ASHRAE‐Chicago
Air Distribution Selection Basics
           June 8, 2010
ASHRAE ‐ Air Distribution Systems
              2007 Applications Handbook, Ch. 56
            Fully Stratified                                    Partially Mixed                                                Fully Mixed

                                                                                             Upper Zone
             Upper Zone                       Upper Zone
                                                                                                   height varies
                                                                                                                                  Fully Mixed




                                                                               Elevation




                                                                                                                   Elevation
                                Elevation
Elevation




             Lower Zone                       Lower Zone                                    Lower Zone




                  Local Temp.                     Local Temp.                                    Local Temp.                        Local Temp.
            CO2 Concentration               CO2 Concentration                              CO2 Concentration                   CO2 Concentration

                                                    Partially Mixed Room Air Distribution Systems




       Displacement                              Under Floor Air Distribution                                                         G.R.D.



                                                             © 2010. All rights reserved
ASHRAE Standard 55‐2004 
Occupant Comfort Goal
Dry Bulb = 73-77 °F.
Relative Humidity = 25-60%.
Local Velocities =
    Heating < 30 fpm.
    Cooling < 50 fpm.
Clo. Rate 0.5 - 1.1
Met. Rates 1.0 - 2.0
Floor level to 66”; < 5.4 °F (3 °C)
Occupied Zone: Floor to 6’0”; except:
    (Clear, Near, Adjacent) Zone.

                   © 2010. All rights reserved
Occupied Zone for Comfort
                                                Mixed Air Outlet

     Ceiling



      1'
6'                                         F
               Occupied Zone


     Floor
                    Underfloor Plenum                                    D.V.
                                                           UFAD Outlet


                             © 2010. All rights reserved
Fully Mixed Air Distribution
Air Patterns
Mapping Room Air Motion
Vertical Projection
ADPI
Perimeter Heating


                   © 2010. All rights reserved
Air Flow Patterns
High Sidewall – No Ceiling
   Horizontal Pattern
     Deflected (less drop)
     Spread (shorter throw)

High Sidewall with Ceiling
   Longer throw with less drop
High Sidewall near Ceiling
   Deflect up for longer throw/less drop

                        © 2010. All rights reserved
Supply Sidewall Grilles
Adjustable:
     Horizontal
     (spread)

     Vertical
     (deflection)

Duct Mounting
   Velocity & Pressure
   Air Patterns

                     © 2010. All rights reserved
Return Sidewall Grilles
Return
   Non Adjustable

   Zero Degree Deflection

   30-45 Deflection

   Other




                       © 2010. All rights reserved
Air Flow Patterns
Radial Air Pattern
   Shorter Throw
   More Induction




                      © 2010. All rights reserved
Round Pattern Diffusers




                © 2010. All rights reserved
Air Flow Patterns
Cross Flow
   Longer Throw

   Increased Drop




                     © 2010. All rights reserved
Cross Pattern Diffusers




                 © 2010. All rights reserved
Linear with Plenum or T‐Bar Diffusers
 With Spreader                           W/O Spreader

    Linear
    Plenum




                   With                              Without
                  Spread                             Spread




                       © 2010. All rights reserved
Linear‐Plenum Slot Diffusers




                © 2010. All rights reserved
Air Flow Patterns
Radial Pattern - Exposed Duct




                  © 2010. All rights reserved
Air Flow Patterns
Cross Pattern - Exposed Duct




                  © 2010. All rights reserved
POOR PATTERN EXAMPLE
             POORLY ADJUSTED
                DIFFUSER




THERMOSTAT




              © 2010. All rights reserved
GOOD PATTERN EXAMPLE
             PROPERLY ADJUSTED
             DIFFUSER




THERMOSTAT




              © 2010. All rights reserved
Mapping Room Air Motion
5-step approach
   Primary air
   Total air
   Convection currents
   Room intake
   Room air


                     © 2010. All rights reserved
Step 1: Identify the Primary Air
Primary Air - mixture                      Primary air patterns are
  of air supplied to the outlet              temperature independent1
  and induced room air                      Catalog Throw:
  within an envelope of
  velocities > 150 FPM                         150 – 100 – 50
                                               10 - 17 - 25


     Inside                       Step 1                       Exposed
      Wall                     Primary Air                       Wall




                                                   Outlet




                         © 2010. All rights reserved
Step 2: Identify the Total Air
 Total Air - mixture of                       Temperature difference
   primary air and room air                     between total air and room air
   which is under the influence                 produces a buoyancy effect
   of the outlet conditions                     which cause the cool air to drop
                                                and the warm air to rise
 Air has a tendency                           Total air has no defined
   to scrub surfaces                            terminal velocity limit


                                     Step 2
                                    Total Air




                            © 2010. All rights reserved
Step 3: Identify Natural 
Convection Currents
 Natural Convection                      Affects room air motion
  Currents - Caused by                        and affects the comfort
  difference in temperature                   in the space
  between room air and air
  in contact with a warm
  or cold surface


                               Step 3
                               Natural
                             convection
                            currents and
                            stratification
                                zone




                       © 2010. All rights reserved
Step 4: Identify the Return Intake
 Return Intake - return                   Even natural convection
  intake affects only the                      currents will overcome the
  air motion within its                        draw of the intake
  immediate vicinity




                        © 2010. All rights reserved
Step 5: Identify the Room Air
 Room Air Diagram is complete                Most uniform air motion is
  when remaining room air drifts               between stratification zone
  back towards the primary air                 and total air
  and total air                               Highest air motion is in and
 Lowest air motion is                         near the primary and total air
  in stratification zone




                           © 2010. All rights reserved
Mapping Throw




                © 2010. All rights reserved
Mapping Throw

                Cooling




                © 2010. All rights reserved
Estimating Downward Projection
 Chart provides
  vertical throw of a
  free jet to 50 fpm for
  heating and cooling
  with the same
  diffuser.
                                                                 23    40   28
                                                     1000 fpm
 Typically, cfm and jet
  velocity are known.

 2009 Fundamentals
  Chapter 20


                                                     1000 cfm
                                                                +10   -20   0
                           © 2010. All rights reserved
ADPI & Comfort
Air Diffusion Performance Index
Statistically related the space conditions of local
 or transversed temperature and velocities to
 occupants’ thermal comfort
ADPI >= 80 is considered acceptable
Effective draft temperature
   = (tx-tc) – 0.07(Vx-30)
   % of points where -3<= <= +2 = ADPI
   Velocity below 70 fpm


                     © 2010. All rights reserved
ADPI
The grey area
 represents
 -3<= <= +2
You can vary
 temperature
 or velocity to
 maintain comfort
15 fpm = 1 °F



                    © 2010. All rights reserved
Throw vs. Characteristic Length




                © 2010. All rights reserved
ADPI Selection Illustration


                                       Point A




      ADPI      Min                  80 ADPI Min
                                                              Max
                  0.6                                           1.2




             20x20 Room
             400 cfm = 1 cfm/sq ft
             Characteristic Length = 10
             Therefore, look for T50 = 12 feet at 400 cfm (Max VAV)
             Check Turndown point at .6 T50/L (Min VAV)
             Set constant volume systems at Point A.




                                          T50/L


                               © 2010. All rights reserved
Recommended ADPI Ranges for Outlets
       Outlet          T50/L      Range       Calculated         T50 & L    Data

Sidewall Grilles                     L             10              15         20        25      30
                        1.3-2.0     T50           13-20           20-30      26-40     33-50   39-60
Ceiling Diffusers                    L               5              10         15       20      25
Round Pattern
                        0.6-1.2     T50             3-6            6-12       9-18     12-24   15-30
Ceiling Diffusers                    L               5              10         15       20      25
Cross Pattern
                        1.0-2.0     T50            5-10           10-20      15-30     20-40   25-50
Slot Diffusers                       L               5              10         15       20      25
                        0.5-3.3     T50            3-18            5-33       9-50     10-66   15-83
Light Troffer                        L               4                  6          8    10      12
Diffusers

                        1.0-5.0     T50            4-20            6-30       8-40     10-50   12-60
Sill & Floor Grilles                 L               5              10        15        20      25
      All Types         0.7-1.7     T50             4-9            7-17      11-26     14-34   18-13




                                          © 2010. All rights reserved
ASHRAE Standard 62.1 Table 6.2
        Ventilation Air Ez Factor
Ceiling supply of cool air                      1.0
Ceiling supply warm air < 15 °F Δt              1.0
    150 fpm supply jet reaches 4.5’ AFF
Ceiling supply warm air >15 °F Δt               0.8
Floor supply cooling ceiling return UFAD:
  T 50 > 4.5’ AFF                               1.0
  T 50 < 4.5 AFF (RP-1373)                      1.2
Displacement Ventilation                        1.2



                   © 2010. All rights reserved
Typical Perimeter Solution
 50/50 throw pattern is
  the best compromise for
  both heating and cooling
 Half of the air is always
  directed in the wrong
  direction
 ASHRAE Std. 62.1-2007
    T150 to 4’-5’ AFF
    Max Δt = 15 °F



                       © 2010. All rights reserved
Auto Changeover Diffuser Solution
                                                          Diffuser



             Cooling




                                                                            Window
  Air flow does not pause in
  intermittent pattern to cause
  sustained drafts pop action
  of air flow pattern.




                                                                     Sill
                                                        Heating




                          © 2010. All rights reserved
Auto Changeover Diffuser
 Vertical Pattern For
  Heating
 Horizontal Pattern For
  Cooling
 30% Increase In Energy
  Efficiency
 Room reaches set-point
  faster
 Room Stratification for
  heating similar to cooling



                         © 2010. All rights reserved
Sills & Soffits on Perimeter
 Soffits cause air to turn                                 Soffit
  up prematurely
    Aim air under the soffit
      to hit the glass or cold wall



 Sills deflect cold air
  into the room
    Sill height sets the stratification
      layer height



                                                             Sill


                              © 2010. All rights reserved
Air Distribution, Partition Effects




            © 2010. All rights reserved
Partially Mixed Air Distribution
UFAD – Interior Zone
Perimeter with Series Fan Terminal
Perimeter with Plenum VAV Cooling
Perimeter with Passive Heating




                  © 2010. All rights reserved
Underfloor Air Distribution (UFAD)


                                              Stratified
                                                Zone




                © 2010. All rights reserved
Round Access Floor Diffuser
High induction air flow pattern
Occupant adjustable damper
   Actuated version available

Typical design point is 80-100 cfm
Throw between 4-5 ft.
Low NC

                      © 2010. All rights reserved
Interior Applications
Use Conventional Components…
   Round (Swirl) Diffusers
   Rectangular Diffusers

In Conventional Applications
   One per worker or area measure


                   © 2010. All rights reserved
Series Fan Terminal for Perimeter
Used in perimeter and conference rooms
   Any room with varying loads
10 ½”, and 14” tall units for 12” and 16” raised
 floors
300 cfm to 1200 cfm
Standard series fan
  powered terminal
Primary supply
 air damper
   Supply pulls from the floor
   Option for two dampers

                    © 2010. All rights reserved
Typical Perimeter Installation
Low horsepower fan powered terminal unit
 ducted to rectangular floor diffuser plenums




                   © 2010. All rights reserved
Plenums 
Plenum sizes vary
   8” x 16”
   10” x 10”
   12” x 12”


Cores are available in multi-piece
   2-way or 4 way blow



                     © 2010. All rights reserved
ECM Motor
Electronically Commutated Motor




                  © 2010. All rights reserved
ECM Motor
Brushless, DC motor
Converts AC to DC for motor
Ultra high efficiency motor
   Efficiencies of up to 70% across the entire operating
    range
Energy savings
Control of fan speed through DDC controller



                      © 2010. All rights reserved
Energy Savings
350 watts savings = .350 kW

250 days/year x 12 hours/day
 = 3000 operating hours/year

.350 kW x 3000 hours = 1050 kWh

1050 kWh x $.10 per kWh
 = $105 per unit per year energy savings!
   Does not include demand charges


                   © 2010. All rights reserved
PWM 
The ECM motor is controlled by a PWM (Pulse
 Width Modulated) signal
Voltage pulses over a specific time period
Voltage is proportional to cfm
Low voltage device
Manual PWM is adjusted like a SCR, with a
 screwdriver
Remote PWM is controlled by a 0-10V signal from
 the DDC controller


                  © 2010. All rights reserved
Additional ECM Benefits
Soft start
  Motors are set to start up slowly
No brushes
  No noise associated with brushes
  Titus has found no significant overall sound reduction
     with the ECM motor
    No wearing of brushes
ECM motor life is ~90,000 hours (30 years of
 typical series fan box life)
Cooler operation

                       © 2010. All rights reserved
Linear Perimeter System
 (Variable Air Volume)

 (Water Heat)

 (SCR Electric Heat)

 (Return)



                     © 2010. All rights reserved
Perimeter Linear Diffuser Solution




                 © 2010. All rights reserved
Transverse Apertures

      © 2010. All rights reserved
Transverse Apertures

      © 2010. All rights reserved
Transverse Apertures

      © 2010. All rights reserved
Perimeter Smoke Demo Video




              © 2010. All rights reserved
Interior Zone VAV Cooling




     Conference                                 Waiting Area


                  © 2010. All rights reserved
Underfloor  System Christman




                                             Linear Heat
                                             3900 Btu/h
                                              4’ Length



               © 2010. All rights reserved
Fin tube application




                © 2010. All rights reserved
Fully Stratified Air Systems
Energy & Comfort Optimization (ECO)
Basic system concepts
Displacement diffusers




                  © 2010. All rights reserved
DV‐ Basic Concepts




                                                             Supply Air
                                                             TL = 65°F



 Higher supply air temperature
 Air change effectiveness factor of 1.2                   Clear
                                                           Zone


                             © 2010. All rights reserved
Displacement Ventilation Applications
Good application
   Room height > 9.5 ft
   Open Plan Offices, Classrooms, & Meeting
   Rooms

   Casinos, Restaurants, Theaters, &
   Auditoriums



                  © 2010. All rights reserved
Displacement Ventilation Applications
Poor application
   Room height < 8 ft
   Surplus heat is the main problem – not air
   quality

   In combination with chilled beams



                  © 2010. All rights reserved
System Equipment
Higher equipment efficiency
  Uses warmer supply air
     65°F compared to 55°F
  Energy consumption is often reduced by raising
   discharge temperature




                   © 2010. All rights reserved
System Equipment
Lower horsepower fans
  0.04 in. pressure is required for proper
   diffuser performance

  Results in lower horsepower fans required




                  © 2010. All rights reserved
HVAC System Benefits
Heat sources outside the
 stratification layer are not
 considered in airflow calculations
   Lighting load is designed as “equipment
   load”, but not as “space load”

   Effects cooling load capacity, but not air
   distribution capacity


                   © 2010. All rights reserved
Perimeter Heating
Perimeter heating cannot be
 accomplished with the displacement
 ventilation system

Separate system is required:




               © 2010. All rights reserved
Return Air
Located at ceiling

Allows heat from ceiling light to be
 returned before it is able to mix with
 occupied zone




               © 2010. All rights reserved
Return Air
If 55oF supply air is used for
 humidity reasons, return air can be
 mixed with plenum air to achieve
 65oF air

If 65oF supply air is used, return air
 can be brought back to the air
 handling unit to be filtered and
 dehumidified
               © 2010. All rights reserved
Temperature Gradient
ASHRAE Standard 55:
   Occupied Zone
   < 5.4°F

Risk of draft increases
 if ∆t > 36°F between
 supply and exhaust air


                                                  (Displacement ventilation, REHVA)




                    © 2010. All rights reserved
Temperature Gradient
Ceiling Height 9’-14’

50% Rule is applied

62°F – 72°F – 82°F
   10°F    -   10°F
                                             (Displacement ventilation, REHVA)




               © 2010. All rights reserved
Temperature Gradient
33% Rule for > 14’
 room heights
                                              33%   67%

64°F – 72°F – 86°F
   8°F   -   14°F

                                                    (Displacement ventilation, REHVA)




                © 2010. All rights reserved
Adjacent zone
Discharge
 Velocity < 80 fpm
Area where air
 velocity exceeds
 50 fpm
Occupants
 should not be
 stationed within
 the adjacent zone


                  © 2010. All rights reserved
Comfort with Adjustable Air Patterns


  Standard adjacent zone from
   factory




  Modified adjacent zone after
   adjusting pattern controllers to
   change pattern




                           © 2010. All rights reserved
Comfort Air Distribution
The ASHRAE 2009 Fundamentals handbook,
 Chapter 20, 2007 Applications handbook Chapter
 56, and 2008 Systems & Equipment handbook
 provides guidance on diffuser selection.
Select throw at Max. & Min. to meet ADPI
 guidelines.
It cost less for install a good design than to
 replace a bad design.
Employees cost 70 times the cost of Energy.


                  © 2010. All rights reserved
Questions?

More Related Content

PPT
Cem 350 hvac distribution systems sizing 10 2016
PPTX
Cooling Systems - Chiller Technologies
PDF
Hvac course
PPTX
Air Conditioning Systems in Refrigeration and Air Conditioning
PDF
Air Distribution Systems
PPTX
Air conditioning
PPTX
HVAC Basic Concepts of Air Conditioning
PDF
Cooling tower
Cem 350 hvac distribution systems sizing 10 2016
Cooling Systems - Chiller Technologies
Hvac course
Air Conditioning Systems in Refrigeration and Air Conditioning
Air Distribution Systems
Air conditioning
HVAC Basic Concepts of Air Conditioning
Cooling tower

What's hot (20)

PDF
Duct design
PPT
AIR CONDITIONING SYSTEM DESINGING
PPTX
Chilled water systems
PPTX
Hvac complete final
PDF
Hvac formulas
PPTX
Airconditioning ppt
PPTX
cooling tower
PPTX
HVAC Systems- A Complete Guide
PPTX
CONDENSATE RECOVERY SYSTEMS
PPTX
S3 Lec 2 (Condenser) Note
PPTX
Chiller water systems
PPTX
B.tech i eme u 4 r & ac
PPTX
Types orifice and mouthpiece
PDF
How to Calculate Chiller’s Performance & ROI when Replacing- كيف تحسب كفاءة ا...
PPT
Steam condensors
PPTX
Duct Design & Air distribution
PPTX
Chilled water piping basics
PPTX
Packaged air conditioners
PPTX
VARIABLE REFRIGERATE FLOW
PPTX
Centrifugal compressor
Duct design
AIR CONDITIONING SYSTEM DESINGING
Chilled water systems
Hvac complete final
Hvac formulas
Airconditioning ppt
cooling tower
HVAC Systems- A Complete Guide
CONDENSATE RECOVERY SYSTEMS
S3 Lec 2 (Condenser) Note
Chiller water systems
B.tech i eme u 4 r & ac
Types orifice and mouthpiece
How to Calculate Chiller’s Performance & ROI when Replacing- كيف تحسب كفاءة ا...
Steam condensors
Duct Design & Air distribution
Chilled water piping basics
Packaged air conditioners
VARIABLE REFRIGERATE FLOW
Centrifugal compressor
Ad

Similar to 10 air distribution basics (20)

PPT
Building Energy Fundementals_Halsall
PPTX
(Apr 12 2012) Chilled Beam Presentation
PPTX
Indoor air quality
PPTX
Duct design .ppt
PPT
Articmaster Refrigerant Management System
PPTX
Ventilation rate
PDF
Air curtains catalog 2011
PDF
Building services group report
PDF
Bservices report
PDF
Cold weather destratification energy savings of a warehousing facility.
PPTX
Underfloor Air Distribution
PPT
William Kidd CEO Institute of Specialist Surveyors and Engineers - plans for ...
PPT
Air movement cold chain management cold storage
PDF
Utilizing Energy Recovery and Optimizing Air
PDF
Heating and-air-conditioning-of-building-faber-and-kell-chapter-14-air-condit...
PDF
R _ AC-16.pdfRefregeration and air conditioning very important slides for duc...
PDF
Ductwork
PPTX
OmniVent Motorized Diffuser
PPTX
Ov Md Black Ppt[Ver 2]
Building Energy Fundementals_Halsall
(Apr 12 2012) Chilled Beam Presentation
Indoor air quality
Duct design .ppt
Articmaster Refrigerant Management System
Ventilation rate
Air curtains catalog 2011
Building services group report
Bservices report
Cold weather destratification energy savings of a warehousing facility.
Underfloor Air Distribution
William Kidd CEO Institute of Specialist Surveyors and Engineers - plans for ...
Air movement cold chain management cold storage
Utilizing Energy Recovery and Optimizing Air
Heating and-air-conditioning-of-building-faber-and-kell-chapter-14-air-condit...
R _ AC-16.pdfRefregeration and air conditioning very important slides for duc...
Ductwork
OmniVent Motorized Diffuser
Ov Md Black Ppt[Ver 2]
Ad

More from Illinois ASHRAE (20)

PPTX
Assessing Your Building Energy Costs: Benefits of Energy Modeling to Owners
PDF
Modeling, It's Not Just For Calendars and Energy
PDF
Preliminary Modeling & Life Cycle Costing: Underpinnings of Integrated Design.
PPT
Measurement & Verification
PPTX
Building EQ
PPTX
Chicago Energy Modeling Conference Welcome Address
PPT
Chicago Energy Modeling Conference Key Note
PDF
Illinois ASHRAE 2011 Technology Awards
PPT
Illinois ASHRAE Research Promotion
PDF
Net Zero Energy Buildings
PDF
Standard 90.1-2010 Update
PDF
High performance-chilled-water-systems ashrae-chicago
PDF
Waterside energy-recovery hourlong-chicago_ashrae
PPTX
YEA ASHRAE Kick-Off Meeting 2011
PPTX
Illinois ASHRAE Kick-Off Meeting 2011
PDF
ASHRAE Standard 189.1
PDF
ComEd Retro-Commissioning Program
PDF
Smart Ideas for Your Business
PPTX
Nicor Gas Non-Residential Energy Efficiency Programs
PPT
ASHRAE Standard 100
Assessing Your Building Energy Costs: Benefits of Energy Modeling to Owners
Modeling, It's Not Just For Calendars and Energy
Preliminary Modeling & Life Cycle Costing: Underpinnings of Integrated Design.
Measurement & Verification
Building EQ
Chicago Energy Modeling Conference Welcome Address
Chicago Energy Modeling Conference Key Note
Illinois ASHRAE 2011 Technology Awards
Illinois ASHRAE Research Promotion
Net Zero Energy Buildings
Standard 90.1-2010 Update
High performance-chilled-water-systems ashrae-chicago
Waterside energy-recovery hourlong-chicago_ashrae
YEA ASHRAE Kick-Off Meeting 2011
Illinois ASHRAE Kick-Off Meeting 2011
ASHRAE Standard 189.1
ComEd Retro-Commissioning Program
Smart Ideas for Your Business
Nicor Gas Non-Residential Energy Efficiency Programs
ASHRAE Standard 100

Recently uploaded (20)

PDF
1911 Gold Corporate Presentation Aug 2025.pdf
PDF
Nante Industrial Plug Factory: Engineering Quality for Modern Power Applications
PPTX
Astra-Investor- business Presentation (1).pptx
PPTX
Slide gioi thieu VietinBank Quy 2 - 2025
DOCX
Center Enamel A Strategic Partner for the Modernization of Georgia's Chemical...
PDF
Ron Thomas - Top Influential Business Leaders Shaping the Modern Industry – 2025
DOCX
Hand book of Entrepreneurship 4 Chapters.docx
PPTX
2 - Self & Personality 587689213yiuedhwejbmansbeakjrk
PDF
Susan Semmelmann: Enriching the Lives of others through her Talents and Bless...
PDF
#1 Safe and Secure Verified Cash App Accounts for Purchase.pdf
PPTX
chapter 2 entrepreneurship full lecture ppt
PDF
Satish NS: Fostering Innovation and Sustainability: Haier India’s Customer-Ce...
PDF
Keppel_Proposed Divestment of M1 Limited
PPTX
basic introduction to research chapter 1.pptx
PDF
NISM Series V-A MFD Workbook v December 2024.khhhjtgvwevoypdnew one must use ...
PDF
TyAnn Osborn: A Visionary Leader Shaping Corporate Workforce Dynamics
PDF
Robin Fischer: A Visionary Leader Making a Difference in Healthcare, One Day ...
PDF
Tortilla Mexican Grill 发射点犯得上发射点发生发射点犯得上发生
PDF
Kishore Vora - Best CFO in India to watch in 2025.pdf
PPT
Lecture 3344;;,,(,(((((((((((((((((((((((
1911 Gold Corporate Presentation Aug 2025.pdf
Nante Industrial Plug Factory: Engineering Quality for Modern Power Applications
Astra-Investor- business Presentation (1).pptx
Slide gioi thieu VietinBank Quy 2 - 2025
Center Enamel A Strategic Partner for the Modernization of Georgia's Chemical...
Ron Thomas - Top Influential Business Leaders Shaping the Modern Industry – 2025
Hand book of Entrepreneurship 4 Chapters.docx
2 - Self & Personality 587689213yiuedhwejbmansbeakjrk
Susan Semmelmann: Enriching the Lives of others through her Talents and Bless...
#1 Safe and Secure Verified Cash App Accounts for Purchase.pdf
chapter 2 entrepreneurship full lecture ppt
Satish NS: Fostering Innovation and Sustainability: Haier India’s Customer-Ce...
Keppel_Proposed Divestment of M1 Limited
basic introduction to research chapter 1.pptx
NISM Series V-A MFD Workbook v December 2024.khhhjtgvwevoypdnew one must use ...
TyAnn Osborn: A Visionary Leader Shaping Corporate Workforce Dynamics
Robin Fischer: A Visionary Leader Making a Difference in Healthcare, One Day ...
Tortilla Mexican Grill 发射点犯得上发射点发生发射点犯得上发生
Kishore Vora - Best CFO in India to watch in 2025.pdf
Lecture 3344;;,,(,(((((((((((((((((((((((

10 air distribution basics