SlideShare a Scribd company logo
Transformer Calculations
Transformer Overcurrent
Protection
Calculations & Settings
Transformer Overcurrent
Protection
Calculations & Settings
Transformer Calculations
X
XF3
F4
X
X
F1
F2
51
50 51
51G
87T
63
SPR
ANSI / IEEE C37.91
F1: Fault cleared by
transformer primary side
relays
F2: Fault cleared by
transformer primary
side devices or neutral
protection relays
F3: Fault cleared by
transformer primary
side devices or by
secondary side relays
F4: Fault cleared by feeder
protection relays
Transformer Calculations
Transformer Calculations
X
XF3
F4
X
X
F1
F2
50 51
50G 51G
87H87T
50 51
87GD
Current Function
50 – Phase Instantaneous
Overcurrent
51 – Phase Time Overcurrent
Transformer Calculations
Typical Single Line Diagram
Transformer Calculations
1. Instantaneous units should be set so they do not
trip for fault levels equal or lower to those at
busbars or elements protected by downstream
instantaneous relays.
2. Time delay units should be set to clear faults in a
selective and reliable way, assuring the proper
coverage of the thermal limits of the equipment
protected.
Protection Coordinate Principles
Transformer Calculations
R1
CURRENT
t
R2
Coordination
Time Interval
Overcurrent inverse time relay curves associated
with two breakers on the same feeder
Coordination of TOC Delay
Transformer Calculations
A margin between two successive devices in the
order of 0.2 to 0.4 seconds should be used to avoid
losing selectivity due to one or more of the following
reasons:
Instantaneous units should be set so they do not
trip for fault levels equal or lower to those at
busbars or elements protected by downstream
instantaneous relays.
Time delay units should be set to clear faults in a
selective and reliable way, assuring the proper
coverage of the thermal limits of the equipment
protected.
Coordination Time Interval (CTI)
Transformer Calculations
Operating time defined by IEC and ANSI/IEEE:
t = Relay operating time in
seconds
TD = Time dial, or time multiplier
setting
I = Fault current level in
secondary amps
IP = Tap or pick up current
selected
B = Constant
p = Slope constant
A = Slope constant
P
M =
I
I
* IEEE equation constants are defined at TD of 5
=
A
TDt
− 1M
p
IEEE equation *
IEC equation
=t B+
A
− 1M
p
TD
5
Expression for Time Delay Setting
Transformer Calculations
Setting Time Delay on Overcurrent Relays
IDMT Curve Description Standard p A B
Moderately Inverse IEEE 0.02 0.0515 0.114
Very Inverse IEEE 2 19.61 0.491
Extremely Inverse IEEE 2 28.2 0.1217
Standard Inverse IEC 0.02 0.14
Very inverse IEC 1.0 13.5
Extremely inverse IEC 2.0 80.0
ANSI/IEEE and IEC constants for overcurrent relays
* IEEE equation constants are defined at TD of 5
Transformer Calculations
Operatingtime(s)
Current (Multiples of Is)
IEC EI
IEC VI
IEC SI
UK LTI
Current (Multiples of Is)
Operatingtime(s)
IEEE MI
IEEE VI
IEEE EI
US C08
US C02
IEC/UK
overcurrent
relay curves
IEEE/US
overcurrent
relay curves
IEC curves are IMDT
(Inverse Minimum Definite Time)
Standards of Time/Current Characteristics
Transformer Calculations
Dac Y
Dy11
X
X
X
1.0
1.0
1.0 1.0
1.0
1.0
1.0
1.0
1.0
0.58
0.58
0.58
Three phase fault on secondary
I
X
VI LG
F
==
31
2
I
N
N
IIdelta
==
III deltaprimary
== 3
Coordination across D-y Transformer
Transformer Calculations
Dac Y
Dy11
X
X
0.5
1.0
0.5 0.87
0.87
0
0.87
0.87
0
0.5
0.5
0
Phase-to-Phase Fault
I
x
V
X
V
I LG
F
2
3
2
3
2
===
22
3
1
2 I
N
N
IIdelta
=××=
III deltaprimary == 2
LL
Coordination across D-y Transformer
Transformer Calculations
Dac Y
Dy11
X
X
0
0.58
0.58 1.0
0
0
1.0
0
0
0.58
0
0
Phase-to-Ground Fault
3
I
Iprimary
=
31
2
I
N
N
IIdelta
==
I
X
VI LG
F
==
Coordination across D-y Transformer
Transformer Calculations
Fault Iprimary Isecondary
Three phase I I
Phase-to-phase
I 0.87I
Phase-to-earth 0.58I I
For SLGF on wye side, current withstand capability is
58% of that utilized for Delta-Delta
For Phase-Phase Faults on wye side, only 87% fault
current flows in secondary while 100% flows in primary
protector. 16% margin must be taken into account to
maintain primary to secondary protection selectivity.
Coordination across D-y Transformer
Transformer Calculations
A
t
If
2
3
If
0.4 Sec
Coordination of overcurrent relays for a Dy transformer
Coordination across D-y Transformer
Transformer Calculations
Minimum nameplate (kVA)
Category Single-phase Three-phase
I 5-500 15-500
II 501-1667 501-5000
III 1668-10,000 5001-30,000
IV above 10,000 above 30,000
IEEE Std. C57.109-1985 Curves
Transformer Categories
Transformer Calculations
X
XF3
F4
X
X
F1
F2
Infrequent Fault
Incident Zone
Frequent Fault
Incident Zone
Category 2 > 10
Category 3 > 5
Mechanical Damage:
Number Faults in Lifetime
Category II & III Fault Frequency
Transformer Calculations
Category II:
Thermal Limit: I ² t = 1250
Mechanical Limit: I ² t = K = (1/ZT) ² x t
K is determined at t = 2 seconds and at maximum I
in terms of multiples of self-cooled full load current.
The transition from thermal to mechanical plot
occurs at 70% of max possible multiplies of I, or
0.70x(1/ZT)
Category II Transformers
Transformer Calculations
2
Thermal Limit: I t = 1250
Category II – Transformer Through Fault Curves
Transformer Calculations
Thermal Limit: I ² t = 1250
ANSI C57.12 Appendix
Short-time thermal loading capability oil-immersed transformers
Time Multiples of I RATED
2 s 25.0 x
10 s 11.3 x
30 s 6.3 x
60 s 4.75 x
300 s 3.0 x
1800 s 2.0 x
All Category Transformers
Transformer Calculations
Times Normal Base Current
I TN = 16.67 p.u.
Transition from the Mechanical to
Thermal curve occurs at 70% of I TN:
0.70 x (1/ZT) = 11.67 p.u.
I TN = 11.67 p.u.
2
Thermal Limit: I t = 1250
ITN = Times Normal Current
K = I TN = (16.67) x 2 = 556
2
Mechanical Limit: K = I t = (1/ZT) t
defined at t = 2 seconds.
for ZT = 6%
I TN = 1/.06 =16.67 p.u.
2 2
2
t = 556 / (11.67) = 4.0
K = I t = (11.67) x t =5562 2
Wye-Wye or
Delta-Delta
Category II – Transformer Through Fault Curves
Transformer Calculations
Category 3:
Thermal Limit: I 2 t = 1250
Mechanical Limit: I 2 t = K = [ 1 / (ZT + ZS) ]2 x t
K is determined at t = 2 seconds and at maximum I in
terms of multiples of self-cooled full load current. The
transition from thermal to mechanical occurs at 50% of
max possible multiples of I, or
0.50x1/(ZT + ZS)
Category III Transformers
Transformer Calculations
Mechanical to Thermal
occurs at 50% of I TN:
0.50 x 1/(ZT+ ZS) = 7.15 p.u.
I TN = 7.15 p.u.
I TN = 14.3 p.u.
I TN = Times Normal Current
Thermal Limit: I t = 1250
2
K = (I TN) x t = (7.15) x t = 40922
t = 409 / (7.15) = 8.0
2
2
Mechanical Limit
K = I t = [1/ (ZS + ZT)]
defined at t = 2 seconds.
for ZT = 6% & ZS = 1%
K = (I TN) x t = (14.3) x 2 = 40922
I TN = (1/.07) = 14.3 p.u.
Wye-Wye or
Delta-Delta
Category III – Transformer Through Fault Curves
Transformer Calculations
Mechanical to Thermal
occurs at 50% of I TN:
0.50 x 1/(ZT+ ZS) = 7.14 p.u.
Delta-wye:
7.14 p.u. x 0.58 = 4.14 p.u.
I TN = 4.1 p.u.
I TN = 8.3 p.u.
2 2
Mechanical Limit
2
t = 138 / (4.14) = 8.0
I TN = Times Normal Current
Thermal Limit: I t = 1250
2
K = I TN x t = (8.3) x 2 = 138
22
K = I t = [1/ (ZS + ZT)]
defined at t = 2 seconds.
for ZT = 6% & ZS = 1%
I TN = 1/.07 =14.3 p.u.
Delta-wye:
14.3p.u. x 0.58 = 8.3 p.u.
Delta-Wye
Category III – Transformer Through Fault Curves
Transformer Calculations
OFAF (OA/FA/FOA)
30/40/50 MVA
230kV / 34.5 kV
X
X
X
X
F1 F2
F3 F4
Zs230kV
Z= 7%
Calculation Setting Example
Transformer Calculations
0.01 p.u. 0.07 p.u. 4.80 p.u.
VS = 1.0 p.u.
F1
X
F2/F3
X
F4
X
X
F1 ZT
A B
50
X
F3
Vs = 230kV
51
230kV / 34.5kV
30/40/50MVA
Z = 7%
ZLT = 25 MVAZS = 1.0%
on 230kV
ZS = 0.01 p.u.
ZT = 0.07 p.u.
F2
X
F4
X
51
51
50
Z Base =
30MVA
230kV 2
= 1763.3 ohm
ZLT =
25MVA
34.5kV 2
= 47.6 ohms
VBase = 230kV
MVA Base = 30MVA
Z LT at 230kV =
34.5kV
230kV 2
x 47.6 ohms = 2115.6 ohms
Z LT = (2115.6/1763.3) = 1.20 p.u.
ZL4 = 6.25MVA
Z L4 = 4.8 p.u.
ZL4 = 1/4 ZL4
Calculation Setting Example
Transformer Calculations
0.01 p.u. 0.07 p.u. 4.80 p.u.VS = 1.00 p.u. F1
X
F2/F3
X
F4
X
IBase at 230kV =
30MVA
3 x 230kV
= 75.3 A IBase at 34.5kV =
30MVA
3 x 34.5kV
= 502 A
IF1 =
IF2/F3 =
IF4 =
= 100.0 p.u.
= 12.5 p.u.
= 0.205 p.u.
0.01
(0.01 + 0.07)
(0.01 + 0.07 + 4.80)
1.00
1.00
1.00
IF1 = 100.0 x 75.3A = 7530A
12.5 x 75.3A = 941A
0.205 x 502A =103A at 34.5kV
IF4 =
IF2/F3 =
12.5 x 502 = 6275A at 34.5kV
0.205 x 75.3A = 15.4A
Short Circuit Currents
Transformer Calculations
Compatible with transformer overload capacity ≈ 200% of self-
cooled rating for wye CT’s and 350% (√3 x 200%) for Delta-
connected CT’s.
Wye - Wye CT’s:
230kV: IFL = 75.3A IF1 = 7530A
IF1(ASYS) = 1.6 x 7530A = 12,048A
Select CT 600:5 CTR = 120
34.5kV: IFL = 502A IF2 = 6275A
IF2(ASYS) = 1.6 x 6275A = 10,040A
CT Selected at 2 x IFL
Select CT 1000:5 CTR = 200
CT Criteria
Transformer Calculations
Set above Inrush current:
8 x IFL (Transformers 500 to 2500KVA)
10 x IFL (Transformers > 2500KVA) *
Inrush point at 0.1 second
* For Digital Relay using DFT use 5-6 x IFL
Set above maximum asymmetrical secondary fault current:
1.6 x IF SYM for Voltage > 5kV
1.5 x IF SYM for Voltage < 5kV
IOC Setting Criteria
Transformer Calculations
IOC Setting Criteria
Secondary side of transformer
The IOC function at the LV side is not used unless there
is communication (interlocking) with relays protecting
the feeders
Transformer Calculations
Set above Inrush current: ≈ 10 x IFL at 0.1 second.
10 X 73.5A = 735A
Set above maximum asymmetrical secondary fault current:
≈ 1.6 x IF SYM
1.6 x 941 = 1506A = 20.0 x IFL
I PICKUP = 1506A ÷ CTR = 1526A ÷ 120 = 12.65 Amps
IFL =
30MVA
3x 230kV
= 75.3 A IF2/F3 = 954A
IOC Relay Setting
Transformer Calculations
For phase relays, three-phase faults and
maximum short time overload should be
considered
For ground relays, line-to-ground faults and max
3Io should be considered
TOC Setting Criteria
Transformer Calculations
For phase relays, the Pickup value is determined by:
Pickup = (OLF x IFL) ÷ CTR
For ground fault relays, the Pickup value is determined,
with the maximum unbalance, typically around 20%:
Pickup = [(0.2) x IFL] ÷ CTR
Typical OLF for transformers = 1.25 to 1.5
TOC Setting Criteria
Transformer Calculations
Transformer: ZT < 6%
Primary Setting < 6 x IFL
Secondary Setting < 3 x IFL
Transformer: 6% > ZT < 10%
Primary Setting < 4 x IFL
Secondary Setting < 2.5 x IFL
Tap is set to meet NEC 450-3 and ANSI C37.91*
* Primary & secondary >600V with circuit breakers
TOC Setting Criteria
Transformer Calculations
Pickup = OLF x IFL ÷ CTR
I Pickup = 1.5 x 75.3 ÷ 120 = 0.94 Amps
I Relay setting = 0.94 ÷ 1.5 = 0.63 Amps
TD # 8 Very Inverse Curve
IFL =
30MVA
3x 230kV
= 75.3 A IF2/F3 = 954A
TOC Relay Setting
Transformer Calculations
I RELAY = 0.63 Amps
TD # 8
Very Inverse Curve
TOC Relay Curve
Transformer Calculations
50% of I TN = 0.50 x 1/(ZT+ ZS)
t = 105.1 / (3.625) = 8.0
I TN = Times Normal Current
Thermal Limit: I t = 1250
2
Mechanical Limit
K = I TN = (7.6) x 2 = 105.1
2
defined at t = 2 seconds.
for ZT = 7% & ZS = 1.0%
I TN = 1/.08 =12.5 p.u.
Delta-wye:
2 2
K = I t = [1/ (ZS + ZT)] x t
58% x 12.5 p.u. = 7.25 p.u.
Mechanical to Thermal
Delta-wye:
50% of I TN = 0.50 x 12.5 = 6.25 p.u.
58% x 6.25 p.u. = 3.625 p.u.
IOC set at 12.6A pickup
1.6 x IFL/CTR = 1.6 x 941/120 = 12.6A
1.6 x IFL =1.6 x 12.5p.u. = 20.0 ITN
TOC set at 0.63A pickup
1.5 x ITN/CTR = 1.5 x 73.5A/120 = 0.94A
Minimum multiple of pickup is 1.5
0.94A/1.5 = 0.63A, TD#8
Very Inverse TOC curve
0
0
1
10
100
1000
10000
0 1 10 100
TIMES NORMAL BASE CURRENT
TIME(SECONDS)
IFLSYM
IFL
I inrush
0.1
0.01
0.1
2.5xIFL
4.0xIFL
IFLASYM
2
IFL SYM
3-phase
IFL SYM
phase-phase
Coordination
Interval
50/51
51
50/51
51
2
IOC & TOC Coordination
Transformer Calculations
Questions ?Questions ?
©2008 Beckwith Electric Co., Inc.

More Related Content

PDF
Relay Setting Calculation For REF615/ REJ601
PPTX
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
PDF
Transformer differential protection
PDF
Practical handbook-for-relay-protection-engineers
PDF
Power transformer protection
PDF
Tutorial on Distance and Over Current Protection
PPTX
Stability test of transformer
PDF
Bus Bar protection
Relay Setting Calculation For REF615/ REJ601
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
Transformer differential protection
Practical handbook-for-relay-protection-engineers
Power transformer protection
Tutorial on Distance and Over Current Protection
Stability test of transformer
Bus Bar protection

What's hot (20)

PDF
Sample calculation-for-differential-relays
PPTX
Power Transformer Protection
PDF
Generator protection calculations settings
PDF
Transformer & OLTC
PPTX
Lecture 7 Relay Coordination.pptx
ODP
Transformers protection, an introduction
PPTX
Current Transformer.pptx
PDF
Overcurrent protection
PDF
Transformer testing on sight and off sight
PPTX
Generator Protection
PDF
LBB & BUSBAR PPT Rev 4.5.pdf
PDF
Power system protection topic 1
PPT
Transformer design and protection
PPTX
protection of transformer
PPTX
Generator protection
PDF
Generator Protection By - Er Rahul Sharma
PDF
Transformer testing
PDF
Transformer protection
PPTX
On load tap changer
PPTX
Switchgear - complete guide
Sample calculation-for-differential-relays
Power Transformer Protection
Generator protection calculations settings
Transformer & OLTC
Lecture 7 Relay Coordination.pptx
Transformers protection, an introduction
Current Transformer.pptx
Overcurrent protection
Transformer testing on sight and off sight
Generator Protection
LBB & BUSBAR PPT Rev 4.5.pdf
Power system protection topic 1
Transformer design and protection
protection of transformer
Generator protection
Generator Protection By - Er Rahul Sharma
Transformer testing
Transformer protection
On load tap changer
Switchgear - complete guide
Ad

Viewers also liked (12)

PDF
Scheme logic implement pwr plant cntrl
PDF
Interconnet protection of
PDF
oshpd emergency power supply systems
PDF
Out of step
PDF
Ieee pes psrc
PDF
Upgrading gen protect and grounding
PDF
Digital transformer protection systems
PDF
Auto synch considerations methods
PDF
Transformer protection commissioning tools
PDF
Automatic synch of gen
PDF
Selective Coodination
PDF
Generator basic concepts
Scheme logic implement pwr plant cntrl
Interconnet protection of
oshpd emergency power supply systems
Out of step
Ieee pes psrc
Upgrading gen protect and grounding
Digital transformer protection systems
Auto synch considerations methods
Transformer protection commissioning tools
Automatic synch of gen
Selective Coodination
Generator basic concepts
Ad

Similar to Transformer overcurrent (20)

PPT
5010566.ppt
PDF
Overcurrent coordination
PDF
Short circuit calculations
PDF
3_Overcurrent Protection.pdf
PDF
TR Protection relay testing with details Abb
PDF
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
PDF
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
PPT
Current-Transformer-ppt.ppt
PPT
180953548-Current-Transformer-ppt.ppt
PDF
ETAP - Coordination and protecion
DOC
Transformerprotectionrelaycalculations.doc
PPT
03-Non-Dir. Overcurrent.ppt
PDF
IRJET- Numerical Differential Protection of 220/132KV, 250 MVA Auto Transform...
PPTX
Differential protection of power transformer
DOCX
1. Determine the voltage drop at the motor frame for an earth .docx
PPSX
ECNG 6503 #2
PDF
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
PDF
Current Transformers parameter design and graphs - size and design requirements
PDF
05-Transformer protection system and.pdf
PPT
Electrical Protection systems Circuit breakers
5010566.ppt
Overcurrent coordination
Short circuit calculations
3_Overcurrent Protection.pdf
TR Protection relay testing with details Abb
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
Current-Transformer-ppt.ppt
180953548-Current-Transformer-ppt.ppt
ETAP - Coordination and protecion
Transformerprotectionrelaycalculations.doc
03-Non-Dir. Overcurrent.ppt
IRJET- Numerical Differential Protection of 220/132KV, 250 MVA Auto Transform...
Differential protection of power transformer
1. Determine the voltage drop at the motor frame for an earth .docx
ECNG 6503 #2
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Current Transformers parameter design and graphs - size and design requirements
05-Transformer protection system and.pdf
Electrical Protection systems Circuit breakers

More from michaeljmack (20)

PDF
Auburn, NY - 200 Years of History 1793-1993
PDF
Auburn High School, Auburn, NY, 1982 Yearbook
PDF
Auburn High School, Auburn, NY, 1980 Yearbook
PDF
Surge Protection
PDF
Diesel Particulate Filters Control Systems
PDF
Understanding Arc Flash
PDF
Siemens MV GIS Switchgear
PDF
Fundamentals of transformer inrush
PDF
Building information modeling
PDF
15 years of experience stator ground fault protection
PPT
Emergency, Legally Required and Optional Standby Systems
PDF
Lighting Control Solutions for Daylit Spaces
PDF
COPS: An Arresting Look at NEC Article 708
PDF
Seismic Compliance of Electrical Distribution
PDF
Generator Set Transient Performance
PDF
Modeling of a digital protective relay in a RT Digital Simulator
PDF
Facts on Grid Friendly Wind Plants
PDF
Power Plant Horror Stories
PDF
Blackout Avoidance & Undervoltage Load Shedding
PDF
Transformer Fundamentals
Auburn, NY - 200 Years of History 1793-1993
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
Surge Protection
Diesel Particulate Filters Control Systems
Understanding Arc Flash
Siemens MV GIS Switchgear
Fundamentals of transformer inrush
Building information modeling
15 years of experience stator ground fault protection
Emergency, Legally Required and Optional Standby Systems
Lighting Control Solutions for Daylit Spaces
COPS: An Arresting Look at NEC Article 708
Seismic Compliance of Electrical Distribution
Generator Set Transient Performance
Modeling of a digital protective relay in a RT Digital Simulator
Facts on Grid Friendly Wind Plants
Power Plant Horror Stories
Blackout Avoidance & Undervoltage Load Shedding
Transformer Fundamentals

Recently uploaded (20)

DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PPT
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PDF
Digital Logic Computer Design lecture notes
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PPTX
Geodesy 1.pptx...............................................
PDF
Well-logging-methods_new................
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPTX
Welding lecture in detail for understanding
PDF
composite construction of structures.pdf
PPTX
Sustainable Sites - Green Building Construction
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PPTX
Construction Project Organization Group 2.pptx
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
Foundation to blockchain - A guide to Blockchain Tech
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
Digital Logic Computer Design lecture notes
R24 SURVEYING LAB MANUAL for civil enggi
Geodesy 1.pptx...............................................
Well-logging-methods_new................
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
Welding lecture in detail for understanding
composite construction of structures.pdf
Sustainable Sites - Green Building Construction
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
Construction Project Organization Group 2.pptx

Transformer overcurrent

  • 1. Transformer Calculations Transformer Overcurrent Protection Calculations & Settings Transformer Overcurrent Protection Calculations & Settings
  • 2. Transformer Calculations X XF3 F4 X X F1 F2 51 50 51 51G 87T 63 SPR ANSI / IEEE C37.91 F1: Fault cleared by transformer primary side relays F2: Fault cleared by transformer primary side devices or neutral protection relays F3: Fault cleared by transformer primary side devices or by secondary side relays F4: Fault cleared by feeder protection relays Transformer Calculations
  • 3. Transformer Calculations X XF3 F4 X X F1 F2 50 51 50G 51G 87H87T 50 51 87GD Current Function 50 – Phase Instantaneous Overcurrent 51 – Phase Time Overcurrent Transformer Calculations Typical Single Line Diagram
  • 4. Transformer Calculations 1. Instantaneous units should be set so they do not trip for fault levels equal or lower to those at busbars or elements protected by downstream instantaneous relays. 2. Time delay units should be set to clear faults in a selective and reliable way, assuring the proper coverage of the thermal limits of the equipment protected. Protection Coordinate Principles
  • 5. Transformer Calculations R1 CURRENT t R2 Coordination Time Interval Overcurrent inverse time relay curves associated with two breakers on the same feeder Coordination of TOC Delay
  • 6. Transformer Calculations A margin between two successive devices in the order of 0.2 to 0.4 seconds should be used to avoid losing selectivity due to one or more of the following reasons: Instantaneous units should be set so they do not trip for fault levels equal or lower to those at busbars or elements protected by downstream instantaneous relays. Time delay units should be set to clear faults in a selective and reliable way, assuring the proper coverage of the thermal limits of the equipment protected. Coordination Time Interval (CTI)
  • 7. Transformer Calculations Operating time defined by IEC and ANSI/IEEE: t = Relay operating time in seconds TD = Time dial, or time multiplier setting I = Fault current level in secondary amps IP = Tap or pick up current selected B = Constant p = Slope constant A = Slope constant P M = I I * IEEE equation constants are defined at TD of 5 = A TDt − 1M p IEEE equation * IEC equation =t B+ A − 1M p TD 5 Expression for Time Delay Setting
  • 8. Transformer Calculations Setting Time Delay on Overcurrent Relays IDMT Curve Description Standard p A B Moderately Inverse IEEE 0.02 0.0515 0.114 Very Inverse IEEE 2 19.61 0.491 Extremely Inverse IEEE 2 28.2 0.1217 Standard Inverse IEC 0.02 0.14 Very inverse IEC 1.0 13.5 Extremely inverse IEC 2.0 80.0 ANSI/IEEE and IEC constants for overcurrent relays * IEEE equation constants are defined at TD of 5
  • 9. Transformer Calculations Operatingtime(s) Current (Multiples of Is) IEC EI IEC VI IEC SI UK LTI Current (Multiples of Is) Operatingtime(s) IEEE MI IEEE VI IEEE EI US C08 US C02 IEC/UK overcurrent relay curves IEEE/US overcurrent relay curves IEC curves are IMDT (Inverse Minimum Definite Time) Standards of Time/Current Characteristics
  • 10. Transformer Calculations Dac Y Dy11 X X X 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.58 0.58 0.58 Three phase fault on secondary I X VI LG F == 31 2 I N N IIdelta == III deltaprimary == 3 Coordination across D-y Transformer
  • 11. Transformer Calculations Dac Y Dy11 X X 0.5 1.0 0.5 0.87 0.87 0 0.87 0.87 0 0.5 0.5 0 Phase-to-Phase Fault I x V X V I LG F 2 3 2 3 2 === 22 3 1 2 I N N IIdelta =××= III deltaprimary == 2 LL Coordination across D-y Transformer
  • 12. Transformer Calculations Dac Y Dy11 X X 0 0.58 0.58 1.0 0 0 1.0 0 0 0.58 0 0 Phase-to-Ground Fault 3 I Iprimary = 31 2 I N N IIdelta == I X VI LG F == Coordination across D-y Transformer
  • 13. Transformer Calculations Fault Iprimary Isecondary Three phase I I Phase-to-phase I 0.87I Phase-to-earth 0.58I I For SLGF on wye side, current withstand capability is 58% of that utilized for Delta-Delta For Phase-Phase Faults on wye side, only 87% fault current flows in secondary while 100% flows in primary protector. 16% margin must be taken into account to maintain primary to secondary protection selectivity. Coordination across D-y Transformer
  • 14. Transformer Calculations A t If 2 3 If 0.4 Sec Coordination of overcurrent relays for a Dy transformer Coordination across D-y Transformer
  • 15. Transformer Calculations Minimum nameplate (kVA) Category Single-phase Three-phase I 5-500 15-500 II 501-1667 501-5000 III 1668-10,000 5001-30,000 IV above 10,000 above 30,000 IEEE Std. C57.109-1985 Curves Transformer Categories
  • 16. Transformer Calculations X XF3 F4 X X F1 F2 Infrequent Fault Incident Zone Frequent Fault Incident Zone Category 2 > 10 Category 3 > 5 Mechanical Damage: Number Faults in Lifetime Category II & III Fault Frequency
  • 17. Transformer Calculations Category II: Thermal Limit: I ² t = 1250 Mechanical Limit: I ² t = K = (1/ZT) ² x t K is determined at t = 2 seconds and at maximum I in terms of multiples of self-cooled full load current. The transition from thermal to mechanical plot occurs at 70% of max possible multiplies of I, or 0.70x(1/ZT) Category II Transformers
  • 18. Transformer Calculations 2 Thermal Limit: I t = 1250 Category II – Transformer Through Fault Curves
  • 19. Transformer Calculations Thermal Limit: I ² t = 1250 ANSI C57.12 Appendix Short-time thermal loading capability oil-immersed transformers Time Multiples of I RATED 2 s 25.0 x 10 s 11.3 x 30 s 6.3 x 60 s 4.75 x 300 s 3.0 x 1800 s 2.0 x All Category Transformers
  • 20. Transformer Calculations Times Normal Base Current I TN = 16.67 p.u. Transition from the Mechanical to Thermal curve occurs at 70% of I TN: 0.70 x (1/ZT) = 11.67 p.u. I TN = 11.67 p.u. 2 Thermal Limit: I t = 1250 ITN = Times Normal Current K = I TN = (16.67) x 2 = 556 2 Mechanical Limit: K = I t = (1/ZT) t defined at t = 2 seconds. for ZT = 6% I TN = 1/.06 =16.67 p.u. 2 2 2 t = 556 / (11.67) = 4.0 K = I t = (11.67) x t =5562 2 Wye-Wye or Delta-Delta Category II – Transformer Through Fault Curves
  • 21. Transformer Calculations Category 3: Thermal Limit: I 2 t = 1250 Mechanical Limit: I 2 t = K = [ 1 / (ZT + ZS) ]2 x t K is determined at t = 2 seconds and at maximum I in terms of multiples of self-cooled full load current. The transition from thermal to mechanical occurs at 50% of max possible multiples of I, or 0.50x1/(ZT + ZS) Category III Transformers
  • 22. Transformer Calculations Mechanical to Thermal occurs at 50% of I TN: 0.50 x 1/(ZT+ ZS) = 7.15 p.u. I TN = 7.15 p.u. I TN = 14.3 p.u. I TN = Times Normal Current Thermal Limit: I t = 1250 2 K = (I TN) x t = (7.15) x t = 40922 t = 409 / (7.15) = 8.0 2 2 Mechanical Limit K = I t = [1/ (ZS + ZT)] defined at t = 2 seconds. for ZT = 6% & ZS = 1% K = (I TN) x t = (14.3) x 2 = 40922 I TN = (1/.07) = 14.3 p.u. Wye-Wye or Delta-Delta Category III – Transformer Through Fault Curves
  • 23. Transformer Calculations Mechanical to Thermal occurs at 50% of I TN: 0.50 x 1/(ZT+ ZS) = 7.14 p.u. Delta-wye: 7.14 p.u. x 0.58 = 4.14 p.u. I TN = 4.1 p.u. I TN = 8.3 p.u. 2 2 Mechanical Limit 2 t = 138 / (4.14) = 8.0 I TN = Times Normal Current Thermal Limit: I t = 1250 2 K = I TN x t = (8.3) x 2 = 138 22 K = I t = [1/ (ZS + ZT)] defined at t = 2 seconds. for ZT = 6% & ZS = 1% I TN = 1/.07 =14.3 p.u. Delta-wye: 14.3p.u. x 0.58 = 8.3 p.u. Delta-Wye Category III – Transformer Through Fault Curves
  • 24. Transformer Calculations OFAF (OA/FA/FOA) 30/40/50 MVA 230kV / 34.5 kV X X X X F1 F2 F3 F4 Zs230kV Z= 7% Calculation Setting Example
  • 25. Transformer Calculations 0.01 p.u. 0.07 p.u. 4.80 p.u. VS = 1.0 p.u. F1 X F2/F3 X F4 X X F1 ZT A B 50 X F3 Vs = 230kV 51 230kV / 34.5kV 30/40/50MVA Z = 7% ZLT = 25 MVAZS = 1.0% on 230kV ZS = 0.01 p.u. ZT = 0.07 p.u. F2 X F4 X 51 51 50 Z Base = 30MVA 230kV 2 = 1763.3 ohm ZLT = 25MVA 34.5kV 2 = 47.6 ohms VBase = 230kV MVA Base = 30MVA Z LT at 230kV = 34.5kV 230kV 2 x 47.6 ohms = 2115.6 ohms Z LT = (2115.6/1763.3) = 1.20 p.u. ZL4 = 6.25MVA Z L4 = 4.8 p.u. ZL4 = 1/4 ZL4 Calculation Setting Example
  • 26. Transformer Calculations 0.01 p.u. 0.07 p.u. 4.80 p.u.VS = 1.00 p.u. F1 X F2/F3 X F4 X IBase at 230kV = 30MVA 3 x 230kV = 75.3 A IBase at 34.5kV = 30MVA 3 x 34.5kV = 502 A IF1 = IF2/F3 = IF4 = = 100.0 p.u. = 12.5 p.u. = 0.205 p.u. 0.01 (0.01 + 0.07) (0.01 + 0.07 + 4.80) 1.00 1.00 1.00 IF1 = 100.0 x 75.3A = 7530A 12.5 x 75.3A = 941A 0.205 x 502A =103A at 34.5kV IF4 = IF2/F3 = 12.5 x 502 = 6275A at 34.5kV 0.205 x 75.3A = 15.4A Short Circuit Currents
  • 27. Transformer Calculations Compatible with transformer overload capacity ≈ 200% of self- cooled rating for wye CT’s and 350% (√3 x 200%) for Delta- connected CT’s. Wye - Wye CT’s: 230kV: IFL = 75.3A IF1 = 7530A IF1(ASYS) = 1.6 x 7530A = 12,048A Select CT 600:5 CTR = 120 34.5kV: IFL = 502A IF2 = 6275A IF2(ASYS) = 1.6 x 6275A = 10,040A CT Selected at 2 x IFL Select CT 1000:5 CTR = 200 CT Criteria
  • 28. Transformer Calculations Set above Inrush current: 8 x IFL (Transformers 500 to 2500KVA) 10 x IFL (Transformers > 2500KVA) * Inrush point at 0.1 second * For Digital Relay using DFT use 5-6 x IFL Set above maximum asymmetrical secondary fault current: 1.6 x IF SYM for Voltage > 5kV 1.5 x IF SYM for Voltage < 5kV IOC Setting Criteria
  • 29. Transformer Calculations IOC Setting Criteria Secondary side of transformer The IOC function at the LV side is not used unless there is communication (interlocking) with relays protecting the feeders
  • 30. Transformer Calculations Set above Inrush current: ≈ 10 x IFL at 0.1 second. 10 X 73.5A = 735A Set above maximum asymmetrical secondary fault current: ≈ 1.6 x IF SYM 1.6 x 941 = 1506A = 20.0 x IFL I PICKUP = 1506A ÷ CTR = 1526A ÷ 120 = 12.65 Amps IFL = 30MVA 3x 230kV = 75.3 A IF2/F3 = 954A IOC Relay Setting
  • 31. Transformer Calculations For phase relays, three-phase faults and maximum short time overload should be considered For ground relays, line-to-ground faults and max 3Io should be considered TOC Setting Criteria
  • 32. Transformer Calculations For phase relays, the Pickup value is determined by: Pickup = (OLF x IFL) ÷ CTR For ground fault relays, the Pickup value is determined, with the maximum unbalance, typically around 20%: Pickup = [(0.2) x IFL] ÷ CTR Typical OLF for transformers = 1.25 to 1.5 TOC Setting Criteria
  • 33. Transformer Calculations Transformer: ZT < 6% Primary Setting < 6 x IFL Secondary Setting < 3 x IFL Transformer: 6% > ZT < 10% Primary Setting < 4 x IFL Secondary Setting < 2.5 x IFL Tap is set to meet NEC 450-3 and ANSI C37.91* * Primary & secondary >600V with circuit breakers TOC Setting Criteria
  • 34. Transformer Calculations Pickup = OLF x IFL ÷ CTR I Pickup = 1.5 x 75.3 ÷ 120 = 0.94 Amps I Relay setting = 0.94 ÷ 1.5 = 0.63 Amps TD # 8 Very Inverse Curve IFL = 30MVA 3x 230kV = 75.3 A IF2/F3 = 954A TOC Relay Setting
  • 35. Transformer Calculations I RELAY = 0.63 Amps TD # 8 Very Inverse Curve TOC Relay Curve
  • 36. Transformer Calculations 50% of I TN = 0.50 x 1/(ZT+ ZS) t = 105.1 / (3.625) = 8.0 I TN = Times Normal Current Thermal Limit: I t = 1250 2 Mechanical Limit K = I TN = (7.6) x 2 = 105.1 2 defined at t = 2 seconds. for ZT = 7% & ZS = 1.0% I TN = 1/.08 =12.5 p.u. Delta-wye: 2 2 K = I t = [1/ (ZS + ZT)] x t 58% x 12.5 p.u. = 7.25 p.u. Mechanical to Thermal Delta-wye: 50% of I TN = 0.50 x 12.5 = 6.25 p.u. 58% x 6.25 p.u. = 3.625 p.u. IOC set at 12.6A pickup 1.6 x IFL/CTR = 1.6 x 941/120 = 12.6A 1.6 x IFL =1.6 x 12.5p.u. = 20.0 ITN TOC set at 0.63A pickup 1.5 x ITN/CTR = 1.5 x 73.5A/120 = 0.94A Minimum multiple of pickup is 1.5 0.94A/1.5 = 0.63A, TD#8 Very Inverse TOC curve 0 0 1 10 100 1000 10000 0 1 10 100 TIMES NORMAL BASE CURRENT TIME(SECONDS) IFLSYM IFL I inrush 0.1 0.01 0.1 2.5xIFL 4.0xIFL IFLASYM 2 IFL SYM 3-phase IFL SYM phase-phase Coordination Interval 50/51 51 50/51 51 2 IOC & TOC Coordination
  • 37. Transformer Calculations Questions ?Questions ? ©2008 Beckwith Electric Co., Inc.