SIEMENS SIPROTEC
7SJ64 Relay
Description
 The SIPROTEC 4 7SJ64 can be used as a protective control and
monitoring relay for distribution feeders and transmission lines of any
voltage in networks that are earthed (grounded), low-resistance earthed,
unearthed, or of a compensated neutral point structure. The relay is
suited for networks that are radial or looped, and for lines with single or
multi-terminal feeds. The SIPROTEC 4 7SJ64 is equipped with a
synchronization function which provides the operationmodes
‘synchronization check’ (classical) and ‘synchronous/asynchronous
switching’ (which takes the CBmechanical delay into consideration).
Motor protection comprises undercurrent monitoring, starting time
supervision, restart inhibit, locked rotor, load jamprotection as well
asmotor statistics.
 The 7SJ64 is featuring the "flexible protection functions".Up to 20
protection functions can be added according to individual requirements.
Thus, for example, rate-of-frequency-change protection or reverse power
protection can be implemented.
Description
 The relay provides easy-to-use local control and automation functions.
The number of controllable switchgear depends only on the number of
available inputs and outputs. The integrated programmable logic (CFC)
allows the user to implement their own functions, e.g. for the
automation of switchgear (interlocking). CFC capacity ismuch larger
compared to 7SJ63 due to extended CPU power. The user is able to
generate user-defined messages as well.
 The flexible communication interfaces are open formodern
communication architectures with control systems.
Protection functions
 Overcurrent protection
 Directional overcurrent protection
 Sensitive dir./non-dir. earth-fault detection
 Displacement voltage
 Intermittent earth-fault protection
 Directional intermittent ground fault protection
 High-impedance restricted earth fault
 Inrush restraint
 Motor protection
 Overload protection
 Temperature monitoring
 Under-/overvoltage protection
 Under-/overfrequency protection
 Rate-of-frequency-change protection
 Power protection (e.g. reverse, factor)
 Undervoltage-controlled reactive power protection
 Breaker failure protection
 Negative-sequence protection
 Phase-sequence monitoring
 Synchronization
Monitoring functions
 Operational measured values V, I, f,...
 Energy metering values Wp,Wq
 Circuit-breaker wear monitoring
 Slave pointer
 Trip circuit supervision
 Fuse failure monitor
 8 oscillographic fault records
 Motor Statistics
Control functions/programmable logic
 Flexible number of switching devices
 Position of switching elements is shown on the graphic display
 Local/remote switching via keyoperated switch
 Control via keyboard, binary inputs, DIGSI 4 or SCADA system
 Extended User-defined logic with CFC (e.g. interlocking)
 System interface
– IEC 60870-5-103/ IEC 61850
– PROFIBUS-FMS/-DP
– DNP 3.0/DNP3 TCP/MODBUS RTU
 Service interface for DIGSI 4 (modem)
 Additional interface for temperature detection (RTD-box)
 Front interface for DIGSI 4
 Time synchronization via IRIG B/DCF77
Communication interfaces
Application
The SIPROTEC 4 7SJ64 unit is a numerical protection relay that also
performs control and monitoring functions and therefore supports the user in
cost-effective power system management, and ensures reliable supply of
electric power to the customers. Local operation has been designed according
to ergonomic criteria. A large, easy-to-read graphic display was a major
design aim
Construction
Connection techniques and housing with many advantages
1/3, 1/2 and 1/1-rack sizes These are the available housing widths of the 7SJ64 relays,
referred to a 19” module frame system. This means that previous models can always
be replaced. The height is a uniform 244 mm for flush-mounting housings and 266
mm for surfacemounting housings for all housing widths. All cables can be connected
with or without ring lugs. Plug-in terminals are available as an option. It is thus
possible to employ prefabricated cable harnesses. In the case of surface mounting on
a panel, the connection terminals are located above and below in the form of screw-
type terminals. The communication interfaces are located in a sloped case at the top
and bottom of the housing. The housing can also be supplied optionally with a
detached operator panel (refer to Fig. 5/168), or without operator panel, in order to
allow optimum operation for all types of applications.
Protection functions
Time-overcurrent protection
This function is based on the phase-selective measurement of the three phase currents
and the earth current (four transformers). Three definite-time overcurrent protection
elements (DMT) exist both for the phases and for the earth. The current threshold and
the delay time can be set in a wide range. In addition, inverse-time overcurrent
protection characteristics (IDMTL) can be activated. The inverse-time function provides
– as an option – voltage-restraint or voltage-controlled operating modes. With the
"flexible protection functions", further definite-time overcurrent stages can be
implemented in the 7SJ64 unit.
Functions
Motor control
The SIPROTEC 4 7SJ64 with high performance relays is well-suited for
direct activation of the circuit-breaker, disconnector and earthing switch
operating mechanisms in automated substations.
Chatter disable
Chatter disable feature evaluates whether, in a configured period of time,
the number of status changes of indication input exceeds a specified figure.
If exceeded, the indication input is blocked for a certain period, so that the
event list will not record excessive operations.
Indication derivation
A further indication (or a command) can be derived from an existing
indication. Group indications can also be formed. The volume of
information to the system interface can thus be reduced and restricted to
the most important signals.
Communication
In terms of communication, the units offer substantial flexibility in the context of
connection to industrial and power automation standards. Communication can be
extended or added on thanks to modules for retrofitting on which the common
protocols run. Therefore, also in the future it will be possible to optimally
integrate units into the changing communication infrastructure, for example in
Ethernet networks (which will also be used increasingly in the power supply
sector in the years to come).
Serial front interface
There is a serial RS232 interface on the front of all the units. All of the unit’s
functions can be set on a PC by means of the DIGSI 4 protection operation
program.
Rear-mounted interfaces
A number of communication modules suitable for various applications can be
fitted in the rear of the flush-mounting housing.
PROFIBUS-DP protocol
PROFIBUS-DP is the most widespread protocol in industrial automation. Via
PROFIBUS-DP, SIPROTEC units make their information available to a
SIMATIC controller or, in the control direction, receive commands from a central
SIMATIC. Measured values can also be transferred
Connection diagram
Dimension drawing
Mob No:
Mr. Piyush Rathi- +91-9819614841
Website:
www.reliservsolution.com
Email-ID:
piyush@reliserv.in
sales1@reliserv.in
Address:
Office No: 9, Space Heights,
Plot No. 53/54 , Sector 34,
Kamothe,Navi Mumbai- 410209
Contact us

More Related Content

DOCX
Tutor logo!
PDF
Controladores lógicos programables por Frank D. Petruzella.pdf
DOCX
Tabla tuberia cable
PDF
FACTOR DE POTENCIA
PDF
Transformador depulsos
PDF
Original Power Suply IC TOP227YN TOP227Y TOP227 227 TO-220 NewOriginal Power ...
PDF
Ece 523 project – fully differential two stage telescopic op amp
PDF
Electroneumática: Sistemas neumáticos principios y mantenimiento S. R. Majumd...
Tutor logo!
Controladores lógicos programables por Frank D. Petruzella.pdf
Tabla tuberia cable
FACTOR DE POTENCIA
Transformador depulsos
Original Power Suply IC TOP227YN TOP227Y TOP227 227 TO-220 NewOriginal Power ...
Ece 523 project – fully differential two stage telescopic op amp
Electroneumática: Sistemas neumáticos principios y mantenimiento S. R. Majumd...

What's hot (17)

PDF
Realizacion de un Amplificador de Audio con Etapa de Salida a Transistores MO...
PDF
Lógica Digital CI 7400
PPT
Tranf fourier
PDF
Puntas terminales
PDF
01 TALLER CIRCUITOS CON CONTACTORES OK.pdf
PDF
Megger Cable Fault Locators - Power Cable Fault Locators, Van mountable Solut...
PDF
Problemas sistemas lti
PDF
7 E Cantida De Cables Por Tuberia Conduit
PDF
IEEE 1427-2006
PDF
Diseño de subestaciones
PPT
TRANSFORMADA DISCRETA DE FOURIER
PDF
Normas de cableado interno CANTV 23 05-12
PPTX
Corrección del factor de potencia en sistemas trifásicos
PDF
El-poder-del-aire.pdf
PPT
Modelos equivalentes de pequeña señal de los transistores fet
PDF
Circuitos eléctricos 8ed Svoboda.pdf
PPT
Configuraciones subestaciones-electricas
Realizacion de un Amplificador de Audio con Etapa de Salida a Transistores MO...
Lógica Digital CI 7400
Tranf fourier
Puntas terminales
01 TALLER CIRCUITOS CON CONTACTORES OK.pdf
Megger Cable Fault Locators - Power Cable Fault Locators, Van mountable Solut...
Problemas sistemas lti
7 E Cantida De Cables Por Tuberia Conduit
IEEE 1427-2006
Diseño de subestaciones
TRANSFORMADA DISCRETA DE FOURIER
Normas de cableado interno CANTV 23 05-12
Corrección del factor de potencia en sistemas trifásicos
El-poder-del-aire.pdf
Modelos equivalentes de pequeña señal de los transistores fet
Circuitos eléctricos 8ed Svoboda.pdf
Configuraciones subestaciones-electricas
Ad

Similar to 7SJ64 Relay (20)

PDF
7SJ62 Multifunction Over Current Protection Relay
PDF
7SJ61 Over Current Relay
PDF
7SJ63 BCPU Multifunction Protection Relay
PDF
7SJ80 Overcurrent Relay
PDF
7RW80 Voltage Frequency Protection Relay
PDF
7SA61 Distance Protection Relay For All Voltage Levels
PDF
7SK81 Motor Protection Relay
PDF
7VK61 Breaker Management Protective Relay
PDF
7SJ66 BCU Protective Relay
PDF
7SJ81 Overcurrent Relay
PDF
7SD80 Cable Differential Relay
PDF
7UT613 Differential Protection Relay For Three Winding
PDF
7UT612 Transformer Differential Protection relay
PDF
7SK80 Motor Protection Relay
PDF
7UT63 Differential Protection Relay
PDF
7SC80 Feeder Automation Controller
PDF
7 um62xx catalog_sip-2006_en
DOC
siprotec
DOC
siprotec
PDF
7SA63 Protective Relays
7SJ62 Multifunction Over Current Protection Relay
7SJ61 Over Current Relay
7SJ63 BCPU Multifunction Protection Relay
7SJ80 Overcurrent Relay
7RW80 Voltage Frequency Protection Relay
7SA61 Distance Protection Relay For All Voltage Levels
7SK81 Motor Protection Relay
7VK61 Breaker Management Protective Relay
7SJ66 BCU Protective Relay
7SJ81 Overcurrent Relay
7SD80 Cable Differential Relay
7UT613 Differential Protection Relay For Three Winding
7UT612 Transformer Differential Protection relay
7SK80 Motor Protection Relay
7UT63 Differential Protection Relay
7SC80 Feeder Automation Controller
7 um62xx catalog_sip-2006_en
siprotec
siprotec
7SA63 Protective Relays
Ad

More from ashwini reliserv (20)

PDF
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
PDF
SICAM FSI – Fault Sensor Indicator
PDF
SICAM FCG-Fault Collector Gateway
PDF
SICAM FPI - Fault Passage Indicator
PDF
SICAM FCM – Feeder Condition Monitor
PDF
Small Control Center System SICAM 230
PDF
SICAM Diamond (6MD552)
PDF
SICAM Disto substation automation
PDF
SICAM PQ Analyzer
PDF
SICAM SCC (6MD55) automation
PDF
SICAM AK 3 automation
PDF
SICAM PAS Software (6MD90)
PDF
RUGGEDCOM RSL910 vdsl modems
PDF
RUGGEDCOM SFPs accessories
PDF
RUGGEDCOM RPS1300 accessories
PDF
RUGGEDCOM REFLEX software
PDF
RUGGEDCOM ELAN software
PDF
RUGGEDCOM RP110 Ethernet injectors
PDF
RUGGEDCOM RP100 Ethernet injectors
PDF
RUGGEDCOM RS910W wireless lan
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
SICAM FSI – Fault Sensor Indicator
SICAM FCG-Fault Collector Gateway
SICAM FPI - Fault Passage Indicator
SICAM FCM – Feeder Condition Monitor
Small Control Center System SICAM 230
SICAM Diamond (6MD552)
SICAM Disto substation automation
SICAM PQ Analyzer
SICAM SCC (6MD55) automation
SICAM AK 3 automation
SICAM PAS Software (6MD90)
RUGGEDCOM RSL910 vdsl modems
RUGGEDCOM SFPs accessories
RUGGEDCOM RPS1300 accessories
RUGGEDCOM REFLEX software
RUGGEDCOM ELAN software
RUGGEDCOM RP110 Ethernet injectors
RUGGEDCOM RP100 Ethernet injectors
RUGGEDCOM RS910W wireless lan

Recently uploaded (20)

PPTX
CCC-Ancillary-Slidesk powerpoint present.pptx
PDF
The Future of Fremont: Raj Salwan’s Inclusive Vision
PDF
Nursery Admissions in Panipat | PIET Sanskriti Ansals
PDF
Understanding HIPAA Compliance: Why It Matters and How Experts Help
PPTX
Optimize with BIM Clash Detection 3.pptx
PDF
Top Benefits of Using Unified Communications for Your Company
PDF
Best IPTV Reseller Program & Best IPTV Reseller Panel 2025
PDF
Employee Movement Tracking System_ 1 SGD Mobile Attendance.pdf
PDF
Wearable Devices App Development Company.pdf
PPTX
Financial_Document_Reconciliation_Full_Presentation.pptx
PDF
MangoPeel Final - Dr. Skin Clinic Kerala
PPTX
Courier-Delivery-App-Development-Unlocking-the-Future-of-Logistics.pptx
PPTX
The Rise of the Agentic Edge Salesforce’s Bold Move with Regrello GetOnCRM.pptx
PDF
Engine Volvo EC200B Excavator Repair Manual.pdf
PPTX
Comprehensive Plumbing and Piping Engineering
PDF
The Future of Transport and Logistics in Southeast Asia.pdf
PDF
data_center_optimization_playbook_v4_239872_0 (1).pdf
PPT
Wireless communication is strictly prohibited to the topic of topic name is t...
PDF
D6E Volvo EC200B Excavator Service Repair Manual.pdf
PDF
The Essential Role of Gutter Guard Mesh in Safeguarding Your Property
CCC-Ancillary-Slidesk powerpoint present.pptx
The Future of Fremont: Raj Salwan’s Inclusive Vision
Nursery Admissions in Panipat | PIET Sanskriti Ansals
Understanding HIPAA Compliance: Why It Matters and How Experts Help
Optimize with BIM Clash Detection 3.pptx
Top Benefits of Using Unified Communications for Your Company
Best IPTV Reseller Program & Best IPTV Reseller Panel 2025
Employee Movement Tracking System_ 1 SGD Mobile Attendance.pdf
Wearable Devices App Development Company.pdf
Financial_Document_Reconciliation_Full_Presentation.pptx
MangoPeel Final - Dr. Skin Clinic Kerala
Courier-Delivery-App-Development-Unlocking-the-Future-of-Logistics.pptx
The Rise of the Agentic Edge Salesforce’s Bold Move with Regrello GetOnCRM.pptx
Engine Volvo EC200B Excavator Repair Manual.pdf
Comprehensive Plumbing and Piping Engineering
The Future of Transport and Logistics in Southeast Asia.pdf
data_center_optimization_playbook_v4_239872_0 (1).pdf
Wireless communication is strictly prohibited to the topic of topic name is t...
D6E Volvo EC200B Excavator Service Repair Manual.pdf
The Essential Role of Gutter Guard Mesh in Safeguarding Your Property

7SJ64 Relay

  • 2. Description  The SIPROTEC 4 7SJ64 can be used as a protective control and monitoring relay for distribution feeders and transmission lines of any voltage in networks that are earthed (grounded), low-resistance earthed, unearthed, or of a compensated neutral point structure. The relay is suited for networks that are radial or looped, and for lines with single or multi-terminal feeds. The SIPROTEC 4 7SJ64 is equipped with a synchronization function which provides the operationmodes ‘synchronization check’ (classical) and ‘synchronous/asynchronous switching’ (which takes the CBmechanical delay into consideration). Motor protection comprises undercurrent monitoring, starting time supervision, restart inhibit, locked rotor, load jamprotection as well asmotor statistics.  The 7SJ64 is featuring the "flexible protection functions".Up to 20 protection functions can be added according to individual requirements. Thus, for example, rate-of-frequency-change protection or reverse power protection can be implemented.
  • 3. Description  The relay provides easy-to-use local control and automation functions. The number of controllable switchgear depends only on the number of available inputs and outputs. The integrated programmable logic (CFC) allows the user to implement their own functions, e.g. for the automation of switchgear (interlocking). CFC capacity ismuch larger compared to 7SJ63 due to extended CPU power. The user is able to generate user-defined messages as well.  The flexible communication interfaces are open formodern communication architectures with control systems.
  • 4. Protection functions  Overcurrent protection  Directional overcurrent protection  Sensitive dir./non-dir. earth-fault detection  Displacement voltage  Intermittent earth-fault protection  Directional intermittent ground fault protection  High-impedance restricted earth fault  Inrush restraint  Motor protection  Overload protection  Temperature monitoring  Under-/overvoltage protection  Under-/overfrequency protection  Rate-of-frequency-change protection  Power protection (e.g. reverse, factor)  Undervoltage-controlled reactive power protection  Breaker failure protection  Negative-sequence protection  Phase-sequence monitoring  Synchronization
  • 5. Monitoring functions  Operational measured values V, I, f,...  Energy metering values Wp,Wq  Circuit-breaker wear monitoring  Slave pointer  Trip circuit supervision  Fuse failure monitor  8 oscillographic fault records  Motor Statistics Control functions/programmable logic  Flexible number of switching devices  Position of switching elements is shown on the graphic display  Local/remote switching via keyoperated switch  Control via keyboard, binary inputs, DIGSI 4 or SCADA system  Extended User-defined logic with CFC (e.g. interlocking)
  • 6.  System interface – IEC 60870-5-103/ IEC 61850 – PROFIBUS-FMS/-DP – DNP 3.0/DNP3 TCP/MODBUS RTU  Service interface for DIGSI 4 (modem)  Additional interface for temperature detection (RTD-box)  Front interface for DIGSI 4  Time synchronization via IRIG B/DCF77 Communication interfaces
  • 7. Application The SIPROTEC 4 7SJ64 unit is a numerical protection relay that also performs control and monitoring functions and therefore supports the user in cost-effective power system management, and ensures reliable supply of electric power to the customers. Local operation has been designed according to ergonomic criteria. A large, easy-to-read graphic display was a major design aim
  • 8. Construction Connection techniques and housing with many advantages 1/3, 1/2 and 1/1-rack sizes These are the available housing widths of the 7SJ64 relays, referred to a 19” module frame system. This means that previous models can always be replaced. The height is a uniform 244 mm for flush-mounting housings and 266 mm for surfacemounting housings for all housing widths. All cables can be connected with or without ring lugs. Plug-in terminals are available as an option. It is thus possible to employ prefabricated cable harnesses. In the case of surface mounting on a panel, the connection terminals are located above and below in the form of screw- type terminals. The communication interfaces are located in a sloped case at the top and bottom of the housing. The housing can also be supplied optionally with a detached operator panel (refer to Fig. 5/168), or without operator panel, in order to allow optimum operation for all types of applications.
  • 9. Protection functions Time-overcurrent protection This function is based on the phase-selective measurement of the three phase currents and the earth current (four transformers). Three definite-time overcurrent protection elements (DMT) exist both for the phases and for the earth. The current threshold and the delay time can be set in a wide range. In addition, inverse-time overcurrent protection characteristics (IDMTL) can be activated. The inverse-time function provides – as an option – voltage-restraint or voltage-controlled operating modes. With the "flexible protection functions", further definite-time overcurrent stages can be implemented in the 7SJ64 unit.
  • 10. Functions Motor control The SIPROTEC 4 7SJ64 with high performance relays is well-suited for direct activation of the circuit-breaker, disconnector and earthing switch operating mechanisms in automated substations. Chatter disable Chatter disable feature evaluates whether, in a configured period of time, the number of status changes of indication input exceeds a specified figure. If exceeded, the indication input is blocked for a certain period, so that the event list will not record excessive operations. Indication derivation A further indication (or a command) can be derived from an existing indication. Group indications can also be formed. The volume of information to the system interface can thus be reduced and restricted to the most important signals.
  • 11. Communication In terms of communication, the units offer substantial flexibility in the context of connection to industrial and power automation standards. Communication can be extended or added on thanks to modules for retrofitting on which the common protocols run. Therefore, also in the future it will be possible to optimally integrate units into the changing communication infrastructure, for example in Ethernet networks (which will also be used increasingly in the power supply sector in the years to come). Serial front interface There is a serial RS232 interface on the front of all the units. All of the unit’s functions can be set on a PC by means of the DIGSI 4 protection operation program. Rear-mounted interfaces A number of communication modules suitable for various applications can be fitted in the rear of the flush-mounting housing. PROFIBUS-DP protocol PROFIBUS-DP is the most widespread protocol in industrial automation. Via PROFIBUS-DP, SIPROTEC units make their information available to a SIMATIC controller or, in the control direction, receive commands from a central SIMATIC. Measured values can also be transferred
  • 14. Mob No: Mr. Piyush Rathi- +91-9819614841 Website: www.reliservsolution.com Email-ID: piyush@reliserv.in sales1@reliserv.in Address: Office No: 9, Space Heights, Plot No. 53/54 , Sector 34, Kamothe,Navi Mumbai- 410209 Contact us