SlideShare a Scribd company logo
2
Most read
3
Most read
5
Most read
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
ABCDEFG
ABCDEFG
Date
WORKED
22.12.15
QASIM.M EPI WAREHOUSES, WHO, NIH ISLAMABAD
SIEMENS (PAKISTAN) ENGINEERING CO. LTD.
I CS/671544043015-1
TRAMRI
GRID
800A MCCB
450A
BUSBAR 400V
250A
PEL TRA NSFORMER
400 KVA, 11KV/
400V, 20.99A/
55OA, 3-PHASE,
DYn11
SIEM ENS
TRA NSFORMER 630
KVA, 11KV/400V,
33.1A/876.5A, 3-
PHASE, DYn11
BANK FEDERAL DRUG
SURVELLIANCE
LABORATORY
ISLAMABAD
NATIONAL
CONTROL
LABORATORY
FOR
BIOLOGICALS
MALE HOSTEL ALLERGY
CENTRE
POST OFFICE GENERAL
HOSPITAL
PEL TRA NSFORMER
50 KVA, 11KV/
400V, 2.62A/
69.56A, 3-PHASE,
DYn11
ATS
600A MCCB
PHASE FAILURE PANEL
MANUAL
CHANGE
OVER 600A
250A200A150A
G
CAT DG GENSET
300KVA, 400V,
433A,50HZ,4-POL E
COLD
WARE
HOUSE-2
COLD
WARE
HOUSE-1
DRY
WARE
HOUSE-2
DRY
WARE
HOUSE-1
4 C , 150mm2 CU/PVC/PVC+ 1 C
75mm2 EARTH CU/PVC/PVC
4X 4 C 150mm2 CU/
PVC/PVC
3 X 1C 400mm2 CU/PVC/PVC+ 1 C 400mm2
NEUTRAL CU/PVC/PVC
2 X 3 1C 185mm2 CU/PVC/PVC
CABLE+ 1C 185mm2 NEUTRAL
CU/PVC/PVC + 185mm2 EARTH
2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC
2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC
2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC
PEL TRA NSFORMER
400 KVA, 11KV/
400V, 20.99A/
556.48A, 3-PHASE,
DYn11
PEL TRA NSFORM ER
500 KVA, 11KV/
400V, 26.24A/
645.6A, 3-PHASE,
DYn11
PEL TRA NSFORMER
25 KVA, 11KV/
400V,1.31A/34.78A
3-PHASE, DYn11
PEL TRA NSFORMER
200 KVA, 11KV/
400V, 10.49A/
278.24A, 3-PHASE,
DYn11
STAFF COLONYFEDERAL
MEDICALAND
DENTAL
COLLEGE
PEL TRA NSFORMER
400 KVA, 11KV/
400V, 20.99A/
556.48, 3-PHASE,
DYn11
HEALTH
ACADEMY
FEDERAL EPI
OFFICE AREA
PEL TRA NSFORMER
500 KVA, 11KV/
400V, 26.24A/
645,6A, 3-PHASE,
DYn11
HOSTEL
ELMETEC
TRA NSFORMER 200
KVA, 11KV/400V,
10.49A/278.24A, 3-
PHASE, DYn11
PEL TRA NSFORMER
200 KVA, 11KV/
400V, 10.49A/
278.24A, 3-PHASE,
DYn11
ELEMETEC
TRA NSFORMER 25
KVA, 11KV/
400V,1.31A/34.78A
3-PHASE, DYn11
PEL TRA NSFORMER
200 KVA, 11KV/
400V, 10.49A/
278.24A, 3-PHASE,
DYn11
PAGE 01/013004496307-A
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
ABCDEFG
ABCDEFG
Date
WORKED
22.12.15
QASIM.M EPI WAREHOUSES, WHO, NIH ISLAMABAD
SIEMENS (PAKISTAN) ENGINEERING CO. LTD.
I CS/671544043015-1
Barakoh
Grid
Air circuit breaker In=1000A ICU=25KA at 500V with motorized operation mechanismBUSBAR 400V
MCCB 400A
ATS G
Breaker
MCB 400A
BUSBAR
16A
2000A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip,
breaker tripping signal with MECH, on and off push button, 12KV, 2000A, 25KA, 50Hz, 12/ 36/95KV
CT = Double core 100A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA 1s, 12/36/95KV (Protection and metering)
PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV
Trafo = 500KVA
11/0.415KV,26.25/
722A,
DYn11
MCB 300A
BUSBAR
70A
RMU
Automatic Voltage Regulator
2000A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip,
breaker tripping signal with MECH, on and off push button, 12KV, 2000A, 25KA 1s, 50Hz, 12/ 36/95KV
CT = Double core 100A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection and metering)
PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV
ATS
Breaker
MCB 300A
250A 100A
16A 225A
To DB 1
(Virology)
DWG. No: VIR/
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 2.5
square mm
To DB 2
(Virology)
DWG. No: VIR/
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 120
square mm
To DB 3
(Virology)
DWG. No: VIR/
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 35
square mm
To DB 1
DWG. No:
MBL /
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 16
square mm
To DB 2
DWG. No:
MBL /
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 2.5
square mm
To DB 3
DWG. No:
MBL /
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 95
square mm
MCB 400A
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 xcore CU/PVC/PVC 4x3 + 2x1 95 square mm
3 xcore XLPE240 square mm
3 xcore XLPE240 square mm
3 xcore XLPE35 square mm
AVR= 3xSinglePhase,
100Amps, Rated V =
11000V ,BIL 95KV
300-
500KVAR
Capacitor
Bank
800AVCB
800A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker
motorized F coil closing coil with counter, 210mm pole spacing 6 no
plus 6 nc with varistorcircuit, 24 pole terminalstrip,
breaker tripping signal with MECH, on and off push button, 12KV,
800A, 25KA 1s, 50Hz, 12/ 36/95KV
CT = Double core 50A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA,
0.5M5, 25KA, 12/36/95KV (Protection and metering)
PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/
36/95KV
1250AVCB
To EPI Warehouse
Drawing Page/02
3 xcore XLPE150 square mm 900meter
1250A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter,
210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip,
breaker tripping signal with MECH, on and off push button, 12KV, 1250A, 25KA 1s, 50Hz,12/ 36/95KV
CT = Double core 60A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection
and metering)
PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV
BUSBAR 11kV
PAGE 01/04
SIEMENS GENSET
100KVA, 415V,
130A, 50HZ, 4-POL EG
DENYO POWER
GENSET 300KVA,
400V, 433A,50HZ,4-
POL E
(OPTION 1 ) RECOMMENDED AMMENDMENT IN PREVIOUS PROPOSED DESIGN DRAWING ON THE BASIS OF
EXISTING LOAD DETAILS WITH FUTURE COLD UNITS IN DRY WARE HOUSE AND NINE NEW UNITS IN COLD
WARE HOUSE
3 xcore XLPE240 square mm
3004496307-P
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
ABCDEFG
ABCDEFG
Date
WORKED
22.12.15
QASIM.M EPI WAREHOUSES, WHO, NIH ISLAMABAD
SIEMENS (PAKISTAN) ENGINEERING CO. LTD.
I CS/671544043015-1
1200A,BUSBAR
400V
250A
PEL TRA NSFORMER
1000 KVA, 11KV/
400V, 52/1391A, 3-
PHASE, DYn11
ATS
1250A ACB, TP DRAW OUT TYPE
250A200A150A
COLD
WARE
HOUSE-2
SMDB 1
COLD
WARE
HOUSE-1
SMDB 1
DRY
WARE
HOUSE-2
SMDB 1
DRY
WARE
HOUSE-1
SMDB 1
G
800A MCCB
2 X 3 1C 240mm2 CU/PVC/SWA CABLE+
1C 240mm2 NEUTRAL CU/PVC/PVC +
240mm2 EARTH CU/PVC
DG GENSET 500KVA,
400V, 665A,50HZ,4-
POL E
EXISTING DRAWING
PROPOSED SINGLELINE
DIAGRAM
1250A,TP 1250A ACB BREAKER DRAW OUT TYPE SHOULD BE USEDFOR ISOLATING THE BUS BAR
LEGENDS :
ECC EARTH COPPER CONDUCTER
2C X 240mm2 PVC+ 1C X 120mm2 PVC EARTHCU/PVC
2 X 3 1C 240mm2 CU/PVC/PVC CABLE + 1C 240mm2 NEUTRAL CU/PVC/PVC+
240mm2 EARTH CU/PVC
4 C , 150mm2 CU/PVC/PVC+ 1 C
75mm2 EARTH CU/PVC
250A
200-400kVAR POWER FACTOR
IMPROVEMENT PANEL
From Drawing
Page/01
150A
COLD
WARE
HOUSE-2
SMDB 1
150A
COLD
WARE
HOUSE-1
SMDB 1
(OPTION 1) PROPOSED DESIGN DRAWING ON THE BASIS OF EXISTING LOAD DETAILS
WITH NINE NEW COLD UNITS AND FUTURE COLD UNITS IN DRY WARE HOUSE
1250A,TP
G
800AMCCB
2 X 3 1C 240mm2 CU/PVC/SWA CABLE+
1C 240mm2 NEUTRAL CU/PVC/PVC +
240mm2 EARTH CU/PVC
DG GENSET 500KVA,
400V, 665A,50HZ,4-
POL E
AUTO
SYNCHRONOZING
PANEL, 50HZ, 415V
2 X 3 1C 240mm2 CU/PVC/PVC CABLE+
1C 240mm2 NEUTRAL CU/PVC/PVC +
240mm2 EARTH CU/PVC
2 X 3 1C 240mm2 CU/PVC/PVC CABLE+
1C 240mm2 NEUTRAL CU/PVC/PVC +
240mm2 EARTH CU PVC
2 X 3 1C 240mm2 CU/PVC/PVC CABLE + 1C 240mm2 NEUTRAL CU/PVC/PVC+
240mm2 EARTH CU/PVC
1250A VCB, TP
UNDER GROUND CABLEFROM
NIH SUBSTATION
2 X 3 1C 240mm2 CU/PVC/PVC CABLE + 1C 240mm2 NEUTRAL CU/PVC/PVC+
240mm2 EARTH CU/PVC
3C 150mm2 CU/XLPE/STA/PVC CABLE
3C 150mm2 CU/XLPE/STA/PVC CABLE1250A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter,
210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip,
breaker tripping signal with MECH, on and off push button, 12KV, 1250A, 25KA 1s, 50Hz, 12/ 36/95KV
CT = Double core 60A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection
and metering)
PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV , under and over voltage
Overcurrent, earth fault, short circuit protection
3004496307-P PAGE 02/04
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
ABCDEFG
ABCDEFG
Date
WORKED
22.12.15
QASIM.M EPI WAREHOUSES, WHO, NIH ISLAMABAD
SIEMENS (PAKISTAN) ENGINEERING CO. LTD.
I CS/671544043015-1
Barakoh
Grid
800A Air circuit breaker In=1000A ICU=25KA at 500V with motorized operation mechanismBUSBAR 400V
MCCB 400A
ATS G
Breaker
MCB 400A
BUSBAR
16A
1250A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip,
breaker tripping signal with MECH, on and off push button, 12KV, 1250A, 50KA, 50Hz, 12/ 36/95KV
CT = Double core 70A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA 1s, 12/36/95KV (Protection and metering)
PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV
Trafo = 500KVA
11/0.415KV,26.25/
722A,
DYn11
MCB 300A
BUSBAR
70A
RMU
Automatic Voltage Regulator
1250A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip,
breaker tripping signal with MECH, on and off push button, 12KV, 1250A, 50KA 1s, 50Hz, 12/ 36/95KV
CT = Double core 70A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection and metering)
PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV
ATS
Breaker
MCB 300A
250A 100A
16A 225A
To DB 1
(Virology)
DWG. No: VIR/
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 2.5
square mm
To DB 2
(Virology)
DWG. No: VIR/
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 120
square mm
To DB 3
(Virology)
DWG. No: VIR/
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 35
square mm
To DB 1
DWG. No:
MBL /
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 16
square mm
To DB 2
DWG. No:
MBL /
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 2.5
square mm
To DB 3
DWG. No:
MBL /
DB01.2014-15
Feeder Cable :
4 x coreCU/
PVC/PVC 95
square mm
MCB 400A
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm
1 xcore CU/PVC/PVC 4x3 + 2x1 95 square mm
3 xcore XLPE35 square mm
3 xcore XLPE150 square mm
3 xcore XLPE150 square mm
AVR= 3xSinglePhase,
100Amps,, BIL 95KV
300-
500KVAR
Capacitor
Bank
800AVCB
800A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter,
210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip,
breaker trippingsignal with MECH, on and off push button,12KV, 800A, 25KA 1s, 50Hz, 12/ 36/95KV
CT = Double core 50A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection
and metering)
PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV
800AVCB
To EPI Warehouse
Drawing Page/04
3 xcore XLPE35 square mm 900meter
800A VCB Incoming/ Outgoing feeder (Vacuum circuit breakermotorized F coilclosing coilwith counter,
210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip,
breaker tripping signal with MECH, on and off push button, 12KV, 800A, 25KA 1s, 50Hz, 12/ 36/95KV
CT = Double core 50A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection
and metering)
PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV
BUSBAR 11kV
SIEMENS GENSET
100KVA, 415V,
130A, 50HZ, 4-POL EG
DENYO POWER
GENSET 300KVA,
400V, 433A,50HZ,4-
POL E
(OPTION 2) AMMENDMENT IN PROPOSED DESIGN DRAWING ON
THE BASIS OF EXISTING LOAD DETAILS WITH OUT ANY FUTURE COLD
UNITS IN DRY WARE HOUSES
3004496307-P PAGE 03/04
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
ABCDEFG
ABCDEFG
Date
WORKED
22.12.15
QASIM.M EPI WAREHOUSES, WHO, NIH ISLAMABAD
SIEMENS (PAKISTAN) ENGINEERING CO. LTD.
I CS/671544043015-1
450A
BUSBAR 400V
250A
PEL TRA NSFORMER
400 KVA, 11KV/
400V, 20.99A/
55OA, 3-PHASE,
DYn11
ATS
800A OPTIONAL IF REQUIRED
EXISTING PHASE FAILURE PANEL
MANUAL
CHANGE
OVER 600A
250A200A150A
G
CAT DG GENSET
300KVA, 400V,
433A,50HZ,4-POL E
COLD
WARE
HOUSE-2
SMDB 1
COLD
WARE
HOUSE-1
SMDB 1
DRY
WARE
HOUSE-2
SMDB 1
DRY
WARE
HOUSE-1
SMDB 1
G
450A
2 X 3 1C 185mm2 CU/PVC/SWA
CABLE+ 1C 185mm2 NEUTRAL CU/
PVC/PVC + 185mm2 EARTH CU/ PVC
(OPTIONAL) IF
REQU IRED
DG GENSET 300KVA,
400V, 433A,50HZ,4-
POL E
EXISTING DRAWING
PROPOSED SINGLELINE
DIAGRAM
600A
600A MCCB PHASE
FAILURE PANEL
BREAKER TO BE
REPLACEDWITH 800A
MCCB
600A MCCB BREAKER SHOULD BE USED FOR ISOLATING THE BUS BAR
LEGENDS :
ECC EARTH COPPER CONDUCTER
2 X SINGLE CORE 185mm2 CABLE
CU/PVC/PVC
3 X 1C 400mm2 CU/PVC/PVC+ 1 C 400mm2 NEUTRAL CU/PVC/PVC
2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC+
185mm2 EARTH CU/PVC SHOULD BE PROVIDED
2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC+
185mm2 EARTH CU/PVC SHOULD BE PROVIDED
2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC+
185mm2 EARTH CU/ PVC SHOULD BE PROVIDED
2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC+
185mm2 EARTH CU/ PVC SHOULD BE PROVIDED
4 C , 150mm2 CU/PVC/PVC+ 1 C
75mm2 ECC CU/PVC
250A
200-400kVAR POWER FACTOR
IMPROVEMENT PANEL
From Drawing
Page/03
150A
COLD
WARE
HOUSE-2
SMDB 1
150A
COLD
WARE
HOUSE-1
SMDB 1
HT OVER HEAD LINE FROM TRAMRI GRID
WITH FUSE LINK WILL BE REPLACEDWITH
UNDERGROUND CABLE COMING FROM
NIH SUBSTATION
(OPTION 2) THIS PROPOSED DESIGN DRAWING IS ON THE BASIS OF EXISTING LOAD DETAILS WITH NINE NEW
COLD UNITS AND WITH OUT ANY SPARE BREAKERS LOAD FOR FUTURE COLD UNITS IN DRY WARE HOUSE
800A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter,
210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip,
breaker tripping signal with MECH, on and off push button, 12kV, 800A, 25KA 1s, 50Hz, 12/ 36/95KV
CT = Double core 50A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV
PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV, under and over voltage ,
overcurrent, over current, earth fault and short circuit protection
800AVCB
3 xcore XLPE35 square mm 900meter
3 xcore XLPE35 square mm
3004496307-P PAGE 04/04

More Related Content

PDF
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
PDF
Principles and Design of LV System
PPTX
Electrical substation (one and half breaker scheme)
PDF
Single line diagram ats apfc
PPTX
Basics of electrical control panel
PDF
400kV GIS Substation
PPS
Electrical wiring domestic and industries
PPTX
Substations
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
Principles and Design of LV System
Electrical substation (one and half breaker scheme)
Single line diagram ats apfc
Basics of electrical control panel
400kV GIS Substation
Electrical wiring domestic and industries
Substations

What's hot (20)

PPT
Types of wires and cables
PPTX
220 kv gss
PPT
Cable and laying
PDF
Types of Cables.pdf
DOCX
132 kv sub-station, power transmission
PPTX
Traction assembly shop
PPTX
Underground cables vs overhead lines
PPT
Types of wires and cables ic
PPTX
presentation on substation layout and BUS bar arrangement.
PDF
Stringing Chart for 400 KV D/C Quad Transmission Line
PPT
Fault level calculations
PPTX
report on electrical wiring
PPT
Switchyard final
DOCX
PPTX
Distribution systems
PPT
Survey & ts for ehv lines
DOC
ELECTRICAL WIRING
PDF
33/11 KV SUBSTATION
PPTX
Transformer repairing & manufacturing.pptx
PDF
2 delugevalve a
Types of wires and cables
220 kv gss
Cable and laying
Types of Cables.pdf
132 kv sub-station, power transmission
Traction assembly shop
Underground cables vs overhead lines
Types of wires and cables ic
presentation on substation layout and BUS bar arrangement.
Stringing Chart for 400 KV D/C Quad Transmission Line
Fault level calculations
report on electrical wiring
Switchyard final
Distribution systems
Survey & ts for ehv lines
ELECTRICAL WIRING
33/11 KV SUBSTATION
Transformer repairing & manufacturing.pptx
2 delugevalve a
Ad

Viewers also liked (20)

PPT
Electrical Wiring Practices and Diagrams
DOCX
33/11 kV substation (u.p.p.c.l.)
PDF
Mount Isa Mines 11kV Protection Relays Upgrade
PDF
GC_Europe_GM_short
PDF
Folha Dominical - 28.06.09 Nº280
PDF
Utility Tool - LV HV Cable Jointing, Cable Preparation & Overhead Line Toolin...
PPTX
Pole mounted substaion in kerala
PDF
Integrated Rural Electrification
PPTX
Rural electrification status of India
RTF
Training report of 33/11kv substation Mohamdabad, Tundla
PPTX
Rural electrification
PPTX
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
PDF
Rural electrification
PPTX
Earthing
PPT
Basics of earthing
PPTX
Earthing
PPT
Substation Training presentation
PPS
electrical distribution system ppt/13b61a0221
PPT
Earthing Concepts
PPTX
Electrical earthing
Electrical Wiring Practices and Diagrams
33/11 kV substation (u.p.p.c.l.)
Mount Isa Mines 11kV Protection Relays Upgrade
GC_Europe_GM_short
Folha Dominical - 28.06.09 Nº280
Utility Tool - LV HV Cable Jointing, Cable Preparation & Overhead Line Toolin...
Pole mounted substaion in kerala
Integrated Rural Electrification
Rural electrification status of India
Training report of 33/11kv substation Mohamdabad, Tundla
Rural electrification
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Rural electrification
Earthing
Basics of earthing
Earthing
Substation Training presentation
electrical distribution system ppt/13b61a0221
Earthing Concepts
Electrical earthing
Ad

Similar to As built and proposed SLD (20)

PDF
3vj-mccb-brochure-march-2021.pdf
PDF
Mcbelcb
PDF
Low voltage circuit breakers & contactors general leaflet ls
PDF
M. standard-stock-materials-for-33k v-system
PDF
Crane drawing swl 20/5 ton used for hoisting application in rolling mills and...
PDF
CHiNT Price List LV Pakistan
PDF
33-11kV SUBSTATION SLD to configure load distribution
PDF
Curso Selectividad - Sesión 3 clases3.pdf
PPTX
Installation testing and_commissioning_o (1)
PDF
Catalog ls metasol mc e_1004
PDF
Catalog ls metasol mc_e_1008_denhathe.vn
PDF
Catalog ls metasol mc e_1004_denhathe.vn
PDF
Catalog ls metasol mc_e_1008
PDF
Catalogue mccb doi moi cua hang h yundai
PPTX
Product: UPS: UniStar VP
PDF
Catalog CB tép MCB 2P 3P 4P BKN BKH LS
PDF
sqd-app-guide-2-25c.pdf
PDF
SMC LET Primary Injection Test Sets
3vj-mccb-brochure-march-2021.pdf
Mcbelcb
Low voltage circuit breakers & contactors general leaflet ls
M. standard-stock-materials-for-33k v-system
Crane drawing swl 20/5 ton used for hoisting application in rolling mills and...
CHiNT Price List LV Pakistan
33-11kV SUBSTATION SLD to configure load distribution
Curso Selectividad - Sesión 3 clases3.pdf
Installation testing and_commissioning_o (1)
Catalog ls metasol mc e_1004
Catalog ls metasol mc_e_1008_denhathe.vn
Catalog ls metasol mc e_1004_denhathe.vn
Catalog ls metasol mc_e_1008
Catalogue mccb doi moi cua hang h yundai
Product: UPS: UniStar VP
Catalog CB tép MCB 2P 3P 4P BKN BKH LS
sqd-app-guide-2-25c.pdf
SMC LET Primary Injection Test Sets

As built and proposed SLD

  • 1. 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 ABCDEFG ABCDEFG Date WORKED 22.12.15 QASIM.M EPI WAREHOUSES, WHO, NIH ISLAMABAD SIEMENS (PAKISTAN) ENGINEERING CO. LTD. I CS/671544043015-1 TRAMRI GRID 800A MCCB 450A BUSBAR 400V 250A PEL TRA NSFORMER 400 KVA, 11KV/ 400V, 20.99A/ 55OA, 3-PHASE, DYn11 SIEM ENS TRA NSFORMER 630 KVA, 11KV/400V, 33.1A/876.5A, 3- PHASE, DYn11 BANK FEDERAL DRUG SURVELLIANCE LABORATORY ISLAMABAD NATIONAL CONTROL LABORATORY FOR BIOLOGICALS MALE HOSTEL ALLERGY CENTRE POST OFFICE GENERAL HOSPITAL PEL TRA NSFORMER 50 KVA, 11KV/ 400V, 2.62A/ 69.56A, 3-PHASE, DYn11 ATS 600A MCCB PHASE FAILURE PANEL MANUAL CHANGE OVER 600A 250A200A150A G CAT DG GENSET 300KVA, 400V, 433A,50HZ,4-POL E COLD WARE HOUSE-2 COLD WARE HOUSE-1 DRY WARE HOUSE-2 DRY WARE HOUSE-1 4 C , 150mm2 CU/PVC/PVC+ 1 C 75mm2 EARTH CU/PVC/PVC 4X 4 C 150mm2 CU/ PVC/PVC 3 X 1C 400mm2 CU/PVC/PVC+ 1 C 400mm2 NEUTRAL CU/PVC/PVC 2 X 3 1C 185mm2 CU/PVC/PVC CABLE+ 1C 185mm2 NEUTRAL CU/PVC/PVC + 185mm2 EARTH 2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC 2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC 2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC PEL TRA NSFORMER 400 KVA, 11KV/ 400V, 20.99A/ 556.48A, 3-PHASE, DYn11 PEL TRA NSFORM ER 500 KVA, 11KV/ 400V, 26.24A/ 645.6A, 3-PHASE, DYn11 PEL TRA NSFORMER 25 KVA, 11KV/ 400V,1.31A/34.78A 3-PHASE, DYn11 PEL TRA NSFORMER 200 KVA, 11KV/ 400V, 10.49A/ 278.24A, 3-PHASE, DYn11 STAFF COLONYFEDERAL MEDICALAND DENTAL COLLEGE PEL TRA NSFORMER 400 KVA, 11KV/ 400V, 20.99A/ 556.48, 3-PHASE, DYn11 HEALTH ACADEMY FEDERAL EPI OFFICE AREA PEL TRA NSFORMER 500 KVA, 11KV/ 400V, 26.24A/ 645,6A, 3-PHASE, DYn11 HOSTEL ELMETEC TRA NSFORMER 200 KVA, 11KV/400V, 10.49A/278.24A, 3- PHASE, DYn11 PEL TRA NSFORMER 200 KVA, 11KV/ 400V, 10.49A/ 278.24A, 3-PHASE, DYn11 ELEMETEC TRA NSFORMER 25 KVA, 11KV/ 400V,1.31A/34.78A 3-PHASE, DYn11 PEL TRA NSFORMER 200 KVA, 11KV/ 400V, 10.49A/ 278.24A, 3-PHASE, DYn11 PAGE 01/013004496307-A
  • 2. 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 ABCDEFG ABCDEFG Date WORKED 22.12.15 QASIM.M EPI WAREHOUSES, WHO, NIH ISLAMABAD SIEMENS (PAKISTAN) ENGINEERING CO. LTD. I CS/671544043015-1 Barakoh Grid Air circuit breaker In=1000A ICU=25KA at 500V with motorized operation mechanismBUSBAR 400V MCCB 400A ATS G Breaker MCB 400A BUSBAR 16A 2000A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip, breaker tripping signal with MECH, on and off push button, 12KV, 2000A, 25KA, 50Hz, 12/ 36/95KV CT = Double core 100A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA 1s, 12/36/95KV (Protection and metering) PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV Trafo = 500KVA 11/0.415KV,26.25/ 722A, DYn11 MCB 300A BUSBAR 70A RMU Automatic Voltage Regulator 2000A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip, breaker tripping signal with MECH, on and off push button, 12KV, 2000A, 25KA 1s, 50Hz, 12/ 36/95KV CT = Double core 100A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection and metering) PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV ATS Breaker MCB 300A 250A 100A 16A 225A To DB 1 (Virology) DWG. No: VIR/ DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 2.5 square mm To DB 2 (Virology) DWG. No: VIR/ DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 120 square mm To DB 3 (Virology) DWG. No: VIR/ DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 35 square mm To DB 1 DWG. No: MBL / DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 16 square mm To DB 2 DWG. No: MBL / DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 2.5 square mm To DB 3 DWG. No: MBL / DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 95 square mm MCB 400A 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 xcore CU/PVC/PVC 4x3 + 2x1 95 square mm 3 xcore XLPE240 square mm 3 xcore XLPE240 square mm 3 xcore XLPE35 square mm AVR= 3xSinglePhase, 100Amps, Rated V = 11000V ,BIL 95KV 300- 500KVAR Capacitor Bank 800AVCB 800A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coil closing coil with counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip, breaker tripping signal with MECH, on and off push button, 12KV, 800A, 25KA 1s, 50Hz, 12/ 36/95KV CT = Double core 50A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection and metering) PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/ 36/95KV 1250AVCB To EPI Warehouse Drawing Page/02 3 xcore XLPE150 square mm 900meter 1250A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip, breaker tripping signal with MECH, on and off push button, 12KV, 1250A, 25KA 1s, 50Hz,12/ 36/95KV CT = Double core 60A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection and metering) PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV BUSBAR 11kV PAGE 01/04 SIEMENS GENSET 100KVA, 415V, 130A, 50HZ, 4-POL EG DENYO POWER GENSET 300KVA, 400V, 433A,50HZ,4- POL E (OPTION 1 ) RECOMMENDED AMMENDMENT IN PREVIOUS PROPOSED DESIGN DRAWING ON THE BASIS OF EXISTING LOAD DETAILS WITH FUTURE COLD UNITS IN DRY WARE HOUSE AND NINE NEW UNITS IN COLD WARE HOUSE 3 xcore XLPE240 square mm 3004496307-P
  • 3. 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 ABCDEFG ABCDEFG Date WORKED 22.12.15 QASIM.M EPI WAREHOUSES, WHO, NIH ISLAMABAD SIEMENS (PAKISTAN) ENGINEERING CO. LTD. I CS/671544043015-1 1200A,BUSBAR 400V 250A PEL TRA NSFORMER 1000 KVA, 11KV/ 400V, 52/1391A, 3- PHASE, DYn11 ATS 1250A ACB, TP DRAW OUT TYPE 250A200A150A COLD WARE HOUSE-2 SMDB 1 COLD WARE HOUSE-1 SMDB 1 DRY WARE HOUSE-2 SMDB 1 DRY WARE HOUSE-1 SMDB 1 G 800A MCCB 2 X 3 1C 240mm2 CU/PVC/SWA CABLE+ 1C 240mm2 NEUTRAL CU/PVC/PVC + 240mm2 EARTH CU/PVC DG GENSET 500KVA, 400V, 665A,50HZ,4- POL E EXISTING DRAWING PROPOSED SINGLELINE DIAGRAM 1250A,TP 1250A ACB BREAKER DRAW OUT TYPE SHOULD BE USEDFOR ISOLATING THE BUS BAR LEGENDS : ECC EARTH COPPER CONDUCTER 2C X 240mm2 PVC+ 1C X 120mm2 PVC EARTHCU/PVC 2 X 3 1C 240mm2 CU/PVC/PVC CABLE + 1C 240mm2 NEUTRAL CU/PVC/PVC+ 240mm2 EARTH CU/PVC 4 C , 150mm2 CU/PVC/PVC+ 1 C 75mm2 EARTH CU/PVC 250A 200-400kVAR POWER FACTOR IMPROVEMENT PANEL From Drawing Page/01 150A COLD WARE HOUSE-2 SMDB 1 150A COLD WARE HOUSE-1 SMDB 1 (OPTION 1) PROPOSED DESIGN DRAWING ON THE BASIS OF EXISTING LOAD DETAILS WITH NINE NEW COLD UNITS AND FUTURE COLD UNITS IN DRY WARE HOUSE 1250A,TP G 800AMCCB 2 X 3 1C 240mm2 CU/PVC/SWA CABLE+ 1C 240mm2 NEUTRAL CU/PVC/PVC + 240mm2 EARTH CU/PVC DG GENSET 500KVA, 400V, 665A,50HZ,4- POL E AUTO SYNCHRONOZING PANEL, 50HZ, 415V 2 X 3 1C 240mm2 CU/PVC/PVC CABLE+ 1C 240mm2 NEUTRAL CU/PVC/PVC + 240mm2 EARTH CU/PVC 2 X 3 1C 240mm2 CU/PVC/PVC CABLE+ 1C 240mm2 NEUTRAL CU/PVC/PVC + 240mm2 EARTH CU PVC 2 X 3 1C 240mm2 CU/PVC/PVC CABLE + 1C 240mm2 NEUTRAL CU/PVC/PVC+ 240mm2 EARTH CU/PVC 1250A VCB, TP UNDER GROUND CABLEFROM NIH SUBSTATION 2 X 3 1C 240mm2 CU/PVC/PVC CABLE + 1C 240mm2 NEUTRAL CU/PVC/PVC+ 240mm2 EARTH CU/PVC 3C 150mm2 CU/XLPE/STA/PVC CABLE 3C 150mm2 CU/XLPE/STA/PVC CABLE1250A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip, breaker tripping signal with MECH, on and off push button, 12KV, 1250A, 25KA 1s, 50Hz, 12/ 36/95KV CT = Double core 60A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection and metering) PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV , under and over voltage Overcurrent, earth fault, short circuit protection 3004496307-P PAGE 02/04
  • 4. 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 ABCDEFG ABCDEFG Date WORKED 22.12.15 QASIM.M EPI WAREHOUSES, WHO, NIH ISLAMABAD SIEMENS (PAKISTAN) ENGINEERING CO. LTD. I CS/671544043015-1 Barakoh Grid 800A Air circuit breaker In=1000A ICU=25KA at 500V with motorized operation mechanismBUSBAR 400V MCCB 400A ATS G Breaker MCB 400A BUSBAR 16A 1250A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip, breaker tripping signal with MECH, on and off push button, 12KV, 1250A, 50KA, 50Hz, 12/ 36/95KV CT = Double core 70A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA 1s, 12/36/95KV (Protection and metering) PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV Trafo = 500KVA 11/0.415KV,26.25/ 722A, DYn11 MCB 300A BUSBAR 70A RMU Automatic Voltage Regulator 1250A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip, breaker tripping signal with MECH, on and off push button, 12KV, 1250A, 50KA 1s, 50Hz, 12/ 36/95KV CT = Double core 70A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection and metering) PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV ATS Breaker MCB 300A 250A 100A 16A 225A To DB 1 (Virology) DWG. No: VIR/ DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 2.5 square mm To DB 2 (Virology) DWG. No: VIR/ DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 120 square mm To DB 3 (Virology) DWG. No: VIR/ DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 35 square mm To DB 1 DWG. No: MBL / DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 16 square mm To DB 2 DWG. No: MBL / DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 2.5 square mm To DB 3 DWG. No: MBL / DB01.2014-15 Feeder Cable : 4 x coreCU/ PVC/PVC 95 square mm MCB 400A 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 coreCU/PVC/PVC 2x3 + 1x1 95 square mm 1 xcore CU/PVC/PVC 4x3 + 2x1 95 square mm 3 xcore XLPE35 square mm 3 xcore XLPE150 square mm 3 xcore XLPE150 square mm AVR= 3xSinglePhase, 100Amps,, BIL 95KV 300- 500KVAR Capacitor Bank 800AVCB 800A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip, breaker trippingsignal with MECH, on and off push button,12KV, 800A, 25KA 1s, 50Hz, 12/ 36/95KV CT = Double core 50A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection and metering) PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV 800AVCB To EPI Warehouse Drawing Page/04 3 xcore XLPE35 square mm 900meter 800A VCB Incoming/ Outgoing feeder (Vacuum circuit breakermotorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip, breaker tripping signal with MECH, on and off push button, 12KV, 800A, 25KA 1s, 50Hz, 12/ 36/95KV CT = Double core 50A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV (Protection and metering) PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV BUSBAR 11kV SIEMENS GENSET 100KVA, 415V, 130A, 50HZ, 4-POL EG DENYO POWER GENSET 300KVA, 400V, 433A,50HZ,4- POL E (OPTION 2) AMMENDMENT IN PROPOSED DESIGN DRAWING ON THE BASIS OF EXISTING LOAD DETAILS WITH OUT ANY FUTURE COLD UNITS IN DRY WARE HOUSES 3004496307-P PAGE 03/04
  • 5. 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 ABCDEFG ABCDEFG Date WORKED 22.12.15 QASIM.M EPI WAREHOUSES, WHO, NIH ISLAMABAD SIEMENS (PAKISTAN) ENGINEERING CO. LTD. I CS/671544043015-1 450A BUSBAR 400V 250A PEL TRA NSFORMER 400 KVA, 11KV/ 400V, 20.99A/ 55OA, 3-PHASE, DYn11 ATS 800A OPTIONAL IF REQUIRED EXISTING PHASE FAILURE PANEL MANUAL CHANGE OVER 600A 250A200A150A G CAT DG GENSET 300KVA, 400V, 433A,50HZ,4-POL E COLD WARE HOUSE-2 SMDB 1 COLD WARE HOUSE-1 SMDB 1 DRY WARE HOUSE-2 SMDB 1 DRY WARE HOUSE-1 SMDB 1 G 450A 2 X 3 1C 185mm2 CU/PVC/SWA CABLE+ 1C 185mm2 NEUTRAL CU/ PVC/PVC + 185mm2 EARTH CU/ PVC (OPTIONAL) IF REQU IRED DG GENSET 300KVA, 400V, 433A,50HZ,4- POL E EXISTING DRAWING PROPOSED SINGLELINE DIAGRAM 600A 600A MCCB PHASE FAILURE PANEL BREAKER TO BE REPLACEDWITH 800A MCCB 600A MCCB BREAKER SHOULD BE USED FOR ISOLATING THE BUS BAR LEGENDS : ECC EARTH COPPER CONDUCTER 2 X SINGLE CORE 185mm2 CABLE CU/PVC/PVC 3 X 1C 400mm2 CU/PVC/PVC+ 1 C 400mm2 NEUTRAL CU/PVC/PVC 2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC+ 185mm2 EARTH CU/PVC SHOULD BE PROVIDED 2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC+ 185mm2 EARTH CU/PVC SHOULD BE PROVIDED 2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC+ 185mm2 EARTH CU/ PVC SHOULD BE PROVIDED 2 X 3 1C 185mm2 CU/PVC/PVC CABLE + 1C 185mm2 NEUTRAL CU/PVC/PVC+ 185mm2 EARTH CU/ PVC SHOULD BE PROVIDED 4 C , 150mm2 CU/PVC/PVC+ 1 C 75mm2 ECC CU/PVC 250A 200-400kVAR POWER FACTOR IMPROVEMENT PANEL From Drawing Page/03 150A COLD WARE HOUSE-2 SMDB 1 150A COLD WARE HOUSE-1 SMDB 1 HT OVER HEAD LINE FROM TRAMRI GRID WITH FUSE LINK WILL BE REPLACEDWITH UNDERGROUND CABLE COMING FROM NIH SUBSTATION (OPTION 2) THIS PROPOSED DESIGN DRAWING IS ON THE BASIS OF EXISTING LOAD DETAILS WITH NINE NEW COLD UNITS AND WITH OUT ANY SPARE BREAKERS LOAD FOR FUTURE COLD UNITS IN DRY WARE HOUSE 800A VCB Incoming/ Outgoing feeder (Vacuum circuit breaker motorized F coilclosing coilwith counter, 210mm pole spacing 6 no plus 6 nc with varistorcircuit, 24 pole terminalstrip, breaker tripping signal with MECH, on and off push button, 12kV, 800A, 25KA 1s, 50Hz, 12/ 36/95KV CT = Double core 50A/5A/5A Core 1 =15VA, 5P10, Core 2 =10VA, 0.5M5, 25KA, 12/36/95KV PT = Single Core, 11KV/Sqrt 3 / 112V/Sqrt 3, AC 100VA, Class 0.5 12/36/95KV, under and over voltage , overcurrent, over current, earth fault and short circuit protection 800AVCB 3 xcore XLPE35 square mm 900meter 3 xcore XLPE35 square mm 3004496307-P PAGE 04/04