ARE HARMONICS
STILLAPROBLEM
IN DATACENTERS ?
by Mohammad Al – Rawashdeh,
Lead Consultant, Data Center Engineering Services
info@edaratgroup.com | www.edaratgroup.com 2
edarat group  Are Harmonics Still A Problem In Data Centers?
INTRODUCTION
Harmonics are a mathematical way of describing distortion to a voltage or current waveform. The term
harmonic refers to a component of a wave form that occurs at an integer multiple of the fundamental
frequency. Fourier theory tells us that any repetitive waveform can be defined in terms of summing si-
nusoidal waveforms which are integer multiples (or harmonics) of the fundamental frequency. For the
purpose of a steady state waveform with equal positive and negative half-cycles, the Fourier series can be
expressed as follows:
F (t) = S
∞
n = 1
An . Sin (nPt / T)
where
f(t) is the time domain function
n is the harmonic number (only odd values of n are required)
An is the amplitude of the nth harmonic component
T is the length of one cycle in seconds
A common term that is used in relation to harmonics is THD or Total Harmonic distortion. THD can be
used to describe voltage or current distortion and is calculated as follows:
THD (%) = √(ID1
² + ID2
² + ... + IDn
²)
where
IDn
: is the magnitude of the nth harmonic as a percentage of the fundamental (individual distortion).
info@edaratgroup.com | www.edaratgroup.com 3
edarat group  Are Harmonics Still A Problem In Data Centers?
Harmonics are currents or voltages with frequencies that are integer multiples of the fundamental power
frequency. If the fundamental power frequency is 60 Hz, then the 2nd
harmonic is 120 Hz, the 3rd
is 180 Hz,
etc. (see Figure 1). When harmonic frequencies are prevalent, electrical power panels and transformers
become mechanically resonant to the magnetic fields generated by higher frequency harmonics. When
this happens, the power panel or transformer vibrates and emits a buzzing sound for the different har-
monic frequencies. Harmonic frequencies from the 3rd
to the 25th
are the most common range of fre-
quencies measured in electrical distribution systems.
Distorted wave form (60 Hz - Fundamental + 3rd Harmonic)
3rd Harmonic (180 Hz)
Fundamental (60 Hz)
Figure 1
When all harmonic currents are added to the fundamental a waveform known as complex wave is formed.
An example of complex wave consisting of the fundamental (1st
harmonic), 3rd
harmonic and 5th
harmonic
is illustrated in Figure 2:
50 Hz Waveform
150 Hz Waveform
200 Hz Waveform
Symmetrical
Complex
Waveform
1
0.8
-45 0 45 90 135 180 225 270 315
0.6
0.4
0.2
0
-0.2
-0.4
-0.6
-0.8
-1
Figure 2
info@edaratgroup.com | www.edaratgroup.com 4
edarat group  Are Harmonics Still A Problem In Data Centers?
The total harmonic distortion (THD) of a signal is a measurement of the harmonic distortion present and is
defined as the ratio of the sum of the powers of all harmonic components to the power of the fundamen-
tal. It provides an indication of the degree to which a voltage or current signal is distorted (see Figure 3).
THD = 98%
Harmonic
%-Fund.
0
20
40
60
80
100
0 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Figure 3
info@edaratgroup.com | www.edaratgroup.com 5
edarat group  Are Harmonics Still A Problem In Data Centers?
NON-LINEAR LOADS
A linear load draws current that is instantaneously proportional to the voltage, such as in Figure 4 (Linear
time-aligned (unity or 100% power factor) voltage and current waveforms) and Figure 5 (Linear shifted
alignment (at 80% leading power factor) between voltage and current). One example of a linear load is a
resistive load, such as an incandescent light bulb.
1
0.8
0.6
0.4
0.2
0
-0.2
-0.4
-0.6
-0.8
-1
0
40
90
130
180
220
270
310
360
Figure 4
1
0.8
0.6
0.4
0.2
0
-0.2
-0.4
-0.6
-0.8
-1
0
45
90
1.35
180
225
270
315
360
Figure 5
info@edaratgroup.com | www.edaratgroup.com 6
edarat group  Are Harmonics Still A Problem In Data Centers?
A nonlinear load either draws a current waveform that is not instantaneously proportional to the voltage
or is a load that causes current to distort its sinusoidal shape. The current waveform also leads or lags
voltage or phase.
Harmonics are distortions of the normal electrical current waveform, generally transmitted by nonlinear
loads -Non-linear loads occur when the resistance is not a constant and changes during each sine wave
of the applied voltage waveform, resulting in a series of positive and negative pulses. Switch-mode power
supplies (SMPS), variable speed motors and drives, photocopiers, personal computers, laser printers, fax
machines, battery chargers, and UPSs are examples of nonlinear loads. Single-phase nonlinear loads are
prevalent in modern office buildings- Data Center, while 3-phase nonlinear loads are common in facto-
ries and industrial plants.
A large portion of the nonlinear electrical loads in most electrical distribution systems comes from SMPS
equipment. For example, all computer systems use SMPS that convert utility AC voltage to regulat-
ed low-voltage DC for internal
electronics. These nonlinear
power supplies draw current
in high-amplitude short pulses
that create significant distortion
intheelectricalcurrentandvolt-
age wave shape (see Figure 6).
This harmonic distortion, mea-
sured as total harmonic distor-
tion (THD), travels back into the
power source and can affect
other equipment connected to
the same source.
Most power systems can accommodate a certain level of harmonic currents but will experience prob-
lems when harmonics become a significant component of the overall load. As these higher frequencies
harmonic currents flow through the power system, they can cause communication errors, overheating
and hardware damage, such as:
zz Overheating of electrical distribution equipment, cables, transformers, standby generators, etc.
zz High voltages and circulating currents caused by harmonic resonance
zz Equipment malfunctions due to excessive voltage distortion
zz Increased internal energy losses in connected equipment, causing component failure and shortened
life span
zz False tripping of branch circuit breakers
zz Metering errors
zz Fires in wiring and distribution systems
zz Generator failures
zz Crest factors and related problems
zz Lower system power factor, resulting in penalties on monthly utility bills
Figure 6
info@edaratgroup.com | www.edaratgroup.com 7
edarat group  Are Harmonics Still A Problem In Data Centers?
HARMONICS REDUCTION SOLUTIONS
To determine if harmonic mitigation is necessary, should conduct an assessment to precisely measure
the harmonics affecting the data center and identify their origin. Options for harmonic mitigation vary
in complexity and cost and can be deployed individually or in combination. The strategy that makes the
most sense for a facility will vary based on the loads it supports, its budget, and the nature of the harmon-
ic-related problems it is experiencing.
There are several approaches that can be taken to compensate for or reduce harmonics in the power
system, with varying degrees of effectiveness and efficiency.
200% neutral conductors
One option is to specify an 200% neutral conductor or to use separate neutral conductors. Triple n har-
monics (3, 9, 15, etc.) can produce neutral currents that can be up to the theoretical maximum of 173% of
the phase current, which is why a 200% neutral conductor is usually specified.
K-rated transformers:
A standard transformer is not designed for high harmonic currents produced by nonlinear loads.
It will overheat and fail prematurely when connected to these loads. Therefore, when harmon-
ics were first introduced into electrical systems at levels that showed detrimental effects (cir-
ca 1980), the industry responded by developing the K-rated transformer. K-rated transform-
ers are not used to eliminate harmonics, but to manage the heat generated by harmonic currents.
K factor ratings range between 1 and 50. A standard transformer designed for linear loads is designated
with a K-factor of 1. The higher the K-factor, the more heat from harmonic currents the transformer is
able to withstand. When selecting a K rating, managers should consider the trade-offs between size, effi-
ciency, and heat tolerance. For example, transformers with higher K factors are typically larger than those
with lower K factors. The table 1 below shows appropriate K ratings to use for different percentages of
nonlinear current in the electrical system.
Non-linear load K- Rating
Incidental electronic equipment representing less than 5% K 1
Harmonic producing equipment representing less than 35 % K4
Harmonic producing equipment representing less than 50 % K 7
Harmonic producing equipment representing less than 75 % K 13
Harmonic producing equipment representing less than 100 % K 20
Table 1
info@edaratgroup.com | www.edaratgroup.com 8
edarat group  Are Harmonics Still A Problem In Data Centers?
Uninterruptable Power Supply- UPS
Since UPSs and the loads they serve have historically been considered some of the most significant har-
monic loads on a power system, companies can also use harmonic-mitigating UPSs to reduce line har-
monics. Much like active filters, harmonic-mitigating UPSs eliminate harmonic distortion by inserting
equal and opposite current into the line. They also compensate for reactive power from low power factor
loads and balance loads across three phases to avoid stranded capacity, while providing clean and con-
tinuous power during utility outages or in response to electrical disturbances.
Harmonics filters
Harmonic filters remove harmonics and correct the phase of the fundamental current, thus converting
non-linear loads into linear loads. Passive, and Active filters, it can be either used as a standalone part
integral to a large nonlinear load or can be used for a multiple small single phase nonlinear loads by con-
necting it to a switch board.
Passive filter
A Passive Filter uses inductors capacitors and resistors in combination to create the filter. Passive imple-
mentations of linear filters are based on combinations of resistors (R), inductors (L) and capacitors (C).
These types are collectively known as passive filters, because they do not depend upon an external power
supply and/or they do not contain active components such as transistors.
Active filter
This method uses sophisticated electronics and power section IGBTs to inject equal and opposite har-
monics onto the power system to cancel those generated by other equipment. These filters monitor the
nonlinear currents demanded from nonlinear loads and electronically generate currents that match and
cancel the destructive harmonic currents. Active filters are inherently non-resonating and are easily con-
nected in parallel with system loads.
PRINCIPLE DRAWING
LOAD MAINS
MAINSi
MAINSH
MAINSi
LOADH
LOADi
MAINS
Connection
AHF
AHFi
LOADi
info@edaratgroup.com | www.edaratgroup.com 9
edarat group  Are Harmonics Still A Problem In Data Centers?
Advantages
zz Guarantee compliance with IEEE 519 1992 if sized correctly
zz Harmonic cancellation from the 2nd to 51st harmonic
zz No series connection provides easy installation with no major systema rework
zz Provide VAR currents, improving system power factor
Disadvantages
zz Can be more expensive than other methods due to the high performance control and power sections
zz The filter’s input semiconductors are exposed to line transients.
With increase in use of non-linear loads, the issues of power supply harmonics are more noticeable than
ever. Controlling and monitoring industrial system designs and their effects on utility distribution systems
are potential problems for the industrial consumer, who is responsible for complying with the IEEE 519,
recommended practices and procedures.
Industrial facilities should include a system evaluation, including a harmonic distortion analysis, while
planning facility construction or expansion. Vendors of non-linear loads, such as variable frequency
drives, can provide services and recommend equipment that will reduce harmonics in order to comply
with IEEE 519 guidelines.
Generally, at any point the measured value of total harmonic voltage distortion should not exceed 5%
and that of any individual harmonic voltage distortion should not exceeding 3% of the fundamental value
of the line voltage. Normally, in typical applications, the harmonics are measured up to 25th
order, but in
critical applications, those are measured up to 50th
or 100th
order.
A better way to handle harmonics in the data center is to simply design better systems and devices, which
fortunately has already been accomplished for the most part. In order to offer products in the world-wide
market, nearly every computer equipment manufacture is in compliance.
To comply with the regulation, global computer equipment vendors developed Power Factor Corrected
(PFC) power supply technology. Power factor is the ratio of the real power to the load and the apparent
power and is a number between zero and one (e.g., 0.5 pf = 50%pf). Real power is the capacity of the
circuit. Apparent power is the product of the current and voltage in the circuit. If energy is stored in the
load and returned to the source, or if is distorted by a non-linear load, the apparent power will be greater
than the real power. Loads with a high power factor draw less current than loads with low power factors,
and these higher currents increase energy loss and require larger equipment.
Switched-mode power supplies have a low power factor. PFC power supplies control the harmonic cur-
rent using either a filter or an electronic system that controls the amount of power drawn by the load. The
purpose of the PFC is to make the power factor as close to one as possible, where the current waveform
is proportional to the voltage waveform. When this is the case, the voltage and current are in phase and
the reactive power consumption is zero, enabling power companies to efficiently deliver power. In other
words, all of the energy supplied by the source is consumed by the load and none is returned to the source.
info@edaratgroup.com | www.edaratgroup.com 10
edarat group  Are Harmonics Still A Problem In Data Centers?
CONCLUSION
Harmonics in the data center was a real concern in the past. Fortunately, it is one of those issues that are
close to being solved, at least for computing equipment, by regulatory agencies and computer equipment
manufactures. It’s not an issue that receives a lot of press or marketing, as companies tend to focus more
on the more tangible benefit of energy efficiency and reduced energy costs, which is why the subject of
harmonics is still occasionally raised as an issue when designing new power distribution systems. Facilities
managers or electrical architects who are unfamiliar with modern computer equipment might specify
costly solutions such as K-factor transformers or 200% neutral conductors, to handle non-linear loads
and harmonic neutral currents that are relatively rare in today’s IT environments. Data center managers
who are armed with the knowledge that computer vendors are compliant with harmonic elimination
standards can help drive more realistic and cost-effective power distribution designs in the data center
and be more proactive in replacing non-conforming, legacy equipment. Simply stated, 100% rated neutral
conductors are suitable for the vast majority of applications.
Circumstances might arise where oversize neutral conductors are necessary for the remaining non-linear
loads in the data center, such as lighting and cooling equipment, or legacy equipment that must be main-
tained for a particular application.
info@edaratgroup.com | www.edaratgroup.com 11
edarat group  Are Harmonics Still A Problem In Data Centers?
References
Mitigating data center harmonics
http://pqlit.eaton.com/ll_download_bylitcode.asp?doc_id=26534
Neutral Ratings for Power Distribution Systems in the Data Center
http://www.starlinepower.com/busway/uploads/docs/en/UE_NeutralRatings.pdf
Harmonics in your electrical system
http://www.newark.com/pdfs/techarticles/eaton/Eaton_Technical_Articles/UPS_Training/Powerware_
Training/HarmonicsInYourElecSystem.pdf.
Harmonic reduction methods
http://www.eaton.com/ecm/idcplg?IdcService=GET_FILEdID=687518.

More Related Content

PPTX
Transformer Diagnostics | Sweep Frequency Response Analysis
PPTX
Rotor earth fault protection of electric generator
PPTX
Transformer tests
PDF
Loss of excitation
PPTX
Boiler Reheater protection
PPT
Generator protection by bhushan kumbhalkar
PPTX
Starters of induction motor and protection equipment
Transformer Diagnostics | Sweep Frequency Response Analysis
Rotor earth fault protection of electric generator
Transformer tests
Loss of excitation
Boiler Reheater protection
Generator protection by bhushan kumbhalkar
Starters of induction motor and protection equipment

What's hot (20)

PPTX
POWER HARMONICS- SOURCES, ISSUES AND MITIGATION
PPTX
On load tap changer
PDF
Testing of Transformers.
DOC
(7) overfluxing
PPTX
Transformers
PPSX
ABT (Availability Based Tariff) - UI (Unscheduled Interchange)
PDF
PPTX
Transformer Parts and functions
PPTX
PPTX
Power Quality
PPT
rajwest thermal power plant
PPT
Feedwater heaters in thermal power plants
PPT
Unit protection scheme
DOCX
RGPV EX7102 unit I
PDF
Generator Protection By - Er Rahul Sharma
PPT
Electro Hydro Governing system for turbine ppt
PDF
Power cable - Installation methods
PDF
Shaft Sealing System on Steam Turbines.pdf
PPTX
Harmonics Presentation by Baldev Raj Narang CEO Clariant Power System Ltd
PPTX
EHVAC transmission line maintenance techniques
POWER HARMONICS- SOURCES, ISSUES AND MITIGATION
On load tap changer
Testing of Transformers.
(7) overfluxing
Transformers
ABT (Availability Based Tariff) - UI (Unscheduled Interchange)
Transformer Parts and functions
Power Quality
rajwest thermal power plant
Feedwater heaters in thermal power plants
Unit protection scheme
RGPV EX7102 unit I
Generator Protection By - Er Rahul Sharma
Electro Hydro Governing system for turbine ppt
Power cable - Installation methods
Shaft Sealing System on Steam Turbines.pdf
Harmonics Presentation by Baldev Raj Narang CEO Clariant Power System Ltd
EHVAC transmission line maintenance techniques
Ad

Viewers also liked (8)

PDF
Efficient Data Center Transformer Practices
PPT
Lọc sóng hài, nhấp nháy điện, nổ tụ bù www.powermore.vn
PDF
InPhase Power - IPC 150 Active Harmonic Filter
PPTX
Sự phát sóng hài bậc II
PPTX
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
PDF
Harmonics mitigation solutions
PDF
Hormonics impact and_mitigation
DOCX
Harmonics
Efficient Data Center Transformer Practices
Lọc sóng hài, nhấp nháy điện, nổ tụ bù www.powermore.vn
InPhase Power - IPC 150 Active Harmonic Filter
Sự phát sóng hài bậc II
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
Harmonics mitigation solutions
Hormonics impact and_mitigation
Harmonics
Ad

Similar to Are Harmonics Still a Problem in Data Centers ? (20)

PDF
Power System Harmonics
PPTX
Harmonics and its types based on harmonic numbers.pptx
PDF
IRJET-Power Quality Effects on Nonlinear Loads
PDF
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
PDF
38_286_Study_on_Mitigation_of_Harmonics_by_Using_Passive_Filter_and_Active_Fi...
DOCX
overview
PPSX
Mill harmonics r1
PDF
Waveforms Cause and effects
PPS
Harmonics in power system
PPTX
Harmonics: Root cause of Premature failure of Distribution transformers feedi...
PPTX
Identification and minimization of Harmonics
PPTX
05 ETAP Harmonic Analysis.pptx
PPT
PQ-1.ppt
PDF
Harmonics: Causes and Effects
PDF
Harmonics
PPTX
2014-09-15 IEEE IAS Atl - Harmonics Study.pptx
PDF
International Journal of Computational Engineering Research(IJCER)
PDF
An Overview of Harmonic Sources in Power System
PPT
Power System Harmonics Causes and Effect.ppt
PPTX
Analysis of harmonic at different level on distribution system ,its effect a...
Power System Harmonics
Harmonics and its types based on harmonic numbers.pptx
IRJET-Power Quality Effects on Nonlinear Loads
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
38_286_Study_on_Mitigation_of_Harmonics_by_Using_Passive_Filter_and_Active_Fi...
overview
Mill harmonics r1
Waveforms Cause and effects
Harmonics in power system
Harmonics: Root cause of Premature failure of Distribution transformers feedi...
Identification and minimization of Harmonics
05 ETAP Harmonic Analysis.pptx
PQ-1.ppt
Harmonics: Causes and Effects
Harmonics
2014-09-15 IEEE IAS Atl - Harmonics Study.pptx
International Journal of Computational Engineering Research(IJCER)
An Overview of Harmonic Sources in Power System
Power System Harmonics Causes and Effect.ppt
Analysis of harmonic at different level on distribution system ,its effect a...

More from Edarat Group (10)

PDF
ADVANTAGES OF FUEL POLISHING SYSTEMS
PDF
Wet stacking effects
PDF
The influence of EMF (electro magnetic field) on data center
PDF
كيفية قياس البنية المؤسسية
PDF
تأثير انعدام الاستقرار السياسي على استراتيجيات استمرارية الأعمال
PDF
Impact of political instability on business continuity
PDF
شركات الاتصالات – فوائد تقييم منشأة الاتصالاتمركز البيانات
PDF
The real cost of business downtime
PDF
Role of cloud in business growth
PDF
How to Better Manage Your IT Infrastructure
ADVANTAGES OF FUEL POLISHING SYSTEMS
Wet stacking effects
The influence of EMF (electro magnetic field) on data center
كيفية قياس البنية المؤسسية
تأثير انعدام الاستقرار السياسي على استراتيجيات استمرارية الأعمال
Impact of political instability on business continuity
شركات الاتصالات – فوائد تقييم منشأة الاتصالاتمركز البيانات
The real cost of business downtime
Role of cloud in business growth
How to Better Manage Your IT Infrastructure

Recently uploaded (20)

PDF
MIND Revenue Release Quarter 2 2025 Press Release
PDF
Getting Started with Data Integration: FME Form 101
PDF
Per capita expenditure prediction using model stacking based on satellite ima...
PPTX
MYSQL Presentation for SQL database connectivity
PDF
Mobile App Security Testing_ A Comprehensive Guide.pdf
PPTX
1. Introduction to Computer Programming.pptx
PDF
Optimiser vos workloads AI/ML sur Amazon EC2 et AWS Graviton
PDF
7 ChatGPT Prompts to Help You Define Your Ideal Customer Profile.pdf
PPTX
KOM of Painting work and Equipment Insulation REV00 update 25-dec.pptx
PDF
Agricultural_Statistics_at_a_Glance_2022_0.pdf
PDF
Advanced methodologies resolving dimensionality complications for autism neur...
PDF
gpt5_lecture_notes_comprehensive_20250812015547.pdf
PDF
Diabetes mellitus diagnosis method based random forest with bat algorithm
PPTX
20250228 LYD VKU AI Blended-Learning.pptx
PPTX
Machine Learning_overview_presentation.pptx
PPTX
SOPHOS-XG Firewall Administrator PPT.pptx
PDF
NewMind AI Weekly Chronicles - August'25-Week II
PDF
The Rise and Fall of 3GPP – Time for a Sabbatical?
PPTX
Group 1 Presentation -Planning and Decision Making .pptx
PDF
TokAI - TikTok AI Agent : The First AI Application That Analyzes 10,000+ Vira...
MIND Revenue Release Quarter 2 2025 Press Release
Getting Started with Data Integration: FME Form 101
Per capita expenditure prediction using model stacking based on satellite ima...
MYSQL Presentation for SQL database connectivity
Mobile App Security Testing_ A Comprehensive Guide.pdf
1. Introduction to Computer Programming.pptx
Optimiser vos workloads AI/ML sur Amazon EC2 et AWS Graviton
7 ChatGPT Prompts to Help You Define Your Ideal Customer Profile.pdf
KOM of Painting work and Equipment Insulation REV00 update 25-dec.pptx
Agricultural_Statistics_at_a_Glance_2022_0.pdf
Advanced methodologies resolving dimensionality complications for autism neur...
gpt5_lecture_notes_comprehensive_20250812015547.pdf
Diabetes mellitus diagnosis method based random forest with bat algorithm
20250228 LYD VKU AI Blended-Learning.pptx
Machine Learning_overview_presentation.pptx
SOPHOS-XG Firewall Administrator PPT.pptx
NewMind AI Weekly Chronicles - August'25-Week II
The Rise and Fall of 3GPP – Time for a Sabbatical?
Group 1 Presentation -Planning and Decision Making .pptx
TokAI - TikTok AI Agent : The First AI Application That Analyzes 10,000+ Vira...

Are Harmonics Still a Problem in Data Centers ?

  • 1. ARE HARMONICS STILLAPROBLEM IN DATACENTERS ? by Mohammad Al – Rawashdeh, Lead Consultant, Data Center Engineering Services
  • 2. info@edaratgroup.com | www.edaratgroup.com 2 edarat group Are Harmonics Still A Problem In Data Centers? INTRODUCTION Harmonics are a mathematical way of describing distortion to a voltage or current waveform. The term harmonic refers to a component of a wave form that occurs at an integer multiple of the fundamental frequency. Fourier theory tells us that any repetitive waveform can be defined in terms of summing si- nusoidal waveforms which are integer multiples (or harmonics) of the fundamental frequency. For the purpose of a steady state waveform with equal positive and negative half-cycles, the Fourier series can be expressed as follows: F (t) = S ∞ n = 1 An . Sin (nPt / T) where f(t) is the time domain function n is the harmonic number (only odd values of n are required) An is the amplitude of the nth harmonic component T is the length of one cycle in seconds A common term that is used in relation to harmonics is THD or Total Harmonic distortion. THD can be used to describe voltage or current distortion and is calculated as follows: THD (%) = √(ID1 ² + ID2 ² + ... + IDn ²) where IDn : is the magnitude of the nth harmonic as a percentage of the fundamental (individual distortion).
  • 3. info@edaratgroup.com | www.edaratgroup.com 3 edarat group Are Harmonics Still A Problem In Data Centers? Harmonics are currents or voltages with frequencies that are integer multiples of the fundamental power frequency. If the fundamental power frequency is 60 Hz, then the 2nd harmonic is 120 Hz, the 3rd is 180 Hz, etc. (see Figure 1). When harmonic frequencies are prevalent, electrical power panels and transformers become mechanically resonant to the magnetic fields generated by higher frequency harmonics. When this happens, the power panel or transformer vibrates and emits a buzzing sound for the different har- monic frequencies. Harmonic frequencies from the 3rd to the 25th are the most common range of fre- quencies measured in electrical distribution systems. Distorted wave form (60 Hz - Fundamental + 3rd Harmonic) 3rd Harmonic (180 Hz) Fundamental (60 Hz) Figure 1 When all harmonic currents are added to the fundamental a waveform known as complex wave is formed. An example of complex wave consisting of the fundamental (1st harmonic), 3rd harmonic and 5th harmonic is illustrated in Figure 2: 50 Hz Waveform 150 Hz Waveform 200 Hz Waveform Symmetrical Complex Waveform 1 0.8 -45 0 45 90 135 180 225 270 315 0.6 0.4 0.2 0 -0.2 -0.4 -0.6 -0.8 -1 Figure 2
  • 4. info@edaratgroup.com | www.edaratgroup.com 4 edarat group Are Harmonics Still A Problem In Data Centers? The total harmonic distortion (THD) of a signal is a measurement of the harmonic distortion present and is defined as the ratio of the sum of the powers of all harmonic components to the power of the fundamen- tal. It provides an indication of the degree to which a voltage or current signal is distorted (see Figure 3). THD = 98% Harmonic %-Fund. 0 20 40 60 80 100 0 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 Figure 3
  • 5. info@edaratgroup.com | www.edaratgroup.com 5 edarat group Are Harmonics Still A Problem In Data Centers? NON-LINEAR LOADS A linear load draws current that is instantaneously proportional to the voltage, such as in Figure 4 (Linear time-aligned (unity or 100% power factor) voltage and current waveforms) and Figure 5 (Linear shifted alignment (at 80% leading power factor) between voltage and current). One example of a linear load is a resistive load, such as an incandescent light bulb. 1 0.8 0.6 0.4 0.2 0 -0.2 -0.4 -0.6 -0.8 -1 0 40 90 130 180 220 270 310 360 Figure 4 1 0.8 0.6 0.4 0.2 0 -0.2 -0.4 -0.6 -0.8 -1 0 45 90 1.35 180 225 270 315 360 Figure 5
  • 6. info@edaratgroup.com | www.edaratgroup.com 6 edarat group Are Harmonics Still A Problem In Data Centers? A nonlinear load either draws a current waveform that is not instantaneously proportional to the voltage or is a load that causes current to distort its sinusoidal shape. The current waveform also leads or lags voltage or phase. Harmonics are distortions of the normal electrical current waveform, generally transmitted by nonlinear loads -Non-linear loads occur when the resistance is not a constant and changes during each sine wave of the applied voltage waveform, resulting in a series of positive and negative pulses. Switch-mode power supplies (SMPS), variable speed motors and drives, photocopiers, personal computers, laser printers, fax machines, battery chargers, and UPSs are examples of nonlinear loads. Single-phase nonlinear loads are prevalent in modern office buildings- Data Center, while 3-phase nonlinear loads are common in facto- ries and industrial plants. A large portion of the nonlinear electrical loads in most electrical distribution systems comes from SMPS equipment. For example, all computer systems use SMPS that convert utility AC voltage to regulat- ed low-voltage DC for internal electronics. These nonlinear power supplies draw current in high-amplitude short pulses that create significant distortion intheelectricalcurrentandvolt- age wave shape (see Figure 6). This harmonic distortion, mea- sured as total harmonic distor- tion (THD), travels back into the power source and can affect other equipment connected to the same source. Most power systems can accommodate a certain level of harmonic currents but will experience prob- lems when harmonics become a significant component of the overall load. As these higher frequencies harmonic currents flow through the power system, they can cause communication errors, overheating and hardware damage, such as: zz Overheating of electrical distribution equipment, cables, transformers, standby generators, etc. zz High voltages and circulating currents caused by harmonic resonance zz Equipment malfunctions due to excessive voltage distortion zz Increased internal energy losses in connected equipment, causing component failure and shortened life span zz False tripping of branch circuit breakers zz Metering errors zz Fires in wiring and distribution systems zz Generator failures zz Crest factors and related problems zz Lower system power factor, resulting in penalties on monthly utility bills Figure 6
  • 7. info@edaratgroup.com | www.edaratgroup.com 7 edarat group Are Harmonics Still A Problem In Data Centers? HARMONICS REDUCTION SOLUTIONS To determine if harmonic mitigation is necessary, should conduct an assessment to precisely measure the harmonics affecting the data center and identify their origin. Options for harmonic mitigation vary in complexity and cost and can be deployed individually or in combination. The strategy that makes the most sense for a facility will vary based on the loads it supports, its budget, and the nature of the harmon- ic-related problems it is experiencing. There are several approaches that can be taken to compensate for or reduce harmonics in the power system, with varying degrees of effectiveness and efficiency. 200% neutral conductors One option is to specify an 200% neutral conductor or to use separate neutral conductors. Triple n har- monics (3, 9, 15, etc.) can produce neutral currents that can be up to the theoretical maximum of 173% of the phase current, which is why a 200% neutral conductor is usually specified. K-rated transformers: A standard transformer is not designed for high harmonic currents produced by nonlinear loads. It will overheat and fail prematurely when connected to these loads. Therefore, when harmon- ics were first introduced into electrical systems at levels that showed detrimental effects (cir- ca 1980), the industry responded by developing the K-rated transformer. K-rated transform- ers are not used to eliminate harmonics, but to manage the heat generated by harmonic currents. K factor ratings range between 1 and 50. A standard transformer designed for linear loads is designated with a K-factor of 1. The higher the K-factor, the more heat from harmonic currents the transformer is able to withstand. When selecting a K rating, managers should consider the trade-offs between size, effi- ciency, and heat tolerance. For example, transformers with higher K factors are typically larger than those with lower K factors. The table 1 below shows appropriate K ratings to use for different percentages of nonlinear current in the electrical system. Non-linear load K- Rating Incidental electronic equipment representing less than 5% K 1 Harmonic producing equipment representing less than 35 % K4 Harmonic producing equipment representing less than 50 % K 7 Harmonic producing equipment representing less than 75 % K 13 Harmonic producing equipment representing less than 100 % K 20 Table 1
  • 8. info@edaratgroup.com | www.edaratgroup.com 8 edarat group Are Harmonics Still A Problem In Data Centers? Uninterruptable Power Supply- UPS Since UPSs and the loads they serve have historically been considered some of the most significant har- monic loads on a power system, companies can also use harmonic-mitigating UPSs to reduce line har- monics. Much like active filters, harmonic-mitigating UPSs eliminate harmonic distortion by inserting equal and opposite current into the line. They also compensate for reactive power from low power factor loads and balance loads across three phases to avoid stranded capacity, while providing clean and con- tinuous power during utility outages or in response to electrical disturbances. Harmonics filters Harmonic filters remove harmonics and correct the phase of the fundamental current, thus converting non-linear loads into linear loads. Passive, and Active filters, it can be either used as a standalone part integral to a large nonlinear load or can be used for a multiple small single phase nonlinear loads by con- necting it to a switch board. Passive filter A Passive Filter uses inductors capacitors and resistors in combination to create the filter. Passive imple- mentations of linear filters are based on combinations of resistors (R), inductors (L) and capacitors (C). These types are collectively known as passive filters, because they do not depend upon an external power supply and/or they do not contain active components such as transistors. Active filter This method uses sophisticated electronics and power section IGBTs to inject equal and opposite har- monics onto the power system to cancel those generated by other equipment. These filters monitor the nonlinear currents demanded from nonlinear loads and electronically generate currents that match and cancel the destructive harmonic currents. Active filters are inherently non-resonating and are easily con- nected in parallel with system loads. PRINCIPLE DRAWING LOAD MAINS MAINSi MAINSH MAINSi LOADH LOADi MAINS Connection AHF AHFi LOADi
  • 9. info@edaratgroup.com | www.edaratgroup.com 9 edarat group Are Harmonics Still A Problem In Data Centers? Advantages zz Guarantee compliance with IEEE 519 1992 if sized correctly zz Harmonic cancellation from the 2nd to 51st harmonic zz No series connection provides easy installation with no major systema rework zz Provide VAR currents, improving system power factor Disadvantages zz Can be more expensive than other methods due to the high performance control and power sections zz The filter’s input semiconductors are exposed to line transients. With increase in use of non-linear loads, the issues of power supply harmonics are more noticeable than ever. Controlling and monitoring industrial system designs and their effects on utility distribution systems are potential problems for the industrial consumer, who is responsible for complying with the IEEE 519, recommended practices and procedures. Industrial facilities should include a system evaluation, including a harmonic distortion analysis, while planning facility construction or expansion. Vendors of non-linear loads, such as variable frequency drives, can provide services and recommend equipment that will reduce harmonics in order to comply with IEEE 519 guidelines. Generally, at any point the measured value of total harmonic voltage distortion should not exceed 5% and that of any individual harmonic voltage distortion should not exceeding 3% of the fundamental value of the line voltage. Normally, in typical applications, the harmonics are measured up to 25th order, but in critical applications, those are measured up to 50th or 100th order. A better way to handle harmonics in the data center is to simply design better systems and devices, which fortunately has already been accomplished for the most part. In order to offer products in the world-wide market, nearly every computer equipment manufacture is in compliance. To comply with the regulation, global computer equipment vendors developed Power Factor Corrected (PFC) power supply technology. Power factor is the ratio of the real power to the load and the apparent power and is a number between zero and one (e.g., 0.5 pf = 50%pf). Real power is the capacity of the circuit. Apparent power is the product of the current and voltage in the circuit. If energy is stored in the load and returned to the source, or if is distorted by a non-linear load, the apparent power will be greater than the real power. Loads with a high power factor draw less current than loads with low power factors, and these higher currents increase energy loss and require larger equipment. Switched-mode power supplies have a low power factor. PFC power supplies control the harmonic cur- rent using either a filter or an electronic system that controls the amount of power drawn by the load. The purpose of the PFC is to make the power factor as close to one as possible, where the current waveform is proportional to the voltage waveform. When this is the case, the voltage and current are in phase and the reactive power consumption is zero, enabling power companies to efficiently deliver power. In other words, all of the energy supplied by the source is consumed by the load and none is returned to the source.
  • 10. info@edaratgroup.com | www.edaratgroup.com 10 edarat group Are Harmonics Still A Problem In Data Centers? CONCLUSION Harmonics in the data center was a real concern in the past. Fortunately, it is one of those issues that are close to being solved, at least for computing equipment, by regulatory agencies and computer equipment manufactures. It’s not an issue that receives a lot of press or marketing, as companies tend to focus more on the more tangible benefit of energy efficiency and reduced energy costs, which is why the subject of harmonics is still occasionally raised as an issue when designing new power distribution systems. Facilities managers or electrical architects who are unfamiliar with modern computer equipment might specify costly solutions such as K-factor transformers or 200% neutral conductors, to handle non-linear loads and harmonic neutral currents that are relatively rare in today’s IT environments. Data center managers who are armed with the knowledge that computer vendors are compliant with harmonic elimination standards can help drive more realistic and cost-effective power distribution designs in the data center and be more proactive in replacing non-conforming, legacy equipment. Simply stated, 100% rated neutral conductors are suitable for the vast majority of applications. Circumstances might arise where oversize neutral conductors are necessary for the remaining non-linear loads in the data center, such as lighting and cooling equipment, or legacy equipment that must be main- tained for a particular application.
  • 11. info@edaratgroup.com | www.edaratgroup.com 11 edarat group Are Harmonics Still A Problem In Data Centers? References Mitigating data center harmonics http://pqlit.eaton.com/ll_download_bylitcode.asp?doc_id=26534 Neutral Ratings for Power Distribution Systems in the Data Center http://www.starlinepower.com/busway/uploads/docs/en/UE_NeutralRatings.pdf Harmonics in your electrical system http://www.newark.com/pdfs/techarticles/eaton/Eaton_Technical_Articles/UPS_Training/Powerware_ Training/HarmonicsInYourElecSystem.pdf. Harmonic reduction methods http://www.eaton.com/ecm/idcplg?IdcService=GET_FILEdID=687518.