SlideShare a Scribd company logo
2
Most read
3
Most read
4
Most read
1. A 25 MVA, 11kV generator has a X’’d = 0.2 pu. It’s negative and zero sequence reactances are
   respectively 0.3 and 0.1 pu. The neutral of the generator is solidly grounded. Determine the
   subtransient current in the generator and the line-to-line voltages for the subtransient
   conditions when an LG fault occurs at the generator terminals. Assume that before the
   occurrence of the fault, the generator is operating at no load at rated voltage. Ignore
   resistances.

2. Repeat problem 1 for (a) an LL fault and (b) an LLG fault.

3. A synchronous generator is rated 25 MVA, 11kV. It is star-connected with the neutral point
   solidly grounded. The generator is operating at no load at rated voltage. Its reactances are X’’
   = X2 = 0.2 and X0 = 0.08 pu. Calculate the symmetrical subtransient line currents for (a) single
   line-to-ground fault (b) double line fault (c) double line-to-ground fault and (d) symmetrical
   three-phase fault. Compare these currents and comment.

4. For the generator in problem 3, calculate the value of reactances to be included in the
   generator neutral and ground, so that line-to-ground fault current equals the three-phase
   fault current. What will be the value of the grounding resistance to achieve the same
   condition? With the reactance value (as calculated here) included between neutral and
   ground, calculate the double line fault current and also double line-to-ground fault current.

5. Two 25 MVA, 11 kV synchronous generators are connected to a common bus bar which
   supplies a feeder. The star point of one of the generators is grounded through resistance of
   1.0 ohm. While that of the other generator is isolated. A line-to-ground fault occurs at the
   far end of the feeder. Determine (a) the fault current (b) the voltage to ground of the sound
   phases of the feeder at the fault point and (c) voltage of the star point of the grounded
   generator with respect to ground. The impedances to sequence currents of each generator
   and feeder are given below :

                                         Generator (per unit)            Feeder (ohms/phase)
   Positive Sequence                            j0.2                             j0.4
   Negative Sequence                            j0.15                            j0.4
   Zero Sequence                                j0.08                            j0.4
6. Determine the fault currents in each phase following a double line-to-ground short circuit at
   the terminals of a star-connected synchronous generator operating initially on an open
   circuit voltage of 1.0 pu. The positive, negative and zero sequence reactance of the
   generator are respectively j0.35, j0.5 and j0.20 and its star point is isolated from ground.

7. A three-phase synchronous generator has positive, negative and zero sequence reactances
   per phase respectively of 1.0, 0.8 and 0.4 ohm. The sequence winding resistances are
   negligible. The phase sequence of the generator is RYB with a no load voltage of 11 kV
   between lines. A short circuit occurs between lines Y and B and earth at the generator
   terminals. Calculate sequence currents in phase R and current in the earth return circuit (a) if
   the generator neutral is solidly earthed and (b) if the generator neutral is isolated. Use R
   phase voltage as reference.

8. A generator supplies a group of identical motors as shown in the figure. The motors are
   rated 600 V, 90% efficiency at full load unity power factor with sum of their output ratings
being 5 MW. The motors are sharing equally a load of 4 MW at rated voltage 0.8 power
    factor lagging and 90% efficiency when an LG fault occurs at the low voltage side of the
    transformer. Specify completely the sequence networks so simulate the fault so as to
    include the effect of prefault current. The group of motors can be treated as a single
    equivalent motor. Find the subtransient line currents in all parts of the system with prefault
    current ignored.




9. A double line-to-ground fault occurs on lines b and c at point F in the system of given figure.
   Find the subtransient current in phase c of machine 1 assuming prefault currents to be zero.
   Both machines are 5%. Each three-phase transformer is rated 1200 kVA, 600 V-Δ/3300 V.
   The reactances of the neutral grounding reactors are 5% on the kVA base of the machines.




10. A synchronous machine 1 generating 1 pu voltage is connected through a Y/Y transformer of
    reactance 0.1 pu to two transmission lines in parallel. The other ends of the lines are
    connected through a Y/Y transformer of reactance 0.1 pu to a machine 2 generating 1 pu
    voltage. For both transformers X1 = X2 = X0. Calculate the current fed into a double line-to-
    ground fault on the line side terminals of the transformer fed from machine 2. The star point
    of machine 1 and of the two transformers is solidly grounded. The reactances of the
    machines and lines referred to a common base are :
X1                       X2                       X0
    Machine 1                       0.35                     0.25                     0.05
    Machine 2                       0.30                     0.20                     0.04
    Line (each)                     0.40                     0.40                     0.80
11. The given figure shows a power network with two generators connected in parallel to a
    transformer feeding a transmission line. The far end of the line is connected to an infinite
    bus through another transformer. Star point of each transformer. Generator 1 and infinite
    bus are solidly grounded. The positive, negative and zero sequence reactances of various
    components in per unit on a common base are :

                                    Positive                Negative                  Zero
    Generator 1                      0.15                     0.15                     0.08
    Generator 2                      0.25                     0.25                ∞(i.e. neutral
                                                                                    isolated)
    Each Transformer             0.15                   0.15                           0.15
    Infinite Bus                 0.15                   0.15                           0.05
    Line                         0.20                   0.20                           0.40
    (a) Draw the sequence networks of the power system.

    (b) With both generators and infinite bus operating at 1.0 pu voltage on no load, a line-to-
        ground fault occurs at one of the terminals of the star-connected winding of the
        transformer A. Calculate the currents flowing (i) in the fault (ii) through the transformer
        A.




12. A star connected synchronous generator feeds bus bar 1 of a power system. Bus bar 1 is
    connected to bus bar 2 through a star/delta transformer in series with a transmission line.
    The power network connected to bus bar 2 can be equivalently represented by a star-
    connected generator with equal positive and negative sequences reactances. All star points
    are solidly connected to ground. The per unit sequence reactance of various components are
    given below :

                                  Positive               Negative                           Zero
   Generator                       0.20                    0.15                           0.05
   Transformer                     0.12                    0.12                           0.12
   Transmission Line               0.30                    0.30                           0.50
   Power Network                     X                         X                          0.10
13. The reactance data for the three-phase system of the given figure is :

    Generator                                            X1 = X2 = 0.1 pu. X0 = 0.05 pu
Xg (grounding reactance) = 0.02 pu
Transformer                                           X1 = X2 = 0.1 pu
                                                      Xg (grounding resistance) = 0.04 pu
Form the positive, negative and zero sequence bus impedance matrices. For a solid LG fault
at bus 1, calculate the fault current and its contributions from the generator and
transformer.




Answers:

1. –j6.56 kA, ΙVbcΙ = 12.83 kV, ΙVabΙ = 6.61 kV, ΙVcaΙ = 6.61 kV

2. (a) Vab = Vac = 1.8 pu, Ib = Ic = -2√3 pu

     (b)Vab = Vac = 0.816 pu, ΙIbΙ = ΙIcΙ = 5.69 pu

3.   (i)–j6.25 (ii)-4.33 (iii) 6.01 (iv)-j5 pu

      In order of decreasing magnitude of line currents the faults can be listed as: (a) LG (b)

      LLG (c) 3-phase (d) LL

4. 0.1936 ohm. 0.581 ohm, -4.33 pu, j5 pu

5. (a) 3.51 pu (b) Vb = 1.19(-159.50) pu, Vc = 168(129.80) pu (c) 0.726 pu

6. Ib = -Ic = -2.881 pu

7. (a) IY = -5.79 + j5.01 kA, IB = 5.79 + j5.01 kA, IG = j10.02 kA

     (b)I8 = -IY = -6.111 kA, IG = 0

8. Iag = 0, Ibg = -j2.08 pu, Icg = j2.08 pu, Iam = -j3.51 pu, Ibm = -j1.2 pu, Icm = -j1.2 pu

9. 5,266 A

10. j2.0 pu

11. If = -j6.732 pu, Ia(A) = -j4.779 pu, Ib(A) = -j0.255 pu, Ic(A) = -j0.255 pu

12. 0.42 pu, -j9.256 pu

13. –j11.152 pu, -j2.478 pu, -j1.239 pu
Unit4questions

More Related Content

PDF
Starting method for 3 phase induction motor
PPTX
COGGING & CRAWLING IN INDUCTION MOTOR
PPTX
Static Relay Presentation
PPTX
Dc generator characteristics
PPTX
Braking methods of induction motor
PPTX
Dc fed chopper
PPTX
DC GENERATOR
PPTX
Synchronous motor drive
Starting method for 3 phase induction motor
COGGING & CRAWLING IN INDUCTION MOTOR
Static Relay Presentation
Dc generator characteristics
Braking methods of induction motor
Dc fed chopper
DC GENERATOR
Synchronous motor drive

What's hot (20)

PPTX
Series and Shunt Compensation.pptx
PPTX
Representation of power system components
PPTX
Unsymmetrical fault in transmission line
PPT
Testing of dc motor
PDF
Power flow solution
PDF
Power Electronics - Power Semi – Conductor Devices
PDF
DC motors characteristics, Torque & Speed Equations, Torque -Armature current...
PDF
Drives lec 11_12_Braking of DC Motors
PPT
Cycloconverters
PPT
Voltage commutated chopper
PDF
Closed Loop Control of DC Drives
PPTX
Thyristor turn on methods
PDF
Chapter 5
PPT
Per unit system
PPTX
Unit-1 Per Unit System.pptx
PPTX
PDF
THREE PHASE INDUCTION MOTOR, Rotating Magnetic Field (RMF), Slip, Constructio...
PPTX
PPTX
Three phase inverter - 180 and 120 Degree Mode of Conduction
PPTX
Induction Motor, three phase induction motor
Series and Shunt Compensation.pptx
Representation of power system components
Unsymmetrical fault in transmission line
Testing of dc motor
Power flow solution
Power Electronics - Power Semi – Conductor Devices
DC motors characteristics, Torque & Speed Equations, Torque -Armature current...
Drives lec 11_12_Braking of DC Motors
Cycloconverters
Voltage commutated chopper
Closed Loop Control of DC Drives
Thyristor turn on methods
Chapter 5
Per unit system
Unit-1 Per Unit System.pptx
THREE PHASE INDUCTION MOTOR, Rotating Magnetic Field (RMF), Slip, Constructio...
Three phase inverter - 180 and 120 Degree Mode of Conduction
Induction Motor, three phase induction motor
Ad

Viewers also liked (9)

DOC
Unit1 And 2 Sample Solutions
PPT
Thermal power plant
DOC
Questions practice unit iv
DOC
Solutions -unit4
DOCX
Practice questions for unit ii
PDF
Practice questions
DOC
Power system Stability, Equal area criteria
PDF
Swing equation
PPT
Thermal power plant
Unit1 And 2 Sample Solutions
Thermal power plant
Questions practice unit iv
Solutions -unit4
Practice questions for unit ii
Practice questions
Power system Stability, Equal area criteria
Swing equation
Thermal power plant
Ad

Similar to Unit4questions (20)

DOC
Questions unit4
DOC
Unit 2 Questions_Nagrath kothari
PPT
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
DOC
Unit1 and 2 sample solutions
DOC
Unit 1, Power system Analysis
PPT
Unit7-DC_Motors.ppt
PPT
Unit7 dc motors
PPT
Unit7-DC_Motors.ppt
PPT
Unit7-DC_Motors.ppt
PPT
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
PPT
Unit7-DC_Motors.ppt
PPT
Unit7-DC_Motors.ppt
PPT
132232442681497329.pptfgggggggggggggggggg
PPT
Ohmslawweb
DOCX
Single phase transformer
PDF
Ee 1351 power system analysis
PPT
Active and reactive power and its equations
PDF
EE6501 Power System Analysis Rejinpaul_Important_Questions
PPTX
UNIT-3-PPT-Reactive Power Voltage control
PPT
UNIT-III complex reactive three phase.ppt
Questions unit4
Unit 2 Questions_Nagrath kothari
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
Unit1 and 2 sample solutions
Unit 1, Power system Analysis
Unit7-DC_Motors.ppt
Unit7 dc motors
Unit7-DC_Motors.ppt
Unit7-DC_Motors.ppt
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors.ppt
Unit7-DC_Motors.ppt
132232442681497329.pptfgggggggggggggggggg
Ohmslawweb
Single phase transformer
Ee 1351 power system analysis
Active and reactive power and its equations
EE6501 Power System Analysis Rejinpaul_Important_Questions
UNIT-3-PPT-Reactive Power Voltage control
UNIT-III complex reactive three phase.ppt

More from Abha Tripathi (19)

DOC
Questions unit3
DOC
Unit 2 samplesolutions
DOC
Non Conventional (Renewable) Energy Sources 01
DOC
Conventional sources of energy (power generation) 01
PDF
Symmetrical components
PDF
Representation of power system components
DOC
Questions unit2 ch3
DOC
Unit1questions
PPT
Renewable Sor
PPT
Gas and diesel Plant
PPT
NPP, Nuclear Power Plant,
PPT
Hydro E
DOC
Soln unit5
DOC
DOC
Questions From 1st Unit Nagrath
DOC
Unit 3 Part 1
DOC
Grading The Insulator Problem
DOC
Dc Distribution
DOC
Dc Distributed Load
Questions unit3
Unit 2 samplesolutions
Non Conventional (Renewable) Energy Sources 01
Conventional sources of energy (power generation) 01
Symmetrical components
Representation of power system components
Questions unit2 ch3
Unit1questions
Renewable Sor
Gas and diesel Plant
NPP, Nuclear Power Plant,
Hydro E
Soln unit5
Questions From 1st Unit Nagrath
Unit 3 Part 1
Grading The Insulator Problem
Dc Distribution
Dc Distributed Load

Recently uploaded (20)

PPTX
Final Presentation General Medicine 03-08-2024.pptx
PDF
O5-L3 Freight Transport Ops (International) V1.pdf
PDF
Classroom Observation Tools for Teachers
PPTX
Cell Structure & Organelles in detailed.
PPTX
Institutional Correction lecture only . . .
PDF
O7-L3 Supply Chain Operations - ICLT Program
PDF
BÀI TẬP BỔ TRỢ 4 KỸ NĂNG TIẾNG ANH 9 GLOBAL SUCCESS - CẢ NĂM - BÁM SÁT FORM Đ...
PDF
Complications of Minimal Access Surgery at WLH
PDF
The Lost Whites of Pakistan by Jahanzaib Mughal.pdf
PDF
Microbial disease of the cardiovascular and lymphatic systems
PPTX
GDM (1) (1).pptx small presentation for students
PPTX
PPT- ENG7_QUARTER1_LESSON1_WEEK1. IMAGERY -DESCRIPTIONS pptx.pptx
PDF
STATICS OF THE RIGID BODIES Hibbelers.pdf
PDF
Insiders guide to clinical Medicine.pdf
PDF
Computing-Curriculum for Schools in Ghana
PDF
Physiotherapy_for_Respiratory_and_Cardiac_Problems WEBBER.pdf
PPTX
school management -TNTEU- B.Ed., Semester II Unit 1.pptx
PDF
Supply Chain Operations Speaking Notes -ICLT Program
PDF
01-Introduction-to-Information-Management.pdf
PPTX
Pharmacology of Heart Failure /Pharmacotherapy of CHF
Final Presentation General Medicine 03-08-2024.pptx
O5-L3 Freight Transport Ops (International) V1.pdf
Classroom Observation Tools for Teachers
Cell Structure & Organelles in detailed.
Institutional Correction lecture only . . .
O7-L3 Supply Chain Operations - ICLT Program
BÀI TẬP BỔ TRỢ 4 KỸ NĂNG TIẾNG ANH 9 GLOBAL SUCCESS - CẢ NĂM - BÁM SÁT FORM Đ...
Complications of Minimal Access Surgery at WLH
The Lost Whites of Pakistan by Jahanzaib Mughal.pdf
Microbial disease of the cardiovascular and lymphatic systems
GDM (1) (1).pptx small presentation for students
PPT- ENG7_QUARTER1_LESSON1_WEEK1. IMAGERY -DESCRIPTIONS pptx.pptx
STATICS OF THE RIGID BODIES Hibbelers.pdf
Insiders guide to clinical Medicine.pdf
Computing-Curriculum for Schools in Ghana
Physiotherapy_for_Respiratory_and_Cardiac_Problems WEBBER.pdf
school management -TNTEU- B.Ed., Semester II Unit 1.pptx
Supply Chain Operations Speaking Notes -ICLT Program
01-Introduction-to-Information-Management.pdf
Pharmacology of Heart Failure /Pharmacotherapy of CHF

Unit4questions

  • 1. 1. A 25 MVA, 11kV generator has a X’’d = 0.2 pu. It’s negative and zero sequence reactances are respectively 0.3 and 0.1 pu. The neutral of the generator is solidly grounded. Determine the subtransient current in the generator and the line-to-line voltages for the subtransient conditions when an LG fault occurs at the generator terminals. Assume that before the occurrence of the fault, the generator is operating at no load at rated voltage. Ignore resistances. 2. Repeat problem 1 for (a) an LL fault and (b) an LLG fault. 3. A synchronous generator is rated 25 MVA, 11kV. It is star-connected with the neutral point solidly grounded. The generator is operating at no load at rated voltage. Its reactances are X’’ = X2 = 0.2 and X0 = 0.08 pu. Calculate the symmetrical subtransient line currents for (a) single line-to-ground fault (b) double line fault (c) double line-to-ground fault and (d) symmetrical three-phase fault. Compare these currents and comment. 4. For the generator in problem 3, calculate the value of reactances to be included in the generator neutral and ground, so that line-to-ground fault current equals the three-phase fault current. What will be the value of the grounding resistance to achieve the same condition? With the reactance value (as calculated here) included between neutral and ground, calculate the double line fault current and also double line-to-ground fault current. 5. Two 25 MVA, 11 kV synchronous generators are connected to a common bus bar which supplies a feeder. The star point of one of the generators is grounded through resistance of 1.0 ohm. While that of the other generator is isolated. A line-to-ground fault occurs at the far end of the feeder. Determine (a) the fault current (b) the voltage to ground of the sound phases of the feeder at the fault point and (c) voltage of the star point of the grounded generator with respect to ground. The impedances to sequence currents of each generator and feeder are given below : Generator (per unit) Feeder (ohms/phase) Positive Sequence j0.2 j0.4 Negative Sequence j0.15 j0.4 Zero Sequence j0.08 j0.4 6. Determine the fault currents in each phase following a double line-to-ground short circuit at the terminals of a star-connected synchronous generator operating initially on an open circuit voltage of 1.0 pu. The positive, negative and zero sequence reactance of the generator are respectively j0.35, j0.5 and j0.20 and its star point is isolated from ground. 7. A three-phase synchronous generator has positive, negative and zero sequence reactances per phase respectively of 1.0, 0.8 and 0.4 ohm. The sequence winding resistances are negligible. The phase sequence of the generator is RYB with a no load voltage of 11 kV between lines. A short circuit occurs between lines Y and B and earth at the generator terminals. Calculate sequence currents in phase R and current in the earth return circuit (a) if the generator neutral is solidly earthed and (b) if the generator neutral is isolated. Use R phase voltage as reference. 8. A generator supplies a group of identical motors as shown in the figure. The motors are rated 600 V, 90% efficiency at full load unity power factor with sum of their output ratings
  • 2. being 5 MW. The motors are sharing equally a load of 4 MW at rated voltage 0.8 power factor lagging and 90% efficiency when an LG fault occurs at the low voltage side of the transformer. Specify completely the sequence networks so simulate the fault so as to include the effect of prefault current. The group of motors can be treated as a single equivalent motor. Find the subtransient line currents in all parts of the system with prefault current ignored. 9. A double line-to-ground fault occurs on lines b and c at point F in the system of given figure. Find the subtransient current in phase c of machine 1 assuming prefault currents to be zero. Both machines are 5%. Each three-phase transformer is rated 1200 kVA, 600 V-Δ/3300 V. The reactances of the neutral grounding reactors are 5% on the kVA base of the machines. 10. A synchronous machine 1 generating 1 pu voltage is connected through a Y/Y transformer of reactance 0.1 pu to two transmission lines in parallel. The other ends of the lines are connected through a Y/Y transformer of reactance 0.1 pu to a machine 2 generating 1 pu voltage. For both transformers X1 = X2 = X0. Calculate the current fed into a double line-to- ground fault on the line side terminals of the transformer fed from machine 2. The star point of machine 1 and of the two transformers is solidly grounded. The reactances of the machines and lines referred to a common base are :
  • 3. X1 X2 X0 Machine 1 0.35 0.25 0.05 Machine 2 0.30 0.20 0.04 Line (each) 0.40 0.40 0.80 11. The given figure shows a power network with two generators connected in parallel to a transformer feeding a transmission line. The far end of the line is connected to an infinite bus through another transformer. Star point of each transformer. Generator 1 and infinite bus are solidly grounded. The positive, negative and zero sequence reactances of various components in per unit on a common base are : Positive Negative Zero Generator 1 0.15 0.15 0.08 Generator 2 0.25 0.25 ∞(i.e. neutral isolated) Each Transformer 0.15 0.15 0.15 Infinite Bus 0.15 0.15 0.05 Line 0.20 0.20 0.40 (a) Draw the sequence networks of the power system. (b) With both generators and infinite bus operating at 1.0 pu voltage on no load, a line-to- ground fault occurs at one of the terminals of the star-connected winding of the transformer A. Calculate the currents flowing (i) in the fault (ii) through the transformer A. 12. A star connected synchronous generator feeds bus bar 1 of a power system. Bus bar 1 is connected to bus bar 2 through a star/delta transformer in series with a transmission line. The power network connected to bus bar 2 can be equivalently represented by a star- connected generator with equal positive and negative sequences reactances. All star points are solidly connected to ground. The per unit sequence reactance of various components are given below : Positive Negative Zero Generator 0.20 0.15 0.05 Transformer 0.12 0.12 0.12 Transmission Line 0.30 0.30 0.50 Power Network X X 0.10 13. The reactance data for the three-phase system of the given figure is : Generator X1 = X2 = 0.1 pu. X0 = 0.05 pu
  • 4. Xg (grounding reactance) = 0.02 pu Transformer X1 = X2 = 0.1 pu Xg (grounding resistance) = 0.04 pu Form the positive, negative and zero sequence bus impedance matrices. For a solid LG fault at bus 1, calculate the fault current and its contributions from the generator and transformer. Answers: 1. –j6.56 kA, ΙVbcΙ = 12.83 kV, ΙVabΙ = 6.61 kV, ΙVcaΙ = 6.61 kV 2. (a) Vab = Vac = 1.8 pu, Ib = Ic = -2√3 pu (b)Vab = Vac = 0.816 pu, ΙIbΙ = ΙIcΙ = 5.69 pu 3. (i)–j6.25 (ii)-4.33 (iii) 6.01 (iv)-j5 pu In order of decreasing magnitude of line currents the faults can be listed as: (a) LG (b) LLG (c) 3-phase (d) LL 4. 0.1936 ohm. 0.581 ohm, -4.33 pu, j5 pu 5. (a) 3.51 pu (b) Vb = 1.19(-159.50) pu, Vc = 168(129.80) pu (c) 0.726 pu 6. Ib = -Ic = -2.881 pu 7. (a) IY = -5.79 + j5.01 kA, IB = 5.79 + j5.01 kA, IG = j10.02 kA (b)I8 = -IY = -6.111 kA, IG = 0 8. Iag = 0, Ibg = -j2.08 pu, Icg = j2.08 pu, Iam = -j3.51 pu, Ibm = -j1.2 pu, Icm = -j1.2 pu 9. 5,266 A 10. j2.0 pu 11. If = -j6.732 pu, Ia(A) = -j4.779 pu, Ib(A) = -j0.255 pu, Ic(A) = -j0.255 pu 12. 0.42 pu, -j9.256 pu 13. –j11.152 pu, -j2.478 pu, -j1.239 pu