SlideShare a Scribd company logo
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . .
. . . .
. . . .
. . . .
. .
AFFINITY
Building
Automation
HVAC/R Drive
Pocket Start Up
WARNING: This is a brief guide only. It does not give safety
information. Incorrect installation or operation of the drive could
cause personal injury or equipment damage. Refer to
AFFINITY User Guide for essential safety information.!
0474-0001-03
3 2 1
2www.controltechniques.com
Motor
L2L1 L3 U V WPE
AC Connections
Optional EMC
filter
Optional line
reactor
sesuF
Optional ground connectionSupply Ground Mains Supply
L2 L3L1
WARNING: For complete wiring and fusing instructions refer to the
AFFINITY User Guide
POWER WIRING SIZES 1 TO 3
!
4 5 6
U V W
Motor
Optional ground
connection
Output connections
Input connections
Mains
Supply
L1 L2
Optional
line reactor
Optional
EMC filter
Fuses
L3
L1 L2 L3
PE
Supply
ground
Size 6 only:
Heatsink
fan supply
connections
www.controltechniques.com 3
POWER WIRING SIZES 4 TO 6
The AFFINITY default control mode is Off
Terminal strips
Default terminal functions. Digital I/O can be reconfigured
using menu 8.
www.controltechniques.com 4
CONTROL WIRING
10
11
8
9
6
7
4
5
3
1
2
30
28
29
26
27
24
25
23
21
22
31
38
36
37
35
39
41
42
1
35 39
11
Polarized signal
connectors
21 31
41 42
0V common
24V dc external supply input
0V
0V
Analog input 2
Analog input 3
Analog input
1/2 select
Spare
A (+)
B (-)
GNDBuilding automation network
A (+)
B (-)
Reset
Drive active
0V common
24V dc
Run forward
Fire mode
activate
Drive
enable
Status relay
Drive OK }
}
0V common
Analog output 1 (speed)
Analog output 2
0V common
+10V dc
Speed
reference
input
0V common
www.controltechniques.com 5
KEYPAD & DISPLAY
Reset to factory defaults
Enter the appropriate value shown below into Pr 0.00 and then press
the button.
Display Function
Resets parameters to Eur (50Hz) supply default
Resets parameters to USA (60Hz) supply default
Display modes
Use * keys
to select parameter for editing
To enter Edit Mode,
press key
Status
Mode
(Display
not
flashing)
Parameter
Mode
(Parameter
number
on upper
line
flashing)
Edit Mode
(Flashing character on upper line to be edited)
Change parameter values using keys.
When returning
to Parameter
Mode use the
keys to select
another parameter
to change, if
required
To exit Edit Mode,
press key
To enter Parameter
Mode, press key or
*
Temporary
Parameter
Mode
(Parameter
number
on upper line
flashing)
Timeout** Timeout**
To return to
Status Mode,
press key
r d y 0 rpm
E s t i m a t e d m o t o r
R P M
0. 1 0 0 rpm
E s t i m a t e d m o t o r
R P M
0. 0 0 0
F r e q u e c yn
R e f e r e c en s
0. 0 0 0
F r e q u e c yn
R e f e r e c en s
0. 0 0 0
F r e q u e c yn
R e f e r e c en s
Timeout**
RO
parameter
R/W
parameter
*can only be used to move between menus if L2 access has been enabled (Pr 0.49).
**Timeout defined by Pr 11.41 (default value = 240s)
1233
1244
Upper Line
Displays the parameter
number or drive status on
the left, and parameter value
or trip code on the right
Lower Lines
Displays the parameter
name or help text
Mode (black) Button
Changes between parameter,
edit and status mode
Help Button
Displays text, briefly
describing the
selected parameter
Joypad
Used to select a parameter and change its value
Control Buttons
Auto (blue) button
Off/reset (red) button
Hand (green) button
www.controltechniques.com 6
OPEN LOOP START-UP
The AFFINITY default operating mode is Open Loop.
The AFFINITY default control mode is Off.
See Control Wiring diagram for default connections.
Before power-up
Ensure:
The drive enable signal is open (terminal 31)
Motor is connected
Power-up the drive
Ensure:
Drive displays ‘inh’
If the drive trips, see Trip Codes.
Enter motor nameplate details
Enter:
Motor rated frequency in Pr 0.47 (Hz)
Motor rated current in Pr 0.46 (A)
Motor rated voltage in Pr 0.44 (V)
Motor rated power factor in Pr 0.43 if available
Set maximum and minimum frequency
Enter:
Maximum frequency in Pr 0.02 (Hz)
Minimum frequency in Pr 0.01 (Hz)
Set acceleration/deceleration rates
Enter:
Acceleration rate in Pr 0.03 (seconds/100Hz)
Deceleration rate in Pr 0.04 (seconds/100Hz)
7
OPEN LOOP START-UP CONTINUED
Autotune (optional)
AFFINITY is able to perform either a stationary or a rotating
autotune. The motor must be at a standstill before an autotune is
enabled. A rotating autotune should be used whenever possible.
WARNING: A rotating autotune will cause the motor to accelerate up to 2/3
base speed in the direction selected regardless of the reference provided.
Once complete the motor will coast to a stop. The enable signal must be
opened before the drive can be made to run at the required reference.
The drive can be stopped at any time by removing the drive enable.
A stationary autotune can be used when the motor is loaded and it is
not possible to remove the load from the motor shaft. A stationary
autotune does not measure the power factor of the motor so the
value on the name plate must be entered into Pr 0.43.
A rotating autotune should only be used if the motor is unloaded or
the load is uncoupled.
To perform an autotune
Set Pr 0.40 = 1 for a stationary autotune or set Pr 0.40 = 2 for a
rotating autotune.
Close the enable signal (terminal 31). The drive will display ‘off’.
Press the green Hand button. The lower display will flash ‘Autotune
in progress’ while the drive is performing the autotune.
Wait for the drive to display ‘inh’ and for the motor to come to
a standstill.
Open the enable signal from the drive.
Run
Drive is now ready to run.
Close the enable signal (terminal 31).
Press the green Hand button to start the motor.
Press the up arrow button on the joypad to increase the speed.
Press the down arrow button on the joypad to decrease the speed.
Press the red Off/reset button to stop the motor.
Auto
Close the enable signal (terminal 31).
Press the blue Auto button.
Close the run forward signal (terminal 26).
The drive will now run under the control of the reference signal
(terminal 5).
Open the run forward signal to stop the motor.
!
www.controltechniques.com
8
DISPLAY MESSAGES
Status messages
dEC Decelerating. The drive is decelerating the motor.
inh Inhibit. The drive is inhibited and cannot be run.
The drive enable signal is open on terminal 31 or
Pr 6.15 is set to 0.
rdY Ready. The drive is ready to be run in auto.
StoP Stop or holding zero speed.
The drive is holding zero speed.
triP Trip condition. The drive has tripped and is no longer
controlling the motor. The trip code appears on the
upper display.
OVLd Motor overload alarm. If the load is not reduced
an It.AC trip will occur.
Hand Drive is runing in Hand.
Auto Drive is runing in Auto.
Off Drive is Off.
Heat Motor pre-heat is active.
Trip codes
Et External trip
It. AC Motor overload
OI.AC Instantaneous overcurrent
OU Overvoltage
PH Input power phase loss
th Motor overtemp or thermistor open circuit
UU Undervoltage
For other status messages and trip codes please refer to User Guide.
www.controltechniques.com
9
BASIC PARAMETERS (MENU 0)
OPEN LOOP (refer to the User Guide for RFC mode)
Parameter Default( )
0.00 xx.00 {x.00} 0 to 32,767 0
0.00.01 Minimum reference clamp {1.07} ±3,000.0Hz
0.02 Maximum reference clamp {1.06} 0 to 3,000.0Hz
EUR> 50.0
USA> 60.0
EUR> 40.0
USA> 33.3
EUR> Std (0)
USA> US (2)
EUR> 40.0
USA> 33.3
0.03 Acceleration rate {2.11} 0.0 to 3,200.0 s/100Hz
0.04 Deceleration rate { 2.21} 0.0 to 3,200.0 s/100Hz
0.05 Reference select {1.14}
A1.A2 (0), A1.Pr (1), A2.Pr (2),
Pr (3), PAd (4), Prc (5)
A1.A2 (0)
0.06 Current limit { 4.07} 0 to Current_limit_max % 110
0.07 Voltage mode select { 5.14}
Ur_S (0), Ur (1), Fd (2),
Ur_Auto (3), Ur_I (4), SrE (5)
Fd (2)
0.08 Voltage boost {5.15}
0.0 to 25.0% of motor
rated voltage
Size 1 to 3: 3.0
Size 4 & 5: 2.0
Size 6 upwards: 1.0
0.09 Dynamic V/F {5.13} OFF (0) or On (1)
0.10 Estimated motor speed {5.04} ±180,000 rpm
0.11 Drive output frequency {5.01} ±Speed_freq_max Hz
0.12 Total motor current {4.01} 0 to Drive_current_max A
0.13 Percentage load { 4.20}
0.14 Ramp mode select {2.04}
FASt (0),
Std (1),
Std.hV (2)
-User_current_max to
User_current_max %
Std (1)
0.15 Sleep threshold { 6.53} ±SPEED_FREQ_MAX Hz/rpm 0.0
OFF (0)
0.16 Sleep delay time {6.54} 0.0 to 250.0s 10.0
0.18 Spin start boost 0.0 to 10.0 1.0
0.19 Analog input 2 mode {7.11}
0-20 (0), 20-0 (1),
4-20tr (2), 20-4tr (3), 4-20 (4),
20-4 (5), VOLt (6)
4-20 (4)
0.20 Analog input 2 destination {7.14} Pr 0.00 to Pr 50.99 Pr 1.37
0.21 Analog input 3 mode {7.15}
0-20 (0), 20-0 (1), 4-20tr (2),
20-4tr (3), 4-20 (4), 20-4 (5),
VOLt (6), th.SC (7),
th (8), th.diSp (9)
VOLt (6)
0.22 Date {6.16} 0 to 311299
0.00 to 23.590.23 Time {6.17}
0.24 Date/Time selector { 6.19} 0 to 5 3
0.25 Date format { 6.20} Std (0), Std.ds (1),
US (2), US.ds (3)
0.26 Low load detection level {4.27} 0.0 to 100.0% 0.0
0.27 Low load detection speed/
frequency threshold
{4.28} 0.0 to +Speed_freq_
max Hz/rpm
0.0
Range( )
www.controltechniques.com
10
BASIC PARAMETERS (MENU 0)
CONTINUED
0.28 Trip on abnormal load detection {4.29} OFF (0)
0.29 SMARTCARD parameter data {11.36}
0.30 Parameter cloning {11.42}
nonE (0), rEAd (1), Prog (2),
AutO (3), boot (4)
nonE (0)
0.31 Drive rated voltage {11.33} 200 (0), 400 (1),
575 (2), 690 (3) V
0.32 Drive current scaling {11.32}
0.33 Catch a spinning motor {6.09}
0.34 User security code {11.30}
0.35 PC comms mode {11.24}
0.36 PC comms baud rate {11.25}
300 (0), 600 (1), 1200 (2),
2400 (3), 4800 (4), 9600 (5),
19200 (6), 38400 (7),
Modbus RTU only: 57600 (8),
Modbus RTU only: 115200 (9)
19200 (6)
0.37 PC comms address {11.23}
0.38
Hold zero speed/
Motor pre-heat enable
{6.08}
0.39
Motor pre-heat
current magnitude
{6.52} 0
0.40 Autotune {5.12}
0.41
Maximum switching
frequency
{5.18}
3 (0), 4 (1), 6 (2), 8 (3),
12 (4), 16 (5) kHz
3 (0)
0.42 No. of motor poles {5.11} 0 to 60 (Auto to 120 pole) 0 (Auto)
0.43 Motor rated power factor {5.10}
0.44 Motor rated voltage {5.09}
0 to
AC_voltage_set_max
V
200V drive: 230
400V drive:
EUR> 400,
USA> 460
575V drive: 575
690V drive: 690
0.45
Motor rated full load
speed (rpm)
{5.08}
EUR> 1,500,
USA> 1,800
0.46 Motor rated current {5.07}
0 to
Rated_current_max A
Drive rated
current [11.32]
0.47 Rated frequency {5.06}
EUR> 50.0,
USA> 60.0
0.48 Operating mode selector {11.31} OPEn LP (1), rfc (2) OPEn LP (1)
0.49 Security status {11.44} L1 (0), L2 (1), Loc (2)
0.50 Software version {11.29}
Parameter Default( )Range( )
OFF (0) or On (1)
OFF (0)OFF (0) or On (1)
0 to 999
0.00 to 9999.99A
0
00 to 3
00 to 999
rtu (1)AnSI (0), rtu (1), Lcd (2)
10 to 247
0 to 100%
00 to 2
0.8500.000 to 1.000
0 to 180,000 rpm
0 to 3,000.0 Hz
1.00 to 99.99
0.51 Positive logic select { 8.29} OFF (0) or On (1) On (1)
0.52 Timer 1 start date {9.35} 0 to 311299
0 to 311299
0
0.53 Timer 1 start time {9.36} 0.00 to 23.59 0.00
0.55 Timer 1 stop time {9.38} 0.00 to 23.59 0.00
0.56 Timer 1 repeat function {9.39} 0 to 6 0
0.57 Timer 1 enable {9.40} OFF (0) or On (1) OFF (0)
0.58 Timer 1 destination { 9.40} Pr 0.00 to Pr 50.99 Pr 0.00
0.54 Timer 1 stop date {9.37} 0
www.controltechniques.com
11
Drive reads all parameters from
the
Pr 0.30 = rEAD +
Programs all drive parameters to
the
Drive automatically writes to the
when a parameter
save is performed
Auto
Save
Drive boots from the
on power up and automatically
writes to the when a
parameter save is performed
Pr 0.30 = Prog +
Pr 0.30 = AutO + Pr 0.30 = boot +
Auto
Save
Boot
Parameter storage/cloning
www.controltechniques.com
12
1. Remove keypad
2. Insert the smartcard into the slot
(contacts facing the right-hand side of the drive)
3. Re-fit keypad
4. Set parameter zero in any menu (Pr xx.00)
equal to the selected 4 digit Macro Number
found on the front of the smartcard
5. Press the red reset button to load the macro
Refer to the AFFINITY User Guide for further information
To load a Macro...
www.controltechniques.com
Pre-programmed Macros
Macro Macro
Number Name
6501 Fan Control - No Bypass (Eur, 50Hz)
6502 Pump Control - No Bypass (Eur, 50Hz)
6601 Fan Control - No Bypass (USA, 60Hz)
6602 Pump Control - No Bypass (USA, 60Hz)
6603 Fan Control - With Bypass (USA, 60Hz)
6604 Pump Control - With Bypass (USA, 60Hz)

More Related Content

PDF
Ford OBD1 Code List (PDF)
PDF
JCB-diagnostic-trouble-codes-pdf
PDF
Biến tần LS iG5 - Tài liệu biến tần LS iG5 (English manual, P.1)
PDF
How to use MST-12000 Universal Automotive Test Platform And ECU Signal Simula...
PDF
KTM LC4/LC8 Failure code
DOCX
Codigos de averias u (bus comunicaciones)
DOC
Cataloge ge 3.control and_automation_dienhathe.com-4_16_vat300_e_c6-6-1_rev_a
PDF
The Emerald Datasheet
Ford OBD1 Code List (PDF)
JCB-diagnostic-trouble-codes-pdf
Biến tần LS iG5 - Tài liệu biến tần LS iG5 (English manual, P.1)
How to use MST-12000 Universal Automotive Test Platform And ECU Signal Simula...
KTM LC4/LC8 Failure code
Codigos de averias u (bus comunicaciones)
Cataloge ge 3.control and_automation_dienhathe.com-4_16_vat300_e_c6-6-1_rev_a
The Emerald Datasheet

What's hot (20)

PDF
Power flex400
PDF
Biến tần ls i g5
PDF
Bảng giá biến tần - Fuji Electric 2015
PDF
Advanced motion controls azbe40a8
PDF
Electro-Pneumatic Pressure Controller and I/P Transducer
PDF
Applied motion products pdo 5580 datasheet
PDF
Advanced motion controls azxbh6c20
DOC
MAY CAT RECLOSER
PDF
Mack Trucks' Body Builder Instructions
DOC
Crp680 new common rail pump tester
PDF
Regolatore Controller-Ucontrol
PDF
Điều khiển nhiệt độ - Catalogue điều khiển nhiệt độ HX series (tiếng Anh)
PDF
Catalog biến tần Frenic ACE Fuji Electric mới nhất
PDF
Axpert i-sine - Multi Function Active Harmonic Filter
PDF
Catalog biến tần Frenic Lift - Fuji Electric mới nhất 2019
PDF
Bộ điều khiển nhiệt độ (Temperature Controller) Fuji Electric PXF4
PDF
Bộ điều khiển nhiệt độ (Temperature Controller) Fuji Electric PXF5
PDF
Catalog Frenic mini(NEW) -www.haophuong.com
PDF
Fermator door operator_vvvf3
Power flex400
Biến tần ls i g5
Bảng giá biến tần - Fuji Electric 2015
Advanced motion controls azbe40a8
Electro-Pneumatic Pressure Controller and I/P Transducer
Applied motion products pdo 5580 datasheet
Advanced motion controls azxbh6c20
MAY CAT RECLOSER
Mack Trucks' Body Builder Instructions
Crp680 new common rail pump tester
Regolatore Controller-Ucontrol
Điều khiển nhiệt độ - Catalogue điều khiển nhiệt độ HX series (tiếng Anh)
Catalog biến tần Frenic ACE Fuji Electric mới nhất
Axpert i-sine - Multi Function Active Harmonic Filter
Catalog biến tần Frenic Lift - Fuji Electric mới nhất 2019
Bộ điều khiển nhiệt độ (Temperature Controller) Fuji Electric PXF4
Bộ điều khiển nhiệt độ (Temperature Controller) Fuji Electric PXF5
Catalog Frenic mini(NEW) -www.haophuong.com
Fermator door operator_vvvf3
Ad

Viewers also liked (19)

PDF
VltFC 102 hvac drive operating instructions
PDF
Instrucsia chf100 a
PDF
F5 b c_g_instruction manual
PDF
Tech pv series
PDF
Abb acs55-users-guide
PDF
En 600stdprg fwmanual
PDF
F6 instruction manual
PDF
Unidrive m200 m201 sheet issue 1
PDF
Vf fs1 instruction manual
PDF
Fr f700
PDF
PDF
Vlt hvac basic_quick_start_guide_fc101
PDF
Fuji fvr-e9-manual
PDF
Vlt micro drive fc51
PDF
Goodrive10 english-manual
PDF
Danfoss vlt-5000
PDF
Ct2000 pro plus_manual_english[1]
PDF
Vf as1 operation-man
PDF
Ct2000 v english_ver 1.36
VltFC 102 hvac drive operating instructions
Instrucsia chf100 a
F5 b c_g_instruction manual
Tech pv series
Abb acs55-users-guide
En 600stdprg fwmanual
F6 instruction manual
Unidrive m200 m201 sheet issue 1
Vf fs1 instruction manual
Fr f700
Vlt hvac basic_quick_start_guide_fc101
Fuji fvr-e9-manual
Vlt micro drive fc51
Goodrive10 english-manual
Danfoss vlt-5000
Ct2000 pro plus_manual_english[1]
Vf as1 operation-man
Ct2000 v english_ver 1.36
Ad

Similar to Affinity quick start guide issue 3 (20)

PDF
Advanced motion controls b100a400ac
PDF
Advanced motion controls b100a40ac
PDF
Advanced motion controls ab100c200
PDF
Advanced motion controls b060a400ac
PDF
Advanced motion controls b60a40ac
PDF
Advanced motion controls b100a20
PDF
Advanced motion controls ab125a200
PDF
Advanced motion controls b100a40
PDF
Advanced motion controls b30a40ac
PDF
Advanced motion controls ab200a100
PDF
Advanced motion controls b40a40ac
PDF
Advanced motion controls b100a8
PDF
Advanced motion controls b40a40
PDF
PLC y Electroneumática: inversor de control vectorial
PDF
Ac servo drive&motor _Kunlin Tech
PDF
Advanced motion controls b30a40
PDF
Advanced motion controls s100a40ac
PDF
Advanced motion controls azb40a8
PPTX
FRENIC-Eco Product Presentation__r1.pptx
PDF
Advanced motion controls azbe12a8
Advanced motion controls b100a400ac
Advanced motion controls b100a40ac
Advanced motion controls ab100c200
Advanced motion controls b060a400ac
Advanced motion controls b60a40ac
Advanced motion controls b100a20
Advanced motion controls ab125a200
Advanced motion controls b100a40
Advanced motion controls b30a40ac
Advanced motion controls ab200a100
Advanced motion controls b40a40ac
Advanced motion controls b100a8
Advanced motion controls b40a40
PLC y Electroneumática: inversor de control vectorial
Ac servo drive&motor _Kunlin Tech
Advanced motion controls b30a40
Advanced motion controls s100a40ac
Advanced motion controls azb40a8
FRENIC-Eco Product Presentation__r1.pptx
Advanced motion controls azbe12a8

More from Toàn Huỳnh (20)

PDF
Fr f700
PDF
Ct2000 f manual_english
PDF
Ct2000 ev manual_english_version 1.1
PDF
Ct2000 es manual_english_version_1[1].0
PDF
En acs880 fw_man_d
PDF
En acs800 standard_fw_l
PDF
En acs150 um rev c_a4_screen
PDF
En ach550 01_um_f_a4_lo_screenres
PDF
En acq810 fw manual b
PDF
Acs550 x1-rev e
PDF
Acs550 02-us-04
PDF
PDF
Abb acs850-04-firmware-manual
PDF
Abb acs310-users-guide
PDF
Sv i s5 user manual-100520
PDF
Sv i p5a-manual_(english)
PDF
PDF
I v5 eng_110526
PDF
I s7 eng_101201
PDF
Fr f700
Ct2000 f manual_english
Ct2000 ev manual_english_version 1.1
Ct2000 es manual_english_version_1[1].0
En acs880 fw_man_d
En acs800 standard_fw_l
En acs150 um rev c_a4_screen
En ach550 01_um_f_a4_lo_screenres
En acq810 fw manual b
Acs550 x1-rev e
Acs550 02-us-04
Abb acs850-04-firmware-manual
Abb acs310-users-guide
Sv i s5 user manual-100520
Sv i p5a-manual_(english)
I v5 eng_110526
I s7 eng_101201

Recently uploaded (20)

PPTX
wegen seminar ppt.pptxhkjbkhkjjlhjhjhlhhvg
PDF
EVs U-5 ONE SHOT Notes_c49f9e68-5eac-4201-bf86-b314ef5930ba.pdf
PDF
TAIPANQQ SITUS MUDAH MENANG DAN MUDAH MAXWIN SEGERA DAFTAR DI TAIPANQQ DAN RA...
PDF
Rare Big Band Arrangers Who Revolutionized Big Band Music in USA.pdf
PDF
High-Quality PDF Backlinking for Better Rankings
PPTX
the Honda_ASIMO_Presentation_Updated.pptx
PPTX
SPARSH-SVNITs-Annual-Cultural-Fest presentation for orientation
PPTX
Hacking Movie – Best Films on Cybercrime & Digital Intrigue
DOCX
Nina Volyanska Controversy in Fishtank Live_ Unraveling the Mystery Behind th...
DOCX
Lambutchi Calin Claudiu had a discussion with the Buddha about the restructur...
PPTX
PRECISION AGRICULTURE- 1.pptx for agriculture
PDF
oppenheimer and the story of the atomic bomb
PPT
business model and some other things that
PPTX
What Makes an Entertainment App Addictive?
PPTX
shbthd htsh htrw hw htr 5w h5e 54 y.pptx
PDF
How Old Radio Shows in the 1940s and 1950s Helped Ella Fitzgerald Grow.pdf
PDF
Ct.pdffffffffffffffffffffffffffffffffffff
PDF
Western Pop Music: From Classics to Chart-Toppers
PDF
TAIPANQQ SITUS MUDAH MENANG DAN MUDAH MAXWIN SEGERA DAFTAR DI TAIPANQQ DAN RA...
PDF
Between the Reels and the Revolution Enzo Zelocchi’s Unscripted Path Through ...
wegen seminar ppt.pptxhkjbkhkjjlhjhjhlhhvg
EVs U-5 ONE SHOT Notes_c49f9e68-5eac-4201-bf86-b314ef5930ba.pdf
TAIPANQQ SITUS MUDAH MENANG DAN MUDAH MAXWIN SEGERA DAFTAR DI TAIPANQQ DAN RA...
Rare Big Band Arrangers Who Revolutionized Big Band Music in USA.pdf
High-Quality PDF Backlinking for Better Rankings
the Honda_ASIMO_Presentation_Updated.pptx
SPARSH-SVNITs-Annual-Cultural-Fest presentation for orientation
Hacking Movie – Best Films on Cybercrime & Digital Intrigue
Nina Volyanska Controversy in Fishtank Live_ Unraveling the Mystery Behind th...
Lambutchi Calin Claudiu had a discussion with the Buddha about the restructur...
PRECISION AGRICULTURE- 1.pptx for agriculture
oppenheimer and the story of the atomic bomb
business model and some other things that
What Makes an Entertainment App Addictive?
shbthd htsh htrw hw htr 5w h5e 54 y.pptx
How Old Radio Shows in the 1940s and 1950s Helped Ella Fitzgerald Grow.pdf
Ct.pdffffffffffffffffffffffffffffffffffff
Western Pop Music: From Classics to Chart-Toppers
TAIPANQQ SITUS MUDAH MENANG DAN MUDAH MAXWIN SEGERA DAFTAR DI TAIPANQQ DAN RA...
Between the Reels and the Revolution Enzo Zelocchi’s Unscripted Path Through ...

Affinity quick start guide issue 3

  • 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AFFINITY Building Automation HVAC/R Drive Pocket Start Up WARNING: This is a brief guide only. It does not give safety information. Incorrect installation or operation of the drive could cause personal injury or equipment damage. Refer to AFFINITY User Guide for essential safety information.! 0474-0001-03
  • 2. 3 2 1 2www.controltechniques.com Motor L2L1 L3 U V WPE AC Connections Optional EMC filter Optional line reactor sesuF Optional ground connectionSupply Ground Mains Supply L2 L3L1 WARNING: For complete wiring and fusing instructions refer to the AFFINITY User Guide POWER WIRING SIZES 1 TO 3 !
  • 3. 4 5 6 U V W Motor Optional ground connection Output connections Input connections Mains Supply L1 L2 Optional line reactor Optional EMC filter Fuses L3 L1 L2 L3 PE Supply ground Size 6 only: Heatsink fan supply connections www.controltechniques.com 3 POWER WIRING SIZES 4 TO 6
  • 4. The AFFINITY default control mode is Off Terminal strips Default terminal functions. Digital I/O can be reconfigured using menu 8. www.controltechniques.com 4 CONTROL WIRING 10 11 8 9 6 7 4 5 3 1 2 30 28 29 26 27 24 25 23 21 22 31 38 36 37 35 39 41 42 1 35 39 11 Polarized signal connectors 21 31 41 42 0V common 24V dc external supply input 0V 0V Analog input 2 Analog input 3 Analog input 1/2 select Spare A (+) B (-) GNDBuilding automation network A (+) B (-) Reset Drive active 0V common 24V dc Run forward Fire mode activate Drive enable Status relay Drive OK } } 0V common Analog output 1 (speed) Analog output 2 0V common +10V dc Speed reference input 0V common
  • 5. www.controltechniques.com 5 KEYPAD & DISPLAY Reset to factory defaults Enter the appropriate value shown below into Pr 0.00 and then press the button. Display Function Resets parameters to Eur (50Hz) supply default Resets parameters to USA (60Hz) supply default Display modes Use * keys to select parameter for editing To enter Edit Mode, press key Status Mode (Display not flashing) Parameter Mode (Parameter number on upper line flashing) Edit Mode (Flashing character on upper line to be edited) Change parameter values using keys. When returning to Parameter Mode use the keys to select another parameter to change, if required To exit Edit Mode, press key To enter Parameter Mode, press key or * Temporary Parameter Mode (Parameter number on upper line flashing) Timeout** Timeout** To return to Status Mode, press key r d y 0 rpm E s t i m a t e d m o t o r R P M 0. 1 0 0 rpm E s t i m a t e d m o t o r R P M 0. 0 0 0 F r e q u e c yn R e f e r e c en s 0. 0 0 0 F r e q u e c yn R e f e r e c en s 0. 0 0 0 F r e q u e c yn R e f e r e c en s Timeout** RO parameter R/W parameter *can only be used to move between menus if L2 access has been enabled (Pr 0.49). **Timeout defined by Pr 11.41 (default value = 240s) 1233 1244 Upper Line Displays the parameter number or drive status on the left, and parameter value or trip code on the right Lower Lines Displays the parameter name or help text Mode (black) Button Changes between parameter, edit and status mode Help Button Displays text, briefly describing the selected parameter Joypad Used to select a parameter and change its value Control Buttons Auto (blue) button Off/reset (red) button Hand (green) button
  • 6. www.controltechniques.com 6 OPEN LOOP START-UP The AFFINITY default operating mode is Open Loop. The AFFINITY default control mode is Off. See Control Wiring diagram for default connections. Before power-up Ensure: The drive enable signal is open (terminal 31) Motor is connected Power-up the drive Ensure: Drive displays ‘inh’ If the drive trips, see Trip Codes. Enter motor nameplate details Enter: Motor rated frequency in Pr 0.47 (Hz) Motor rated current in Pr 0.46 (A) Motor rated voltage in Pr 0.44 (V) Motor rated power factor in Pr 0.43 if available Set maximum and minimum frequency Enter: Maximum frequency in Pr 0.02 (Hz) Minimum frequency in Pr 0.01 (Hz) Set acceleration/deceleration rates Enter: Acceleration rate in Pr 0.03 (seconds/100Hz) Deceleration rate in Pr 0.04 (seconds/100Hz)
  • 7. 7 OPEN LOOP START-UP CONTINUED Autotune (optional) AFFINITY is able to perform either a stationary or a rotating autotune. The motor must be at a standstill before an autotune is enabled. A rotating autotune should be used whenever possible. WARNING: A rotating autotune will cause the motor to accelerate up to 2/3 base speed in the direction selected regardless of the reference provided. Once complete the motor will coast to a stop. The enable signal must be opened before the drive can be made to run at the required reference. The drive can be stopped at any time by removing the drive enable. A stationary autotune can be used when the motor is loaded and it is not possible to remove the load from the motor shaft. A stationary autotune does not measure the power factor of the motor so the value on the name plate must be entered into Pr 0.43. A rotating autotune should only be used if the motor is unloaded or the load is uncoupled. To perform an autotune Set Pr 0.40 = 1 for a stationary autotune or set Pr 0.40 = 2 for a rotating autotune. Close the enable signal (terminal 31). The drive will display ‘off’. Press the green Hand button. The lower display will flash ‘Autotune in progress’ while the drive is performing the autotune. Wait for the drive to display ‘inh’ and for the motor to come to a standstill. Open the enable signal from the drive. Run Drive is now ready to run. Close the enable signal (terminal 31). Press the green Hand button to start the motor. Press the up arrow button on the joypad to increase the speed. Press the down arrow button on the joypad to decrease the speed. Press the red Off/reset button to stop the motor. Auto Close the enable signal (terminal 31). Press the blue Auto button. Close the run forward signal (terminal 26). The drive will now run under the control of the reference signal (terminal 5). Open the run forward signal to stop the motor. ! www.controltechniques.com
  • 8. 8 DISPLAY MESSAGES Status messages dEC Decelerating. The drive is decelerating the motor. inh Inhibit. The drive is inhibited and cannot be run. The drive enable signal is open on terminal 31 or Pr 6.15 is set to 0. rdY Ready. The drive is ready to be run in auto. StoP Stop or holding zero speed. The drive is holding zero speed. triP Trip condition. The drive has tripped and is no longer controlling the motor. The trip code appears on the upper display. OVLd Motor overload alarm. If the load is not reduced an It.AC trip will occur. Hand Drive is runing in Hand. Auto Drive is runing in Auto. Off Drive is Off. Heat Motor pre-heat is active. Trip codes Et External trip It. AC Motor overload OI.AC Instantaneous overcurrent OU Overvoltage PH Input power phase loss th Motor overtemp or thermistor open circuit UU Undervoltage For other status messages and trip codes please refer to User Guide. www.controltechniques.com
  • 9. 9 BASIC PARAMETERS (MENU 0) OPEN LOOP (refer to the User Guide for RFC mode) Parameter Default( ) 0.00 xx.00 {x.00} 0 to 32,767 0 0.00.01 Minimum reference clamp {1.07} ±3,000.0Hz 0.02 Maximum reference clamp {1.06} 0 to 3,000.0Hz EUR> 50.0 USA> 60.0 EUR> 40.0 USA> 33.3 EUR> Std (0) USA> US (2) EUR> 40.0 USA> 33.3 0.03 Acceleration rate {2.11} 0.0 to 3,200.0 s/100Hz 0.04 Deceleration rate { 2.21} 0.0 to 3,200.0 s/100Hz 0.05 Reference select {1.14} A1.A2 (0), A1.Pr (1), A2.Pr (2), Pr (3), PAd (4), Prc (5) A1.A2 (0) 0.06 Current limit { 4.07} 0 to Current_limit_max % 110 0.07 Voltage mode select { 5.14} Ur_S (0), Ur (1), Fd (2), Ur_Auto (3), Ur_I (4), SrE (5) Fd (2) 0.08 Voltage boost {5.15} 0.0 to 25.0% of motor rated voltage Size 1 to 3: 3.0 Size 4 & 5: 2.0 Size 6 upwards: 1.0 0.09 Dynamic V/F {5.13} OFF (0) or On (1) 0.10 Estimated motor speed {5.04} ±180,000 rpm 0.11 Drive output frequency {5.01} ±Speed_freq_max Hz 0.12 Total motor current {4.01} 0 to Drive_current_max A 0.13 Percentage load { 4.20} 0.14 Ramp mode select {2.04} FASt (0), Std (1), Std.hV (2) -User_current_max to User_current_max % Std (1) 0.15 Sleep threshold { 6.53} ±SPEED_FREQ_MAX Hz/rpm 0.0 OFF (0) 0.16 Sleep delay time {6.54} 0.0 to 250.0s 10.0 0.18 Spin start boost 0.0 to 10.0 1.0 0.19 Analog input 2 mode {7.11} 0-20 (0), 20-0 (1), 4-20tr (2), 20-4tr (3), 4-20 (4), 20-4 (5), VOLt (6) 4-20 (4) 0.20 Analog input 2 destination {7.14} Pr 0.00 to Pr 50.99 Pr 1.37 0.21 Analog input 3 mode {7.15} 0-20 (0), 20-0 (1), 4-20tr (2), 20-4tr (3), 4-20 (4), 20-4 (5), VOLt (6), th.SC (7), th (8), th.diSp (9) VOLt (6) 0.22 Date {6.16} 0 to 311299 0.00 to 23.590.23 Time {6.17} 0.24 Date/Time selector { 6.19} 0 to 5 3 0.25 Date format { 6.20} Std (0), Std.ds (1), US (2), US.ds (3) 0.26 Low load detection level {4.27} 0.0 to 100.0% 0.0 0.27 Low load detection speed/ frequency threshold {4.28} 0.0 to +Speed_freq_ max Hz/rpm 0.0 Range( ) www.controltechniques.com
  • 10. 10 BASIC PARAMETERS (MENU 0) CONTINUED 0.28 Trip on abnormal load detection {4.29} OFF (0) 0.29 SMARTCARD parameter data {11.36} 0.30 Parameter cloning {11.42} nonE (0), rEAd (1), Prog (2), AutO (3), boot (4) nonE (0) 0.31 Drive rated voltage {11.33} 200 (0), 400 (1), 575 (2), 690 (3) V 0.32 Drive current scaling {11.32} 0.33 Catch a spinning motor {6.09} 0.34 User security code {11.30} 0.35 PC comms mode {11.24} 0.36 PC comms baud rate {11.25} 300 (0), 600 (1), 1200 (2), 2400 (3), 4800 (4), 9600 (5), 19200 (6), 38400 (7), Modbus RTU only: 57600 (8), Modbus RTU only: 115200 (9) 19200 (6) 0.37 PC comms address {11.23} 0.38 Hold zero speed/ Motor pre-heat enable {6.08} 0.39 Motor pre-heat current magnitude {6.52} 0 0.40 Autotune {5.12} 0.41 Maximum switching frequency {5.18} 3 (0), 4 (1), 6 (2), 8 (3), 12 (4), 16 (5) kHz 3 (0) 0.42 No. of motor poles {5.11} 0 to 60 (Auto to 120 pole) 0 (Auto) 0.43 Motor rated power factor {5.10} 0.44 Motor rated voltage {5.09} 0 to AC_voltage_set_max V 200V drive: 230 400V drive: EUR> 400, USA> 460 575V drive: 575 690V drive: 690 0.45 Motor rated full load speed (rpm) {5.08} EUR> 1,500, USA> 1,800 0.46 Motor rated current {5.07} 0 to Rated_current_max A Drive rated current [11.32] 0.47 Rated frequency {5.06} EUR> 50.0, USA> 60.0 0.48 Operating mode selector {11.31} OPEn LP (1), rfc (2) OPEn LP (1) 0.49 Security status {11.44} L1 (0), L2 (1), Loc (2) 0.50 Software version {11.29} Parameter Default( )Range( ) OFF (0) or On (1) OFF (0)OFF (0) or On (1) 0 to 999 0.00 to 9999.99A 0 00 to 3 00 to 999 rtu (1)AnSI (0), rtu (1), Lcd (2) 10 to 247 0 to 100% 00 to 2 0.8500.000 to 1.000 0 to 180,000 rpm 0 to 3,000.0 Hz 1.00 to 99.99 0.51 Positive logic select { 8.29} OFF (0) or On (1) On (1) 0.52 Timer 1 start date {9.35} 0 to 311299 0 to 311299 0 0.53 Timer 1 start time {9.36} 0.00 to 23.59 0.00 0.55 Timer 1 stop time {9.38} 0.00 to 23.59 0.00 0.56 Timer 1 repeat function {9.39} 0 to 6 0 0.57 Timer 1 enable {9.40} OFF (0) or On (1) OFF (0) 0.58 Timer 1 destination { 9.40} Pr 0.00 to Pr 50.99 Pr 0.00 0.54 Timer 1 stop date {9.37} 0 www.controltechniques.com
  • 11. 11 Drive reads all parameters from the Pr 0.30 = rEAD + Programs all drive parameters to the Drive automatically writes to the when a parameter save is performed Auto Save Drive boots from the on power up and automatically writes to the when a parameter save is performed Pr 0.30 = Prog + Pr 0.30 = AutO + Pr 0.30 = boot + Auto Save Boot Parameter storage/cloning www.controltechniques.com
  • 12. 12 1. Remove keypad 2. Insert the smartcard into the slot (contacts facing the right-hand side of the drive) 3. Re-fit keypad 4. Set parameter zero in any menu (Pr xx.00) equal to the selected 4 digit Macro Number found on the front of the smartcard 5. Press the red reset button to load the macro Refer to the AFFINITY User Guide for further information To load a Macro... www.controltechniques.com Pre-programmed Macros Macro Macro Number Name 6501 Fan Control - No Bypass (Eur, 50Hz) 6502 Pump Control - No Bypass (Eur, 50Hz) 6601 Fan Control - No Bypass (USA, 60Hz) 6602 Pump Control - No Bypass (USA, 60Hz) 6603 Fan Control - With Bypass (USA, 60Hz) 6604 Pump Control - With Bypass (USA, 60Hz)