Fault Identification of In-Service Power Transformer using
Depolarization Current Analysis
M.A. Talib1
, N.A. Muhamad2
, Z.A. Malek3
, B. T. Phung4
1,3
Institute of High Voltage & High Current, Fakulty of Electrical Engineering, Universiti Teknologi Malaysia,
81310 Johor Bahru, Johor, Malaysia
1
TNB Research Sdn Bhd, No 1 Jalan Air Itam, Kajang Selangor, Malaysia
2
School of Electrical and Electronic Engineering, Engineering Campus, University Sains Malaysia, 14300 Nibong Tebal,
Penang, Malaysia
4
School of Electrical Engineering & Telecommunications, University of New South Wales, Sydney, Australia
Article Info ABSTRACT
Article history:
Received Apr 7, 2016
Revised Oct 4, 2016
Accepted Oct 18, 2016
Preventive diagnostic testing of in-service power transformers require system
outage and expert‟s knowledge and experiences in interpreting the
measurement results. The chemical oil analysis may cause significant
variance to measurement results due to the different practices in oil sampling,
storage, handling and transportation. Thus, a cost effective measuring
technique by means of a simpler method that is able provide an accurate
measurement results is highly required. The extended application of
Polarization and Depolarization Current (PDC) measurement for
characterization of different faults conditions on in-service power
transformer has been presented in this paper. The oil sample from in-service
power transformers with normal and 3 different faults type conditions were
sampled and tested for Dissolved Gases Analysis (DGA) and PDC
measurement. The DGA results was used to confirm type of faults inside the
transformer while the PDC pattern of oil with normal, partial discharge,
overheating and arcing were correlated to the oil sample conditions. The
analysis result shows that depolarization current provides significant
information to defferenciate fault types in power transformer. Thus this
finding provides a new alternative in identifying incipient faults and such
knowledge can be used to avoid catastrophic failures of power transformers.
Keyword:
Depolarization current
Dielectric response
Fault diagnosis
Polarization current
Transformer fault
Copyright © 2017 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
M. A. Talib
Institute of High Voltage & High Current,
Faculty of Electrical Engineering,
Universiti Teknologi Malaysia,
81310 Skudai Johor MALAYSIA
Email: mohdaizam@tnbr.com.my
1. INTRODUCTION
The continuous supply of electricity from generating stations to the customer is very much
dependent on reliability of power transformers installed in the substations [1]. The failures of this strategic
unit at any substation can cause interruption of power supply and substantial damage to other components. It
may also become potentially dangerous for utility personnel as failures may result to explosions and fire.
Therefore, determining their condition would be of tremendous importance to the power utilities. Presently,
the maintenance paradigm has moved from scheduled based maintenance to condition based maintenance
with the objective to minimize the operational cost and improve the reliability of transformers [2], [3]. A new
material and maintenance techniques mainly towards condition based maintenance thus continuously
developed to sustain high power reliability and availability [4].
 ISSN:2088-8708
IJECE Vol. 7, No. 2, April 2017 : 559–567
560
Well established chemical and electrical diagnostic testing methods have been used to assess the
condition of the transformer and classified them according to different fault and ageing mechanisms. For
example, the presence of moisture in insulation system can be determined by dielectric dissipation factor
(DDF) and insulation resistance (IR) measurement [5], while the mechanical integrity of winding and core
clamping structure due to short circuit forces can be confirmed by Frequency Response Analysis (FRA)
[6], [7] and the problems with bad joints or connections are identified through winding resistance
measurement [8]. For instance, decomposition of the hydrocarbon chain caused by thermal and electrical
faults will liberate small quantities of gases and can be classified and quantified by means of DGA [9-11].
Nevertheless, the existing diagnostic technique particularly electrical measurement require electrical
isolation or transformer outage before the measurement can be performed. Beside that, the duration for the
complete measurement on one transformer which can last for several hours has concerned the power utilities
which limit the measurement on basic routine testing and applied on the selected critical transformer due to
difficulties of long hour outages. In some situations, due to system overloading the outage of power
transformer is not permitted and caused the insulation ageing is not being assessed and determined.
Even though, the chemical analyses on transformer oil insulation provide direct information on
parameters like oil moisture content, sludge, acidity, Degree of Polymerization (DP) and DGA [12-14],
however, most of the chemical analyses are conducted under laboratory condition where sample sampling,
storage and transportation cause significant variance due to different practices and location of the site. All
these will incurred high cost to the power utilities as part of their condition based maintenance activities.
In order to avoid any unwanted circumstances, accurate assessment of transformer condition is
crucial so that replacement or refurbishment of the assets can be taken before failures take place. Thus, a cost
effective measuring technique, simpler but can provide an accurate measurement results is highly required.
In this paper, the PDC was investigated to be used as an alternative diagnostic technique to
determine the incipient fault occurs in power transformers. The oil samples was taken from various
transformers and tested for its condition. The analysis of PDC pattern for transformers with normal, partial
discharge, overheating and arcing faults conditions are presented in this paper. An Artificial Neural Network
(ANN) was used to identify each spectrum characteristic for faults identification and the results was
compared with other established diagnostic interpretation techniques.
2. POLARIZATION AND DEPOLARIZATION CURRENT MEASUREMENT
This section covers the details of experimental test set-up and the testing procedure of PDC
measurement.
2.1. Measuring Test Circuit
The polarization and depolarization current are measured using the commercial PDC known as
Analyzer-1MOD manufactured by Alff Engineering Switzerland. The analyzer can supply the excitation
voltage up to 2kV DC and measure the dielectric response in time domain up to 10000s [15]. The analyzer is
then connected to the test cell with electrode gap of 1.5mm and capacitance of 60pF. Two electrodes circuit
were used, one for application of the test voltage and the other is for current measurement. The amount of
insulating liquid required for the measurement is about 210ml. Figure 1 shows the measurement set-up used
in the laboratory experimental works. All the measurements were carried out at 1000V and polarization and
depolarization times of 10,000s each.
Figure 1. Laboratory Experimental Test Set-Up [15]
S1
S2
Control
voltage
Computer
with DSP
board A
+
-
Test VesselMeasured
current
PDC Analyzer 1MOD
IJECE ISSN: 2088-8708 
Fault Identification of In-Service Power Transformer Using Depolarization Current Analysis (M. A. Talib)
561
2.2. Oil Test Sample
The oil samples used in this experiment are hydrocarbon based mineral oil obtained from in-service
transformers operating at Malaysia power distribution network. The operating conditions of these
transformers had previously been identified based on DGA data of their respective oil samples. The test
samples were classified into four conditions; normal, partial discharge, overheating and arcing. Prior to PDC
measurement, the DGA was performed again on the oil samples to confirm the presence of combustible gases
and its nature of faults.
In each condition, the oil samples were taken from 10 units of power transformers and every unit
has 3 samples; i.e. there are 30 oil samples for each condition. Each PDC assessment was repeated for five
times on all oil samples. The aim of having such a large number of the same samples and repetition of PDC
assessment process was to ascertain the reproducibility of the test results.
To avoid the effect of moisture on polarization and depolarization current measurement, it was
crucial that the oil samples were dry. Thus, the selection of transformers are limited to the units with moisture
content less than 30ppm; considered dry according to IEC 60422-2013 [12].
2.3. Testing Procedure
The consistency of experimental test results is highly dependent on the PDC test procedure used.
The test vessel must be cleaned prior to each measurement process as contamination from previous oil
samples could affect the next test results. The residual charges can also affect the polarization current results,
thus before the excitation voltage is applied to the test sample, the test object was discharged for 500s. For
safety purposes, the test sample was placed in the shielded case. Figure 2 shows the flow chart of
experimental works.
Figure 2. Flow Chart of Experimental Works
3. RESULTS AND DISCUSSIONS
The polarization and depolarization current of oil with different fault conditions in this research are
analyzed based on its graphical pattern obtained from the experiments. Artificial Neutral Network (ANN)
was used to further analyze the measured currents for transformer fault identification.
3.1. Analysis of Polarization and Depolarization Current
Since oil was the only insulation tested in this research, it would be expected that the changes of
measured current is attributed to changes at the initial time response [16]. Figure 3(a) and (b) shows the
average of polarization and depolarization current on oil samples with normal, partial discharge, overheating
and arcing condition. The analysis of polarization current demonstrated that the measured current starts to
Start
Discharged 500s
Check residual
charges. Low and
constant reading
Measured polarization
current (1s -10000s)
Completed?
Measured depolarization
current (1s -10000s)
Completed?
Yes
No
Yes
No
No Yes Re-Test for
5 times.
Completed?
No
Test other
oil sample
Yes
End
 ISSN:2088-8708
IJECE Vol. 7, No. 2, April 2017 : 559–567
562
stabilize and saturated almost after 100s of being charged until the completion of polarization process.
Meanwhile, the depolarization current takes a longer time and only after 1000s the measured currents are
starts to stabilize until the end of discharging process.
(a) Polarization current (b) Depolarization current
Figure 3. Polarization and depolarization current pattern of normal, partial discharge, overheating and arcing
oil samples
Figure 4. Depolarization current pattern of oil samples at duration of 4 seconds to 100 seconds
The curves have shown that the oil with normal condition had the least value of polarization current,
while the values were progressively higher in partial discharge, overheating and arcing fault conditions. The
average magnitude of maximum polarization current recorded on normal oil sample is 50.23nA, partial
discharge is 118.33nA, overheating is 184.96nA and arcing is 226.45nA. The high polarization current of oil
samples with fault conditions can be attributed to the fact that faults in power transformer cause breakdown
of hydrocarbon structures of oil; thus leading to higher charge carrier mobility and high current magnitude
when any external electric field is applied. In addition, it can be seen that the polarization current pattern
10
1
10
2
-4
-3.5
-3
-2.5
-2
-1.5
-1
-0.5
0
x 10
-9
time,t,[s]
DepolarizationCurrent,Idepol,[A]
Normal
Partial discharge
Overheating
Arcing
DepolarizationCurrent,Idepol,[A]
time,t[s]
10
0
10
1
10
2
10
3
10
4
0
0.5
1
1.5
2
2.5
x 10
-7
time,t,[s]
AveragePolarizationCurrent,Ipol,[A]
Normal
Partial discharge
Overheating
Arcing
10
0
10
1
10
2
10
3
10
4
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
x 10
-9
time,t,[s]
AverageDepolarizationCurrent,Idepol,[A]
Normal
Partial discharge
Overheating
Arcing
AverageDepolarizationCurrent,Idepol,[A]
time,t[s]
AveragePolarizationCurrent,Ipol,[A]
time,t[s]
IJECE ISSN: 2088-8708 
Fault Identification of In-Service Power Transformer Using Depolarization Current Analysis (M. A. Talib)
563
seemingly correspond to degree of fault; the initial slopes of the oil samples with fault conditions are steeper
than the oil with normal condition.
The plot of depolarization current on oil samples with normal, partial discharge, overheating and
arcing fault conditions shows that the depolarization curves are almost identical. The average magnitude of
maximum depolarization current recorded is -7.12nA for normal oil samples, -7.06nA for partial discharge,
-8.31nA for overheating and -8.28nA for arcing samples.
An interesting point was observed on depolarization current pattern at duration of 4 seconds to 100
seconds as the responses are changes with different transformer conditions, as shown in Figure 4 It can be
seen that the normal oil condition has low current pattern and as the energy of the fault increases the current
pattern of oil samples with fault conditions are also increases.
3.2. Selection of Current for Fault Identification
According to [17], the polarization current is the combination of the absorption current due to
polarization and the conduction current. On the other hand, the depolarization current consists only of the
absorption current because conduction current exists only when the voltage is applied to the dielectric. From
the results, both polarization and depolarization currents were found to have correlation with faults in power
transformer. Nevertheless, it is important to identify and classify the currents that are effectively used to
characterize incipient faults in power transformers.
In this research, an Artificial Neural Network (ANN) was used to further analyze the currents for
transformer fault identification. The design and simulation of the ANN was done using Neural Network
Toolbox provided in MATLAB.
Initially, the input data was normalized with the objective of ensuring a uniform statistical
distribution of each input value. In this research, the maximum and minimum values of a group of data are
used to normalize each single input using the following equation
[ ] (1)
where I is the normalized value of a single data. Imin and Imax are the input range of the ANN and the
typical range is -1 to 1 or 0 to 1. D is the input value for each data while Dmin and Dmax are the minimum and
maximum values of the input data.
The ANN is a 3 layered structure comprised of input, hidden and output layer. In order to increase
the prediction capability of the network, the ANN utilized 2 hidden layers with 100 neurons on each layer.
Initially, the learning algorithm employed to train the ANN is Back Propagation (BP). However, the
algorithm is too slow for practical problem due to the fact that multilayer networks use sigmoid transfer
functions in the hidden layers. These functions, known as „squashing‟, compress infinite input range into a
finite output range. Sigmoid function is characterized by the fact that their slope must approach zero as the
input gets large. This causes a problem when using steepest descent to train a multilayer network with
sigmoid function because the gradient can have a very small magnitude; therefore causing small changes in
the weights and biases, even though the weights and biases are far from their optimal values. Thus, a faster
Back Propagation (BP) algorithm known as Resilient Back Propagation (Rprop) was used as learning
algorithm to train the ANN.
This algorithm eliminates the harmful effects of the magnitudes of the partial derivatives. Only the
sign of the derivative determines the direction of the weight update. The size of the weight change is
determined by a separate update value. The update value for each weight and bias is increased by a factor that
depends on the derivative of the performance function with respect to weight changes sign from the previous
iteration. If the derivative is zero, the update value remains the same. Whenever the weights are oscillating,
the weight change is reduced. If the weight continues to change in the same direction for several iterations,
the magnitude of the weight change increases.
Table 1. Relationship of ANN output value and type of fault
Output Neuron
Value
Type of Fault
1000 Normal
0100 Partial discharge
0010 Overheating
0001 Arcing
 ISSN:2088-8708
IJECE Vol. 7, No. 2, April 2017 : 559–567
564
A PDC sample with a total of 21,900 input data were used to train the ANN and later was tested
with another PDC sample data that is separated from the earlier training data. The output will then refer to
different types of faults as shown in Table 1. The training procedure and the ANN structure with 2 hidden
layers are shown in Figure 5 and Figure 6 respectively.
Figure 5. ANN training procedure
Figure 6. Schematic diagram of the ANN
Finally, the accuracy and performance of the ANN output is determined by the following equation,
(2)
Start
Get the database
Matching?
No
YesReaching the
performance goal?
Test the ANN
Set input data of
training
Normalization of data
Set the target output
Start training the
ANN
Accept Denied
End
Yes No
IJECE ISSN: 2088-8708 
Fault Identification of In-Service Power Transformer Using Depolarization Current Analysis (M. A. Talib)
565
The results of ANN analysis on polarization and depolarization current are shown in Table 2.0 and
Table 3.0 respectively.
Table 2. ANN result of polarization current
Condition
Correct output
recognised
Wrong output
recognised
% ANN
Accuracy
Normal 87 3 97
Partial discharge 58 7 80
Overheating 15 5 75
Arcing 36 9 90
Table 3. ANN result of depolarization current
Condition
Correct output
recognised
Wrong output
recognised
% ANN
Accuracy
Normal 86 4 96
Partial discharge 60 5 92
Overheating 19 1 95
Arcing 43 2 96
The ANN analysis of polarization current demonstrated that higher accuracy of more than 90% was
observed for oil samples on transformer with normal and arcing fault conditions. On the other hand, lower
accuracy was observed for identification and classification of partial discharge and thermal overheating faults
as the accuracy recorded is only 80% and 75% respectively.
Meanwhile, higher accuracy of more than 90% was recorded for depolarization current on all
conditions. Both normal and arcing condition has ANN accuracy of 96%, whereas thermal overheating fault
has accuracy of 95%. The partial discharge fault was observed slightly lower with ANN accuracy of 92%.
Based on this ANN simulation results, depolarization current yielded a better accuracy in identifying and
classifying different transformer conditions as compared to polarization current and identified as the current
of main interest that can be uniquely used for fault identification of in-service power transformer.
The results has confirmed the initial research done by Bhumiwat [18] on overheating of transformer
solid insulation stated that the condition can be identified by the prominently crooked shape of the
depolarization current.
4. CONCLUSION
In this paper, the extended application of PDC measurement for characterization of different faults
conditions of in-service power transformer was investigated. The oil sample with normal, partial discharge,
overheating and arcing condition were taken from respective units and tested for its combustible fault gases,
polarization and depolarization current.
The changes of the molecular properties of the insulating oil material due to different fault
conditions was found influences the initial time response of both measured currents. The sensitivity analysis
using Artificial Neural Network (ANN) shows that depolarization current gives a better accuracy in
identifying and classifying different transformer conditions as compared to polarization current. Thus,
depolarization current measurements provide a new alternative in identifying incipient faults and such
knowledge can be used to avoid catastrophic failures of power transformers.
ACKNOWLEDGEMENTS
The authors would like to acknowledge the support of TNB and Malaysia Ministry of Higher
Education, Universiti Teknologi Malaysia (Vot 05J82, 04H67, 4L014, and 4L607) for technical and financial
support.
REFERENCES
[1] Sunil M, Jaralikar, Aruna M, “Study of Performance of Power Station for Operational Optimization”, International
Journal of Electrical and Computer Engineering (IJECE),Vol. 2, No. 1, February 2012, pp. 17-25.
[2] J.A. Lapworth, P.N. Jarman and I.R. Funnell, “Condition Assessment Techniques For Large Power Transformers”,
2nd International Conference on the Reliability of Transmission and Distribution Equipment, pp 85-90, 1995.
[3] R. Schwarz, M. Muhr, “Diagnostic Methods for Transformer”, IEEE International Conference on Condition
Monitoring and Diagnosis, pp 974-977, 2008.
 ISSN:2088-8708
IJECE Vol. 7, No. 2, April 2017 : 559–567
566
[4] H. Borsi, E. Gockenbach, “Comparison between Oil Immersed and SF6 Gas Power Transformers Ratings”,
TechCon Asia-Pacific Conference, 1-2 May 2007, Sydney, Australia.
[5] Wang, M.; Vandermaar, A.J.; Srivastava, K.D., “Review Of Condition Assessment Of Power Transformer In
Service”, IEEE Electrical Insulation Magazine, Vol 18, Issue 6, pp 12-25, 2002.
[6] Liu Yong, Xiaochen ; Ji, Shengchang “Study On Sweep Frequency Impedance Method For Detecting Internal
Winding Short Circuit Fault In Power Transformer” IEEE International Conference on Power Modulator and High
Voltage (IPMHVC), pp 137-140, 2014.
[7] Aljohani, O.; Abu-Siada, A. “Application Of FRA Polar Plot Technique To Diagnose Internal Faults In Power
Transformers”, IEEE PES General Meeting Conference & Exposition, pp 1-5, 2014.
[8] IEEE Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors, IEEE
C57.152-2013.
[9] IEC Standard, Mineral Oil-impregnated Electrical Equipment in Service - Guide to the Interpretation of Dissolved
and Free Gases Analysis, IEC 60599:2015.
[10] Duval. M, dePablo. A, “Interpretation of Gas-in-oil Analysis Using New IEC Publication 60599 and IEC TC10
Database”, IEEE Electrical Insulation Magazine, Vol 17(2) March/April, pp 31-41, 2001.
[11] Sherif S. M. Ghoneim, Sayed A. Ward, “Dissolved Gas Analysis as a Diagnostic Tools for Early Detection of
Transformer Faults”, Advances in Electrical Engineering Systems (AEES) 152 Vol. 1, No. 3, 2012.
[12] IEC Standard, Mineral Insulating Oils in Electrical Equipment – Supervision and Maintenance Guidance, IEC
60422:2013.
[13] Priyesh Kumar Pandey, Zakir Husain, R.K. Jarial, “ANFIS Based Approach to Estimate Remnant Life of Power
Transformer by Predicting Furan Contents”, International Journal of Electrical and Computer Engineering
(IJECE),Vol. 4, No. 4, August 2014, pp. 463-470.
[14] A.A. Suleiman, N.A. Muhamad, N. Bashir, N.S. Murad and Y.Z. Arief. “Effect of Moisture on Breakdown Voltage
and Structure of Palm Based Insulation Oils”. IEEE Transactions on Dielectric and Electrical Insulation (TDEI),
21(5) October 2014.
[15] PDC-Analyzer 1MOD User Guide Hardware, Alff Engineering, Switzerland.
[16] A. Küchler, T. Leibfried, B. Breitenbauch, J.J. Alff, V. Der Houhanessian, W.S. Zaengl, “Transformer Insulation
Diagnosis by Polarization and Depolarization Current Analysis”, Proceeding of 48. Internationales
Wissenschaftliches Kolloquium, Technische Universität Ilmenau, 2003.
[17] S.A. Bhumiwat, “The Latest On-Site Non-Destructive Technique for Insulation Analysis of Electrical Power
Apparatus”, Weidman ACTI Annual Technical Conference, 2004.
[18] S.A. Bhumiwat, “Identification of Overheating in Transformer Solid Insulation by Polarization Depolarization
Current Analysis”, IEEE Electrical Insulation Conference (EIC2013), pp 449-453, 2013.
BIOGRAPHIES OF AUTHORS
Mohd Aizam Talib received his Bachelor in Electrical Engineering from the University of
Portsmouth, UK in 1997, and Master degree in Electrical Engineering from Universiti Tenaga
Nasional (UNITEN), Malaysia in 2001. Upon graduation in 1997, he worked with ABB
Transmission and Distribution Sdn Bhd as a Design Engineer. Since 1998, he has been employed
by TNB Research Sdn Bhd as a Research Engineer. His research interests are in transformer
condition monitoring, insulation diagnostic and dielectric measurements. He is currently a Ph.D.
degree student at Universiti Teknologi Malaysia.
Nor Asiah Muhamad is senior lectures in School of Electrical and Electronic Engineering
Universiti Sains Malaysia since Sep 2016. She has over 13 experince working with Institute of
High Voltage and High Current (IVAT) Universiti Teknologi Malaysia as lecturer as well as
researcher. Received her PhD in 2009 from University of New South Wales, Australia in area oil
insulation monitoring and diagnosis. Received Bachelor degree in Electrical and Electronic
Engineering from Universiti Teknologi PETRONAS, Malaysia in 2002 and Master degree in
Electrical Power Engineering from University of South Australia in 2006. Start doing research in
power system equipment monitoring since 2005 and the main topics related to her work are
insulation diagnosis, new material for HV insulation and condition monitoring systems.
IJECE ISSN: 2088-8708 
Fault Identification of In-Service Power Transformer Using Depolarization Current Analysis (M. A. Talib)
567
Zulkurnain Abdul-Malek was born in Kuantan, Malaysia in 1965. He obtained his B.E. from
Monash University (Melbourne) in 1989 and his MSc and PhD degrees from University of
Wales Cardiff in 1995 and 1999 respectively. Since 1989 he has been a member of the Electrical
Engineering Faculty at UTM. He is currently an Associate Professor and the Director of UTM
Institute of High Voltage and High Current. His research interests include intelligent condition
monitoring of HV equipment, lightning detection and warning systems, nanodielectrics and fast
transient response of high voltage surge arresters.
B.T. Phung Gained a Ph.D. in Electrical Engineering in 1998 and is currently a Senior Lecturer
in the School of Electrical Engineering at the University of New South Wales, Sydney,
Australia. He has over 30 years of practical research/development experience in partial discharge
measurement, and in on-line condition monitoring of high- voltage equipment. His research
interests include electrical insulation (dielectric materials and diagnostic methods), high-voltage
engineering (generation, testing and measurement techniques), electromagnetic transients in
power systems, and power system equipment (design and condition monitoring methods).

More Related Content

PDF
Ig3415411546
PDF
Methods to determine the overall health and condition of large power transfor...
PDF
11.methods to determine the overall health and condition of large power trans...
PDF
Guidelines for Unconventional Partial Discharge Measurement (CIGRE 444)
PDF
Clock Gating Cells for Low Power Scan Testing By Dft Technique
PDF
IRJET- A Survey Approach: Device for Biosensing Application
PDF
Fpga versus dsp for wavelet transform based voltage sags detection
PDF
rf based complex impedance measurement
Ig3415411546
Methods to determine the overall health and condition of large power transfor...
11.methods to determine the overall health and condition of large power trans...
Guidelines for Unconventional Partial Discharge Measurement (CIGRE 444)
Clock Gating Cells for Low Power Scan Testing By Dft Technique
IRJET- A Survey Approach: Device for Biosensing Application
Fpga versus dsp for wavelet transform based voltage sags detection
rf based complex impedance measurement

What's hot (19)

PDF
Fault detection in power transformers using random neural networks
PDF
CLASS D POWER AMPLIFIER FOR MEDICAL APPLICATION
PDF
Performance Analysis of Faults Detection in Wind Turbine Generator Based on H...
PDF
Test Scheduling of Core Based SOC Using Greedy Algorithm
PDF
03 tec literaturereview
PDF
PWM-Switching pattern-based diagnosis scheme for single and multiple open-swi...
PDF
CORROSION INSPECTION IN OIL AND GAS PIPELINE
PDF
Analytical Method Development
PDF
Review of DC Offset Compensation Techniques for Grid Connected Inverters
PDF
Cost effective test methodology using pmu for automated test equipment systems
PDF
Online Condition Monitoring And Diagnosis Of Power Transformers Their Bushin...
PDF
THE PRESSURE SIGNAL CALIBRATION TECHNOLOGY OF THE COMPREHENSIVE TEST SYSTEM
PDF
Sensoring Leakage Current to Predict Pollution Levels to Improve Transmission...
PDF
CORROSION INSPECTION IN OIL AND GAS PIPELINE
PDF
Short-circuit fault diagnosis of the DC-Link capacitor and its impact on an ...
PDF
Improved Sensitivity and Dynamic Range Using the Clarus SQ 8 GC/MS System for...
PDF
Design and Implementation of Multiplier using Advanced Booth Multiplier and R...
PDF
Power Quality Improvement Using GUPFC
PDF
Measuring the filtration efficiency and particle indoor outdoor concentration...
Fault detection in power transformers using random neural networks
CLASS D POWER AMPLIFIER FOR MEDICAL APPLICATION
Performance Analysis of Faults Detection in Wind Turbine Generator Based on H...
Test Scheduling of Core Based SOC Using Greedy Algorithm
03 tec literaturereview
PWM-Switching pattern-based diagnosis scheme for single and multiple open-swi...
CORROSION INSPECTION IN OIL AND GAS PIPELINE
Analytical Method Development
Review of DC Offset Compensation Techniques for Grid Connected Inverters
Cost effective test methodology using pmu for automated test equipment systems
Online Condition Monitoring And Diagnosis Of Power Transformers Their Bushin...
THE PRESSURE SIGNAL CALIBRATION TECHNOLOGY OF THE COMPREHENSIVE TEST SYSTEM
Sensoring Leakage Current to Predict Pollution Levels to Improve Transmission...
CORROSION INSPECTION IN OIL AND GAS PIPELINE
Short-circuit fault diagnosis of the DC-Link capacitor and its impact on an ...
Improved Sensitivity and Dynamic Range Using the Clarus SQ 8 GC/MS System for...
Design and Implementation of Multiplier using Advanced Booth Multiplier and R...
Power Quality Improvement Using GUPFC
Measuring the filtration efficiency and particle indoor outdoor concentration...
Ad

Similar to Fault Identification of In-Service Power Transformer using Depolarization Current Analysis (20)

PDF
2003 cigre mexico_tenbohlen
PDF
MY PAPER
PDF
Application of Dielectric Spectroscopy to Monitor Insulating Materials
PPT
Transfomer diagnostics/sanjeet-1308143
PDF
I42055158
PDF
Iaetsd detection, recognition and localization of partial discharge
PDF
Power-Transformer-Testing-Brochure-ENU.pdf
PDF
Electrical condition monitoring part 2
PDF
Power-Transformer-Testing-Brochure-ENU.pdf
DOCX
The value of power factor testing
PDF
Paper 2
PDF
Ieeepes boston xfmrdiagnosticssweetser
PDF
Research on typical discharge mode of power transformer (www.himalayal.com)
PPT
Transformer oil analysis
PDF
Use of Plat-Bar Electrode Media to Detect Partial En.pdf
PPTX
Partial discharge testing
PPT
13. Condition monitoring and Preventive Maintenance.ppt
PDF
IRJET - A Review of an Investigation of Partial Discharge Sources and Loc...
PDF
Fg34974984
PDF
PD Behaviors of Monoester Insulating Oil under Different Moisture Contents
2003 cigre mexico_tenbohlen
MY PAPER
Application of Dielectric Spectroscopy to Monitor Insulating Materials
Transfomer diagnostics/sanjeet-1308143
I42055158
Iaetsd detection, recognition and localization of partial discharge
Power-Transformer-Testing-Brochure-ENU.pdf
Electrical condition monitoring part 2
Power-Transformer-Testing-Brochure-ENU.pdf
The value of power factor testing
Paper 2
Ieeepes boston xfmrdiagnosticssweetser
Research on typical discharge mode of power transformer (www.himalayal.com)
Transformer oil analysis
Use of Plat-Bar Electrode Media to Detect Partial En.pdf
Partial discharge testing
13. Condition monitoring and Preventive Maintenance.ppt
IRJET - A Review of an Investigation of Partial Discharge Sources and Loc...
Fg34974984
PD Behaviors of Monoester Insulating Oil under Different Moisture Contents
Ad

More from IJECEIAES (20)

PDF
Redefining brain tumor segmentation: a cutting-edge convolutional neural netw...
PDF
Embedded machine learning-based road conditions and driving behavior monitoring
PDF
Advanced control scheme of doubly fed induction generator for wind turbine us...
PDF
Neural network optimizer of proportional-integral-differential controller par...
PDF
An improved modulation technique suitable for a three level flying capacitor ...
PDF
A review on features and methods of potential fishing zone
PDF
Electrical signal interference minimization using appropriate core material f...
PDF
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
PDF
Bibliometric analysis highlighting the role of women in addressing climate ch...
PDF
Voltage and frequency control of microgrid in presence of micro-turbine inter...
PDF
Enhancing battery system identification: nonlinear autoregressive modeling fo...
PDF
Smart grid deployment: from a bibliometric analysis to a survey
PDF
Use of analytical hierarchy process for selecting and prioritizing islanding ...
PDF
Enhancing of single-stage grid-connected photovoltaic system using fuzzy logi...
PDF
Enhancing photovoltaic system maximum power point tracking with fuzzy logic-b...
PDF
Adaptive synchronous sliding control for a robot manipulator based on neural ...
PDF
Remote field-programmable gate array laboratory for signal acquisition and de...
PDF
Detecting and resolving feature envy through automated machine learning and m...
PDF
Smart monitoring technique for solar cell systems using internet of things ba...
PDF
An efficient security framework for intrusion detection and prevention in int...
Redefining brain tumor segmentation: a cutting-edge convolutional neural netw...
Embedded machine learning-based road conditions and driving behavior monitoring
Advanced control scheme of doubly fed induction generator for wind turbine us...
Neural network optimizer of proportional-integral-differential controller par...
An improved modulation technique suitable for a three level flying capacitor ...
A review on features and methods of potential fishing zone
Electrical signal interference minimization using appropriate core material f...
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
Bibliometric analysis highlighting the role of women in addressing climate ch...
Voltage and frequency control of microgrid in presence of micro-turbine inter...
Enhancing battery system identification: nonlinear autoregressive modeling fo...
Smart grid deployment: from a bibliometric analysis to a survey
Use of analytical hierarchy process for selecting and prioritizing islanding ...
Enhancing of single-stage grid-connected photovoltaic system using fuzzy logi...
Enhancing photovoltaic system maximum power point tracking with fuzzy logic-b...
Adaptive synchronous sliding control for a robot manipulator based on neural ...
Remote field-programmable gate array laboratory for signal acquisition and de...
Detecting and resolving feature envy through automated machine learning and m...
Smart monitoring technique for solar cell systems using internet of things ba...
An efficient security framework for intrusion detection and prevention in int...

Recently uploaded (20)

PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PDF
Digital Logic Computer Design lecture notes
PPT
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
Internet of Things (IOT) - A guide to understanding
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PDF
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
PPTX
bas. eng. economics group 4 presentation 1.pptx
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PDF
composite construction of structures.pdf
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PPT
introduction to datamining and warehousing
PDF
PPT on Performance Review to get promotions
PPTX
Construction Project Organization Group 2.pptx
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
Artificial Intelligence
Embodied AI: Ushering in the Next Era of Intelligent Systems
Digital Logic Computer Design lecture notes
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
Foundation to blockchain - A guide to Blockchain Tech
Internet of Things (IOT) - A guide to understanding
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Automation-in-Manufacturing-Chapter-Introduction.pdf
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
bas. eng. economics group 4 presentation 1.pptx
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
composite construction of structures.pdf
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
introduction to datamining and warehousing
PPT on Performance Review to get promotions
Construction Project Organization Group 2.pptx
UNIT-1 - COAL BASED THERMAL POWER PLANTS
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Artificial Intelligence

Fault Identification of In-Service Power Transformer using Depolarization Current Analysis

  • 1. International Journal of Electrical and Computer Engineering (IJECE) Vol. 7, No. 2, April 2017, pp. 559~567 ISSN: 2088-8708, DOI: 10.11591/ijece.v7i2.pp559-567  559 Journal homepage: http://iaesjournal.com/online/index.php/IJECE Fault Identification of In-Service Power Transformer using Depolarization Current Analysis M.A. Talib1 , N.A. Muhamad2 , Z.A. Malek3 , B. T. Phung4 1,3 Institute of High Voltage & High Current, Fakulty of Electrical Engineering, Universiti Teknologi Malaysia, 81310 Johor Bahru, Johor, Malaysia 1 TNB Research Sdn Bhd, No 1 Jalan Air Itam, Kajang Selangor, Malaysia 2 School of Electrical and Electronic Engineering, Engineering Campus, University Sains Malaysia, 14300 Nibong Tebal, Penang, Malaysia 4 School of Electrical Engineering & Telecommunications, University of New South Wales, Sydney, Australia Article Info ABSTRACT Article history: Received Apr 7, 2016 Revised Oct 4, 2016 Accepted Oct 18, 2016 Preventive diagnostic testing of in-service power transformers require system outage and expert‟s knowledge and experiences in interpreting the measurement results. The chemical oil analysis may cause significant variance to measurement results due to the different practices in oil sampling, storage, handling and transportation. Thus, a cost effective measuring technique by means of a simpler method that is able provide an accurate measurement results is highly required. The extended application of Polarization and Depolarization Current (PDC) measurement for characterization of different faults conditions on in-service power transformer has been presented in this paper. The oil sample from in-service power transformers with normal and 3 different faults type conditions were sampled and tested for Dissolved Gases Analysis (DGA) and PDC measurement. The DGA results was used to confirm type of faults inside the transformer while the PDC pattern of oil with normal, partial discharge, overheating and arcing were correlated to the oil sample conditions. The analysis result shows that depolarization current provides significant information to defferenciate fault types in power transformer. Thus this finding provides a new alternative in identifying incipient faults and such knowledge can be used to avoid catastrophic failures of power transformers. Keyword: Depolarization current Dielectric response Fault diagnosis Polarization current Transformer fault Copyright © 2017 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: M. A. Talib Institute of High Voltage & High Current, Faculty of Electrical Engineering, Universiti Teknologi Malaysia, 81310 Skudai Johor MALAYSIA Email: mohdaizam@tnbr.com.my 1. INTRODUCTION The continuous supply of electricity from generating stations to the customer is very much dependent on reliability of power transformers installed in the substations [1]. The failures of this strategic unit at any substation can cause interruption of power supply and substantial damage to other components. It may also become potentially dangerous for utility personnel as failures may result to explosions and fire. Therefore, determining their condition would be of tremendous importance to the power utilities. Presently, the maintenance paradigm has moved from scheduled based maintenance to condition based maintenance with the objective to minimize the operational cost and improve the reliability of transformers [2], [3]. A new material and maintenance techniques mainly towards condition based maintenance thus continuously developed to sustain high power reliability and availability [4].
  • 2.  ISSN:2088-8708 IJECE Vol. 7, No. 2, April 2017 : 559–567 560 Well established chemical and electrical diagnostic testing methods have been used to assess the condition of the transformer and classified them according to different fault and ageing mechanisms. For example, the presence of moisture in insulation system can be determined by dielectric dissipation factor (DDF) and insulation resistance (IR) measurement [5], while the mechanical integrity of winding and core clamping structure due to short circuit forces can be confirmed by Frequency Response Analysis (FRA) [6], [7] and the problems with bad joints or connections are identified through winding resistance measurement [8]. For instance, decomposition of the hydrocarbon chain caused by thermal and electrical faults will liberate small quantities of gases and can be classified and quantified by means of DGA [9-11]. Nevertheless, the existing diagnostic technique particularly electrical measurement require electrical isolation or transformer outage before the measurement can be performed. Beside that, the duration for the complete measurement on one transformer which can last for several hours has concerned the power utilities which limit the measurement on basic routine testing and applied on the selected critical transformer due to difficulties of long hour outages. In some situations, due to system overloading the outage of power transformer is not permitted and caused the insulation ageing is not being assessed and determined. Even though, the chemical analyses on transformer oil insulation provide direct information on parameters like oil moisture content, sludge, acidity, Degree of Polymerization (DP) and DGA [12-14], however, most of the chemical analyses are conducted under laboratory condition where sample sampling, storage and transportation cause significant variance due to different practices and location of the site. All these will incurred high cost to the power utilities as part of their condition based maintenance activities. In order to avoid any unwanted circumstances, accurate assessment of transformer condition is crucial so that replacement or refurbishment of the assets can be taken before failures take place. Thus, a cost effective measuring technique, simpler but can provide an accurate measurement results is highly required. In this paper, the PDC was investigated to be used as an alternative diagnostic technique to determine the incipient fault occurs in power transformers. The oil samples was taken from various transformers and tested for its condition. The analysis of PDC pattern for transformers with normal, partial discharge, overheating and arcing faults conditions are presented in this paper. An Artificial Neural Network (ANN) was used to identify each spectrum characteristic for faults identification and the results was compared with other established diagnostic interpretation techniques. 2. POLARIZATION AND DEPOLARIZATION CURRENT MEASUREMENT This section covers the details of experimental test set-up and the testing procedure of PDC measurement. 2.1. Measuring Test Circuit The polarization and depolarization current are measured using the commercial PDC known as Analyzer-1MOD manufactured by Alff Engineering Switzerland. The analyzer can supply the excitation voltage up to 2kV DC and measure the dielectric response in time domain up to 10000s [15]. The analyzer is then connected to the test cell with electrode gap of 1.5mm and capacitance of 60pF. Two electrodes circuit were used, one for application of the test voltage and the other is for current measurement. The amount of insulating liquid required for the measurement is about 210ml. Figure 1 shows the measurement set-up used in the laboratory experimental works. All the measurements were carried out at 1000V and polarization and depolarization times of 10,000s each. Figure 1. Laboratory Experimental Test Set-Up [15] S1 S2 Control voltage Computer with DSP board A + - Test VesselMeasured current PDC Analyzer 1MOD
  • 3. IJECE ISSN: 2088-8708  Fault Identification of In-Service Power Transformer Using Depolarization Current Analysis (M. A. Talib) 561 2.2. Oil Test Sample The oil samples used in this experiment are hydrocarbon based mineral oil obtained from in-service transformers operating at Malaysia power distribution network. The operating conditions of these transformers had previously been identified based on DGA data of their respective oil samples. The test samples were classified into four conditions; normal, partial discharge, overheating and arcing. Prior to PDC measurement, the DGA was performed again on the oil samples to confirm the presence of combustible gases and its nature of faults. In each condition, the oil samples were taken from 10 units of power transformers and every unit has 3 samples; i.e. there are 30 oil samples for each condition. Each PDC assessment was repeated for five times on all oil samples. The aim of having such a large number of the same samples and repetition of PDC assessment process was to ascertain the reproducibility of the test results. To avoid the effect of moisture on polarization and depolarization current measurement, it was crucial that the oil samples were dry. Thus, the selection of transformers are limited to the units with moisture content less than 30ppm; considered dry according to IEC 60422-2013 [12]. 2.3. Testing Procedure The consistency of experimental test results is highly dependent on the PDC test procedure used. The test vessel must be cleaned prior to each measurement process as contamination from previous oil samples could affect the next test results. The residual charges can also affect the polarization current results, thus before the excitation voltage is applied to the test sample, the test object was discharged for 500s. For safety purposes, the test sample was placed in the shielded case. Figure 2 shows the flow chart of experimental works. Figure 2. Flow Chart of Experimental Works 3. RESULTS AND DISCUSSIONS The polarization and depolarization current of oil with different fault conditions in this research are analyzed based on its graphical pattern obtained from the experiments. Artificial Neutral Network (ANN) was used to further analyze the measured currents for transformer fault identification. 3.1. Analysis of Polarization and Depolarization Current Since oil was the only insulation tested in this research, it would be expected that the changes of measured current is attributed to changes at the initial time response [16]. Figure 3(a) and (b) shows the average of polarization and depolarization current on oil samples with normal, partial discharge, overheating and arcing condition. The analysis of polarization current demonstrated that the measured current starts to Start Discharged 500s Check residual charges. Low and constant reading Measured polarization current (1s -10000s) Completed? Measured depolarization current (1s -10000s) Completed? Yes No Yes No No Yes Re-Test for 5 times. Completed? No Test other oil sample Yes End
  • 4.  ISSN:2088-8708 IJECE Vol. 7, No. 2, April 2017 : 559–567 562 stabilize and saturated almost after 100s of being charged until the completion of polarization process. Meanwhile, the depolarization current takes a longer time and only after 1000s the measured currents are starts to stabilize until the end of discharging process. (a) Polarization current (b) Depolarization current Figure 3. Polarization and depolarization current pattern of normal, partial discharge, overheating and arcing oil samples Figure 4. Depolarization current pattern of oil samples at duration of 4 seconds to 100 seconds The curves have shown that the oil with normal condition had the least value of polarization current, while the values were progressively higher in partial discharge, overheating and arcing fault conditions. The average magnitude of maximum polarization current recorded on normal oil sample is 50.23nA, partial discharge is 118.33nA, overheating is 184.96nA and arcing is 226.45nA. The high polarization current of oil samples with fault conditions can be attributed to the fact that faults in power transformer cause breakdown of hydrocarbon structures of oil; thus leading to higher charge carrier mobility and high current magnitude when any external electric field is applied. In addition, it can be seen that the polarization current pattern 10 1 10 2 -4 -3.5 -3 -2.5 -2 -1.5 -1 -0.5 0 x 10 -9 time,t,[s] DepolarizationCurrent,Idepol,[A] Normal Partial discharge Overheating Arcing DepolarizationCurrent,Idepol,[A] time,t[s] 10 0 10 1 10 2 10 3 10 4 0 0.5 1 1.5 2 2.5 x 10 -7 time,t,[s] AveragePolarizationCurrent,Ipol,[A] Normal Partial discharge Overheating Arcing 10 0 10 1 10 2 10 3 10 4 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 x 10 -9 time,t,[s] AverageDepolarizationCurrent,Idepol,[A] Normal Partial discharge Overheating Arcing AverageDepolarizationCurrent,Idepol,[A] time,t[s] AveragePolarizationCurrent,Ipol,[A] time,t[s]
  • 5. IJECE ISSN: 2088-8708  Fault Identification of In-Service Power Transformer Using Depolarization Current Analysis (M. A. Talib) 563 seemingly correspond to degree of fault; the initial slopes of the oil samples with fault conditions are steeper than the oil with normal condition. The plot of depolarization current on oil samples with normal, partial discharge, overheating and arcing fault conditions shows that the depolarization curves are almost identical. The average magnitude of maximum depolarization current recorded is -7.12nA for normal oil samples, -7.06nA for partial discharge, -8.31nA for overheating and -8.28nA for arcing samples. An interesting point was observed on depolarization current pattern at duration of 4 seconds to 100 seconds as the responses are changes with different transformer conditions, as shown in Figure 4 It can be seen that the normal oil condition has low current pattern and as the energy of the fault increases the current pattern of oil samples with fault conditions are also increases. 3.2. Selection of Current for Fault Identification According to [17], the polarization current is the combination of the absorption current due to polarization and the conduction current. On the other hand, the depolarization current consists only of the absorption current because conduction current exists only when the voltage is applied to the dielectric. From the results, both polarization and depolarization currents were found to have correlation with faults in power transformer. Nevertheless, it is important to identify and classify the currents that are effectively used to characterize incipient faults in power transformers. In this research, an Artificial Neural Network (ANN) was used to further analyze the currents for transformer fault identification. The design and simulation of the ANN was done using Neural Network Toolbox provided in MATLAB. Initially, the input data was normalized with the objective of ensuring a uniform statistical distribution of each input value. In this research, the maximum and minimum values of a group of data are used to normalize each single input using the following equation [ ] (1) where I is the normalized value of a single data. Imin and Imax are the input range of the ANN and the typical range is -1 to 1 or 0 to 1. D is the input value for each data while Dmin and Dmax are the minimum and maximum values of the input data. The ANN is a 3 layered structure comprised of input, hidden and output layer. In order to increase the prediction capability of the network, the ANN utilized 2 hidden layers with 100 neurons on each layer. Initially, the learning algorithm employed to train the ANN is Back Propagation (BP). However, the algorithm is too slow for practical problem due to the fact that multilayer networks use sigmoid transfer functions in the hidden layers. These functions, known as „squashing‟, compress infinite input range into a finite output range. Sigmoid function is characterized by the fact that their slope must approach zero as the input gets large. This causes a problem when using steepest descent to train a multilayer network with sigmoid function because the gradient can have a very small magnitude; therefore causing small changes in the weights and biases, even though the weights and biases are far from their optimal values. Thus, a faster Back Propagation (BP) algorithm known as Resilient Back Propagation (Rprop) was used as learning algorithm to train the ANN. This algorithm eliminates the harmful effects of the magnitudes of the partial derivatives. Only the sign of the derivative determines the direction of the weight update. The size of the weight change is determined by a separate update value. The update value for each weight and bias is increased by a factor that depends on the derivative of the performance function with respect to weight changes sign from the previous iteration. If the derivative is zero, the update value remains the same. Whenever the weights are oscillating, the weight change is reduced. If the weight continues to change in the same direction for several iterations, the magnitude of the weight change increases. Table 1. Relationship of ANN output value and type of fault Output Neuron Value Type of Fault 1000 Normal 0100 Partial discharge 0010 Overheating 0001 Arcing
  • 6.  ISSN:2088-8708 IJECE Vol. 7, No. 2, April 2017 : 559–567 564 A PDC sample with a total of 21,900 input data were used to train the ANN and later was tested with another PDC sample data that is separated from the earlier training data. The output will then refer to different types of faults as shown in Table 1. The training procedure and the ANN structure with 2 hidden layers are shown in Figure 5 and Figure 6 respectively. Figure 5. ANN training procedure Figure 6. Schematic diagram of the ANN Finally, the accuracy and performance of the ANN output is determined by the following equation, (2) Start Get the database Matching? No YesReaching the performance goal? Test the ANN Set input data of training Normalization of data Set the target output Start training the ANN Accept Denied End Yes No
  • 7. IJECE ISSN: 2088-8708  Fault Identification of In-Service Power Transformer Using Depolarization Current Analysis (M. A. Talib) 565 The results of ANN analysis on polarization and depolarization current are shown in Table 2.0 and Table 3.0 respectively. Table 2. ANN result of polarization current Condition Correct output recognised Wrong output recognised % ANN Accuracy Normal 87 3 97 Partial discharge 58 7 80 Overheating 15 5 75 Arcing 36 9 90 Table 3. ANN result of depolarization current Condition Correct output recognised Wrong output recognised % ANN Accuracy Normal 86 4 96 Partial discharge 60 5 92 Overheating 19 1 95 Arcing 43 2 96 The ANN analysis of polarization current demonstrated that higher accuracy of more than 90% was observed for oil samples on transformer with normal and arcing fault conditions. On the other hand, lower accuracy was observed for identification and classification of partial discharge and thermal overheating faults as the accuracy recorded is only 80% and 75% respectively. Meanwhile, higher accuracy of more than 90% was recorded for depolarization current on all conditions. Both normal and arcing condition has ANN accuracy of 96%, whereas thermal overheating fault has accuracy of 95%. The partial discharge fault was observed slightly lower with ANN accuracy of 92%. Based on this ANN simulation results, depolarization current yielded a better accuracy in identifying and classifying different transformer conditions as compared to polarization current and identified as the current of main interest that can be uniquely used for fault identification of in-service power transformer. The results has confirmed the initial research done by Bhumiwat [18] on overheating of transformer solid insulation stated that the condition can be identified by the prominently crooked shape of the depolarization current. 4. CONCLUSION In this paper, the extended application of PDC measurement for characterization of different faults conditions of in-service power transformer was investigated. The oil sample with normal, partial discharge, overheating and arcing condition were taken from respective units and tested for its combustible fault gases, polarization and depolarization current. The changes of the molecular properties of the insulating oil material due to different fault conditions was found influences the initial time response of both measured currents. The sensitivity analysis using Artificial Neural Network (ANN) shows that depolarization current gives a better accuracy in identifying and classifying different transformer conditions as compared to polarization current. Thus, depolarization current measurements provide a new alternative in identifying incipient faults and such knowledge can be used to avoid catastrophic failures of power transformers. ACKNOWLEDGEMENTS The authors would like to acknowledge the support of TNB and Malaysia Ministry of Higher Education, Universiti Teknologi Malaysia (Vot 05J82, 04H67, 4L014, and 4L607) for technical and financial support. REFERENCES [1] Sunil M, Jaralikar, Aruna M, “Study of Performance of Power Station for Operational Optimization”, International Journal of Electrical and Computer Engineering (IJECE),Vol. 2, No. 1, February 2012, pp. 17-25. [2] J.A. Lapworth, P.N. Jarman and I.R. Funnell, “Condition Assessment Techniques For Large Power Transformers”, 2nd International Conference on the Reliability of Transmission and Distribution Equipment, pp 85-90, 1995. [3] R. Schwarz, M. Muhr, “Diagnostic Methods for Transformer”, IEEE International Conference on Condition Monitoring and Diagnosis, pp 974-977, 2008.
  • 8.  ISSN:2088-8708 IJECE Vol. 7, No. 2, April 2017 : 559–567 566 [4] H. Borsi, E. Gockenbach, “Comparison between Oil Immersed and SF6 Gas Power Transformers Ratings”, TechCon Asia-Pacific Conference, 1-2 May 2007, Sydney, Australia. [5] Wang, M.; Vandermaar, A.J.; Srivastava, K.D., “Review Of Condition Assessment Of Power Transformer In Service”, IEEE Electrical Insulation Magazine, Vol 18, Issue 6, pp 12-25, 2002. [6] Liu Yong, Xiaochen ; Ji, Shengchang “Study On Sweep Frequency Impedance Method For Detecting Internal Winding Short Circuit Fault In Power Transformer” IEEE International Conference on Power Modulator and High Voltage (IPMHVC), pp 137-140, 2014. [7] Aljohani, O.; Abu-Siada, A. “Application Of FRA Polar Plot Technique To Diagnose Internal Faults In Power Transformers”, IEEE PES General Meeting Conference & Exposition, pp 1-5, 2014. [8] IEEE Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors, IEEE C57.152-2013. [9] IEC Standard, Mineral Oil-impregnated Electrical Equipment in Service - Guide to the Interpretation of Dissolved and Free Gases Analysis, IEC 60599:2015. [10] Duval. M, dePablo. A, “Interpretation of Gas-in-oil Analysis Using New IEC Publication 60599 and IEC TC10 Database”, IEEE Electrical Insulation Magazine, Vol 17(2) March/April, pp 31-41, 2001. [11] Sherif S. M. Ghoneim, Sayed A. Ward, “Dissolved Gas Analysis as a Diagnostic Tools for Early Detection of Transformer Faults”, Advances in Electrical Engineering Systems (AEES) 152 Vol. 1, No. 3, 2012. [12] IEC Standard, Mineral Insulating Oils in Electrical Equipment – Supervision and Maintenance Guidance, IEC 60422:2013. [13] Priyesh Kumar Pandey, Zakir Husain, R.K. Jarial, “ANFIS Based Approach to Estimate Remnant Life of Power Transformer by Predicting Furan Contents”, International Journal of Electrical and Computer Engineering (IJECE),Vol. 4, No. 4, August 2014, pp. 463-470. [14] A.A. Suleiman, N.A. Muhamad, N. Bashir, N.S. Murad and Y.Z. Arief. “Effect of Moisture on Breakdown Voltage and Structure of Palm Based Insulation Oils”. IEEE Transactions on Dielectric and Electrical Insulation (TDEI), 21(5) October 2014. [15] PDC-Analyzer 1MOD User Guide Hardware, Alff Engineering, Switzerland. [16] A. Küchler, T. Leibfried, B. Breitenbauch, J.J. Alff, V. Der Houhanessian, W.S. Zaengl, “Transformer Insulation Diagnosis by Polarization and Depolarization Current Analysis”, Proceeding of 48. Internationales Wissenschaftliches Kolloquium, Technische Universität Ilmenau, 2003. [17] S.A. Bhumiwat, “The Latest On-Site Non-Destructive Technique for Insulation Analysis of Electrical Power Apparatus”, Weidman ACTI Annual Technical Conference, 2004. [18] S.A. Bhumiwat, “Identification of Overheating in Transformer Solid Insulation by Polarization Depolarization Current Analysis”, IEEE Electrical Insulation Conference (EIC2013), pp 449-453, 2013. BIOGRAPHIES OF AUTHORS Mohd Aizam Talib received his Bachelor in Electrical Engineering from the University of Portsmouth, UK in 1997, and Master degree in Electrical Engineering from Universiti Tenaga Nasional (UNITEN), Malaysia in 2001. Upon graduation in 1997, he worked with ABB Transmission and Distribution Sdn Bhd as a Design Engineer. Since 1998, he has been employed by TNB Research Sdn Bhd as a Research Engineer. His research interests are in transformer condition monitoring, insulation diagnostic and dielectric measurements. He is currently a Ph.D. degree student at Universiti Teknologi Malaysia. Nor Asiah Muhamad is senior lectures in School of Electrical and Electronic Engineering Universiti Sains Malaysia since Sep 2016. She has over 13 experince working with Institute of High Voltage and High Current (IVAT) Universiti Teknologi Malaysia as lecturer as well as researcher. Received her PhD in 2009 from University of New South Wales, Australia in area oil insulation monitoring and diagnosis. Received Bachelor degree in Electrical and Electronic Engineering from Universiti Teknologi PETRONAS, Malaysia in 2002 and Master degree in Electrical Power Engineering from University of South Australia in 2006. Start doing research in power system equipment monitoring since 2005 and the main topics related to her work are insulation diagnosis, new material for HV insulation and condition monitoring systems.
  • 9. IJECE ISSN: 2088-8708  Fault Identification of In-Service Power Transformer Using Depolarization Current Analysis (M. A. Talib) 567 Zulkurnain Abdul-Malek was born in Kuantan, Malaysia in 1965. He obtained his B.E. from Monash University (Melbourne) in 1989 and his MSc and PhD degrees from University of Wales Cardiff in 1995 and 1999 respectively. Since 1989 he has been a member of the Electrical Engineering Faculty at UTM. He is currently an Associate Professor and the Director of UTM Institute of High Voltage and High Current. His research interests include intelligent condition monitoring of HV equipment, lightning detection and warning systems, nanodielectrics and fast transient response of high voltage surge arresters. B.T. Phung Gained a Ph.D. in Electrical Engineering in 1998 and is currently a Senior Lecturer in the School of Electrical Engineering at the University of New South Wales, Sydney, Australia. He has over 30 years of practical research/development experience in partial discharge measurement, and in on-line condition monitoring of high- voltage equipment. His research interests include electrical insulation (dielectric materials and diagnostic methods), high-voltage engineering (generation, testing and measurement techniques), electromagnetic transients in power systems, and power system equipment (design and condition monitoring methods).