INSTITUTE OF ENGINEERING
PURWANCHAL CAMPUS
DHARAN-8, SUNSARI
NEPAL
A
LAB REPORT
ON
TRANSFORMER DESIGN
Submitted by: Submitted to: Gyan Kafle
Bikash Gyawali (072/BEL/05) Asst. Lecturer
Chet Raj Kandel (072/BEL/09) Department of
Bishop Poudel (072/BEL/07) Electrical Engineering
Akash Pandey (072/BEL/02) Purwanchal Campus Dharan
Designa 1000 KVA, 11/66 kv,50 HZ, 3-phase , Δ/Y , core type, oil immersed natural
cooleddistribution transformer .The transformer is provided with tappings ±𝟐 𝟐
𝟏
% ,
±𝟓 𝟐
𝟏
% on the HV winding. Maximum temperature rise not to exceed40℃.
CORE DESIGN:
For 3-𝜙 core type distribution transformer
We use K=0.45
Voltage per turn Et =k√ 𝑄 =0.45√400 = 9V
∴ Flux in the core 𝜙 𝑚 =
Et
4.44×𝑓
=
9
4.44×50
=0.04054054Wb
Hot rolled silicon steel grade 92 is used
so, the Bm is assumed to be 1.3Wb/m2
Net iron area Ai =
0.04054054
1.3
= 30.1185 × 103mm2
Using cruciform core, Ai = 0.56d2
Diameter of circumscribing circle d = √
30.1185 ×10 3
0.56
= 235mm
a=0.85d = 0.85×235=200mm
b= 0.53d = 0.53 × 235 =125mm
Window Design:
The window space factor for 400 KVA transformer is given by formula
kw =
12
30 +𝐾𝑉
=
12
30+66
= 0.125
Current density (𝛿 ) =1.5 Wb/mm2 (assumed)
Q= 3.33fBmkw 𝛿AwAi× 10 -3
Aw =
Q
3.33f 𝐵 𝑚 𝑘 𝑤 𝛿𝐴𝑖×10 −3 =
Q
3.33 ×50×1×0.125×1.5 ×10 6× 0.04054054 ×10 −3 = 0.20611 m2
Aw =206. 11 × 103 mm2
Hw×Ww = 206. 11 × 103
2.5 W 𝑤
2
= 206. 11 × 103
Ww = 290mm
Hw = 720 mm
Aw = Hw×Ww = 290× 720 = 208×103 mm3
D= Ww+d
= 290+235
= 525 mm
Yoke Design
The area of yoke is taken as 1.2 times that of limb
Flux density in yoke = 1.3/1.2= 1.08 Wb/m2
Net area of yoke = 1.2×31.1185 ×103 mm2 = 37.422×103 mm2
Gross area of the yoke =
37.422×103
0.9
= 41.58 ×103 mm2
Taking the yoke as Dy = a= 200mm
Hy =
41.58×103
𝑎
= 200mm
Overall Dimensions of frame
Height of frame (H) = Hw + 2Hy = 720 + 2×200 = 1120mm
Width of frame W = 2D +a =2× 525 + 200 = 1250mm
Depth of frame = a= 200mm
LV Winding
Star connection
Secondary line voltage = 11kv
Secondary phase voltage Vph =
11 ×1000
√3
= 6350V
Number of turns per phase =Vph/Et =6350/9 = 705
Secondary phase current =
400 ×1000
3×6350
= 21 A
A current density= 2.3 A/mm2
Area of secondary conductor, as =
21
2.3
= 9.13mm2
From the table (IS 1897-1962) using a bare conductor = 6.0 × 1.9 mm2
Area of bare conductor as = 9.29mm2
𝛿s = 21/9.29 = 2.26 A/mm2
The dimensions of insulated conductor = 6.5 × 2.4 mm2
Using 7 layers of helical winding.
The no of turns along axial depth =100+1=101
Axial depth of L.V = 101× 6.5= 656.5mm
Height of window= 720mm
Clearance = (720-656.5)/2 = 31.75mm
Radial depth
bs= no of layers × radial depth of conductor + insulation between layers
= 7× 2.4 +6×0.5 = 19.8 mm
Inside diameter of L.V winding= d+2× insulation = 235+ 2× 1.5 = 238mm
Outside diameter of L.V winding = 238+ 2× 19.8 = 277.6 mm
H.V Winding:
Primary voltage (line) = phase voltage = 66000kV (in delta)
No of turns Tp = 66000/9 = 7334
For 5.5% tapping
Tp max= 1.055 × 7334 = 7737
Using 20 coils,
Turns per coil = 7737/20 = 387
Using 19 normal coils of 392 turns and one reinforced coil of 289 turns
Tp=19× 392+ 289= 7737
Taking 24 layers per coil, we have
Turns per layer = 16
H.V winding phase current Ip =
400×1000
3×6600
= 2.02 A
It is below 21 A so cross over coils are used for H.V winding
Taking current density of 2.4 A/mm2
ap = 2.02/2.4 = 0.841 mm2
Diameter = (
4
𝜋
× 0.841)1/2
Diameter of bare conductor =1.034 mm
Using paper covered conductor of (IS: 1897 -1962)
Bare diameter = 1.06mm and insulated diameter =1.26mm with fine covering
Modified area of conductor=
𝜋
4
× (1.26)2
= 1.25mm2
Actual current density is = 2.02/1.25= 1.616 A/mm2
Axial depth of one coil = 16 × 1.26 = 20.16mm
The spacers used between adjacent coils are 5mm in height.
Axial length of H.V winding = no of coils × axial depth of each coil + depth of spacers
=20× 20.16 + 20× 5 = 503.2 mm
The height of window = 720 mm
The clearance = (720- 503.2)/2 = 108.4 mm
Radial depth of H.V coil bp = 24 × 1.26 + 23 × 0.5 = 41.74mm
The thickness of insulation between H.V and L.V is given by = 5+ 0.9KV = 5+0.9× 66 = 64.4 mm
Inside diameter of H.V winding = outer diameter of L.V + 2× thickness of insulation between L.V and H.V
= 277 + 2× 64.4 = 406 mm
Outside diameter of H.V winding = 406 + 2× 41.74 = 490mm
Clearance between windings of two adjacent limbs = 525mm- 490mm=35mm
Resistance
Mean diameter of primary winding =
406 +490
2
= 448mm
Lmtp = 𝜋 × 448 × 10-3 m = 1.41m
Resistance of primary winding at 75℃ rp =
𝑇𝑝 𝜌×𝐿 𝑚𝑡𝑝
𝑎 𝑝
=
7334×0.021×1.41
1.246
= 174.29 Ω
Mean diameter of secondary winding =
238 +277 .6
2
= 257.8mm
Lmts = 𝜋 × 257.8 × 10-3 m = 0.81m
Resistance of secondary winding at 75℃ rs =
705×0.021 ×0.81
9.29
= 1.29 Ω
Total resistance referred to primary side Rp = 174.29 + (
7334
705
)2 × 1.29 = 313.9Ω
P.U resistance of transformer 𝜀r =
𝐼 𝑝 𝑅 𝑝
𝑉𝑝
=
1.29×313 .9
66000
= 0.00613 Ω
Leakage Reactance
Mean diameter of windings =
238+490
2
= 364mm
Length of mean turn Lmt = 𝜋 × 364 × 10-3 m = 1.143 m
Height of winding Lc =
𝐿 𝑐𝑝+ 𝐿 𝐶𝑠
2
=
503 .2+656.5
2
= 579.85mm
Width of duct, a = (364- 277.6)/2 = 43.2 mm
Leakage reactance of transformer referred to primary side
Xp = 2𝜋f µ0 Tp
2 𝐿 𝑚𝑡
𝐿 𝑐
(a+
𝑏 𝑝+ 𝑏 𝑠
3
)
= 2𝜋 ×50×4 𝜋 × 10−7
× (7334)2 ×
1.206
0.579
(a +
𝑏 𝑝+ 𝑏 𝑠
3
)
= 2𝜋 ×50×4 𝜋 × 10−7
× (7334)2 ×
1.206
0.579
(43 +
41.74+ 19.8
3
) × 10-3
= 2808 Ω
P.U leakage reactance 𝜀x = (2.02 × 2808)/66000 = 0.086
P.U impedance 𝜀s = √0.006132 + 0.0862 = 0.08621
Regulation
P.U regulation 𝜀 = 𝜀r cos ∅ + 𝜀x sin ∅
Per unit regulation at unity power factor 𝜀 = 𝜀r = 0.00613
At zero p.f lagging 𝜀 = 𝜀x = 0.086
At 0.8 pf lagging 𝜀 = 𝜀r cos ∅ + 𝜀x sin ∅ = 0.00613 × 0.8 + 0.086× 0.6 = 0.056504
Losses
Copper loss:
At 75℃ = 3I2
Rp = 3× 2.02 2
× 313.9 = 3842 watt
Taking 15% stray loss = 1.15 × 3842 = 4420 watt
Core loss
Taking the density of laminations = 7.6 × 103
kg/m3
Weight of 3 limbs = 3× Hw × Ai × 7.6 × 103
= 3× 0.72 × 0.0301185 ×7.6 × 103
= 494.42kg
The flux in the limbs is 1.3 Wb/mm2
From the specific core loss is 2.03 W/kg
Therefore core loss in limbs = 494.42 × 2.03 = 1003.67 Watt
Weight of two yoke = 2 × length of yoke × area of the cross section × density of laminations
= 2 × 1.250 × 0.037422× 7.6 × 103
= 711 kg
Corresponding to 1.08 Wb/m2
≈ 1 .0 Wb/ m2
, specific core loss =1.2 W/kg
Therefore core loss in yoke = 711 × 1.2 = 853.2 Watt
Total core loss Pi
=
1003.7+ 853.3 =1856.9 ≈ 1857 watt
Efficiency:
Total losses at full load = Pc + Pi = 4420 + 1857 = 6277 watt
Efficiency at full load and unity power factor =
400×1000
400000+6277
=98.45%
For maximum efficiency, x2
PC = Pi
∴ x =√
1857
4420
= 64.81%
Tank Design
Height of frame H =1120 mm
Allowing for 50 mm for the base and 200 mm for oil
Oil level = 1120 + 50+ 200 = 1370 mm
Allowing another 250 mm for leads etc
Height of tank Ht = 1370 + 250 = 1620 mm
The height of tank is taken as 1.65m
Allowing a clearance of 75 mm along the length
Length of the tank Lt = 2D + De + 2l= 2×525 +490 + 2×75 =1690 mm
The length of tank is taken as 1.7m
The width of the tank Wt = De + 2× clearance = 490 + 2× 90 = 670mm ≈ 0.68m
Loss dissipating surface of the tank St = 2(length + width) × height = 2(1.7 + 0.68) × 1.65=7.854m2
Temperature rise =
total loss
12.5 ×𝑆𝑢𝑟𝑓𝑎𝑐𝑒
=
6277
12.5 ×7.854
= 64℃
So we need to design tank with tubes
TANK WITH TUBES
We have
St be the dissipating surface of the tank
The total heat dissipating by tank walls only = 12.5St W/℃
Let the area of tubes = xSt
Total area of tank walls and tubes = St + xSt = St(1+x)
Loss dissipated =
12.5+8.8x
𝑥+1
W/m2 -℃
Now x=
1
8.8
(
𝑃𝑖 +𝑃𝑐
𝑆𝑡 𝜃
− 12.5) =
1
8.8
(
6277
7.854× 35
− 12.5) = 1.175
Area of tubes = xSt = 1.175 × 7.854 = 9.23 m2
Using 50mm diameter tubes spaced 70 mm apart. The average length of tubes is assumed as
1.4m
Dissipating area of each tubes =𝜋 ×0.05 × 1.4 = 0.22m2
Number of tubes to be provided = 9.23/0.22 = 42
Arrangement of tubes:
Along length – 2 rows 11 and 10 tubes
Design Sheet
KVA rating = 400KVA, Phase = 3-phase, Frequency = 50HZ, Delta/star
line voltage [
𝐻. 𝑉 660000𝑉
𝐿. 𝑉 11000𝑉
] phase voltage[
𝐻. 𝑉 660000𝑉
𝐿. 𝑉 6350𝑉
]
line current [
𝐻. 𝑉 3.5𝐴
𝐿. 𝑉 21𝐴
] phase current [
𝐻. 𝑉 2.02𝐴
𝐿. 𝑉 21𝐴
]
Type – Core Type of cooling: Oil Natural
Core Symbols Quantity
1 Material 0.35 mm thick 92 Grade
2 Output constant k 0.25
3 Voltage constant Et 9V
4 Circumscribing circle diameter d 235mm
5 Number of steps 2
6 Dimensions a= 200 mm, b= 125mm
7 Net iron area Ai 30.1185 × 10 3mm2
8 flux density Bm 1.3Wb/m2
9 flux ɸm 0.04054054Wb
10 Weight 494.42Kg
11 Specific iron loss 2.03 W/kg
12 Iron loss 1003.37W
Yoke
1 Depth of yoke Dy 200mm
2 Height of yoke Hy 200mm
3 Net yoke area 37.422×103 mm2
4 Flux density 1.08 Wb/m2
5 Flux 0.04054054Wb
6 Weight 711 kg
7 Specific iron area 1.2W/kg
8 Iron loss 853.2 W
Windows
1 Number 2
2 Window space factor Kw 1.25
3 Height of window Hw 720mm
4 Width of window Ww 290mm
5 Window area Aw 206. 11 × 103 mm2
Frame
1 Distance between adjacent limbs D 525 mm
2 Height of frame H 1120mm
3 Width of frame W 1250mm
4 Depth of frame Dy 200mm
Figure: Overall dimensions of 400KVA, 66/11KV 3 phase, 50Hz, coretype, distribution
transformer
Windings L.V H.V
1 Type of winding Helical Cross over
2 Connection Star Delta
3 Conductor
Dimensions-bare 6.0 × 1.9 mm2
1.06mm
insulated 6.5 × 2.4 mm2 1.26mm
Area 9.29mm2 1.25mm2
Number in parallel
4 Current density 2.26 A/mm2 1.616 A/mm2
5 Turns per phase 705 7334(7735)at 5.5% tap
6 Coils total number 3 3× 20
per core leg 1 20
7 Turns per coil 705 19 of 392 turns, 1 0f 289
per layer 101 16
8 Number of layers 7 24
9 Height of winding 656.8mm 503.2
10 Width of winding 19.8mm 41.74mm
11 Insulation between layers 0.5mm press board 0.5mm paper
between coils 5.0 spacer
12 Coil diameter inside 238mm 406mm
Outside 277.6mm 490mm
13 Length of mean turn 0.81m 1.41m
14 Resistance at 75°C 1.29 Ω 174.29Ω
Insulation
1 Between L.V winding and core
2 Between L.V winding and H.V winding
3 Width of duct between L.V and H.V
Tank
1 Dimensions- Height Ht 1.65m
Length Lt 1.7m
Width Wt 0.68m
2 Oil level 1.37m
3 Tubes
42 tubes
(11 and 10 in parallel)
4 Temperature 64℃
Impedance
1 P.U Resistance 0.00613
2 P.U Reactance 0.086
3 P.U impedance 0.08621
Losses
1 Total core loss 1857W
2 Total copper loss 4420W
3 Total losses at full load 6277W
4 Efficiency at full load and unity p.f 98.45%

More Related Content

PPTX
Distribution Transformer Design (Electrical Machine Design)
PDF
Setp by step design of transformer
PPTX
Project on Transformer Design | Electrical Machine Design
PDF
A Project on Transformer Design.pdf
PDF
Transformer design principles
PDF
Design of Three Phase 11000/433 V And 100 KVA Transformer
PDF
Industrial Automation
PDF
Tranformer Design
Distribution Transformer Design (Electrical Machine Design)
Setp by step design of transformer
Project on Transformer Design | Electrical Machine Design
A Project on Transformer Design.pdf
Transformer design principles
Design of Three Phase 11000/433 V And 100 KVA Transformer
Industrial Automation
Tranformer Design

What's hot (20)

PDF
Project On Transformer(Distribution) Design
PDF
Transformer Design
PDF
Transformer design-and-design-parameters
PPTX
Transformer design (220-110)V 100 VA
PDF
transformer_design.pdf
PDF
A Design Calculation for Single Phase Step Down Transformer
PDF
11kVby400v, 20kVA three phase core type distribution transformer.
PPTX
Presentation Design of Computer aided design of power transformer
PPTX
Transformer Designing
PDF
Design of transformer
PPTX
Distribution transformer
PPT
Transformer design by s u khaparkar
PDF
Three Phase Induction Motor Design (Electrical Machine Design)
DOCX
Transmission and distribution line design final
PPTX
introduction to power system
PPTX
Electrical Machines - II
PPT
Per unit system
PDF
Principles and Design of LV System
PDF
CVT design
Project On Transformer(Distribution) Design
Transformer Design
Transformer design-and-design-parameters
Transformer design (220-110)V 100 VA
transformer_design.pdf
A Design Calculation for Single Phase Step Down Transformer
11kVby400v, 20kVA three phase core type distribution transformer.
Presentation Design of Computer aided design of power transformer
Transformer Designing
Design of transformer
Distribution transformer
Transformer design by s u khaparkar
Three Phase Induction Motor Design (Electrical Machine Design)
Transmission and distribution line design final
introduction to power system
Electrical Machines - II
Per unit system
Principles and Design of LV System
CVT design
Ad

Similar to Transformer design 2072 batch IOE - TU (20)

PDF
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
PPTX
Electrical Machine design
PPT
Intze Tankd s sad sa das dsjkj kkk kds s kkksk
PPT
Intze Tank.ppt
PDF
Numericals on Columns and struts_-_solved
PDF
Columns and struts_-_solved
PPT
Design of transformer and chock coil
PPT
Design of plate girder by LSM flexural cross section.ppt
PPTX
Designing variable choke coil
PDF
Week 9 Lecture Material_watermark.pdf
PDF
Design of Steel Grillage Foundation for an Auditorium
PPT
Manufacture of nitrobenzene
PDF
Worked example extract_flat_slabs
PDF
Worked example extract_flat_slabs
PDF
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
PDF
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
PDF
Diethyl Ether (DEE): Equipments Design
DOCX
350 kl overhead water intze tank design
DOCX
Structural design of 350 kl overhead water tank at telibagh,lucknow
PPTX
Sums on Rigid Pavement Design
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Electrical Machine design
Intze Tankd s sad sa das dsjkj kkk kds s kkksk
Intze Tank.ppt
Numericals on Columns and struts_-_solved
Columns and struts_-_solved
Design of transformer and chock coil
Design of plate girder by LSM flexural cross section.ppt
Designing variable choke coil
Week 9 Lecture Material_watermark.pdf
Design of Steel Grillage Foundation for an Auditorium
Manufacture of nitrobenzene
Worked example extract_flat_slabs
Worked example extract_flat_slabs
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
Diethyl Ether (DEE): Equipments Design
350 kl overhead water intze tank design
Structural design of 350 kl overhead water tank at telibagh,lucknow
Sums on Rigid Pavement Design
Ad

Recently uploaded (20)

PPTX
bas. eng. economics group 4 presentation 1.pptx
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PDF
PPT on Performance Review to get promotions
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
Geodesy 1.pptx...............................................
PPTX
Current and future trends in Computer Vision.pptx
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PDF
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
PDF
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPTX
OOP with Java - Java Introduction (Basics)
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
bas. eng. economics group 4 presentation 1.pptx
R24 SURVEYING LAB MANUAL for civil enggi
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPT on Performance Review to get promotions
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Geodesy 1.pptx...............................................
Current and future trends in Computer Vision.pptx
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
CYBER-CRIMES AND SECURITY A guide to understanding
Foundation to blockchain - A guide to Blockchain Tech
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
OOP with Java - Java Introduction (Basics)
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026

Transformer design 2072 batch IOE - TU

  • 1. INSTITUTE OF ENGINEERING PURWANCHAL CAMPUS DHARAN-8, SUNSARI NEPAL A LAB REPORT ON TRANSFORMER DESIGN Submitted by: Submitted to: Gyan Kafle Bikash Gyawali (072/BEL/05) Asst. Lecturer Chet Raj Kandel (072/BEL/09) Department of Bishop Poudel (072/BEL/07) Electrical Engineering Akash Pandey (072/BEL/02) Purwanchal Campus Dharan
  • 2. Designa 1000 KVA, 11/66 kv,50 HZ, 3-phase , Δ/Y , core type, oil immersed natural cooleddistribution transformer .The transformer is provided with tappings ±𝟐 𝟐 𝟏 % , ±𝟓 𝟐 𝟏 % on the HV winding. Maximum temperature rise not to exceed40℃. CORE DESIGN: For 3-𝜙 core type distribution transformer We use K=0.45 Voltage per turn Et =k√ 𝑄 =0.45√400 = 9V ∴ Flux in the core 𝜙 𝑚 = Et 4.44×𝑓 = 9 4.44×50 =0.04054054Wb Hot rolled silicon steel grade 92 is used so, the Bm is assumed to be 1.3Wb/m2 Net iron area Ai = 0.04054054 1.3 = 30.1185 × 103mm2 Using cruciform core, Ai = 0.56d2 Diameter of circumscribing circle d = √ 30.1185 ×10 3 0.56 = 235mm a=0.85d = 0.85×235=200mm b= 0.53d = 0.53 × 235 =125mm Window Design: The window space factor for 400 KVA transformer is given by formula kw = 12 30 +𝐾𝑉 = 12 30+66 = 0.125 Current density (𝛿 ) =1.5 Wb/mm2 (assumed) Q= 3.33fBmkw 𝛿AwAi× 10 -3 Aw = Q 3.33f 𝐵 𝑚 𝑘 𝑤 𝛿𝐴𝑖×10 −3 = Q 3.33 ×50×1×0.125×1.5 ×10 6× 0.04054054 ×10 −3 = 0.20611 m2 Aw =206. 11 × 103 mm2 Hw×Ww = 206. 11 × 103 2.5 W 𝑤 2 = 206. 11 × 103 Ww = 290mm Hw = 720 mm Aw = Hw×Ww = 290× 720 = 208×103 mm3 D= Ww+d = 290+235 = 525 mm Yoke Design The area of yoke is taken as 1.2 times that of limb Flux density in yoke = 1.3/1.2= 1.08 Wb/m2 Net area of yoke = 1.2×31.1185 ×103 mm2 = 37.422×103 mm2 Gross area of the yoke = 37.422×103 0.9 = 41.58 ×103 mm2
  • 3. Taking the yoke as Dy = a= 200mm Hy = 41.58×103 𝑎 = 200mm Overall Dimensions of frame Height of frame (H) = Hw + 2Hy = 720 + 2×200 = 1120mm Width of frame W = 2D +a =2× 525 + 200 = 1250mm Depth of frame = a= 200mm LV Winding Star connection Secondary line voltage = 11kv Secondary phase voltage Vph = 11 ×1000 √3 = 6350V Number of turns per phase =Vph/Et =6350/9 = 705 Secondary phase current = 400 ×1000 3×6350 = 21 A A current density= 2.3 A/mm2 Area of secondary conductor, as = 21 2.3 = 9.13mm2 From the table (IS 1897-1962) using a bare conductor = 6.0 × 1.9 mm2 Area of bare conductor as = 9.29mm2 𝛿s = 21/9.29 = 2.26 A/mm2 The dimensions of insulated conductor = 6.5 × 2.4 mm2 Using 7 layers of helical winding. The no of turns along axial depth =100+1=101 Axial depth of L.V = 101× 6.5= 656.5mm Height of window= 720mm Clearance = (720-656.5)/2 = 31.75mm Radial depth bs= no of layers × radial depth of conductor + insulation between layers = 7× 2.4 +6×0.5 = 19.8 mm Inside diameter of L.V winding= d+2× insulation = 235+ 2× 1.5 = 238mm Outside diameter of L.V winding = 238+ 2× 19.8 = 277.6 mm H.V Winding: Primary voltage (line) = phase voltage = 66000kV (in delta) No of turns Tp = 66000/9 = 7334 For 5.5% tapping Tp max= 1.055 × 7334 = 7737 Using 20 coils, Turns per coil = 7737/20 = 387 Using 19 normal coils of 392 turns and one reinforced coil of 289 turns
  • 4. Tp=19× 392+ 289= 7737 Taking 24 layers per coil, we have Turns per layer = 16 H.V winding phase current Ip = 400×1000 3×6600 = 2.02 A It is below 21 A so cross over coils are used for H.V winding Taking current density of 2.4 A/mm2 ap = 2.02/2.4 = 0.841 mm2 Diameter = ( 4 𝜋 × 0.841)1/2 Diameter of bare conductor =1.034 mm Using paper covered conductor of (IS: 1897 -1962) Bare diameter = 1.06mm and insulated diameter =1.26mm with fine covering Modified area of conductor= 𝜋 4 × (1.26)2 = 1.25mm2 Actual current density is = 2.02/1.25= 1.616 A/mm2 Axial depth of one coil = 16 × 1.26 = 20.16mm The spacers used between adjacent coils are 5mm in height. Axial length of H.V winding = no of coils × axial depth of each coil + depth of spacers =20× 20.16 + 20× 5 = 503.2 mm The height of window = 720 mm The clearance = (720- 503.2)/2 = 108.4 mm Radial depth of H.V coil bp = 24 × 1.26 + 23 × 0.5 = 41.74mm The thickness of insulation between H.V and L.V is given by = 5+ 0.9KV = 5+0.9× 66 = 64.4 mm Inside diameter of H.V winding = outer diameter of L.V + 2× thickness of insulation between L.V and H.V = 277 + 2× 64.4 = 406 mm Outside diameter of H.V winding = 406 + 2× 41.74 = 490mm Clearance between windings of two adjacent limbs = 525mm- 490mm=35mm Resistance Mean diameter of primary winding = 406 +490 2 = 448mm Lmtp = 𝜋 × 448 × 10-3 m = 1.41m Resistance of primary winding at 75℃ rp = 𝑇𝑝 𝜌×𝐿 𝑚𝑡𝑝 𝑎 𝑝 = 7334×0.021×1.41 1.246 = 174.29 Ω Mean diameter of secondary winding = 238 +277 .6 2 = 257.8mm Lmts = 𝜋 × 257.8 × 10-3 m = 0.81m Resistance of secondary winding at 75℃ rs = 705×0.021 ×0.81 9.29 = 1.29 Ω Total resistance referred to primary side Rp = 174.29 + ( 7334 705 )2 × 1.29 = 313.9Ω P.U resistance of transformer 𝜀r = 𝐼 𝑝 𝑅 𝑝 𝑉𝑝 = 1.29×313 .9 66000 = 0.00613 Ω
  • 5. Leakage Reactance Mean diameter of windings = 238+490 2 = 364mm Length of mean turn Lmt = 𝜋 × 364 × 10-3 m = 1.143 m Height of winding Lc = 𝐿 𝑐𝑝+ 𝐿 𝐶𝑠 2 = 503 .2+656.5 2 = 579.85mm Width of duct, a = (364- 277.6)/2 = 43.2 mm Leakage reactance of transformer referred to primary side Xp = 2𝜋f µ0 Tp 2 𝐿 𝑚𝑡 𝐿 𝑐 (a+ 𝑏 𝑝+ 𝑏 𝑠 3 ) = 2𝜋 ×50×4 𝜋 × 10−7 × (7334)2 × 1.206 0.579 (a + 𝑏 𝑝+ 𝑏 𝑠 3 ) = 2𝜋 ×50×4 𝜋 × 10−7 × (7334)2 × 1.206 0.579 (43 + 41.74+ 19.8 3 ) × 10-3 = 2808 Ω P.U leakage reactance 𝜀x = (2.02 × 2808)/66000 = 0.086 P.U impedance 𝜀s = √0.006132 + 0.0862 = 0.08621 Regulation P.U regulation 𝜀 = 𝜀r cos ∅ + 𝜀x sin ∅ Per unit regulation at unity power factor 𝜀 = 𝜀r = 0.00613 At zero p.f lagging 𝜀 = 𝜀x = 0.086 At 0.8 pf lagging 𝜀 = 𝜀r cos ∅ + 𝜀x sin ∅ = 0.00613 × 0.8 + 0.086× 0.6 = 0.056504 Losses Copper loss: At 75℃ = 3I2 Rp = 3× 2.02 2 × 313.9 = 3842 watt Taking 15% stray loss = 1.15 × 3842 = 4420 watt Core loss Taking the density of laminations = 7.6 × 103 kg/m3 Weight of 3 limbs = 3× Hw × Ai × 7.6 × 103 = 3× 0.72 × 0.0301185 ×7.6 × 103 = 494.42kg The flux in the limbs is 1.3 Wb/mm2 From the specific core loss is 2.03 W/kg Therefore core loss in limbs = 494.42 × 2.03 = 1003.67 Watt Weight of two yoke = 2 × length of yoke × area of the cross section × density of laminations = 2 × 1.250 × 0.037422× 7.6 × 103 = 711 kg Corresponding to 1.08 Wb/m2 ≈ 1 .0 Wb/ m2 , specific core loss =1.2 W/kg Therefore core loss in yoke = 711 × 1.2 = 853.2 Watt Total core loss Pi = 1003.7+ 853.3 =1856.9 ≈ 1857 watt Efficiency: Total losses at full load = Pc + Pi = 4420 + 1857 = 6277 watt Efficiency at full load and unity power factor = 400×1000 400000+6277 =98.45% For maximum efficiency, x2 PC = Pi
  • 6. ∴ x =√ 1857 4420 = 64.81% Tank Design Height of frame H =1120 mm Allowing for 50 mm for the base and 200 mm for oil Oil level = 1120 + 50+ 200 = 1370 mm Allowing another 250 mm for leads etc Height of tank Ht = 1370 + 250 = 1620 mm The height of tank is taken as 1.65m Allowing a clearance of 75 mm along the length Length of the tank Lt = 2D + De + 2l= 2×525 +490 + 2×75 =1690 mm The length of tank is taken as 1.7m The width of the tank Wt = De + 2× clearance = 490 + 2× 90 = 670mm ≈ 0.68m Loss dissipating surface of the tank St = 2(length + width) × height = 2(1.7 + 0.68) × 1.65=7.854m2 Temperature rise = total loss 12.5 ×𝑆𝑢𝑟𝑓𝑎𝑐𝑒 = 6277 12.5 ×7.854 = 64℃ So we need to design tank with tubes TANK WITH TUBES We have St be the dissipating surface of the tank The total heat dissipating by tank walls only = 12.5St W/℃ Let the area of tubes = xSt Total area of tank walls and tubes = St + xSt = St(1+x) Loss dissipated = 12.5+8.8x 𝑥+1 W/m2 -℃ Now x= 1 8.8 ( 𝑃𝑖 +𝑃𝑐 𝑆𝑡 𝜃 − 12.5) = 1 8.8 ( 6277 7.854× 35 − 12.5) = 1.175 Area of tubes = xSt = 1.175 × 7.854 = 9.23 m2 Using 50mm diameter tubes spaced 70 mm apart. The average length of tubes is assumed as 1.4m Dissipating area of each tubes =𝜋 ×0.05 × 1.4 = 0.22m2 Number of tubes to be provided = 9.23/0.22 = 42 Arrangement of tubes: Along length – 2 rows 11 and 10 tubes Design Sheet KVA rating = 400KVA, Phase = 3-phase, Frequency = 50HZ, Delta/star
  • 7. line voltage [ 𝐻. 𝑉 660000𝑉 𝐿. 𝑉 11000𝑉 ] phase voltage[ 𝐻. 𝑉 660000𝑉 𝐿. 𝑉 6350𝑉 ] line current [ 𝐻. 𝑉 3.5𝐴 𝐿. 𝑉 21𝐴 ] phase current [ 𝐻. 𝑉 2.02𝐴 𝐿. 𝑉 21𝐴 ] Type – Core Type of cooling: Oil Natural Core Symbols Quantity 1 Material 0.35 mm thick 92 Grade 2 Output constant k 0.25 3 Voltage constant Et 9V 4 Circumscribing circle diameter d 235mm 5 Number of steps 2 6 Dimensions a= 200 mm, b= 125mm 7 Net iron area Ai 30.1185 × 10 3mm2 8 flux density Bm 1.3Wb/m2 9 flux ɸm 0.04054054Wb 10 Weight 494.42Kg 11 Specific iron loss 2.03 W/kg 12 Iron loss 1003.37W Yoke 1 Depth of yoke Dy 200mm 2 Height of yoke Hy 200mm 3 Net yoke area 37.422×103 mm2 4 Flux density 1.08 Wb/m2 5 Flux 0.04054054Wb 6 Weight 711 kg 7 Specific iron area 1.2W/kg 8 Iron loss 853.2 W Windows 1 Number 2 2 Window space factor Kw 1.25 3 Height of window Hw 720mm 4 Width of window Ww 290mm 5 Window area Aw 206. 11 × 103 mm2 Frame 1 Distance between adjacent limbs D 525 mm 2 Height of frame H 1120mm 3 Width of frame W 1250mm
  • 8. 4 Depth of frame Dy 200mm Figure: Overall dimensions of 400KVA, 66/11KV 3 phase, 50Hz, coretype, distribution transformer
  • 9. Windings L.V H.V 1 Type of winding Helical Cross over 2 Connection Star Delta 3 Conductor Dimensions-bare 6.0 × 1.9 mm2 1.06mm insulated 6.5 × 2.4 mm2 1.26mm Area 9.29mm2 1.25mm2 Number in parallel 4 Current density 2.26 A/mm2 1.616 A/mm2 5 Turns per phase 705 7334(7735)at 5.5% tap 6 Coils total number 3 3× 20 per core leg 1 20 7 Turns per coil 705 19 of 392 turns, 1 0f 289 per layer 101 16 8 Number of layers 7 24 9 Height of winding 656.8mm 503.2 10 Width of winding 19.8mm 41.74mm 11 Insulation between layers 0.5mm press board 0.5mm paper between coils 5.0 spacer 12 Coil diameter inside 238mm 406mm Outside 277.6mm 490mm 13 Length of mean turn 0.81m 1.41m 14 Resistance at 75°C 1.29 Ω 174.29Ω Insulation 1 Between L.V winding and core 2 Between L.V winding and H.V winding 3 Width of duct between L.V and H.V Tank 1 Dimensions- Height Ht 1.65m Length Lt 1.7m Width Wt 0.68m
  • 10. 2 Oil level 1.37m 3 Tubes 42 tubes (11 and 10 in parallel) 4 Temperature 64℃ Impedance 1 P.U Resistance 0.00613 2 P.U Reactance 0.086 3 P.U impedance 0.08621 Losses 1 Total core loss 1857W 2 Total copper loss 4420W 3 Total losses at full load 6277W 4 Efficiency at full load and unity p.f 98.45%