
4. If you wish, you can also enter a comment for the sequencer. In the
"sequencer" view, the comment field is at the top left and can be opened by
clicking it with the mouse.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-14 A5E00105265-01
The following figure shows the completed sequencer.
GRAPH: Programming s7 Sequential Control Systems - Drill...
File Edit Insert PLC Debug View Options Window Help
Drill
T1
Trans1
T4
Trans4
"Drill_d
own"
S2
Cla...
T2
Trans2
S3
Mo...
T3
Trans3
T7
Trans7
T8
Trans8
Drill_ready
Clamp_on
S "Clamp_workp"
Motor_on
S "Dr_mot_on"
Coolant_on
S "Cool_pump_on"
Lower_drill
N "Lower_drill""
S4
Low...
S7
Coo...
T6
"Start_but
ton"
Clamp_pres
s_ok"
"Drill_moto
r_running"
"Coolant_
sel"
"Cool_pres
s_ok"
S1
Dr...
"Drill_moto
r_running
"
"Coolant_
sel"
S5
Rai...
T5
Trans5
"Drill_up"
"Cl_press
_ok"
T6
Trans6
"Cool_press
_ok"
S6
Cla...
S1
CMP
Term_M_pump_off.T
T#500MS
Raise_drill
D "Raise_drill""
T#500MS
Term_M_pump_off
R ""Clamp_workp"
R "Dr_mot_on"
R "Cool_pump_on"
"Drill_mot
or_stopped
"
>=
When programming comparators, you can use the system information for steps as
the addresses. The addresses have the following significance:
• Step_name.T: current or last activation time of the step
• Step_name.U: current or last activation time of the step without the time of a
disturbance
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-15
3.9 Programming Monitoring Functions
To program monitoring functions:
1. Double-click on step 2 to change from the "sequencer" view to the "single step"
view.
2. Select the icon
insert comparator in the "LAD/FBD" toolbar
3. Position the comparator at the appropriate point on the supervision line and
enter the required monitoring time.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-16 A5E00105265-01
3.10 Specifying the Standard Function Block
Executability of the S7 Graph FB
S7 Graph has two options available for creating FBs.
• Full code:
The entire code required to execute each S7 Graph FB is included in the FB. If
you have several S7 Graph FBs, this means a considerable increase in
memory requirements.
• Standard FC required:
To reduce memory requirements, S7 Graph has the two following alternatives:
You use a standard FC containing the main code sections for all FBs. This FC
is copied to your project automatically when you select this option. The FBs
produced using this method are considerably smaller.
For this example, use the compilation option "Full code".
The most suitable FC depends on the performance of your CPU. Select one of the
following standard FCs:
FC Number Functionality
FC72 As default, you work with FC72. Remember, that your CPU must be capable of processing
blocks with more than 8 Kbytes.
FC70/FC71 These two FCs are less than 8 Kbytes in size and can therefore be loaded on a smaller
CPU. FC70 uses the diagnostic functionality of SFC17/18 and can only be used on CPUs
that have these functions available. If your CPU does not have these functions, you must
use FC71 and do without diagnostic capability.
If you want to check whether or not your CPU contains these SFCs, select the menu
command PLC > Obtainable Nodes in the SIMATIC Manager or click the corresponding
button in the toolbar. Open the "Blocks" folder in the S7 program.
FC73 This block requires less than 8 Kbytes of memory so that it can be executed on all CPUs.
Using this FC considerably reduces the memory requirements of the S7 Graph FBs. You
must also select the option "Interface Description: Memory minimized" in the block
settings.
The following restrictions, do, however, apply:
The blocks created do not have diagnostic capability
When you monitor the sequential control system, you will see the status display only for
the selected active element.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-17
Setting the Executability
Select the menu command Options > Block Settings and specify that the
S7 Graph FB can be executed with a standard FC in the Compile/Save tab. Enter
the FC number that matches the performance of your CPU.
The block is automatically copied to the user project if you select FC70/71, FC72 or
FC73 as the block number and there is not yet an FC with this number in the target
project. If you want to use a different number for the standard block, you must copy
and renumber yourself.
3.11 Saving and Closing the Sequencer
When you save the sequencer, it is automatically compiled.
1. Select the menu command File > Save.
Result: The "Select Instance DB" dialog box is opened with the default instance
DB (DB1).
2. Accept the settings by clicking "OK".
Result: The instance data block is automatically created in the "Blocks" folder.
Note
The warning "S1 without content" in the compiler log simply means that no action
is programmed in step 1.
3. To close the sequencer, select the menu command File > Close.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-18 A5E00105265-01
3.12 Including the Sequencer in the STEP 7 Program
Programming OB1
The sequential control program for the drill is called and started in organization
block OB1. You can create OB1 in LAD, FBD, STL or SCL (here it was created in
LAD). Program OB1 as shown in the following diagram. Follow the steps below:
1. Open the "Blocks" folder in the "Drill Program" S7 program in the SIMATIC
Manager.
2. Start the LAD/STL/FBD editor by double-clicking OB1.
3. With the menu command View, select the programming language LAD.
4. Select segment 1 and insert the sequencer call using the program element
catalog by double-clicking FB1 (Seq_drill).
5. Type in the name of the corresponding instance data block (IDB_Seq_drill)
above the LAD box.
6. Select the input parameter INIT_SQ, insert a normally open element using the
"LAD" toolbar and label it M0.0 ("INIT_SQ"). Using this parameter, you can set
the sequencer to the initial step (in the example step 1) in the online mode.
7. Select the menu command File > Save and close the organization block with
the menu command File > Close.
Note
All other block parameters can be ignored for the example.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-19
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-20 A5E00105265-01
3.13 Downloading the Program to the CPU and Testing the
Sequencer
Downloading the User Program
To allow you to download the program to the CPU, you must download all the
blocks (DB1, FB1, OB1, FC70/71, FC72 and/or. FC73) to the CPU of the
programmable controller in the SIMATIC Manager. Follow the steps outlined below:
1. Open the "Drill Program" S7 program in the SIMATIC Manager and select the
"Blocks" folder.
2. Select the menu command PLC > Download.
Caution
It is best to download the S7 Graph block in the STOP mode since following
downloading of the instance DB, the sequencer is automatically set to the initial
state.
You should only download S7 Graph blocks in the RUN-P mode when the
sequencer is in the initial state or in the OFF state. If you download the blocks the
sequencer in a different state, for example when overwriting an old block,
problems may occur in the synchronization of the sequencer with the process.
Testing the User Program
To test the user program, you require an online connection to a CPU.
3. Open the project window in the SIMATIC Manager.
4. Open the sequencer by double-clicking FB1.
5. Select the menu command Debug > Monitor.
Result: The program status is displayed (the initial step is active). Active steps
are displayed in color.
Caution
A monitoring time is programmed in step 2. If the step activation time exceeds the
configured monitoring time (500 ms) in the supervision condition, the system
recognizes a supervision error and the disturbed step is displayed in red. If a fault
occurs, you must first satisfy the condition for progressing to the next transition.
Using the PG function Debug > Control Sequencer you can then enter an
acknowledgment (see also "Control Sequencer").
This does not apply to the inching mode, since the step enabling condition must
be satisfied and the acknowledgment received within one cycle.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-21
3.14 Test Function: Control Sequencer
Control Sequencer is a test function with which you can test the sequencer in
S7 Graph in all modes. All the settings and entries for the dialog box have the
same effect as the corresponding FB parameters.
The entries in the "Control Sequencer" dialog box can be different from the settings
you used to compile the sequencers. The dialog box settings have priority.
"Control Sequencer" Dialog box
The "Control Sequencer" dialog box is used both as an output field that displays
the current settings and as an input field in which you can change the current
status.
If you acknowledge an error, initialize the sequencer, or want to change the step in
the manual mode, call the dialog box with the menu command Debug > Control
Sequencer.
Acknowledge
If the "Acknowledge errors" option is clicked, you acknowledge a pending error
message with the "Acknowledge" button. In this way, you can acknowledge a
disturbance caused, for example, by the configured monitoring time in Step 2 being
exceeded.
Note, however, that before you acknowledge the error you must make sure that the
supervision or interlock conditions that led to the error are no longer satisfied.
After an error has occurred, you can enable the next step in the sequencer by
satisfying the step enable condition because the last step enable condition in the
cycle in which you acknowledge has priority over the supervision. You must
nevertheless acknowledge the error.
If the error was caused because the undisturbed activation time Step name.U has
exceeded the configured monitoring time, you can move on the sequencer by
clicking the "Acknowledge" button.
This is possible because the Step name.U variable is set to "0" when you
acknowledge.
Initialize
With the "Initialize" button, you can restart the sequencer completely with the
defined initial step.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-22 A5E00105265-01
Setting the Mode
If you click one of the round option buttons, you switch the sequencer to the
selected mode.
You can, for example, run your sequencer in the manual mode instead of the
automatic mode. In the manual mode, you can activate or deactivate any step.
Follow the steps outlined below:
1. Enter the step number of the step you want to process in the "Step number"
box or simply click the required step.
2. Select the action to be executed with the step:
- Activate The selected step is activated even if the preceding transition is
not satisfied.
- Deactivate The selected step is deactivated.
Note that before you activate a step you must first deactivate the currently active
step since only one step can be active at any one time in a linear sequencer. In
other words, you can only activate the required step when you have deactivated
the currently active step.
If you have set a new mode, the original mode is indicated in bold face.
After you have controlled your sequencer in the manual mode, you can return to
the automatic mode and close the "Control Sequencer" dialog box.
3.15 Modifying the Sequencer
Often, a program does not run as required at the first attempt. This means that
changes and modifications are required. This is also the case in our sample
program. The configured monitoring time in Step 2 is too short and the program
hangs at this step. The following section explains how to make the required
changes. You must first change to the "offline" mode.
Modifying the Monitoring Time
The monitoring time configured in Step 2 is 500 ms. To give you more time for
setting the "Cl_press_ok" variable, change the monitoring time to 5 s as explained
below:
1. Double-click on step 2 to change from the "sequencer" view to the "single step"
view.
2. Close the status by selecting the menu command Debug > Monitor or clicking
the following button: .
3. Enter the value 5 s for the monitoring time.
4. Save the sequencer with the menu command File > Save, since the sequencer
must be recompiled.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
A5E00105265-01 3-23
Downloading the Modified Sequencer
Once you have compiled the sequencer, you must download it to the CPU. You
can download the sequencer in the SIMATIC Manager or in the S7 Graph editor. In
the S7 Graph editor, follow the steps outlined below:
1. With the FB open, select the menu command PLC > Download or click on the
Download button . The "Download" dialog box is opened.
2. Accept the defaults by clicking "OK".
3. Confirm the prompt to overwrite the existing blocks.
Include Instance DB
If you have not cleared the system default "Include Instance DB", S7 Graph checks
whether the instance DB has changed since it was last downloaded and whether it
must be updated. The option "Download with Instance DB" is clicked in the
"Download" dialog box.
Otherwise, S7 Graph does not check the instance DB and leaves you to decide
whether or not to download the instance DB again. The option "Download with
Instance DB" is not clicked in the "Download" dialog box.
Restarting the Status
To be able to monitor or control the sequencer again, restart Status by selecting
the menu command Debug > Monitor or by selecting the Monitor button.
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com
Designing a Sequential Control System Based on the Example of a Drill
S7 Graph for S7-300/400 Programming Sequential Control Systems
3-24 A5E00105265-01
05.04.0105.04.200105.04.2001
www.dienhathe.vn
www.dienhathe.com

More Related Content

PDF
96000707 gas-turbine-control
PDF
Siemens PLC Programming Example #2
PDF
Technical manual - Omron
PPT
PLC Training Intro
PDF
Plc analog input output programming
PPT
Automationcontrol3
PPT
Ladder
PDF
Manuale Instatore User Manual
96000707 gas-turbine-control
Siemens PLC Programming Example #2
Technical manual - Omron
PLC Training Intro
Plc analog input output programming
Automationcontrol3
Ladder
Manuale Instatore User Manual

What's hot (20)

PPT
PPI-MECHATRONICS
PPT
Ab PLC Cables Drivers Sample
DOC
Alu design-project
PPTX
speed control of induction motor using plc and vfd
PPT
Digitalinputsoutputs
PPTX
8155 GPPI
PDF
AC Drive VFD - Allen Bradley Powerflex 4M
PPTX
8254 Programmable Interval Timer by vijay
PDF
Project single cyclemips processor_verilog
PPTX
PDF
89c5131datasheet
PDF
Advanced processor and controllers
PPTX
Computer arithmetics (computer organisation & arithmetics) ppt
PPTX
CAM ladder logic diagram
PPT
AVR Fundamentals
PPT
ALU project(segma team)
PPTX
Architecture of 8051
DOCX
32 bit ALU Chip Design using IBM 130nm process technology
PPI-MECHATRONICS
Ab PLC Cables Drivers Sample
Alu design-project
speed control of induction motor using plc and vfd
Digitalinputsoutputs
8155 GPPI
AC Drive VFD - Allen Bradley Powerflex 4M
8254 Programmable Interval Timer by vijay
Project single cyclemips processor_verilog
89c5131datasheet
Advanced processor and controllers
Computer arithmetics (computer organisation & arithmetics) ppt
CAM ladder logic diagram
AVR Fundamentals
ALU project(segma team)
Architecture of 8051
32 bit ALU Chip Design using IBM 130nm process technology
Ad

Similar to Siemens s7 300-400-s7 graph for s7-300 400 programming sequential control systems (20)

PDF
Siemens s7 300-400-s7 graph v5.1 for s7-300 400 programming sequential contro...
PDF
Graph7 e
PDF
Comparison list for Siemens S7-300, S7-400, S7-1200, S7-1500 Reference Manual
PDF
s7_1500_compare_table_en_mnemo.pdf
PDF
Siemens s7 300-400-422rfhcpu-e
PDF
Simens simatic s7 400 cpu
PDF
Simens simatic s7 400 cpu
PDF
Siemens s7 300 module data manual
PDF
manuales y guías PLC siemens Simatic S7
PDF
Siemens s7 300-400-hb-cpu312_ifm_bis_318-2dp_e
PDF
Siemens s7-200 starter kit 221
PDF
Manual del sistema del controlador programable S7-200
PDF
Siemens s7 300-400-hb-cpu31x_c_und_cpu31x_e
PDF
s7300_module_data_manual_en-US_en-US.pdf
PDF
Simatic programming-with-step-7
PDF
Siemens s7 300-400-integrated function mudule
PDF
Sce guide trainer_pakete_en_without_prices
PDF
S7 300 stl_programming_manual
PDF
Siemens s7 300-400-standard software for s7-300 and s7-400 pid control
PDF
Siemens s7 300-400-ncm s7 for industrial ethernet
Siemens s7 300-400-s7 graph v5.1 for s7-300 400 programming sequential contro...
Graph7 e
Comparison list for Siemens S7-300, S7-400, S7-1200, S7-1500 Reference Manual
s7_1500_compare_table_en_mnemo.pdf
Siemens s7 300-400-422rfhcpu-e
Simens simatic s7 400 cpu
Simens simatic s7 400 cpu
Siemens s7 300 module data manual
manuales y guías PLC siemens Simatic S7
Siemens s7 300-400-hb-cpu312_ifm_bis_318-2dp_e
Siemens s7-200 starter kit 221
Manual del sistema del controlador programable S7-200
Siemens s7 300-400-hb-cpu31x_c_und_cpu31x_e
s7300_module_data_manual_en-US_en-US.pdf
Simatic programming-with-step-7
Siemens s7 300-400-integrated function mudule
Sce guide trainer_pakete_en_without_prices
S7 300 stl_programming_manual
Siemens s7 300-400-standard software for s7-300 and s7-400 pid control
Siemens s7 300-400-ncm s7 for industrial ethernet
Ad

More from Dien Ha The (20)

PDF
Vnd feb 2020 price list schneider (1)
PDF
Resize bientanfuji-dienhathe.com
PDF
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
PDF
Fed e-quick-start-manual-bientanfuji-dienhathe.com
PDF
Ls bang gia ls ap dung 20 04-2019
PDF
Mitsubishi graphic operation terminal got2000 series parts library book
PDF
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
PDF
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
PDF
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
PDF
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
PDF
Mitsubishi inverter option catalog
PDF
Mitsubishi low voltage ws-v series mccb and elcb
PDF
Mitsubishi graphic operation terminal got2000 series (concise)
PDF
Mitsubishi low voltage ws-v series comparison of previous and new models
PDF
Mitsubishi inverter inverter family
PDF
Mitsubishi low voltage miniature circuit breakers din series
PDF
Mitsubishi inverter freqrol-hc2 series
PDF
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
PDF
Mitsubishi inverter freqrol-f700 pj series
PDF
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Vnd feb 2020 price list schneider (1)
Resize bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Ls bang gia ls ap dung 20 04-2019
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi inverter option catalog
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi inverter inverter family
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi inverter freqrol-hc2 series
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125

Recently uploaded (20)

PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPTX
Current and future trends in Computer Vision.pptx
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PDF
Well-logging-methods_new................
PPTX
UNIT 4 Total Quality Management .pptx
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PPTX
Artificial Intelligence
PPTX
Geodesy 1.pptx...............................................
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PPTX
Safety Seminar civil to be ensured for safe working.
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
Current and future trends in Computer Vision.pptx
Model Code of Practice - Construction Work - 21102022 .pdf
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
R24 SURVEYING LAB MANUAL for civil enggi
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
Well-logging-methods_new................
UNIT 4 Total Quality Management .pptx
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
CYBER-CRIMES AND SECURITY A guide to understanding
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
Artificial Intelligence
Geodesy 1.pptx...............................................
Automation-in-Manufacturing-Chapter-Introduction.pdf
Safety Seminar civil to be ensured for safe working.

Siemens s7 300-400-s7 graph for s7-300 400 programming sequential control systems

  • 1. First Steps The Getting Started for this product is not a stand-alone description. It is a part of the manual and can be called via "First Steps". SIMATIC S7 Graph for S7-300/400 Programming Sequential Control Systems Getting Started Edition 04/2001 First Steps www.dienhathe.vn www.dienhathe.com
  • 2. Copyright © Siemens AG 2001 All rights reserved The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. Siemens AG Bereich Automatisierungs- und Antriebstechnik Geschaeftsgebiet Industrie-Automatisierungssysteme Postfach 4848, D- 90327 Nuernberg Disclaimer of Liability We have checked the contents of this manual for agreement with the hardware and software described. Since deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual are reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for improvement are welcomed. ©Siemens AG 2001 Technical data subject to change. Siemens Aktiengesellschaft 6ES7 811-0CC04-8XB0 Safety Guidelines This manual contains notices intended to ensure personal safety, as well as to protect the products and connected equipment against damage. These notices are highlighted by the symbols shown below and graded according to severity by the following texts: ! Danger indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken. ! Warning indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken. ! Caution indicates that minor personal injury can result if proper precautions are not taken. Caution indicates that property damage can result if proper precautions are not taken. Notice draws your attention to particularly important information on the product, handling the product, or to a particular part of the documentation. Qualified Personnel Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are defined as persons who are authorized to commission, to ground and to tag circuits, equipment, and systems in accordance with established safety practices and standards. Correct Usage Note the following: ! Warning This device and its components may only be used for the applications described in the catalog or the technical description, and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended. Trademarks SIMATIC®, SIMATIC HMI® and SIMATIC NET® are registered trademarks of SIEMENS AG. Third parties using for their own purposes any other names in this document which refer to trademarks might infringe upon the rights of the trademark owners. www.dienhathe.vn www.dienhathe.com
  • 3. S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-1 3 Designing a Sequential Control System Based on the Example of a Drill Welcome to the S7 Graph Beginner’s Example If you take an hour to work through the beginner’s example, you will learn how to create a sequential control system for automating the drill as described below. You first learn how to configure a sequential control system efficiently and will then be guided step by step through the tasks you need to perform in the SIMATIC Manager and in S7 Graph so that you can • create the sequential control system, • download it to the CPU and • test it. The correctly programmed sample is supplied with S7 Graph as a project called "ZEn02_01_S7Graph_Drill". 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 4. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-2 A5E00105265-01 Requirements To allow you to program and test the "drill" example, you require the following hardware and software: • Programming device/PC with - STEP 7 standard package and the S7 Graph optional package - MPI connection to the programmable logic controller • A programmable logic controller (in our example an S7-300) consisting of the following: standard rail, 24V power supply, CPU 314, and a digital input/output module (8DI + 8DO) • As an alternative to the PLC: The "PLC Simulation" S7 optional package Procedure for Creating a Sequential Control System The flow diagram illustrates the procedure for creating the sequential control system for the drill example: Create symbol table Specify structure of sequencer and define signals for system Create drill project in the SIMATIC Manager Create sequencer: • create and open S7 Graph FB1 in the SIMATIC Manager • Program sequencer Program OB1 with FB1 call and corresponding instance DB (DB1) Download sample program (DB1, FB1, OB1) to the CPU in the SIMATIC Manager and test the sequencer Symbolic programming yes no 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 5. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-3 3.1 Technological Task and Functional Diagram Task You want to program a sequential control system to automate a drill. The setup of the drill is shown by a technological drawing and the process sequence in the form of a function diagram. Technological Drawing - Set Up of the Drill The drill consists of the following elements: • Drill motor with feedback signals for drill running/stopped • Start button and coolant switch • Cooling pump with feedback signal for coolant pressure reached • Clamping device with feedback signal for selected clamp pressure reached • Carriage raise/lower drill with limit switches for drill up/down Raise drill Drill motor on Feedback signal: - Drill running - Drill stopped Cooling pump on Feedback signal Coolant pressure reached Start button Feedback signal: Selected clamping pressure reached Limit switch: Drill up Limit switch: Drill down Coolant switch Drill motor Carriage Clamp deviceCooling pump Lower drill 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 6. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-4 A5E00105265-01 Initial State The initial state of the drill is defined as follows: • The drill motor and cooling pump are stopped • The carriage/drill is in the upper position • There is no work piece in the clamping device Functional Diagram - Drilling Sequence The entire drilling sequence can be divided into the following sections: • Insert work piece (manual) • If required, set switch for coolant (depending on the material) • Start the machine with the start button (drill motor starts up) • Clamp the work piece with the selected clamp pressure • Start the cooling pump (if coolant selected) • Lower drill and carriage to the bottom target position (drill) • Wait 0.5 seconds at lower target position (drill) • Raise drill with carriage to upper target position • Remove work piece, turn off drill motor and cooling pump • Remove work piece (manual) Motor running stopped Carriage up down Element State Clamping device- On Off Start 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 7. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-5 3.2 Selecting the Structure of the Sequencer Before you create the program for the sequencer, you should include a concept phase in which you break down the drilling operation into single steps. The basis of the concept design is the technological drawing and the flowchart. Dividing the Drilling Process into Individual Steps - Structure of the Sequencer The drilling process is described by S7 Graph in the form of a sequencer. A sequencer represents a sequence of single steps and conditions that control how the process moves on to the next single step. To specify the structure of the sequencer, follow the steps outlined below: 1. Break down the drilling process into steps and specify the order of the steps (for example "step S2 follows S1" or "step S3 follows either step S4 or S7"). 2. For each step, specify the actions that must be performed in the step (for example in S1 the action "Drill ready" or in S3 the action "Turn on drill motor"). 3. Then decide for every step which conditions must be met so that the process can move on to the next step (for example for T1 the condition "Drill started - start button pressed" or for T5 the condition "Drill in upper position"). 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 8. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-6 A5E00105265-01 T2 S2 T8 T3 T7 S3 S1 T4 T1 T6 S7 S4 Drill ready (initial step) Clamp work piece Turn on drill motor Turn on cooling pump Lower drill (start drilling) Drill program started (start button pressed) Work piece clamped with selected pressure Drill motor running at selected speed (without coolant) Coolant pressure reached Drill in lower position Drill motor running at selected speed (with coolant) S5 S6 T5 T6 S1 Raise drill Release work piece, turn off drill motor and cooling pump Drill in upper position Work piece is released, cooling pump stopped, drill motor stopped Waiting time 500 ms S = step T = transition Monitor clamping 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 9. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-7 3.3 Defining the System Signals Once you have broken down the drilling operation into individual steps, you should then define the input and output parameters for each step. The basis of the concept design is the technological drawing and the flowchart. Defining Inputs and Outputs List the inputs and outputs for the drill in the form of a table. If you want to program symbolically, enter the required symbolic names (for example input I 0.4 "Cl_press_ok") for the absolute inputs and outputs and any comments that will make the program easier to understand (for example "Workpiece clamping pressure reached"). In the drill example, it is assumed that the switches and contactors of the drill are controlled via the inputs and outputs of the digital input/output module of the S7-300 programmable controller. The input/output module has 8 inputs and 8 outputs. The default values of the input and output addresses of the module inserted in slot 4 are as follows: I 0 to I 0.7 and Q =0.0 to Q 0.7. Absolute Addresses Symbolic addresses Explanation Inputs in the program (I) I 0.0 Dr_mot_running Feedback signal for drill running at selected speed I 0.1 Dr_mot_stopped Feedback signal for drill stopped I 0.2 Drill_down Limit switch for drill in lower position I 0.3 Drill_up Limit switch for drill in upper position I 0.4 Cl_press_ok Feedback signal for work piece clamping pressure reached I 0.5 Coolant_sel Selector for coolant (dependent on work piece) I 0.6 Cool_press_ok Feedback signal for coolant pressure reached I 0.7 Start_button Start button of the drill Outputs in the program (Q) Q 0.0 Dr_mot_on Turn on drill motor Q 0.1 Cool_pump_on Turn on cooling pump (dependent on work piece) Q 0.2 Lower_drill Lower drill and carriage to bottom limit position Q 0.3 Raise_drill Raise drill and carriage to the upper limit position Q 0.4 Clamp_workp Clamp work piece at required pressure 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 10. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-8 A5E00105265-01 3.4 Creating the Drill Project in the SIMATIC Manager Creating a Project Projects for sequential control systems do not differ from other projects in STEP 7. To create a new project in the SIMATIC Manager, follow the steps outlined below: 1. Select the menu command File > New. 2. Name the project "Drill". Inserting an S7 Program In this example, hardware configuration is unnecessary since the default addressing of the input/output module in slot 4 is used. You can therefore immediately insert an S7 program in the project folder in the SIMATIC Manager. The S7 program serves as a folder for the blocks of the user program, the source files and the symbols. Follow the steps below: 1. Select the "Drill" project. 2. Select the menu command Insert > Program > S7 Program. 3. Name the S7 program "Drill Program". The folders for source files, blocks, and symbols are created automatically when you insert an S7 program. An empty OB1 is also created in the Blocks folder. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 11. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-9 3.5 Creating a Symbol Table When you program in STEP 7, you work with addresses such as I/O signals, memory bits, counters, timers, data blocks, and function blocks. You can access these addresses in your program in absolute format (for example I1.1, M2.0, FB21). You will find the program much clearer and easier to read if you use symbols (for example Motor_A_on) instead of the absolute addresses. To allow the use of symbols, you can enter a name, the absolute address, the data type and a comment for every address used. Once you have defined a symbol, it can be used throughout the entire user program of a programmable module. Creating a Symbol Table If you want to write your program using symbolic addresses, it is advisable to create the symbol table at this point. 1. Open the symbol table in the "Drill Program" folder by double-clicking "Symbols". 2. Edit the table as shown below. 3. Save the symbol table using the menu command Table > Save. The entries 1 to 14 are required for symbolic representation of the inputs and outputs. The entries 15 to 18 allow symbolic representation of the blocks. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 12. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-10 A5E00105265-01 3.6 Creating an S7 Graph FB and Programming a Sequencer Creating an S7 Graph FB The S7 Graph FB will contain the sequencer. To create an S7 Graph FB, follow the steps outlined below: 1. Open the "Blocks" folder in "Drill Program" in the SIMATIC Manager. 2. Select the menu command Insert > S7 Block > Function Block. 3. Set "S7 Graph" as the language in the "Properties" dialog box. Result: The empty FB with the default number 1 is created in the "Blocks" folder. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 13. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-11 Programming a Sequencer After you have started the S7 Graph editor by double-clicking FB1 the system inserts the first step (initial step) and the first transition. It is advisable to create the structure at the "Sequencer" display level. To display conditions and actions, activate the View > Display With > Conditions and Actions menu command. Using the mouse and the "Sequencer" toolbar at the left-hand edge of the screen, you can then position all the remaining steps and transitions, the alternative branch and the jump from the end of the sequencer to the start of the sequencer. There are two ways of doing this and both are illustrated here. Method 1: "Direct" Mode 1. Select transition 1 and click with the mouse until the icon insert step + transition until you arrive at step/transition 6. 2. Select step 3 and then select the icon open alternative branch. This opens the alternative branch for supplying coolant. The branch begins with transition 7. 3. With the mouse, select the icon insert step + transition, and insert step 7 (S7) and transition 8 (T8). 4. Select the icon close alternative branch and then select transition 3. 5. Now complete the sequencer structure by first selecting transition 6 and then clicking on the icon insert jump and then selecting step 1. Method 2: "Drag-and-Drop" 1. Return to the SIMATIC Manager and create function block FB2 in the "Blocks" folder as described above. Once again select "GRAPH" as the source language. 2. Start the S7 Graph editor by double-clicking FB2 in the "Blocks" folder. 3. Select the menu command Insert > Drag-and-Drop. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 14. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-12 A5E00105265-01 4. With the mouse, select the icon insert step + transition and then click on the last transition of the individual elements until you arrive at step/transition 6. 5. Select the icon open alternative branch and open the alternative branch for the coolant by clicking on step 3. The branch begins with transition 7. 6. With the mouse, select the icon insert step + transition, to insert step 7 (S7) and transition 8 (T8). 7. Select the icon close alternative branch and first select transition 8 and then transition 3. 8. Now complete the sequencer structure with insert jump by first selecting transition 6 and then step 1. Note Before you start to program step actions, close function block FB2. You only created this FB to try out the second method of creating a sequencer structure. When you close the FB, answer all prompts with "No". For the rest of the exercise, you will be working in FB1. 3.7 Programming Step Actions There are also two methods available for programming step actions and transitions: Direct and Drag-and-Drop. The procedure described below assumes you have selected the menu command Insert > Drag-and-Drop: 1. Select the menu command Insert > . Result: The mouse pointer then appears as shown below: 2. Insert an empty action line by clicking the action box. 3. Enter the actions. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 15. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-13 An action consists of an instruction and an address. For the drill program, four different instructions are necessary in the steps: • S Set output • R Reset output • N Non holding: As long as the step is active, the signal state of the address is 1. • D Delay: The address is set to 1 after the defined time has elapsed following activation of the step and is reset when the step is deactivated. 3.8 Programming Transitions The bit logic instructions "normally open contact", "normally closed contact" and "comparator" are used for the step enabling conditions in the transitions. To program transitions: 1. Set the "LAD" view and select the appropriate icons in the "LAD/FBD" toolbar insert normally-open contact insert normally-closed contact insert comparator 2. Position the symbols at the appropriate points by clicking the transition lines. You can exit the insert mode at any time with the ESC key. 3. Enter the addresses. Click the placeholder "??.?" of the required text field. Then enter an absolute or symbolic address (for example I 0.7, "Start_switch"). 4. If you wish, you can also enter a comment for the sequencer. In the "sequencer" view, the comment field is at the top left and can be opened by clicking it with the mouse. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 16. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-14 A5E00105265-01 The following figure shows the completed sequencer. GRAPH: Programming s7 Sequential Control Systems - Drill... File Edit Insert PLC Debug View Options Window Help Drill T1 Trans1 T4 Trans4 "Drill_d own" S2 Cla... T2 Trans2 S3 Mo... T3 Trans3 T7 Trans7 T8 Trans8 Drill_ready Clamp_on S "Clamp_workp" Motor_on S "Dr_mot_on" Coolant_on S "Cool_pump_on" Lower_drill N "Lower_drill"" S4 Low... S7 Coo... T6 "Start_but ton" Clamp_pres s_ok" "Drill_moto r_running" "Coolant_ sel" "Cool_pres s_ok" S1 Dr... "Drill_moto r_running " "Coolant_ sel" S5 Rai... T5 Trans5 "Drill_up" "Cl_press _ok" T6 Trans6 "Cool_press _ok" S6 Cla... S1 CMP Term_M_pump_off.T T#500MS Raise_drill D "Raise_drill"" T#500MS Term_M_pump_off R ""Clamp_workp" R "Dr_mot_on" R "Cool_pump_on" "Drill_mot or_stopped " >= When programming comparators, you can use the system information for steps as the addresses. The addresses have the following significance: • Step_name.T: current or last activation time of the step • Step_name.U: current or last activation time of the step without the time of a disturbance 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 17. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-15 3.9 Programming Monitoring Functions To program monitoring functions: 1. Double-click on step 2 to change from the "sequencer" view to the "single step" view. 2. Select the icon insert comparator in the "LAD/FBD" toolbar 3. Position the comparator at the appropriate point on the supervision line and enter the required monitoring time. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 18. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-16 A5E00105265-01 3.10 Specifying the Standard Function Block Executability of the S7 Graph FB S7 Graph has two options available for creating FBs. • Full code: The entire code required to execute each S7 Graph FB is included in the FB. If you have several S7 Graph FBs, this means a considerable increase in memory requirements. • Standard FC required: To reduce memory requirements, S7 Graph has the two following alternatives: You use a standard FC containing the main code sections for all FBs. This FC is copied to your project automatically when you select this option. The FBs produced using this method are considerably smaller. For this example, use the compilation option "Full code". The most suitable FC depends on the performance of your CPU. Select one of the following standard FCs: FC Number Functionality FC72 As default, you work with FC72. Remember, that your CPU must be capable of processing blocks with more than 8 Kbytes. FC70/FC71 These two FCs are less than 8 Kbytes in size and can therefore be loaded on a smaller CPU. FC70 uses the diagnostic functionality of SFC17/18 and can only be used on CPUs that have these functions available. If your CPU does not have these functions, you must use FC71 and do without diagnostic capability. If you want to check whether or not your CPU contains these SFCs, select the menu command PLC > Obtainable Nodes in the SIMATIC Manager or click the corresponding button in the toolbar. Open the "Blocks" folder in the S7 program. FC73 This block requires less than 8 Kbytes of memory so that it can be executed on all CPUs. Using this FC considerably reduces the memory requirements of the S7 Graph FBs. You must also select the option "Interface Description: Memory minimized" in the block settings. The following restrictions, do, however, apply: The blocks created do not have diagnostic capability When you monitor the sequential control system, you will see the status display only for the selected active element. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 19. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-17 Setting the Executability Select the menu command Options > Block Settings and specify that the S7 Graph FB can be executed with a standard FC in the Compile/Save tab. Enter the FC number that matches the performance of your CPU. The block is automatically copied to the user project if you select FC70/71, FC72 or FC73 as the block number and there is not yet an FC with this number in the target project. If you want to use a different number for the standard block, you must copy and renumber yourself. 3.11 Saving and Closing the Sequencer When you save the sequencer, it is automatically compiled. 1. Select the menu command File > Save. Result: The "Select Instance DB" dialog box is opened with the default instance DB (DB1). 2. Accept the settings by clicking "OK". Result: The instance data block is automatically created in the "Blocks" folder. Note The warning "S1 without content" in the compiler log simply means that no action is programmed in step 1. 3. To close the sequencer, select the menu command File > Close. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 20. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-18 A5E00105265-01 3.12 Including the Sequencer in the STEP 7 Program Programming OB1 The sequential control program for the drill is called and started in organization block OB1. You can create OB1 in LAD, FBD, STL or SCL (here it was created in LAD). Program OB1 as shown in the following diagram. Follow the steps below: 1. Open the "Blocks" folder in the "Drill Program" S7 program in the SIMATIC Manager. 2. Start the LAD/STL/FBD editor by double-clicking OB1. 3. With the menu command View, select the programming language LAD. 4. Select segment 1 and insert the sequencer call using the program element catalog by double-clicking FB1 (Seq_drill). 5. Type in the name of the corresponding instance data block (IDB_Seq_drill) above the LAD box. 6. Select the input parameter INIT_SQ, insert a normally open element using the "LAD" toolbar and label it M0.0 ("INIT_SQ"). Using this parameter, you can set the sequencer to the initial step (in the example step 1) in the online mode. 7. Select the menu command File > Save and close the organization block with the menu command File > Close. Note All other block parameters can be ignored for the example. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 21. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-19 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 22. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-20 A5E00105265-01 3.13 Downloading the Program to the CPU and Testing the Sequencer Downloading the User Program To allow you to download the program to the CPU, you must download all the blocks (DB1, FB1, OB1, FC70/71, FC72 and/or. FC73) to the CPU of the programmable controller in the SIMATIC Manager. Follow the steps outlined below: 1. Open the "Drill Program" S7 program in the SIMATIC Manager and select the "Blocks" folder. 2. Select the menu command PLC > Download. Caution It is best to download the S7 Graph block in the STOP mode since following downloading of the instance DB, the sequencer is automatically set to the initial state. You should only download S7 Graph blocks in the RUN-P mode when the sequencer is in the initial state or in the OFF state. If you download the blocks the sequencer in a different state, for example when overwriting an old block, problems may occur in the synchronization of the sequencer with the process. Testing the User Program To test the user program, you require an online connection to a CPU. 3. Open the project window in the SIMATIC Manager. 4. Open the sequencer by double-clicking FB1. 5. Select the menu command Debug > Monitor. Result: The program status is displayed (the initial step is active). Active steps are displayed in color. Caution A monitoring time is programmed in step 2. If the step activation time exceeds the configured monitoring time (500 ms) in the supervision condition, the system recognizes a supervision error and the disturbed step is displayed in red. If a fault occurs, you must first satisfy the condition for progressing to the next transition. Using the PG function Debug > Control Sequencer you can then enter an acknowledgment (see also "Control Sequencer"). This does not apply to the inching mode, since the step enabling condition must be satisfied and the acknowledgment received within one cycle. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 23. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-21 3.14 Test Function: Control Sequencer Control Sequencer is a test function with which you can test the sequencer in S7 Graph in all modes. All the settings and entries for the dialog box have the same effect as the corresponding FB parameters. The entries in the "Control Sequencer" dialog box can be different from the settings you used to compile the sequencers. The dialog box settings have priority. "Control Sequencer" Dialog box The "Control Sequencer" dialog box is used both as an output field that displays the current settings and as an input field in which you can change the current status. If you acknowledge an error, initialize the sequencer, or want to change the step in the manual mode, call the dialog box with the menu command Debug > Control Sequencer. Acknowledge If the "Acknowledge errors" option is clicked, you acknowledge a pending error message with the "Acknowledge" button. In this way, you can acknowledge a disturbance caused, for example, by the configured monitoring time in Step 2 being exceeded. Note, however, that before you acknowledge the error you must make sure that the supervision or interlock conditions that led to the error are no longer satisfied. After an error has occurred, you can enable the next step in the sequencer by satisfying the step enable condition because the last step enable condition in the cycle in which you acknowledge has priority over the supervision. You must nevertheless acknowledge the error. If the error was caused because the undisturbed activation time Step name.U has exceeded the configured monitoring time, you can move on the sequencer by clicking the "Acknowledge" button. This is possible because the Step name.U variable is set to "0" when you acknowledge. Initialize With the "Initialize" button, you can restart the sequencer completely with the defined initial step. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 24. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-22 A5E00105265-01 Setting the Mode If you click one of the round option buttons, you switch the sequencer to the selected mode. You can, for example, run your sequencer in the manual mode instead of the automatic mode. In the manual mode, you can activate or deactivate any step. Follow the steps outlined below: 1. Enter the step number of the step you want to process in the "Step number" box or simply click the required step. 2. Select the action to be executed with the step: - Activate The selected step is activated even if the preceding transition is not satisfied. - Deactivate The selected step is deactivated. Note that before you activate a step you must first deactivate the currently active step since only one step can be active at any one time in a linear sequencer. In other words, you can only activate the required step when you have deactivated the currently active step. If you have set a new mode, the original mode is indicated in bold face. After you have controlled your sequencer in the manual mode, you can return to the automatic mode and close the "Control Sequencer" dialog box. 3.15 Modifying the Sequencer Often, a program does not run as required at the first attempt. This means that changes and modifications are required. This is also the case in our sample program. The configured monitoring time in Step 2 is too short and the program hangs at this step. The following section explains how to make the required changes. You must first change to the "offline" mode. Modifying the Monitoring Time The monitoring time configured in Step 2 is 500 ms. To give you more time for setting the "Cl_press_ok" variable, change the monitoring time to 5 s as explained below: 1. Double-click on step 2 to change from the "sequencer" view to the "single step" view. 2. Close the status by selecting the menu command Debug > Monitor or clicking the following button: . 3. Enter the value 5 s for the monitoring time. 4. Save the sequencer with the menu command File > Save, since the sequencer must be recompiled. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 25. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems A5E00105265-01 3-23 Downloading the Modified Sequencer Once you have compiled the sequencer, you must download it to the CPU. You can download the sequencer in the SIMATIC Manager or in the S7 Graph editor. In the S7 Graph editor, follow the steps outlined below: 1. With the FB open, select the menu command PLC > Download or click on the Download button . The "Download" dialog box is opened. 2. Accept the defaults by clicking "OK". 3. Confirm the prompt to overwrite the existing blocks. Include Instance DB If you have not cleared the system default "Include Instance DB", S7 Graph checks whether the instance DB has changed since it was last downloaded and whether it must be updated. The option "Download with Instance DB" is clicked in the "Download" dialog box. Otherwise, S7 Graph does not check the instance DB and leaves you to decide whether or not to download the instance DB again. The option "Download with Instance DB" is not clicked in the "Download" dialog box. Restarting the Status To be able to monitor or control the sequencer again, restart Status by selecting the menu command Debug > Monitor or by selecting the Monitor button. 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com
  • 26. Designing a Sequential Control System Based on the Example of a Drill S7 Graph for S7-300/400 Programming Sequential Control Systems 3-24 A5E00105265-01 05.04.0105.04.200105.04.2001 www.dienhathe.vn www.dienhathe.com