The document discusses a case where a new 40-MVA transformer was found to have an elevated power factor during testing. It was returned to the factory, where inspection found treeing on the phase barrier board between the H2 and H3 windings. Power factor and induced voltage tests during teardown identified the source of contamination and explained the earlier high test results. The transformer's winding design and location of the treeing helped determine the cause of the failure.