SlideShare a Scribd company logo
Power Quality Application Guide
0
20
40
60
80
100
1 3 5 7 9 11 13 15 17
Harmonic number
%Magnitude
Degrees
Current(A)
Harmonics
WAVEFORMS
Harmonics
1
Causes and Effects
This section of the Guide covers the origin
of harmonic currents and the effect that
they have in electrical systems.
Reduction methods are discussed in the
‘Harmonic Solutions’ sections.
Harmonic frequencies are integral
multiples of the fundamental supply
frequency, i.e. for a fundamental of 50 Hz,
the third harmonic would be 150 Hz and
the fifth harmonic would be 250 Hz.
Figure 1 shows a fundamental sinewave
with third and fifth harmonics.
Figure 1 - Fundamental with third and fifth harmonics
Figure 2 shows a fundamental with 70 % third harmonic and 50 % fifth harmonic added. Note that in
practice most distorted current waveforms will be much more complex than this example, containing many
more harmonics with a more complex phase relationship.
This waveform is clearly not a sinewave
and that means that normal
measurement equipment, such as
averaging reading rms-calibrated multi-
meters, will give inaccurate readings.
Note also that there are six zero crossing
points per cycle instead of two, so any
equipment that uses zero crossing as a
reference will malfunction. The
waveform contains non-fundamental
frequencies and has to be treated
accordingly.
When talking about harmonics in power
installations it is the current harmonics
that are of most concern because the
harmonics originate as currents and most
of the ill effects are due to these currents.
No useful conclusions can be drawn
without knowledge of the spectrum of the
current harmonics but it is still common to find only the total harmonic distortion (THD) figures quoted.
When harmonics propagate around a distribution system, that is, to branch circuits not concerned with
carrying the harmonic current, they do so as voltages. It is very important that both voltage and current
values are measured and that quoted values are explicitly specified as voltage and current values.
Conventionally, current distortion measurements are suffixed with ‘I’, e.g. 35 % THDI, and voltage distortion
figures with ‘V’, e.g. 4 % THDV.
Harmonic currents have been present in the electricity supply system for many years. Initially they were
produced by the mercury arc rectifiers used to convert AC to DC current for railway electrification and for
DC variable speed drives in industry. More recently the range of types and the number of units of
equipment causing harmonics have risen sharply, and will continue to rise, so designers and specifiers
must now consider harmonics and their side effects very carefully.
This section describes how and why harmonics are generated, how the presence of harmonics affects the
electrical system and equipment and how to minimise these effects.
5th Harmonic
(50%)
Fundamental
3rd Harmonic (70%)
-2
-1
0
1
2
0 90 270 360180
-2
-1
0
1
2
0 90 270 360180
Figure 2 - Distorted current waveform
Causes and Effects
22
Types of equipment that generate harmonics
Harmonic load currents are generated by all non-linear loads. These include:
Single phase loads, e.g.
Switched mode power supplies (SMPS)
Electronic fluorescent lighting ballasts
Small uninterruptible power supplies (UPS) units
Three phase loads, e.g.
Variable speed drives
Large UPS units
Single phase loads
Switched mode power supplies (SMPS)
The majority of modern electronic units use switched mode power supplies (SMPS). These differ from older
units in that the traditional step-down transformer and rectifier is replaced by direct controlled rectification
of the supply to charge a reservoir capacitor from which the direct current for the load is derived by a method
appropriate to the output voltage and current required. The advantage – to the equipment manufacturer –
is that the size, cost and weight is significantly reduced and the power unit can be made in almost any
required form factor. The disadvantage –
to everyone else – is that, rather than
drawing continuous current from the
supply, the power supply unit draws
pulses of current which contain large
amounts of third and higher harmonics
and significant high frequency
components (see Figure 3). A simple filter
is fitted at the supply input to bypass the
high frequency components from line and
neutral to ground but it has no effect on
the harmonic currents that flow back to
the supply. The earth leakage effects of
these filters are discussed in Section 6.
Single phase UPS units exhibit very
similar characteristics to SMPS.
For high power units there has been a recent trend towards so-called power factor corrected inputs. The
aim is to make the power supply load look like a resistive load so that the input current appears sinusoidal
and in phase with the applied voltage. It is achieved by drawing input current as a high frequency triangular
waveform that is averaged by the input filter to a sinusoid. This extra level of sophistication is not yet readily
applicable to the low-cost units that make up most of the load in commercial and industrial installations.
It remains to be seen what problems the wide-scale application of this technology may involve!
Fluorescent lighting ballasts
Electronic lighting ballasts have become popular in recent years following claims for improved efficiency.
Overall they are only a little more efficient than the best magnetic ballasts and in fact, most of the gain is
attributable to the lamp being more efficient when driven at high frequency rather than to the electronic
ballast itself. Their chief advantage is that the light level can be maintained over an extended lifetime by
feedback control of the running current - a practice that reduces the overall lifetime efficiency. Their great
disadvantage is that they generate harmonics in the supply current. So called power-factor corrected types
0
20
40
60
80
100
1 3 5 7 9 11 13 15 17
Harmonic number
%Magnitudewrtfundamental
Figure 3 - Harmonic spectrum of a typical PC
Causes and Effects
3
are available at higher ratings that reduce
the harmonic problems, but at a cost
penalty. Smaller units are usually
uncorrected.
Compact fluorescent lamps (CFL) are
now being sold as replacements for
tungsten filament bulbs. A miniature
electronic ballast, housed in the
connector casing, controls a folded 8mm
diameter fluorescent tube. CFLs rated at
11 watt are sold as replacements for a 60
watt filament lamp and have a life
expectancy of 8000 hours. The harmonic
current spectrum is shown in Figure 4.
These lamps are being widely used to
replace filament bulbs in domestic
properties and especially in hotels where
serious harmonic problems are suddenly
becoming common.
Three phase loads
Variable speed controllers, UPS units and
DC converters in general are usually
based on the three-phase bridge, also
known as the six-pulse bridge because
there are six pulses per cycle (one per half
cycle per phase) on the DC output.
The six pulse bridge produces harmonics
at 6n +/- 1, i.e. at one more and one less
than each multiple of six. In theory, the
magnitude of each harmonic is the
reciprocal of the harmonic number, so
there would be 20 % fifth harmonic and
9 % eleventh harmonic, etc.
A typical spectrum is shown in Figure 6.
The magnitude of the harmonics is
significantly reduced by the use of a
twelve-pulse bridge. This is effectively
two six-pulse bridges, fed from a star and
a delta transformer winding, providing a
30 degrees phase shift between them.
The 6n harmonics are theoretically
removed, but in practice, the amount of
reduction depends on the matching of
the converters and is typically by a factor
between 20 and 50. The 12n harmonics
remain unchanged. Not only is the total
harmonic current reduced, but also those
that remain are of a higher order making
the design of the filter much easier.
0
20
40
60
80
100
%Magnitudewrtfundamental
1ph
1d
0
20
40
60
80
100
1 3 5 7 9 11 13 15 17 19 21 23 25
Harmonic number
%Magnitudewrtfundamental
Figure 4 - Harmonic spectrum of a typical CFL
Figure 5 - Three-phase, or six-pulse, bridge
Figure 6 - Harmonic spectrum of a typical 6-pulse bridge
Causes and Effects
4
Often the equipment manufacturer will
have taken some steps to reduce the
magnitudes of the harmonic currents,
perhaps by the addition of a filter or series
inductors. In the past this has led some
manufacturers to claim that their
equipment is ‘G5/3’ compliant. Since G5/3
is a planning standard applicable to a
complete installation, it cannot be said to
have been met without knowledge of every
piece of equipment on the site.
A further increase in the number of pulses
to 24, achieved by using two parallel
twelve-pulse units with a phase shift of 15
degrees, reduces the total harmonic
current to about 4.5 %. The extra
sophistication increases cost, of course, so
this type of controller would be used only
when absolutely necessary to comply with
the electricity suppliers’ limits.
Theoretical background –
how harmonics are
generated
In an ideal clean power system, the
current and voltage waveforms are pure
sinusoids. In practice, non-sinusoidal
currents result when the current flowing
in the load is not linearly related to the
applied voltage. In a simple circuit
containing only linear circuit elements -
resistance, inductance and capacitance -
the current which flows is proportional to
the applied voltage (at a particular
frequency) so that, if a sinusoidal voltage
is applied, a sinusoidal current will flow,
as illustrated in Figure 9. The load-line is
the relationship between the voltage
applied and the current that results in the
load; that shown in Figure 9 corresponds
to a linear load. Note that where there is
a reactive element there will be a phase
shift between the voltage and current
waveforms; the power factor is reduced,
but the circuit can still be linear.
Figure 10 shows the situation where the
load is a simple full-wave rectifier and
capacitor, such as the input stage of a
typical switched mode power supply. In
this case, current flows only when the
supply voltage exceeds that stored on the
reservoir capacitor, i.e. close to the peak of
Figure 8 - Harmonic spectrum of a typical 12 pulse bridge
Angle
Angle
Voltage Waveform
Current Waveform
V
I
Load Line
Figure 7 - Twelve-pulse bridge
Figure 9 - Current waveform in a linear load
Causes and Effects
5
the voltage sinewave, as shown by the
shape of the load line.
In practice, the load line (and hence the
current waveform) is likely to be much more
complex than shown in this illustrative
example; there may be some asymmetry
and hysteresis and the breakpoints and
slopes will change with loading.
Any cyclical waveform can be de-
constructed into a sinusoid at the
fundamental frequency plus a number of
sinusoids at harmonic frequencies. Thus
the distorted current waveform in
Figure 10 can be represented by the
fundamental plus a percentage of second
harmonic plus a percentage of third
harmonic and so on, possibly up to the
thirtieth harmonic. For symmetrical
waveforms, i.e. where the positive and
negative half cycles are the same shape
and magnitude, all the even numbered
harmonics are zero. Even harmonics are
now relatively rare but were common
when half wave rectification was widely
used.
The equivalent circuit of a non-linear load
is shown in Figure 11. It can be modelled
as a linear load in parallel with a number
of current sources, one source for each
harmonic frequency.
The harmonic currents generated by the
load – or more accurately converted by
the load from fundamental to harmonic
current – have to flow around the circuit
via the source impedance and all other
parallel paths. As a result, harmonic
voltages appear across the supply
impedance and are present throughout the installation. Harmonic generators are sometimes shown as
voltage generators; if this were true then the source impedance would have no influence on the magnitude
of the harmonic voltage across the source. In reality the magnitude of this voltage is proportional (over a
limited range) to the source impedance indicating that the generator behaves as a current source.
Source impedances are very low so the harmonic voltage distortion resulting from a harmonic current is
also low and often hardly above the network background. This can be misleading because it gives the
impression that there is not likely to be a harmonic problem when in fact large harmonic currents are
present. It is rather similar to trying to find a circulating earth current with a voltmeter. Whenever
harmonics are suspected, or when trying to verify their absence, the current must be measured.
Problems caused by harmonics
Harmonic currents cause problems both on the supply system and within the installation. The effects and
the solutions are very different and need to be addressed separately; the measures that are appropriate to
controlling the effects of harmonics within the installation may not necessarily reduce the distortion
caused on the supply and vice versa.
Source Impedance
LinearLoadImpedance
Supply Installation
I 3rd I 5th I 7th
V~
I
Angle
Angle
V
Voltage Waveform
Current Waveform
Load Line
Figure 10 - Current waveform in a non-linear load
Figure 11 - Equivalent circuit of a non-linear load
Causes and Effects
6
Harmonic problems within the installation
There are several common problem areas caused by harmonics: -
Problems caused by harmonic currents:
overloading of neutrals
overheating of transformers
nuisance tripping of circuit breakers
over-stressing of power factor correction capacitors
skin effect
Problems caused by harmonic voltages:
voltage distortion
induction motors
zero-crossing noise
Problems caused when harmonic currents reach the supply
Each of these areas is discussed briefly in the following sections.
Problems caused by harmonic currents
Neutral conductor over-heating
In a three-phase system the voltage waveform from each phase to the neutral star point is displaced by 120°
so that, when each phase is equally loaded, the combined current in the neutral is zero. When the loads are
not balanced only the net out of balance current flows in the neutral. In the past, installers (with the
approval of the standards authorities) have taken advantage of this fact by installing half-sized neutral
conductors. However, although the fundamental currents cancel out, the harmonic currents do not - in fact
those that are an odd multiple of three times the fundamental, the ‘triple-N’ harmonics, add in the neutral.
Figure 12 shows the effect. In this diagram the phase currents, shown at the top, are introduced at 120°
0 120 240 360 480 600 720
Phase 1 Phase 2 Phase 3
Phase 1 3rd harmonic
Phase 2 3rd harmonic
Phase 3 3rd harmonic
3rd harmonic neutral current
Figure 12 – Triple-N currents add in the neutral
Causes and Effects
7
intervals. The third harmonic of each phase is identical, being three times the frequency and one-third of
a (fundamental) cycle offset. The effective third harmonic neutral current is shown at the bottom. In this
case, 70 % third harmonic current in each phase results in 210 % current in the neutral.
Case studies in commercial buildings generally show neutral currents between 150 % and 210 % of the
phase currents, often in a half-sizedconductor!
There is some confusion as to how designers should deal with this issue. The simple solution, where single-
cored cables are used, is to install a double sized neutral, either as two separate conductors or as one single
large conductor. The situation where multi-cored cables are used is not so simple. The ratings of multi-
core cables (for example as given in IEC 60364–5-523 Table 52 and BS 7671 Appendix 4) assume that the load
is balanced and the neutral conductor carries no current, in other words, only three of the four or five cores
carry current and generate heat. Since the cable current carrying capacity is determined solely by the
amount of heat that it can dissipate at the maximum permitted temperature, it follows that cables carrying
triple-N currents must be de-rated. In
the example illustrated above, the cable is
carrying five units of current – three in
the phases and two in the neutral – while
it was rated for three units. It should be
de-rated to about 60 % of the normal
rating.
IEC 60364-5-523 Annex C (Informative)
suggests a range of de-rating factors
according to the triple-N harmonic
current present. Figure 13 shows de-
rating factor against triple-N harmonic
content for the de-rating described in IEC
60364-5-523 Annex C and for the thermal
method used above.
The regulatory position is under discussion at present and it is likely that new requirements and guidance
notes will be introduced into national wiring codes in the near future.
Effects on transformers
Transformers are affected in two ways by harmonics. Firstly, the eddy current losses, normally about 10 % of
the loss at full load, increase with the square of the harmonic number. In practice, for a fully loaded
transformer supplying a load comprising IT equipment the total transformer losses would be twice as high as
for an equivalent linear load. This results in a much higher operating temperature and a shorter life. In fact,
under these circumstances the lifetime would reduce from around 40 years to more like 40 days! Fortunately,
few transformers are fully loaded, but the effect must be taken into account when selecting plant.
The second effect concerns the triple-N harmonics. When reflected back to a delta winding they are all in
phase, so the triple-N harmonic currents circulate in the winding. The triple-N harmonics are effectively
absorbed in the winding and do not propagate onto the supply, so delta wound transformers are useful as
isolating transformers. Note that all other, non triple-N, harmonics pass through. The circulating current
has to be taken into account when rating the transformer.
A detailed discussion on rating transformers for harmonic currents can be found in a later section of the Guide.
Nuisance tripping of circuit breakers
Residual current circuit breakers (RCCB) operate by summing the current in the phase and neutral conductors
and, if the result is not within the rated limit, disconnecting the power from the load. Nuisance tripping can
occur in the presence of harmonics for two reasons. Firstly, the RCCB, being an electromechanical device,
may not sum the higher frequency components correctly and therefore trips erroneously. Secondly, the kind
of equipment that generates harmonics also generates switching noise that must be filtered at the equipment
power connection. The filters normally used for this purpose have a capacitor from line and neutral to
ground, and so leak a small current to earth. This current is limited by standards to less than 3.5 mA, and is
0.4
0.6
0.8
1.0
0 10 20 30 40 50 60 70
% third harmonic
Cablederatingfactor
TThheerrmmaall
IIEECC
Figure 13 - Cable derating for triple-N harmonics
usually much lower, but when equipment
is connected to one circuit the leakage
current can be sufficient to trip the RCCB.
The situation is easily overcome by
providing more circuits, each supplying
fewer loads. A later section of this Guide
covers the problem of high earth leakage in
greater detail.
Nuisance tripping of miniature circuit
breakers (MCB) is usually caused
because the current flowing in the circuit
is higher than that expected from
calculation or simple measurement due
to the presence of harmonic currents.
Most portable measuring instruments do
not measure true RMS values and can
underestimate non-sinusoidal currents
by 40 %. True RMS measurement is
discussed in Section 3.2.2.
Over-stressing of power factor correction
capacitors
Power factor correction capacitors are
provided in order to draw a current with a
leading phase angle to offset lagging
current drawn by an inductive load such
as induction motors. Figure 14 shows the
effective equivalent circuit for a PFC
capacitor with a non-linear load. The
impedance of the PFC capacitor reduces
as frequency rises, while the source
impedance is generally inductive and
increases with frequency. The capacitor is
therefore likely to carry quite high
harmonic currents and, unless it has been
specifically designed to handle them,
damage can result.
A potentially more serious problem is that
the capacitor and the stray inductance of
the supply system can resonate at or near
one of the harmonic frequencies (which,
of course, occur at 100 Hz intervals).
When this happens very large voltages
and currents can be generated, often
leading to the catastrophic failure of the
capacitor system.
Resonance can be avoided by adding an
inductance in series with the capacitor
such that the combination is just
inductive at the lowest significant
harmonic. This solution also limits the
harmonic current that can flow in the
capacitor. The physical size of the
inductor can be a problem, especially
when low order harmonics are present.
Causes and Effects
8
Supply Impedance
Supply
Linear Load Non-linear Load
Supply Voltage
Waveform
Voltage Waveform
applied to Load
Current in
Linear Load
Load Current
Cable
Impedance
Cable
Impedance
Cable
Impedance
Point of
Common
Coupling
Linear Load
Non-linear Load
Supply Voltage
Waveform
Voltage Waveform
applied to Linear-load
Current in
Linear-load Load Current
Voltage Waveform
applied to Non-linear
Load
Figure 16 - Separation of linear and non-linear loads
Figure 15 - Voltage distortion caused by a non-linear load
Source Impedance
LinearLoadImpedance
Supply Installation
I 3rd I 5th I 7th
V~
I 3rd + I 5th + I 7th
PFC
Figure 14 - Equivalent circuit of a non-linear load with a
PFC capacitor
Causes and Effects
9
Skin effect
Alternating current tends to flow on the outer surface of a conductor. This is known as skin effect and is
more pronounced at high frequencies. Skin effect is normally ignored because it has very little effect at
power supply frequencies but above about 350 Hz, i.e. the seventh harmonic and above, skin effect will
become significant, causing additional loss and heating. Where harmonic currents are present, designers
should take skin effect into account and de-rate cables accordingly. Multiple cable cores or laminated
busbars can be used to help overcome this problem. Note also that the mounting systems of busbars must
be designed to avoid mechanical resonance at harmonic frequencies.
Problems caused by harmonic voltages
Because the supply has source impedance, harmonic load currents give rise to harmonic voltage distortion on
the voltage waveform (this is the origin of ‘flat topping’). There are two elements to the impedance: that of the
internal cabling from the point of common coupling (PCC), and that inherent in the supply at the PCC, e.g.
the local supply transformer. The former is illustrated in Figure 15.
The distorted load current drawn by the non-linear load causes a distorted voltage drop in the cable
impedance. The resultant distorted voltage waveform is applied to all other loads connected to the same
circuit, causing harmonic currents to flow in them - even if they are linear loads.
The solution is to separate circuits supplying harmonic generating loads from those supplying loads which are
sensitive to harmonics, as shown in Figure 16. Here separate circuits feed the linear and non-linear loads from
the point of common coupling, so that the voltage distortion caused by the non-linear load does not affect the
linear load.
When considering the magnitude of harmonic voltage distortion it should be remembered that, when the
load is transferred to a UPS or standby generator during a power failure, the source impedance and the
resulting voltage distortion will be much higher.
Where local transformers are installed, they should be selected to have sufficiently low output impedance and
to have sufficient capacity to withstand the additional heating, in other words, by selecting an appropriately
oversized transformer. Note that it is not appropriate to select a transformer design in which the increase in
capacity is achieved simply by forced cooling – such a unit will run at higher internal temperatures and have
a reduced service life. Forced cooling should be reserved for emergency use only and never relied upon for
normal running.
Induction Motors
Harmonic voltage distortion causes increased eddy current losses in motors in the same way as in
transformers. However, additional losses arise due to the generation of harmonic fields in the stator, each
of which is trying to rotate the motor at a different speed either forwards or backwards. High frequency
currents induced in the rotor further increase losses.
Where harmonic voltage distortion is present motors should be de-rated to take account of the additional losses.
Zero-crossing noise
Many electronic controllers detect the point at which the supply voltage crosses zero volts to determine
when loads should be turned on. This is done because switching reactive loads at zero voltage does not
generate transients, so reducing electromagnetic interference (EMI) and stress on the semiconductor
switching devices. When harmonics or transients are present on the supply the rate of change of voltage at
the crossing becomes faster and more difficult to identify, leading to erratic operation. There may in fact be
several zero-crossings per half cycle.
Harmonic problems affecting the supply
When a harmonic current is drawn from the supply it gives rise to a harmonic voltage drop proportional to
the source impedance at the point of common coupling (PCC) and the current. Since the supply network
is generally inductive, the source impedance is higher at higher frequencies. Of course, the voltage at the
PCC is already distorted by the harmonic currents drawn by other consumers and by the distortion inherent
in transformers, and each consumer makes an additional contribution.
Clearly, customers cannot be allowed to add pollution to the system to the detriment of other users, so in
most countries the electrical supply industry has established regulations limiting the magnitude of harmonic
current that can be drawn.
Harmonic mitigation measures
The measures available to control the magnitude of harmonic current drawn are discussed in detail in later
sections of this Guide. In this section a brief overview is given in generic terms. Mitigation methods fall
broadly into three groups; passive filters, isolation and harmonic reduction transformers and active
solutions. Each approach has advantages and disadvantages, so there is no single best solution. It is very
easy to spend a great deal of money on an inappropriate and ineffective solution; the moral is to carry out
a thorough survey – tools suitable for this purpose are described elsewhere in this Guide.
Passive filters
Passive filters are used to provide a low
impedance path for harmonic currents so
that they flow in the filter and not the
supply (Figure 17). The filter may be
designed for a single harmonic or for a
broad band depending on requirements.
Sometimes it is necessary to design a more
complex filter to increase the series
impedance at harmonic frequencies and so
reduce the proportion of current that flows
back onto the supply, as shown in Figure 18.
Simple series band stop filters are
sometimes proposed, either in the phase
or in the neutral. A series filter is intended
to block harmonic currents rather than
provide a controlled path for them so there
is a large harmonic voltage drop across it.
This harmonic voltage appears across the
supply on the load side. Since the supply
voltage is heavily distorted it is no longer
within the standards for which equipment
was designed and warranted. Some
equipment is relatively insensitive to this
distortion, but some is very sensitive.
Series filters can be useful in certain
circumstances, but should be carefully
applied; they cannot be recommended as
a general purpose solution.
Isolation transformers
As mentioned previously, triple-N
currents circulate in the delta windings of
transformers. Although this is a problem
for transformer manufacturers and
specifiers - the extra load has to be taken
into account – it is beneficial to systems
designers because it isolates triple-N
harmonics from the supply.
Causes and Effects
Supply
Load
I3
Figure 19 - Delta star isolation transformer
Source
Impedance
LinearLoadImpedance
Supply Installation
I 3rd I 5th I 7th
V~
Shunt Filter
(band pass)
Series Filter
(band stop)
Ih
Figure 18 - Passive series and shunt filters
Source Impedance
LinearLoadImpedance
Supply Installation
I 3rd I 5th I 7th
V~
Shunt Filter
(band pass)
Ih
Figure 17 - Passive harmonic shunt filter
10
Causes and Effects
11
The same effect can be obtained by using a ‘zig-zag’ wound transformer. Zig-zag transformers are star
configuration auto transformers with a particular phase relationship between the windings that are
connected in shunt with the supply.
Active Filters
The solutions mentioned so far have been suited only to particular harmonics, the isolating transformer
being useful only for triple-N harmonics and passive filters only for their designed harmonic frequency. In
some installations the harmonic content is less predictable. In many IT installations, for example, the
equipment mix and location is constantly changing so that the harmonic culture is also constantly
changing. A convenient solution is the active filter or active conditioner.
As shown in Figure 20, the active filter is a
shunt device. A current transformer
measures the harmonic content of the
load current, and controls a current
generator to produce an exact replica that
is fed back onto the supply on the next
cycle. Since the harmonic current is
sourced from the active conditioner, only
fundamental current is drawn from the
supply. In practice, harmonic current
magnitudes are reduced by 90 % and,
because the source impedance at
harmonic frequencies is reduced, voltage
distortion is reduced.
Conclusion
Virtually all modern electrical and electronic equipment contains a SMPS or involves some form of power
control and so is a non-linear load. Linear loads are comparatively rare, undimmed filament bulbs and
uncontrolled heaters being the only common examples.
Future equipment Standards are discussed in detail in a later section of this Guide, but have not been set
tightly enough to make a real impact on harmonic pollution produced by electronic equipment such as
PCs. It is this class of equipment that is causing many of the harmonic problems seen in industry and
commerce today, partly because there are so many of them installed and partly because the type of
harmonics they produce – the triple-Ns – cause so many problems.
As the quantity of installed equipment rises, and without very strong standards backed up by rigid
enforcement measures, it is likely that harmonic pollution will continue to increase. This is a risk to
business that needs to be managed by investment in good design practice, the right electrical equipment
and good maintenance.
Power Quality Application Guide
Version 0b November 2001
Source
Impedance
LinearLoadImpedance
Supply Installation
I 3rd I 5th I 7th
V~
Ih
Fundamental Current
I fund
Load Current
I load
Active
Conditioner
HarmonicCurrent
Figure 20 - Active harmonic conditioner

More Related Content

PDF
Harmonics
PDF
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
PPTX
Harmonics and mitigation techniques
PPSX
Mill harmonics r1
PPTX
Identification and minimization of Harmonics
PPTX
ELEKTRA_new
PPT
Vivek harmonics
PDF
Harmonics: Causes, Effects and Minimization
Harmonics
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
Harmonics and mitigation techniques
Mill harmonics r1
Identification and minimization of Harmonics
ELEKTRA_new
Vivek harmonics
Harmonics: Causes, Effects and Minimization

What's hot (20)

PPTX
Harmonic presentation 11 6-2018
PPTX
Harmonics Presentation by Baldev Raj Narang CEO Clariant Power System Ltd
PDF
Power factor vs. displacement power factor
PDF
Porper selection of Active & Passive harmonic filters
DOCX
Harmonics In Transformer pdf
PDF
Harmonics: Causes and Effects
PPT
2010 August Harmonics & Energy Efficiency
PDF
Harmonics Effects in Power System
PDF
Thesis on harmonic distortion ps
PPTX
Harmonic mitigating transformer
DOCX
Harmonics
PPTX
POWER HARMONICS- SOURCES, ISSUES AND MITIGATION
PPS
Harmonics in power system
PDF
Harmonic Analysis of 6-Pulse and 12-Pulse Converter Models
DOCX
overview
PPTX
Harmonics
PPTX
Transformer Harmonics
PPTX
Harmonic mitigation
PPT
Harmonic reduction
Harmonic presentation 11 6-2018
Harmonics Presentation by Baldev Raj Narang CEO Clariant Power System Ltd
Power factor vs. displacement power factor
Porper selection of Active & Passive harmonic filters
Harmonics In Transformer pdf
Harmonics: Causes and Effects
2010 August Harmonics & Energy Efficiency
Harmonics Effects in Power System
Thesis on harmonic distortion ps
Harmonic mitigating transformer
Harmonics
POWER HARMONICS- SOURCES, ISSUES AND MITIGATION
Harmonics in power system
Harmonic Analysis of 6-Pulse and 12-Pulse Converter Models
overview
Harmonics
Transformer Harmonics
Harmonic mitigation
Harmonic reduction
Ad

Similar to Waveforms Cause and effects (20)

PDF
IRJET- Harmonics Reduction using Harmonics Injection Method
PDF
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
PDF
Highly efficient Active Front End enables trouble free operation of low harmo...
PDF
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdf
PPTX
Analysis of harmonic at different level on distribution system ,its effect a...
PDF
Ijetr012048
PDF
Power System Harmonics
PDF
Paper id 29201412
PDF
Operational Cost Avoidance through Harmonic Mitigation in Industrial Environm...
PDF
06 Cap 5 - interharmonics-and-flicker-2015.pdf
PDF
Are Harmonics Still a Problem in Data Centers ?
PDF
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
PPTX
Electrical fundamentals terms
PPTX
Electrical fundamentals terms
PDF
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
PDF
An Overview of Harmonic Sources in Power System
PDF
Bus ele tech_lib_short_circuit_current_calculations (1)
PPTX
Harmonics and its types based on harmonic numbers.pptx
PDF
International Journal of Computational Engineering Research(IJCER)
PDF
Theory for How to calculation capacitor bank
IRJET- Harmonics Reduction using Harmonics Injection Method
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
Highly efficient Active Front End enables trouble free operation of low harmo...
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdf
Analysis of harmonic at different level on distribution system ,its effect a...
Ijetr012048
Power System Harmonics
Paper id 29201412
Operational Cost Avoidance through Harmonic Mitigation in Industrial Environm...
06 Cap 5 - interharmonics-and-flicker-2015.pdf
Are Harmonics Still a Problem in Data Centers ?
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Electrical fundamentals terms
Electrical fundamentals terms
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
An Overview of Harmonic Sources in Power System
Bus ele tech_lib_short_circuit_current_calculations (1)
Harmonics and its types based on harmonic numbers.pptx
International Journal of Computational Engineering Research(IJCER)
Theory for How to calculation capacitor bank
Ad

More from J A Simon (6)

PDF
waveforms profile
PDF
Waveforms Mitigation Technique
PDF
ACTIVE vs PASSIVE HARMONICS FILTERS
PDF
Facts
PDF
Intro to Harmonics New
PDF
Introduction Letter
waveforms profile
Waveforms Mitigation Technique
ACTIVE vs PASSIVE HARMONICS FILTERS
Facts
Intro to Harmonics New
Introduction Letter

Waveforms Cause and effects

  • 1. Power Quality Application Guide 0 20 40 60 80 100 1 3 5 7 9 11 13 15 17 Harmonic number %Magnitude Degrees Current(A) Harmonics WAVEFORMS
  • 2. Harmonics 1 Causes and Effects This section of the Guide covers the origin of harmonic currents and the effect that they have in electrical systems. Reduction methods are discussed in the ‘Harmonic Solutions’ sections. Harmonic frequencies are integral multiples of the fundamental supply frequency, i.e. for a fundamental of 50 Hz, the third harmonic would be 150 Hz and the fifth harmonic would be 250 Hz. Figure 1 shows a fundamental sinewave with third and fifth harmonics. Figure 1 - Fundamental with third and fifth harmonics Figure 2 shows a fundamental with 70 % third harmonic and 50 % fifth harmonic added. Note that in practice most distorted current waveforms will be much more complex than this example, containing many more harmonics with a more complex phase relationship. This waveform is clearly not a sinewave and that means that normal measurement equipment, such as averaging reading rms-calibrated multi- meters, will give inaccurate readings. Note also that there are six zero crossing points per cycle instead of two, so any equipment that uses zero crossing as a reference will malfunction. The waveform contains non-fundamental frequencies and has to be treated accordingly. When talking about harmonics in power installations it is the current harmonics that are of most concern because the harmonics originate as currents and most of the ill effects are due to these currents. No useful conclusions can be drawn without knowledge of the spectrum of the current harmonics but it is still common to find only the total harmonic distortion (THD) figures quoted. When harmonics propagate around a distribution system, that is, to branch circuits not concerned with carrying the harmonic current, they do so as voltages. It is very important that both voltage and current values are measured and that quoted values are explicitly specified as voltage and current values. Conventionally, current distortion measurements are suffixed with ‘I’, e.g. 35 % THDI, and voltage distortion figures with ‘V’, e.g. 4 % THDV. Harmonic currents have been present in the electricity supply system for many years. Initially they were produced by the mercury arc rectifiers used to convert AC to DC current for railway electrification and for DC variable speed drives in industry. More recently the range of types and the number of units of equipment causing harmonics have risen sharply, and will continue to rise, so designers and specifiers must now consider harmonics and their side effects very carefully. This section describes how and why harmonics are generated, how the presence of harmonics affects the electrical system and equipment and how to minimise these effects. 5th Harmonic (50%) Fundamental 3rd Harmonic (70%) -2 -1 0 1 2 0 90 270 360180 -2 -1 0 1 2 0 90 270 360180 Figure 2 - Distorted current waveform
  • 3. Causes and Effects 22 Types of equipment that generate harmonics Harmonic load currents are generated by all non-linear loads. These include: Single phase loads, e.g. Switched mode power supplies (SMPS) Electronic fluorescent lighting ballasts Small uninterruptible power supplies (UPS) units Three phase loads, e.g. Variable speed drives Large UPS units Single phase loads Switched mode power supplies (SMPS) The majority of modern electronic units use switched mode power supplies (SMPS). These differ from older units in that the traditional step-down transformer and rectifier is replaced by direct controlled rectification of the supply to charge a reservoir capacitor from which the direct current for the load is derived by a method appropriate to the output voltage and current required. The advantage – to the equipment manufacturer – is that the size, cost and weight is significantly reduced and the power unit can be made in almost any required form factor. The disadvantage – to everyone else – is that, rather than drawing continuous current from the supply, the power supply unit draws pulses of current which contain large amounts of third and higher harmonics and significant high frequency components (see Figure 3). A simple filter is fitted at the supply input to bypass the high frequency components from line and neutral to ground but it has no effect on the harmonic currents that flow back to the supply. The earth leakage effects of these filters are discussed in Section 6. Single phase UPS units exhibit very similar characteristics to SMPS. For high power units there has been a recent trend towards so-called power factor corrected inputs. The aim is to make the power supply load look like a resistive load so that the input current appears sinusoidal and in phase with the applied voltage. It is achieved by drawing input current as a high frequency triangular waveform that is averaged by the input filter to a sinusoid. This extra level of sophistication is not yet readily applicable to the low-cost units that make up most of the load in commercial and industrial installations. It remains to be seen what problems the wide-scale application of this technology may involve! Fluorescent lighting ballasts Electronic lighting ballasts have become popular in recent years following claims for improved efficiency. Overall they are only a little more efficient than the best magnetic ballasts and in fact, most of the gain is attributable to the lamp being more efficient when driven at high frequency rather than to the electronic ballast itself. Their chief advantage is that the light level can be maintained over an extended lifetime by feedback control of the running current - a practice that reduces the overall lifetime efficiency. Their great disadvantage is that they generate harmonics in the supply current. So called power-factor corrected types 0 20 40 60 80 100 1 3 5 7 9 11 13 15 17 Harmonic number %Magnitudewrtfundamental Figure 3 - Harmonic spectrum of a typical PC
  • 4. Causes and Effects 3 are available at higher ratings that reduce the harmonic problems, but at a cost penalty. Smaller units are usually uncorrected. Compact fluorescent lamps (CFL) are now being sold as replacements for tungsten filament bulbs. A miniature electronic ballast, housed in the connector casing, controls a folded 8mm diameter fluorescent tube. CFLs rated at 11 watt are sold as replacements for a 60 watt filament lamp and have a life expectancy of 8000 hours. The harmonic current spectrum is shown in Figure 4. These lamps are being widely used to replace filament bulbs in domestic properties and especially in hotels where serious harmonic problems are suddenly becoming common. Three phase loads Variable speed controllers, UPS units and DC converters in general are usually based on the three-phase bridge, also known as the six-pulse bridge because there are six pulses per cycle (one per half cycle per phase) on the DC output. The six pulse bridge produces harmonics at 6n +/- 1, i.e. at one more and one less than each multiple of six. In theory, the magnitude of each harmonic is the reciprocal of the harmonic number, so there would be 20 % fifth harmonic and 9 % eleventh harmonic, etc. A typical spectrum is shown in Figure 6. The magnitude of the harmonics is significantly reduced by the use of a twelve-pulse bridge. This is effectively two six-pulse bridges, fed from a star and a delta transformer winding, providing a 30 degrees phase shift between them. The 6n harmonics are theoretically removed, but in practice, the amount of reduction depends on the matching of the converters and is typically by a factor between 20 and 50. The 12n harmonics remain unchanged. Not only is the total harmonic current reduced, but also those that remain are of a higher order making the design of the filter much easier. 0 20 40 60 80 100 %Magnitudewrtfundamental 1ph 1d 0 20 40 60 80 100 1 3 5 7 9 11 13 15 17 19 21 23 25 Harmonic number %Magnitudewrtfundamental Figure 4 - Harmonic spectrum of a typical CFL Figure 5 - Three-phase, or six-pulse, bridge Figure 6 - Harmonic spectrum of a typical 6-pulse bridge
  • 5. Causes and Effects 4 Often the equipment manufacturer will have taken some steps to reduce the magnitudes of the harmonic currents, perhaps by the addition of a filter or series inductors. In the past this has led some manufacturers to claim that their equipment is ‘G5/3’ compliant. Since G5/3 is a planning standard applicable to a complete installation, it cannot be said to have been met without knowledge of every piece of equipment on the site. A further increase in the number of pulses to 24, achieved by using two parallel twelve-pulse units with a phase shift of 15 degrees, reduces the total harmonic current to about 4.5 %. The extra sophistication increases cost, of course, so this type of controller would be used only when absolutely necessary to comply with the electricity suppliers’ limits. Theoretical background – how harmonics are generated In an ideal clean power system, the current and voltage waveforms are pure sinusoids. In practice, non-sinusoidal currents result when the current flowing in the load is not linearly related to the applied voltage. In a simple circuit containing only linear circuit elements - resistance, inductance and capacitance - the current which flows is proportional to the applied voltage (at a particular frequency) so that, if a sinusoidal voltage is applied, a sinusoidal current will flow, as illustrated in Figure 9. The load-line is the relationship between the voltage applied and the current that results in the load; that shown in Figure 9 corresponds to a linear load. Note that where there is a reactive element there will be a phase shift between the voltage and current waveforms; the power factor is reduced, but the circuit can still be linear. Figure 10 shows the situation where the load is a simple full-wave rectifier and capacitor, such as the input stage of a typical switched mode power supply. In this case, current flows only when the supply voltage exceeds that stored on the reservoir capacitor, i.e. close to the peak of Figure 8 - Harmonic spectrum of a typical 12 pulse bridge Angle Angle Voltage Waveform Current Waveform V I Load Line Figure 7 - Twelve-pulse bridge Figure 9 - Current waveform in a linear load
  • 6. Causes and Effects 5 the voltage sinewave, as shown by the shape of the load line. In practice, the load line (and hence the current waveform) is likely to be much more complex than shown in this illustrative example; there may be some asymmetry and hysteresis and the breakpoints and slopes will change with loading. Any cyclical waveform can be de- constructed into a sinusoid at the fundamental frequency plus a number of sinusoids at harmonic frequencies. Thus the distorted current waveform in Figure 10 can be represented by the fundamental plus a percentage of second harmonic plus a percentage of third harmonic and so on, possibly up to the thirtieth harmonic. For symmetrical waveforms, i.e. where the positive and negative half cycles are the same shape and magnitude, all the even numbered harmonics are zero. Even harmonics are now relatively rare but were common when half wave rectification was widely used. The equivalent circuit of a non-linear load is shown in Figure 11. It can be modelled as a linear load in parallel with a number of current sources, one source for each harmonic frequency. The harmonic currents generated by the load – or more accurately converted by the load from fundamental to harmonic current – have to flow around the circuit via the source impedance and all other parallel paths. As a result, harmonic voltages appear across the supply impedance and are present throughout the installation. Harmonic generators are sometimes shown as voltage generators; if this were true then the source impedance would have no influence on the magnitude of the harmonic voltage across the source. In reality the magnitude of this voltage is proportional (over a limited range) to the source impedance indicating that the generator behaves as a current source. Source impedances are very low so the harmonic voltage distortion resulting from a harmonic current is also low and often hardly above the network background. This can be misleading because it gives the impression that there is not likely to be a harmonic problem when in fact large harmonic currents are present. It is rather similar to trying to find a circulating earth current with a voltmeter. Whenever harmonics are suspected, or when trying to verify their absence, the current must be measured. Problems caused by harmonics Harmonic currents cause problems both on the supply system and within the installation. The effects and the solutions are very different and need to be addressed separately; the measures that are appropriate to controlling the effects of harmonics within the installation may not necessarily reduce the distortion caused on the supply and vice versa. Source Impedance LinearLoadImpedance Supply Installation I 3rd I 5th I 7th V~ I Angle Angle V Voltage Waveform Current Waveform Load Line Figure 10 - Current waveform in a non-linear load Figure 11 - Equivalent circuit of a non-linear load
  • 7. Causes and Effects 6 Harmonic problems within the installation There are several common problem areas caused by harmonics: - Problems caused by harmonic currents: overloading of neutrals overheating of transformers nuisance tripping of circuit breakers over-stressing of power factor correction capacitors skin effect Problems caused by harmonic voltages: voltage distortion induction motors zero-crossing noise Problems caused when harmonic currents reach the supply Each of these areas is discussed briefly in the following sections. Problems caused by harmonic currents Neutral conductor over-heating In a three-phase system the voltage waveform from each phase to the neutral star point is displaced by 120° so that, when each phase is equally loaded, the combined current in the neutral is zero. When the loads are not balanced only the net out of balance current flows in the neutral. In the past, installers (with the approval of the standards authorities) have taken advantage of this fact by installing half-sized neutral conductors. However, although the fundamental currents cancel out, the harmonic currents do not - in fact those that are an odd multiple of three times the fundamental, the ‘triple-N’ harmonics, add in the neutral. Figure 12 shows the effect. In this diagram the phase currents, shown at the top, are introduced at 120° 0 120 240 360 480 600 720 Phase 1 Phase 2 Phase 3 Phase 1 3rd harmonic Phase 2 3rd harmonic Phase 3 3rd harmonic 3rd harmonic neutral current Figure 12 – Triple-N currents add in the neutral
  • 8. Causes and Effects 7 intervals. The third harmonic of each phase is identical, being three times the frequency and one-third of a (fundamental) cycle offset. The effective third harmonic neutral current is shown at the bottom. In this case, 70 % third harmonic current in each phase results in 210 % current in the neutral. Case studies in commercial buildings generally show neutral currents between 150 % and 210 % of the phase currents, often in a half-sizedconductor! There is some confusion as to how designers should deal with this issue. The simple solution, where single- cored cables are used, is to install a double sized neutral, either as two separate conductors or as one single large conductor. The situation where multi-cored cables are used is not so simple. The ratings of multi- core cables (for example as given in IEC 60364–5-523 Table 52 and BS 7671 Appendix 4) assume that the load is balanced and the neutral conductor carries no current, in other words, only three of the four or five cores carry current and generate heat. Since the cable current carrying capacity is determined solely by the amount of heat that it can dissipate at the maximum permitted temperature, it follows that cables carrying triple-N currents must be de-rated. In the example illustrated above, the cable is carrying five units of current – three in the phases and two in the neutral – while it was rated for three units. It should be de-rated to about 60 % of the normal rating. IEC 60364-5-523 Annex C (Informative) suggests a range of de-rating factors according to the triple-N harmonic current present. Figure 13 shows de- rating factor against triple-N harmonic content for the de-rating described in IEC 60364-5-523 Annex C and for the thermal method used above. The regulatory position is under discussion at present and it is likely that new requirements and guidance notes will be introduced into national wiring codes in the near future. Effects on transformers Transformers are affected in two ways by harmonics. Firstly, the eddy current losses, normally about 10 % of the loss at full load, increase with the square of the harmonic number. In practice, for a fully loaded transformer supplying a load comprising IT equipment the total transformer losses would be twice as high as for an equivalent linear load. This results in a much higher operating temperature and a shorter life. In fact, under these circumstances the lifetime would reduce from around 40 years to more like 40 days! Fortunately, few transformers are fully loaded, but the effect must be taken into account when selecting plant. The second effect concerns the triple-N harmonics. When reflected back to a delta winding they are all in phase, so the triple-N harmonic currents circulate in the winding. The triple-N harmonics are effectively absorbed in the winding and do not propagate onto the supply, so delta wound transformers are useful as isolating transformers. Note that all other, non triple-N, harmonics pass through. The circulating current has to be taken into account when rating the transformer. A detailed discussion on rating transformers for harmonic currents can be found in a later section of the Guide. Nuisance tripping of circuit breakers Residual current circuit breakers (RCCB) operate by summing the current in the phase and neutral conductors and, if the result is not within the rated limit, disconnecting the power from the load. Nuisance tripping can occur in the presence of harmonics for two reasons. Firstly, the RCCB, being an electromechanical device, may not sum the higher frequency components correctly and therefore trips erroneously. Secondly, the kind of equipment that generates harmonics also generates switching noise that must be filtered at the equipment power connection. The filters normally used for this purpose have a capacitor from line and neutral to ground, and so leak a small current to earth. This current is limited by standards to less than 3.5 mA, and is 0.4 0.6 0.8 1.0 0 10 20 30 40 50 60 70 % third harmonic Cablederatingfactor TThheerrmmaall IIEECC Figure 13 - Cable derating for triple-N harmonics
  • 9. usually much lower, but when equipment is connected to one circuit the leakage current can be sufficient to trip the RCCB. The situation is easily overcome by providing more circuits, each supplying fewer loads. A later section of this Guide covers the problem of high earth leakage in greater detail. Nuisance tripping of miniature circuit breakers (MCB) is usually caused because the current flowing in the circuit is higher than that expected from calculation or simple measurement due to the presence of harmonic currents. Most portable measuring instruments do not measure true RMS values and can underestimate non-sinusoidal currents by 40 %. True RMS measurement is discussed in Section 3.2.2. Over-stressing of power factor correction capacitors Power factor correction capacitors are provided in order to draw a current with a leading phase angle to offset lagging current drawn by an inductive load such as induction motors. Figure 14 shows the effective equivalent circuit for a PFC capacitor with a non-linear load. The impedance of the PFC capacitor reduces as frequency rises, while the source impedance is generally inductive and increases with frequency. The capacitor is therefore likely to carry quite high harmonic currents and, unless it has been specifically designed to handle them, damage can result. A potentially more serious problem is that the capacitor and the stray inductance of the supply system can resonate at or near one of the harmonic frequencies (which, of course, occur at 100 Hz intervals). When this happens very large voltages and currents can be generated, often leading to the catastrophic failure of the capacitor system. Resonance can be avoided by adding an inductance in series with the capacitor such that the combination is just inductive at the lowest significant harmonic. This solution also limits the harmonic current that can flow in the capacitor. The physical size of the inductor can be a problem, especially when low order harmonics are present. Causes and Effects 8 Supply Impedance Supply Linear Load Non-linear Load Supply Voltage Waveform Voltage Waveform applied to Load Current in Linear Load Load Current Cable Impedance Cable Impedance Cable Impedance Point of Common Coupling Linear Load Non-linear Load Supply Voltage Waveform Voltage Waveform applied to Linear-load Current in Linear-load Load Current Voltage Waveform applied to Non-linear Load Figure 16 - Separation of linear and non-linear loads Figure 15 - Voltage distortion caused by a non-linear load Source Impedance LinearLoadImpedance Supply Installation I 3rd I 5th I 7th V~ I 3rd + I 5th + I 7th PFC Figure 14 - Equivalent circuit of a non-linear load with a PFC capacitor
  • 10. Causes and Effects 9 Skin effect Alternating current tends to flow on the outer surface of a conductor. This is known as skin effect and is more pronounced at high frequencies. Skin effect is normally ignored because it has very little effect at power supply frequencies but above about 350 Hz, i.e. the seventh harmonic and above, skin effect will become significant, causing additional loss and heating. Where harmonic currents are present, designers should take skin effect into account and de-rate cables accordingly. Multiple cable cores or laminated busbars can be used to help overcome this problem. Note also that the mounting systems of busbars must be designed to avoid mechanical resonance at harmonic frequencies. Problems caused by harmonic voltages Because the supply has source impedance, harmonic load currents give rise to harmonic voltage distortion on the voltage waveform (this is the origin of ‘flat topping’). There are two elements to the impedance: that of the internal cabling from the point of common coupling (PCC), and that inherent in the supply at the PCC, e.g. the local supply transformer. The former is illustrated in Figure 15. The distorted load current drawn by the non-linear load causes a distorted voltage drop in the cable impedance. The resultant distorted voltage waveform is applied to all other loads connected to the same circuit, causing harmonic currents to flow in them - even if they are linear loads. The solution is to separate circuits supplying harmonic generating loads from those supplying loads which are sensitive to harmonics, as shown in Figure 16. Here separate circuits feed the linear and non-linear loads from the point of common coupling, so that the voltage distortion caused by the non-linear load does not affect the linear load. When considering the magnitude of harmonic voltage distortion it should be remembered that, when the load is transferred to a UPS or standby generator during a power failure, the source impedance and the resulting voltage distortion will be much higher. Where local transformers are installed, they should be selected to have sufficiently low output impedance and to have sufficient capacity to withstand the additional heating, in other words, by selecting an appropriately oversized transformer. Note that it is not appropriate to select a transformer design in which the increase in capacity is achieved simply by forced cooling – such a unit will run at higher internal temperatures and have a reduced service life. Forced cooling should be reserved for emergency use only and never relied upon for normal running. Induction Motors Harmonic voltage distortion causes increased eddy current losses in motors in the same way as in transformers. However, additional losses arise due to the generation of harmonic fields in the stator, each of which is trying to rotate the motor at a different speed either forwards or backwards. High frequency currents induced in the rotor further increase losses. Where harmonic voltage distortion is present motors should be de-rated to take account of the additional losses. Zero-crossing noise Many electronic controllers detect the point at which the supply voltage crosses zero volts to determine when loads should be turned on. This is done because switching reactive loads at zero voltage does not generate transients, so reducing electromagnetic interference (EMI) and stress on the semiconductor switching devices. When harmonics or transients are present on the supply the rate of change of voltage at the crossing becomes faster and more difficult to identify, leading to erratic operation. There may in fact be several zero-crossings per half cycle. Harmonic problems affecting the supply When a harmonic current is drawn from the supply it gives rise to a harmonic voltage drop proportional to the source impedance at the point of common coupling (PCC) and the current. Since the supply network is generally inductive, the source impedance is higher at higher frequencies. Of course, the voltage at the PCC is already distorted by the harmonic currents drawn by other consumers and by the distortion inherent in transformers, and each consumer makes an additional contribution.
  • 11. Clearly, customers cannot be allowed to add pollution to the system to the detriment of other users, so in most countries the electrical supply industry has established regulations limiting the magnitude of harmonic current that can be drawn. Harmonic mitigation measures The measures available to control the magnitude of harmonic current drawn are discussed in detail in later sections of this Guide. In this section a brief overview is given in generic terms. Mitigation methods fall broadly into three groups; passive filters, isolation and harmonic reduction transformers and active solutions. Each approach has advantages and disadvantages, so there is no single best solution. It is very easy to spend a great deal of money on an inappropriate and ineffective solution; the moral is to carry out a thorough survey – tools suitable for this purpose are described elsewhere in this Guide. Passive filters Passive filters are used to provide a low impedance path for harmonic currents so that they flow in the filter and not the supply (Figure 17). The filter may be designed for a single harmonic or for a broad band depending on requirements. Sometimes it is necessary to design a more complex filter to increase the series impedance at harmonic frequencies and so reduce the proportion of current that flows back onto the supply, as shown in Figure 18. Simple series band stop filters are sometimes proposed, either in the phase or in the neutral. A series filter is intended to block harmonic currents rather than provide a controlled path for them so there is a large harmonic voltage drop across it. This harmonic voltage appears across the supply on the load side. Since the supply voltage is heavily distorted it is no longer within the standards for which equipment was designed and warranted. Some equipment is relatively insensitive to this distortion, but some is very sensitive. Series filters can be useful in certain circumstances, but should be carefully applied; they cannot be recommended as a general purpose solution. Isolation transformers As mentioned previously, triple-N currents circulate in the delta windings of transformers. Although this is a problem for transformer manufacturers and specifiers - the extra load has to be taken into account – it is beneficial to systems designers because it isolates triple-N harmonics from the supply. Causes and Effects Supply Load I3 Figure 19 - Delta star isolation transformer Source Impedance LinearLoadImpedance Supply Installation I 3rd I 5th I 7th V~ Shunt Filter (band pass) Series Filter (band stop) Ih Figure 18 - Passive series and shunt filters Source Impedance LinearLoadImpedance Supply Installation I 3rd I 5th I 7th V~ Shunt Filter (band pass) Ih Figure 17 - Passive harmonic shunt filter 10
  • 12. Causes and Effects 11 The same effect can be obtained by using a ‘zig-zag’ wound transformer. Zig-zag transformers are star configuration auto transformers with a particular phase relationship between the windings that are connected in shunt with the supply. Active Filters The solutions mentioned so far have been suited only to particular harmonics, the isolating transformer being useful only for triple-N harmonics and passive filters only for their designed harmonic frequency. In some installations the harmonic content is less predictable. In many IT installations, for example, the equipment mix and location is constantly changing so that the harmonic culture is also constantly changing. A convenient solution is the active filter or active conditioner. As shown in Figure 20, the active filter is a shunt device. A current transformer measures the harmonic content of the load current, and controls a current generator to produce an exact replica that is fed back onto the supply on the next cycle. Since the harmonic current is sourced from the active conditioner, only fundamental current is drawn from the supply. In practice, harmonic current magnitudes are reduced by 90 % and, because the source impedance at harmonic frequencies is reduced, voltage distortion is reduced. Conclusion Virtually all modern electrical and electronic equipment contains a SMPS or involves some form of power control and so is a non-linear load. Linear loads are comparatively rare, undimmed filament bulbs and uncontrolled heaters being the only common examples. Future equipment Standards are discussed in detail in a later section of this Guide, but have not been set tightly enough to make a real impact on harmonic pollution produced by electronic equipment such as PCs. It is this class of equipment that is causing many of the harmonic problems seen in industry and commerce today, partly because there are so many of them installed and partly because the type of harmonics they produce – the triple-Ns – cause so many problems. As the quantity of installed equipment rises, and without very strong standards backed up by rigid enforcement measures, it is likely that harmonic pollution will continue to increase. This is a risk to business that needs to be managed by investment in good design practice, the right electrical equipment and good maintenance. Power Quality Application Guide Version 0b November 2001 Source Impedance LinearLoadImpedance Supply Installation I 3rd I 5th I 7th V~ Ih Fundamental Current I fund Load Current I load Active Conditioner HarmonicCurrent Figure 20 - Active harmonic conditioner