Comparative Analysis of Harmonics with and
Without Shunt Active Power Filter
1
Priya Goswami, 2
A. Pachori
1
PG Scholar (High Voltage Engineering), 2
Associate prof, Dept. of Electrical Engineering, JEC, Jabalpur, India
Abstract: Electricity consumption had been increased so rapidly once in line with the development of the country to
achieve its status as the industrial countries. The large consumption of electrical energy, one thing that plays an
important role in a distribution system is the quality of electrical power itself. The distribution system will have
many problems related to efficiency and functionality of electrical equipment. Therefore, the entire system does
not operate efficiently due to the presence of harmonic in the distribution system. Among of them, one of the
disorders that cause poor power quality is harmonic. This disturbance causes electrical equipment used to heat
and cannot function properly. Thereby, the aim of this paper is to design and develop of a three phase shunt active
power filter for harmonics reduction in industrial using MATLAB/SIMULINK[1,2].
Keywords: Power System, Harmonic Distortion, Shunt Active Power Filter, Non-Linear Loads, Total Harmonic
Distortion.
1. INTRODUCTION
Power quality is important in the distribution system. To provide power supply with good quality is not easy because it
depends on the type of load used. Phenomenon that causes an interruption in the electrical system such as overvoltage,
voltage sags, voltage surges and harmonic [3]. Harmonic distortion problem has existed in the power system for a long
time. it causes a wave of the line current and voltage in the power system to be distorted. In the past, discussions about the
existence of harmonics have been discussed. However, at that time, the impact and influence of harmonic distortion is
slightly lower than at present, where it only covers in the delta grounded w-ye connection of the transformer and also in
some design of power transformer [4]. At present, the creation of modern equipment, especially electronic equipment and
also the increased use of non-linear loads in industry has produced harmonic distortion, harmonic distortion in electrical
systems became more serious because the use of electronic equipment are among the largest contributors to the formation
of harmonic distortion. In recent years, with the increasing use of adjustable speed drives, arc furnace, controlled and
uncontrolled rectifiers and other nonlinear loads, the power distribution system is polluted with harmonics. Such
harmonics not only create more voltage and current stress but also are responsible for Electromagnetic interference, more
losses, capacitor failure due to overloading, harmonic resonance, etc. Introduction of strict legislation such as IEEE519
[5] limits the maximum amount of harmonics (THD-Total Harmonic Distortion) that a supply system can tolerate for a
particular type of load. Therefore, use of active or passive type filters is essential. To solve the current harmonic related
problems, passive filters connected in several circuit configurations present a low cost solution. However passive filter
implementations to filter out the current harmonics have the following disadvantages:
• Possibility of resonances with the source Impedance
• Supply impedance dependent system performance
• Fixed compensation
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org
Page | 157
Paper Publications
In order to diminish the preceding disadvantages of the passive filters, active power filters(APF) have been worked on
and developed in recent years. Elimination of the current harmonics, reactive power compensation and voltage regulation
are the main functions of active filters for the improvement of power quality. APFs have a number of advantages over the
passive filters. First of all, they can suppress not only the supply current harmonics, but also the reactive currents.
Moreover, unlike passive filters, they do not cause harmful resonances with the power distribution systems. Consequently,
the APF performances are independent of the power distribution system properties .On the other hand, APFs have some
drawbacks.APF necessitates fast switching of high currents in the power circuit resulting high frequency noise that may
cause an electromagnetic interference (EMI) in the power distribution system.
Fig.1 Active power filter with non-linear load.
2. INSTANTANEOUS ACTIVE AND REACTIVE POWER THEORY
This method offers a good precision and ease of implementation. Its main disadvantage is that it can’t be applied in the
case of unbalanced grid voltage [13]. In this case, A Self Tuning Filter (STF) can be used after the measurement of the
grid voltages to extract the fundamental balanced three phase voltage components of the distorted unbalanced one. This
transformation may be viewed as a projection of the three-phase quantities onto a stationary two-axis reference frame.
The Clarke transformation for the voltage variables is given by [14]:
[ ] =√
[
√ √
√ √ √ ]
[ ] …… ………. (1)
Similarly, this transform can be applied on the distorted load currents to give
[ ] =√
[
√ √
√ √ √ ]
[ ] ………………(2)
The instantaneous active power p(t) can be defined by:
( ) …………… … (3)
This expression is given in the stationary frame by:
( )
( ) ……………….(4)
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org
Page | 158
Paper Publications
Where, p(t) is the instantaneous active power, p0(t) is the instantaneous homo-polar sequence power. Similarly the
instantaneous reactive power can be given by:
( )
√
( ) ( ) ( ) ……(5)
From eqns. 4 and 5, the instantaneous active and reactive power can be given in matrix form by:
[ ] [ ] [ ] …...................(6)
In order to separate the harmonics from the fundamental of the load currents, it is sufficient to separate the alternating
term of the instantaneous power from the direct.After the separation of the direct and alternating terms of instantaneous
power, the harmonic components of the load currents can be given using the inverse of equation (3.6) which gives:
[ ] [ ] [
̃
̃
] …………………….(7)
The inverse Clarke transform can be used as follow:
[ ] √ [ √
√
] [ ] ………………………..(8)
Figure presents the principle of the active and reactive instantaneous power.
Fig.3 Principle of instantaneous active and reactive power theory
3. MODELLING OF SHUNT ACTIVE POWER FILTER
The simulation model of system without SAPF is shown in fig 4.1 and the simulation model of system with SAPF is
shown in fig 3 which shunt active power filter (SAPF) is connected across the non linear load. The control of Shunt active
power filter (SAPF) is divided in two parts. First part is used for the harmonic current extraction. There are instantaneous
active and reactive power method (p-q method). Second part is used for the generation of gate pulse to control of voltage
source inverter. Hysteresis Current Control Method is used.
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org
Page | 159
Paper Publications
3.1 Simulation Model of System without SAPF:
Fig.4. Simulation model of system without SAPF
3.1.1 Simulation Result:
shows source current without shunt active filter. Due to the presence of the non linear load, so the current waveform is in
distorted manner. The current is taken along the Y-axis and time is taken along the X-axis..
Fig.5 Voltage and current waveform without filter
Fig.6 voltage and current waveform without filter
Fig 7.Voltage and Current Waveform without Filter
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org
Page | 160
Paper Publications
3.2 Simulation Model of System with Shunt Active Power Filter:
Fig.8 Simulation model of system with SAPF
3.2.1 Simulation Results:
A number of simulations have been performed to check the working of the shunt active power filter under various non-
linear loadings (w.r.t connection of the loads at the PCC) and nonideal supply. The analysis of the results show that the
working of the active filter is very satisfied to compensate the harmonics and reactive power even under unbalanced and
distorted conditions of distribution supply.
Fig.9 Voltage and current waveform with SAPF
Fig.10 Voltage and current waveform with SAPF
Fig.11 Voltage and current waveform with SAPF
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org
Page | 161
Paper Publications
4. FFT ANALYSIS
The following figure shows the THD analysis of source current without SAF. THD is found to be 20.49% respectively
due to nonlinear load which creates harmonics in the three phase system. In order to reduce the THD the proposed system
is implemented.
Figure FFT analysis without SAPF
Figure FFT analysis with SAPF
Table.1 Comparison of THD in Source Current
THD IN SOURCE CURRENT BEFORE SHUNT
ACTIVE FILTER
THD IN SOURCE CURRENT AFTER SHUNT
ACTIVE FILTER
20.49% 0.53%
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org
Page | 162
Paper Publications
5. CONCLUSION
The three phase three wire shunt active filter with controller based on instantaneous active and reactive power (p-q)
theory is simulated in MATLAB/SIMULINK to compensate the problems of the harmonics and reactive power which are
encountered from power electronic non-linear loads. The performance of the shunt active power filter is investigated
under different scenarios. It is investigated that the p-q theory based active filter manages to compensate the harmonics
and reactive power of the power distribution network even under unbalanced and distorted supply voltages. The active
power filter is able to reduce the THD in source current at a level well below the defined standards specified by power
quality standards. The THD in source current after the active filtering is not exactly zero. It is because internal switching
of the compensator itself generates some harmonics. In each of the case studied, the source current after the working of
the active filter becomes perfectly sinusoidal, free from harmonics and in-phase with voltage of the main supply
maintaining the unity power factor. In each simulation studied, multiple non-linear loads have been used to investigate the
time response of the active filter. In each case it has noted that filter is successfully able to follow the reference currents
with one power cycle with change in loads. It has been noted that if voltage unbalance or distortion or both are present in
the system, the simple p-q theory didn’t work well. It give rise the demand of the fundamental positive sequence voltage
detector to extract the fundamental positive voltage form the unbalanced or distorted voltage. Once the fundamental
positive sequence voltage is extracted, the theory worked very well. Even though the p-q theory has managed to
compensate the harmonics and reactive power of the system and to produce the sinusoidal source current with unity
power factor and free from harmonics.
6. FUTURE WORK
The scope of the future work can be to look for the solution of the following points:
This work is based on three phase three wire system and the active filter does not work well if there is a zero sequence
in the supply voltage. In future, a detailed analysis can be carried out for a 3 phase four wire filter in order to compensate
the zero sequence present in the system.
the APF for the compensation of harmonics and zero sequence.
REFERENCES
[1] 978-1-4673-0455-9/12/$31.00 ©2012 IEEE “Mitigation of Harmonics using Fuzzy Logic Controlled Shunt Active
Power Filter with Different Membership Functions”By Instantaneous Power Theory, Suresh Mikkili and Anup
Kumar Panda.
[2] Akagi, H. 1994. Trends in active power line conditioners. IEEETrans.Power, Electron., vol.9, no.3,pp,263-
268.2.Bhonsle, D.C., Zaveri, N.K., and Dr.Kelkar, R.B. 2008.Designand Simulation Of Single phase Shunt Active
Power Filter for Harmonic mitigation in distribution system.The International Conference on Electrical Engineering.
[3] Allmeling, J. A control structure for fast harmonics compensation in active filter Electron.,vol.19, no. 2, pp. 508-
514, (Mar 2004).
[4] Ali Ajami and Seyed Hossein Hosseini, 2006. “Implementation of a Active Filter”, ECTI Transactions on Electrical
Eng., Electronics, And Communications Vol.4, No.1
[5] Peng, F. Z., Akagi, H. and Nabae, A. A Novel Harmonics Power Filter.IEEE Transaction of Electronics Specialists
Conference. April 11-14. PESC ’88 Record: IEEE. 1988. 1151-1159.
[6] T. Haddad. K. Joos. and A. Jaafari, ”Performance Evaluation of Three Phase Three and Four Wire Active Filters”,
Conference Record of the IEEE IAS Annual Metting, pp. 1016-1023, 1996.
[7] F. Hamoudi., A. Chaghi., H. Amimeur.,E. Merabet, ”Sliding Mode Control of a Three-Phase Three-Leg Voltage
Source Inverter Based Four-Wire Shunt Active Power Filter”, Journal of Electrical Systems, no. 2, pp. 82-86, 2010
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org
Page | 163
Paper Publications
[8] S. Saetio. R. Devaraj. D. Torrey, ”The Design and Implementation of a Three-Phase Active Power Filter Based on
Sliding Mode Control”, IEEE Transactions on Industrial Applications, vol. 31, pp. 993, 1995
[9] H. Akagi. E. Watanabe. M. Aredes,”Instantaneous Power Theory and Applications to Power Conditioning”, edited
by Mohamed E. El- Hawari, ISBN: 978-0-470-10761-4, 2007.
[10] S. Buso. L. Malesani. and P. Mattavelli,”Comparison of current control techniques for active filter applications”,
IEEE transaction on Industrial Elactronics, vol. 45 pp. 722-729, 1998
[11] V. Utkin. J. Guldner. J. Shi,”Sliding Mode Control in Electromechanical Systems”,Prentice-Hall of India Pvt. Ltd.
isbn :0-7484-0116-4, 1998
[12] V. Cardenas. N. Viizquez. C. Hernandez. S. Horti, ”Analysis and Design of a Three Phase Sliding Mode Controller
for a Shunt Active Power Filter”, IEEE transaction, vol. 4, pp. 219-223, 1999 12th IEEE Workshop on Variable
Structure Systems, VSS’12, January 12-14, Mumbai, 2012 978-1
[13] L. Gyugyi and E. C. Strycula, "Active AC power filters", IEEE IIAS Annual Meeting, 1976, p. 529.
[14] H. Akagi, Y. Kanazawa, A. Nabae, “Instantaneous Reactive Power Compensators comprising Switching Devices
without Energy Storage Components”, IEEE Transactions on Industry Applications, Vol. IA-20, No. 3, May/June
1984.

More Related Content

PDF
Ae4301167171
PDF
Control Design For Shunt Active Power Filter Based On p-q Theory In Photovolt...
PDF
Design of Shunt Active Power Filter to eliminate harmonics generated by CFL
PDF
E04562332
PDF
Ag33180185
PDF
OPTIMAL POWER FLOW CONTROL USING TCSC
PDF
A011140104
PDF
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
Ae4301167171
Control Design For Shunt Active Power Filter Based On p-q Theory In Photovolt...
Design of Shunt Active Power Filter to eliminate harmonics generated by CFL
E04562332
Ag33180185
OPTIMAL POWER FLOW CONTROL USING TCSC
A011140104
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...

What's hot (18)

PDF
Experimental Comparative Study of Feedback Linearized Controller and Proporti...
PDF
Performance enhancement of shunt active power filter with fuzzy and hysteresi...
PDF
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
PDF
Improvement of the electric power quality using
PDF
Performance analysis of three phase shunt hybrid active power filter
PDF
Matlab Simulation And Comparison Of Single Phase To Three Phase Converter Fe...
PDF
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
PDF
T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...
PDF
Simulation of three-phase bridge rectifier using MATLAB/ SIMULINK for harmoni...
PDF
Shunt active power filters based on diode clamped multilevel inverter and hys...
PDF
Enhancement of Power Quality Using the Combination of Thyristor-Controlled Re...
PDF
Filter Implementation Using Output Transformer of UPS for Power Quality Impro...
PDF
Review of the Most Applicable Regulator Collections to Control the Parallel A...
PDF
Implementation of hysteresis current control for single phase grid connected ...
PDF
Analysis of Modulation Strategies for Two-Stage Interleaved Voltage Source In...
PDF
H45014650
PDF
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
PDF
A Review on Unified Power Quality Conditioner for 3P4W System
Experimental Comparative Study of Feedback Linearized Controller and Proporti...
Performance enhancement of shunt active power filter with fuzzy and hysteresi...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Improvement of the electric power quality using
Performance analysis of three phase shunt hybrid active power filter
Matlab Simulation And Comparison Of Single Phase To Three Phase Converter Fe...
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...
Simulation of three-phase bridge rectifier using MATLAB/ SIMULINK for harmoni...
Shunt active power filters based on diode clamped multilevel inverter and hys...
Enhancement of Power Quality Using the Combination of Thyristor-Controlled Re...
Filter Implementation Using Output Transformer of UPS for Power Quality Impro...
Review of the Most Applicable Regulator Collections to Control the Parallel A...
Implementation of hysteresis current control for single phase grid connected ...
Analysis of Modulation Strategies for Two-Stage Interleaved Voltage Source In...
H45014650
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
A Review on Unified Power Quality Conditioner for 3P4W System
Ad

Viewers also liked (20)

PDF
What i wish everyone knew about
PDF
Template : Social Enterprise Development Action Plan in SAARC countries
PPTX
Storyboard new
DOC
днепровская л.н омск гимназия_140_мастер-класс
DOCX
Prayer of protection as a shield to ward of all sorts of evil each morning wi...
PPTX
Framtidens digitala konsument prospekt 2017 ver2
PPT
днепровскаялн омск гимназия_140_мастер-класс
PDF
MODELLING AND IMPLEMENTATION OF AN IMPROVED DSVM SCHEME FOR PMSM DTC
PDF
HOME AUTOMATION WITH SPY ROBOT AND SECURITY SYSTEM
PDF
Adaptive Video Watermarking and Quality Estimation
PDF
Energy Efficient Packet Processing Engine
PDF
A Literature Review on Experimental Study of Power Losses in Transmission Lin...
PDF
Hardware Unit for Edge Detection with Comparative Analysis of Different Edge ...
PDF
Power Generation Using Footstep
PDF
Performance Comparison of FFT, DHT and DCT Based OFDM Systems with BPSK as A ...
PDF
Importance of Antennas for Wireless Communication Devices
PDF
A Novel Approach for Allocation of Optimal Capacitor and Distributed Generati...
PDF
Effect of Humidity on the Impulse Breakdown Characteristic of Air
PDF
GSM Based Automatic Meter Reading – A Review
PDF
IMAGE QUALITY OPTIMIZATION USING RSATV
What i wish everyone knew about
Template : Social Enterprise Development Action Plan in SAARC countries
Storyboard new
днепровская л.н омск гимназия_140_мастер-класс
Prayer of protection as a shield to ward of all sorts of evil each morning wi...
Framtidens digitala konsument prospekt 2017 ver2
днепровскаялн омск гимназия_140_мастер-класс
MODELLING AND IMPLEMENTATION OF AN IMPROVED DSVM SCHEME FOR PMSM DTC
HOME AUTOMATION WITH SPY ROBOT AND SECURITY SYSTEM
Adaptive Video Watermarking and Quality Estimation
Energy Efficient Packet Processing Engine
A Literature Review on Experimental Study of Power Losses in Transmission Lin...
Hardware Unit for Edge Detection with Comparative Analysis of Different Edge ...
Power Generation Using Footstep
Performance Comparison of FFT, DHT and DCT Based OFDM Systems with BPSK as A ...
Importance of Antennas for Wireless Communication Devices
A Novel Approach for Allocation of Optimal Capacitor and Distributed Generati...
Effect of Humidity on the Impulse Breakdown Characteristic of Air
GSM Based Automatic Meter Reading – A Review
IMAGE QUALITY OPTIMIZATION USING RSATV
Ad

Similar to Comparative Analysis of Harmonics with and Without Shunt Active Power Filter (20)

PDF
Harmonic Mitigation using Modified Synchronous Reference Frame Theory
PDF
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
PDF
Design of shunt active power filter to mitigate harmonic
PDF
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
PDF
Power Quality Improvement using Shunt Active Power Filter
PDF
Enhancement of power quality using microprocessor based shunt active power fi...
PPTX
Harmonics and mitigation techniques
PDF
Active Power Filter
PDF
Improvement of Power Quality using IRP-Theory Base Shunt Active Power Filter
PDF
Improvement of power quality using series active power filter
PDF
Dynamic Power Factor Correction in a Non Linear Environment
PDF
H010615159
PPTX
Prateek PPT.pptx
PDF
Paper id 29201412
PDF
El34831851
PDF
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
PDF
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
PDF
PDF
Simulation of Shunt Active Power Filter Based on p q Theory
PDF
Performance Investigation of Shunt Active Power Filter Using Hysteresis Curre...
Harmonic Mitigation using Modified Synchronous Reference Frame Theory
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
Design of shunt active power filter to mitigate harmonic
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
Power Quality Improvement using Shunt Active Power Filter
Enhancement of power quality using microprocessor based shunt active power fi...
Harmonics and mitigation techniques
Active Power Filter
Improvement of Power Quality using IRP-Theory Base Shunt Active Power Filter
Improvement of power quality using series active power filter
Dynamic Power Factor Correction in a Non Linear Environment
H010615159
Prateek PPT.pptx
Paper id 29201412
El34831851
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
Simulation of Shunt Active Power Filter Based on p q Theory
Performance Investigation of Shunt Active Power Filter Using Hysteresis Curre...

Recently uploaded (20)

PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PPTX
Sustainable Sites - Green Building Construction
PPTX
UNIT 4 Total Quality Management .pptx
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
DOCX
573137875-Attendance-Management-System-original
PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PPTX
OOP with Java - Java Introduction (Basics)
PPTX
Geodesy 1.pptx...............................................
PPTX
web development for engineering and engineering
PDF
Well-logging-methods_new................
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PPTX
Internet of Things (IOT) - A guide to understanding
PPTX
CH1 Production IntroductoryConcepts.pptx
PPTX
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PPT
Project quality management in manufacturing
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
Embodied AI: Ushering in the Next Era of Intelligent Systems
Sustainable Sites - Green Building Construction
UNIT 4 Total Quality Management .pptx
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
Automation-in-Manufacturing-Chapter-Introduction.pdf
573137875-Attendance-Management-System-original
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
OOP with Java - Java Introduction (Basics)
Geodesy 1.pptx...............................................
web development for engineering and engineering
Well-logging-methods_new................
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
Foundation to blockchain - A guide to Blockchain Tech
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Internet of Things (IOT) - A guide to understanding
CH1 Production IntroductoryConcepts.pptx
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
Project quality management in manufacturing

Comparative Analysis of Harmonics with and Without Shunt Active Power Filter

  • 1. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org Page | 156 Paper Publications Comparative Analysis of Harmonics with and Without Shunt Active Power Filter 1 Priya Goswami, 2 A. Pachori 1 PG Scholar (High Voltage Engineering), 2 Associate prof, Dept. of Electrical Engineering, JEC, Jabalpur, India Abstract: Electricity consumption had been increased so rapidly once in line with the development of the country to achieve its status as the industrial countries. The large consumption of electrical energy, one thing that plays an important role in a distribution system is the quality of electrical power itself. The distribution system will have many problems related to efficiency and functionality of electrical equipment. Therefore, the entire system does not operate efficiently due to the presence of harmonic in the distribution system. Among of them, one of the disorders that cause poor power quality is harmonic. This disturbance causes electrical equipment used to heat and cannot function properly. Thereby, the aim of this paper is to design and develop of a three phase shunt active power filter for harmonics reduction in industrial using MATLAB/SIMULINK[1,2]. Keywords: Power System, Harmonic Distortion, Shunt Active Power Filter, Non-Linear Loads, Total Harmonic Distortion. 1. INTRODUCTION Power quality is important in the distribution system. To provide power supply with good quality is not easy because it depends on the type of load used. Phenomenon that causes an interruption in the electrical system such as overvoltage, voltage sags, voltage surges and harmonic [3]. Harmonic distortion problem has existed in the power system for a long time. it causes a wave of the line current and voltage in the power system to be distorted. In the past, discussions about the existence of harmonics have been discussed. However, at that time, the impact and influence of harmonic distortion is slightly lower than at present, where it only covers in the delta grounded w-ye connection of the transformer and also in some design of power transformer [4]. At present, the creation of modern equipment, especially electronic equipment and also the increased use of non-linear loads in industry has produced harmonic distortion, harmonic distortion in electrical systems became more serious because the use of electronic equipment are among the largest contributors to the formation of harmonic distortion. In recent years, with the increasing use of adjustable speed drives, arc furnace, controlled and uncontrolled rectifiers and other nonlinear loads, the power distribution system is polluted with harmonics. Such harmonics not only create more voltage and current stress but also are responsible for Electromagnetic interference, more losses, capacitor failure due to overloading, harmonic resonance, etc. Introduction of strict legislation such as IEEE519 [5] limits the maximum amount of harmonics (THD-Total Harmonic Distortion) that a supply system can tolerate for a particular type of load. Therefore, use of active or passive type filters is essential. To solve the current harmonic related problems, passive filters connected in several circuit configurations present a low cost solution. However passive filter implementations to filter out the current harmonics have the following disadvantages: • Possibility of resonances with the source Impedance • Supply impedance dependent system performance • Fixed compensation
  • 2. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org Page | 157 Paper Publications In order to diminish the preceding disadvantages of the passive filters, active power filters(APF) have been worked on and developed in recent years. Elimination of the current harmonics, reactive power compensation and voltage regulation are the main functions of active filters for the improvement of power quality. APFs have a number of advantages over the passive filters. First of all, they can suppress not only the supply current harmonics, but also the reactive currents. Moreover, unlike passive filters, they do not cause harmful resonances with the power distribution systems. Consequently, the APF performances are independent of the power distribution system properties .On the other hand, APFs have some drawbacks.APF necessitates fast switching of high currents in the power circuit resulting high frequency noise that may cause an electromagnetic interference (EMI) in the power distribution system. Fig.1 Active power filter with non-linear load. 2. INSTANTANEOUS ACTIVE AND REACTIVE POWER THEORY This method offers a good precision and ease of implementation. Its main disadvantage is that it can’t be applied in the case of unbalanced grid voltage [13]. In this case, A Self Tuning Filter (STF) can be used after the measurement of the grid voltages to extract the fundamental balanced three phase voltage components of the distorted unbalanced one. This transformation may be viewed as a projection of the three-phase quantities onto a stationary two-axis reference frame. The Clarke transformation for the voltage variables is given by [14]: [ ] =√ [ √ √ √ √ √ ] [ ] …… ………. (1) Similarly, this transform can be applied on the distorted load currents to give [ ] =√ [ √ √ √ √ √ ] [ ] ………………(2) The instantaneous active power p(t) can be defined by: ( ) …………… … (3) This expression is given in the stationary frame by: ( ) ( ) ……………….(4)
  • 3. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org Page | 158 Paper Publications Where, p(t) is the instantaneous active power, p0(t) is the instantaneous homo-polar sequence power. Similarly the instantaneous reactive power can be given by: ( ) √ ( ) ( ) ( ) ……(5) From eqns. 4 and 5, the instantaneous active and reactive power can be given in matrix form by: [ ] [ ] [ ] …...................(6) In order to separate the harmonics from the fundamental of the load currents, it is sufficient to separate the alternating term of the instantaneous power from the direct.After the separation of the direct and alternating terms of instantaneous power, the harmonic components of the load currents can be given using the inverse of equation (3.6) which gives: [ ] [ ] [ ̃ ̃ ] …………………….(7) The inverse Clarke transform can be used as follow: [ ] √ [ √ √ ] [ ] ………………………..(8) Figure presents the principle of the active and reactive instantaneous power. Fig.3 Principle of instantaneous active and reactive power theory 3. MODELLING OF SHUNT ACTIVE POWER FILTER The simulation model of system without SAPF is shown in fig 4.1 and the simulation model of system with SAPF is shown in fig 3 which shunt active power filter (SAPF) is connected across the non linear load. The control of Shunt active power filter (SAPF) is divided in two parts. First part is used for the harmonic current extraction. There are instantaneous active and reactive power method (p-q method). Second part is used for the generation of gate pulse to control of voltage source inverter. Hysteresis Current Control Method is used.
  • 4. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org Page | 159 Paper Publications 3.1 Simulation Model of System without SAPF: Fig.4. Simulation model of system without SAPF 3.1.1 Simulation Result: shows source current without shunt active filter. Due to the presence of the non linear load, so the current waveform is in distorted manner. The current is taken along the Y-axis and time is taken along the X-axis.. Fig.5 Voltage and current waveform without filter Fig.6 voltage and current waveform without filter Fig 7.Voltage and Current Waveform without Filter
  • 5. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org Page | 160 Paper Publications 3.2 Simulation Model of System with Shunt Active Power Filter: Fig.8 Simulation model of system with SAPF 3.2.1 Simulation Results: A number of simulations have been performed to check the working of the shunt active power filter under various non- linear loadings (w.r.t connection of the loads at the PCC) and nonideal supply. The analysis of the results show that the working of the active filter is very satisfied to compensate the harmonics and reactive power even under unbalanced and distorted conditions of distribution supply. Fig.9 Voltage and current waveform with SAPF Fig.10 Voltage and current waveform with SAPF Fig.11 Voltage and current waveform with SAPF
  • 6. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org Page | 161 Paper Publications 4. FFT ANALYSIS The following figure shows the THD analysis of source current without SAF. THD is found to be 20.49% respectively due to nonlinear load which creates harmonics in the three phase system. In order to reduce the THD the proposed system is implemented. Figure FFT analysis without SAPF Figure FFT analysis with SAPF Table.1 Comparison of THD in Source Current THD IN SOURCE CURRENT BEFORE SHUNT ACTIVE FILTER THD IN SOURCE CURRENT AFTER SHUNT ACTIVE FILTER 20.49% 0.53%
  • 7. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org Page | 162 Paper Publications 5. CONCLUSION The three phase three wire shunt active filter with controller based on instantaneous active and reactive power (p-q) theory is simulated in MATLAB/SIMULINK to compensate the problems of the harmonics and reactive power which are encountered from power electronic non-linear loads. The performance of the shunt active power filter is investigated under different scenarios. It is investigated that the p-q theory based active filter manages to compensate the harmonics and reactive power of the power distribution network even under unbalanced and distorted supply voltages. The active power filter is able to reduce the THD in source current at a level well below the defined standards specified by power quality standards. The THD in source current after the active filtering is not exactly zero. It is because internal switching of the compensator itself generates some harmonics. In each of the case studied, the source current after the working of the active filter becomes perfectly sinusoidal, free from harmonics and in-phase with voltage of the main supply maintaining the unity power factor. In each simulation studied, multiple non-linear loads have been used to investigate the time response of the active filter. In each case it has noted that filter is successfully able to follow the reference currents with one power cycle with change in loads. It has been noted that if voltage unbalance or distortion or both are present in the system, the simple p-q theory didn’t work well. It give rise the demand of the fundamental positive sequence voltage detector to extract the fundamental positive voltage form the unbalanced or distorted voltage. Once the fundamental positive sequence voltage is extracted, the theory worked very well. Even though the p-q theory has managed to compensate the harmonics and reactive power of the system and to produce the sinusoidal source current with unity power factor and free from harmonics. 6. FUTURE WORK The scope of the future work can be to look for the solution of the following points: This work is based on three phase three wire system and the active filter does not work well if there is a zero sequence in the supply voltage. In future, a detailed analysis can be carried out for a 3 phase four wire filter in order to compensate the zero sequence present in the system. the APF for the compensation of harmonics and zero sequence. REFERENCES [1] 978-1-4673-0455-9/12/$31.00 ©2012 IEEE “Mitigation of Harmonics using Fuzzy Logic Controlled Shunt Active Power Filter with Different Membership Functions”By Instantaneous Power Theory, Suresh Mikkili and Anup Kumar Panda. [2] Akagi, H. 1994. Trends in active power line conditioners. IEEETrans.Power, Electron., vol.9, no.3,pp,263- 268.2.Bhonsle, D.C., Zaveri, N.K., and Dr.Kelkar, R.B. 2008.Designand Simulation Of Single phase Shunt Active Power Filter for Harmonic mitigation in distribution system.The International Conference on Electrical Engineering. [3] Allmeling, J. A control structure for fast harmonics compensation in active filter Electron.,vol.19, no. 2, pp. 508- 514, (Mar 2004). [4] Ali Ajami and Seyed Hossein Hosseini, 2006. “Implementation of a Active Filter”, ECTI Transactions on Electrical Eng., Electronics, And Communications Vol.4, No.1 [5] Peng, F. Z., Akagi, H. and Nabae, A. A Novel Harmonics Power Filter.IEEE Transaction of Electronics Specialists Conference. April 11-14. PESC ’88 Record: IEEE. 1988. 1151-1159. [6] T. Haddad. K. Joos. and A. Jaafari, ”Performance Evaluation of Three Phase Three and Four Wire Active Filters”, Conference Record of the IEEE IAS Annual Metting, pp. 1016-1023, 1996. [7] F. Hamoudi., A. Chaghi., H. Amimeur.,E. Merabet, ”Sliding Mode Control of a Three-Phase Three-Leg Voltage Source Inverter Based Four-Wire Shunt Active Power Filter”, Journal of Electrical Systems, no. 2, pp. 82-86, 2010
  • 8. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 2, Issue 2, pp: (156-163), Month: April 2015 - June 2015, Available at: www.paperpublications.org Page | 163 Paper Publications [8] S. Saetio. R. Devaraj. D. Torrey, ”The Design and Implementation of a Three-Phase Active Power Filter Based on Sliding Mode Control”, IEEE Transactions on Industrial Applications, vol. 31, pp. 993, 1995 [9] H. Akagi. E. Watanabe. M. Aredes,”Instantaneous Power Theory and Applications to Power Conditioning”, edited by Mohamed E. El- Hawari, ISBN: 978-0-470-10761-4, 2007. [10] S. Buso. L. Malesani. and P. Mattavelli,”Comparison of current control techniques for active filter applications”, IEEE transaction on Industrial Elactronics, vol. 45 pp. 722-729, 1998 [11] V. Utkin. J. Guldner. J. Shi,”Sliding Mode Control in Electromechanical Systems”,Prentice-Hall of India Pvt. Ltd. isbn :0-7484-0116-4, 1998 [12] V. Cardenas. N. Viizquez. C. Hernandez. S. Horti, ”Analysis and Design of a Three Phase Sliding Mode Controller for a Shunt Active Power Filter”, IEEE transaction, vol. 4, pp. 219-223, 1999 12th IEEE Workshop on Variable Structure Systems, VSS’12, January 12-14, Mumbai, 2012 978-1 [13] L. Gyugyi and E. C. Strycula, "Active AC power filters", IEEE IIAS Annual Meeting, 1976, p. 529. [14] H. Akagi, Y. Kanazawa, A. Nabae, “Instantaneous Reactive Power Compensators comprising Switching Devices without Energy Storage Components”, IEEE Transactions on Industry Applications, Vol. IA-20, No. 3, May/June 1984.