www.usa.siemens.com/techtopics
TechTopics No. 43
Interposing relay requirements
Answers for infrastructure.
A few salient points extracted from ANSI/IEEE C37.90 are:
	 5.7.1 Tripping output performance requirements:
	“Tripping output circuits shall meet the following
specification for performance: The contacts or output circuit
shall make and carry 30 A for at least 2000 operations in
a duty cycle... The load shall be resistive for both dc and
ac and the current shall be interrupted by independent
means…”
	 5.7.2 Continuous and interrupting ratings of tripping
output circuits:
“Tripping output contacts intended by the manufacturer to
be for tripping duty only shall be identified as such and may
have no continuous or interrupting duty…”
The requirement in ANSI/IEEE C37.90 for a making capability of
30 A is appropriate for older design circuit breakers. However,
the operating currents of modern circuit breakers are often
much lower than those of the historic designs, as indicated in
the table for the type GMSG circuit breaker above.
Remote control of circuit breakers is becoming much more
prevalent as the use of monitoring and central control
equipment grows. When remote control is used, interposing
relays are generally required to avoid a large voltage drop in
the close and trip coil circuits. Here are a few thoughts on the
proper selection of interposing relays.
Current ratings
Interposing relay contacts used in close and trip circuits must
have the ability to make and carry the current of the close
and trip coils. For our type GMSG circuit breakers, the control
current data is as follows:
The interposing relay contact is directly analogous to a tripping
output contact on a protective relay, so it is instructive to
review the requirements of ANSI/IEEE C37.90 for tripping
output contacts of protective relays.
Control voltage and current
Nominal rated control voltage Control voltage range Close coil current (A) Trip coil current (A)
Close Trip
48 Vdc 38-56 28-56 2.9 11.4/301
125 Vdc 100-140 70-140 1.0 4.8/7.41
250 Vdc 200-280 140-280 0.5 2.1/4.21
120 Vac 104-127 104-127 0.9 ---
240 Vac 208-254 208-254 0.4 ---
Footnote:	
1
First value is for five-cycle (83 ms) rated interrupting time, second value is for three-cycle (50 ms) rated interrupting time.
The philosophy embodied in ANSI/IEEE C37.90 is appropriate
for the application to tripping of circuit breakers, and
similar logic applies to application of interposing relays in
closing circuits. The interposing relay has to have a making
capability, but does not have to have a significant interrupting
capacity. This is so because the close and trip coil currents
are interrupted by the “a” or “b” switch contacts on the circuit
breaker.
Therefore, the interposing relay should be able to make the
current of the close or trip coil of the circuit breaker. The
contacts also need to be able to carry the current for the time
necessary for circuit breaker operation, but this is not a severe
requirement. The duration of the closing or tripping current
with modern circuit breakers is several tens of milliseconds,
so the relay is not required to carry the current for a long
time. The interposing relay contacts do not need to be able to
interrupt the coil currents.
Typical interposing relays
A wide variety of relays are suitable for use in interposing
relay applications. The most extensively-used relays over the
decades are the GE type HFA and Westinghouse (ABB) type
SG relays. These are older designs, and take somewhat more
space than newer relays, but have a long record of success.
More recently, a number of smaller relays have been used for
interposing applications. Among these are relays from Potter
 Brumfield (KRP), Struthers  Dunn (219) and even some of
the miniature (“ice cube”) relays from several suppliers. Any of
these relays are suitable provided they meet the voltage and
current requirements of the application.
Typical control scheme
The basic elements of typical controls are shown in the
schematic diagram. A few observations on the control scheme:
	Interposing relays are connected to the same control voltage
supply as is used for the circuit breaker. Many contacts
used to initiate remote closing or tripping, particularly PLC
contacts, cannot handle the higher control voltages (e.g.,
125 Vdc) used in the circuit breaker control scheme. In such
cases, the interposing relay coil should be connected to the
lower control voltage of the PLC (typically, 24 Vdc), and
actuated by the contact from the PLC. The interposing relay
output contact should be connected in the circuit breaker
control circuit.
	Interposing relay contacts must provide a signal duration
of at least 50 ms. Latched-type relays must not be used.
Maintained contacts must never be used to actuate a circuit
breaker close or trip circuit.
	The interposing relay coil should have a very low operating
current, to minimize voltage drop in the control circuit from
the remote actuating contact to the interposing relay coil.
	The minimum pickup voltage for the interposing relay must
be compatible with the minimum control voltage specified
in ANSI/IEEE standards for the switchgear. For dc tripping
circuits, the control voltage range in ANSI/IEEE C37.06 is
56 percent to 112 percent of the rated voltage. For example,
the range for 125 Vdc circuits is 70 to 140 Vdc. In contrast,
the control voltage range given in ANSI/IEEE C37.90 for
protective relays is 80 percent to 112 percent of rated
voltage, or 100 to 140 Vdc for our example.
	In this scheme, the circuit includes truck-operated cell (TOC)
contacts responsive to the position of the circuit breaker
in the cell. These contacts are used to make the local
control switch close contact (CS/C) operative only in the
TEST position. The local control switch trip contact (CS/T) is
operative in both the TEST and CONNECTED position. The
TOC contacts are used to make the remote control contacts
(201T and 201C) operative only in the CONNECTED position.
Most users prefer that remote control contacts be operative
only in the CONNECTED position. User preferences are less
pronounced regarding local control circuits, with some
users desiring that local circuits be operable only in the TEST
position, and others desiring that local control circuits be
operable in both CONNECTED and TEST positions.
The information provided in this document contains merely general
descriptions or characteristics of performance which in case of actual
use do not always apply as described or which may change as a result of
further development of the products. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the terms
of contract.
All product designations may be trademarks or product names of
Siemens AG or supplier companies whose use by third parties for their
own purposes could violate the rights of the owners.
Siemens Industry, Inc.
7000 Siemens Road
Wendell, NC 27591
Subject to change without prior notice.
Order No.: E50001-F710-A331-X-4A00
All rights reserved.
© 2012 Siemens Industry, Inc.
For more information, contact: +1 (800) 347-6659
www.usa.siemens.com/techtopics
Symbols
52/a Aux switch (open when CB open)
52/b Aux switch (closed when CB open)
52SRC Close coil
52T Trip coil
CS/C Control switch (local) close contact
CS/T Control switch (local) trip contact
RL Red indicating lamp
GL Green indicating lamp
201C Interposing relay, close
201T Interposing relay, trip
TOC/a
Truck operated cell switch, closed when CB in
connected position
TOC/b
Truck operated cell switch, open when CB in
connected position
LS Limit switch (spring charged)

More Related Content

PPT
Switchgear Installation Precomissioning Inspection.PPT
PDF
891 Switchboard vs. 1558 Switchgear
PDF
Example of Substation Maintenance & Assessment Audits for Training - Niels In...
PDF
MV MetalClad Switchgear
PDF
Practical handbook-for-relay-protection-engineers
PPT
General Or Gc Electrical Safety
PDF
Lv motor control_products_pricelist_w.e.f_1st_oct_2016
PDF
Lv power distribution_products_pricelist_w.e.f_1st_oct_2016
Switchgear Installation Precomissioning Inspection.PPT
891 Switchboard vs. 1558 Switchgear
Example of Substation Maintenance & Assessment Audits for Training - Niels In...
MV MetalClad Switchgear
Practical handbook-for-relay-protection-engineers
General Or Gc Electrical Safety
Lv motor control_products_pricelist_w.e.f_1st_oct_2016
Lv power distribution_products_pricelist_w.e.f_1st_oct_2016

What's hot (18)

PDF
Relay Setting Calculation For REF615/ REJ601
PDF
Kde200 user manual
PDF
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
PDF
Standing type outdoor full sf6 gas insualted ring main unit
PDF
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
PDF
Selective Coordination
PDF
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
PDF
Equipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
PDF
Fuji sc and sw series contactors
PDF
03 - Control Relays & Timer - Fuji Electric
PDF
Selective Coordination "The Rest of the Story"
PDF
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
PDF
KYN28 12kV Medium voltage metal clad switchgear
PDF
36kV high voltage drawout VCB type switchgear
PDF
01 - Contactor - Fuji Electric
PDF
PDF
Training Adobe
PDF
Catalog Contactor Fuji Electric - Beeteco.com
Relay Setting Calculation For REF615/ REJ601
Kde200 user manual
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Standing type outdoor full sf6 gas insualted ring main unit
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
Selective Coordination
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
Equipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
Fuji sc and sw series contactors
03 - Control Relays & Timer - Fuji Electric
Selective Coordination "The Rest of the Story"
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
KYN28 12kV Medium voltage metal clad switchgear
36kV high voltage drawout VCB type switchgear
01 - Contactor - Fuji Electric
Training Adobe
Catalog Contactor Fuji Electric - Beeteco.com
Ad

Similar to Ansi mv tech_topics43_en (20)

PDF
1MRK508015-BEN_en_H_Auxiliary signalling and tripping relays RXMA 1 RXMA 2 RX...
PPSX
Electrical Basics-VBR
PPTX
Switc gear protection power point resentatiin
PPTX
Protective relay
PPT
34866616-Relay.ppt
DOCX
Relay Switch
PDF
protection11.pdf matireial of protiction
PPTX
Power System Protection and Testing of Electrical Equipment.pptx
DOCX
780063
DOCX
780063
DOCX
780063
PDF
CDG_11.PDF
PPTX
Electrical basics
PDF
Optocoupler & Relay Modules | Relay Connection | WAGO India
PDF
Types of Relay - Which One Should You Use
PDF
Timing functions
PDF
Abb trip ckt supervision relay
PPTX
BHH POWER PLANT ppt.pptx
PDF
PLC: Power PCB Relay de 5V OMRON
1MRK508015-BEN_en_H_Auxiliary signalling and tripping relays RXMA 1 RXMA 2 RX...
Electrical Basics-VBR
Switc gear protection power point resentatiin
Protective relay
34866616-Relay.ppt
Relay Switch
protection11.pdf matireial of protiction
Power System Protection and Testing of Electrical Equipment.pptx
780063
780063
780063
CDG_11.PDF
Electrical basics
Optocoupler & Relay Modules | Relay Connection | WAGO India
Types of Relay - Which One Should You Use
Timing functions
Abb trip ckt supervision relay
BHH POWER PLANT ppt.pptx
PLC: Power PCB Relay de 5V OMRON
Ad

Recently uploaded (20)

PDF
Improvement effect of pyrolyzed agro-food biochar on the properties of.pdf
PDF
Exploratory_Data_Analysis_Fundamentals.pdf
PPTX
ASME PCC-02 TRAINING -DESKTOP-NLE5HNP.pptx
PPTX
Fundamentals of safety and accident prevention -final (1).pptx
PPTX
CyberSecurity Mobile and Wireless Devices
PPTX
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
PPTX
tack Data Structure with Array and Linked List Implementation, Push and Pop O...
PPTX
Fundamentals of Mechanical Engineering.pptx
PPTX
Feature types and data preprocessing steps
PDF
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PPTX
communication and presentation skills 01
PDF
III.4.1.2_The_Space_Environment.p pdffdf
PDF
distributed database system" (DDBS) is often used to refer to both the distri...
PDF
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
PPT
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
PDF
Visual Aids for Exploratory Data Analysis.pdf
PDF
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
PDF
Soil Improvement Techniques Note - Rabbi
PDF
SMART SIGNAL TIMING FOR URBAN INTERSECTIONS USING REAL-TIME VEHICLE DETECTI...
Improvement effect of pyrolyzed agro-food biochar on the properties of.pdf
Exploratory_Data_Analysis_Fundamentals.pdf
ASME PCC-02 TRAINING -DESKTOP-NLE5HNP.pptx
Fundamentals of safety and accident prevention -final (1).pptx
CyberSecurity Mobile and Wireless Devices
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
tack Data Structure with Array and Linked List Implementation, Push and Pop O...
Fundamentals of Mechanical Engineering.pptx
Feature types and data preprocessing steps
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
communication and presentation skills 01
III.4.1.2_The_Space_Environment.p pdffdf
distributed database system" (DDBS) is often used to refer to both the distri...
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
Visual Aids for Exploratory Data Analysis.pdf
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
Soil Improvement Techniques Note - Rabbi
SMART SIGNAL TIMING FOR URBAN INTERSECTIONS USING REAL-TIME VEHICLE DETECTI...

Ansi mv tech_topics43_en

  • 1. www.usa.siemens.com/techtopics TechTopics No. 43 Interposing relay requirements Answers for infrastructure. A few salient points extracted from ANSI/IEEE C37.90 are: 5.7.1 Tripping output performance requirements: “Tripping output circuits shall meet the following specification for performance: The contacts or output circuit shall make and carry 30 A for at least 2000 operations in a duty cycle... The load shall be resistive for both dc and ac and the current shall be interrupted by independent means…” 5.7.2 Continuous and interrupting ratings of tripping output circuits: “Tripping output contacts intended by the manufacturer to be for tripping duty only shall be identified as such and may have no continuous or interrupting duty…” The requirement in ANSI/IEEE C37.90 for a making capability of 30 A is appropriate for older design circuit breakers. However, the operating currents of modern circuit breakers are often much lower than those of the historic designs, as indicated in the table for the type GMSG circuit breaker above. Remote control of circuit breakers is becoming much more prevalent as the use of monitoring and central control equipment grows. When remote control is used, interposing relays are generally required to avoid a large voltage drop in the close and trip coil circuits. Here are a few thoughts on the proper selection of interposing relays. Current ratings Interposing relay contacts used in close and trip circuits must have the ability to make and carry the current of the close and trip coils. For our type GMSG circuit breakers, the control current data is as follows: The interposing relay contact is directly analogous to a tripping output contact on a protective relay, so it is instructive to review the requirements of ANSI/IEEE C37.90 for tripping output contacts of protective relays. Control voltage and current Nominal rated control voltage Control voltage range Close coil current (A) Trip coil current (A) Close Trip 48 Vdc 38-56 28-56 2.9 11.4/301 125 Vdc 100-140 70-140 1.0 4.8/7.41 250 Vdc 200-280 140-280 0.5 2.1/4.21 120 Vac 104-127 104-127 0.9 --- 240 Vac 208-254 208-254 0.4 --- Footnote: 1 First value is for five-cycle (83 ms) rated interrupting time, second value is for three-cycle (50 ms) rated interrupting time.
  • 2. The philosophy embodied in ANSI/IEEE C37.90 is appropriate for the application to tripping of circuit breakers, and similar logic applies to application of interposing relays in closing circuits. The interposing relay has to have a making capability, but does not have to have a significant interrupting capacity. This is so because the close and trip coil currents are interrupted by the “a” or “b” switch contacts on the circuit breaker. Therefore, the interposing relay should be able to make the current of the close or trip coil of the circuit breaker. The contacts also need to be able to carry the current for the time necessary for circuit breaker operation, but this is not a severe requirement. The duration of the closing or tripping current with modern circuit breakers is several tens of milliseconds, so the relay is not required to carry the current for a long time. The interposing relay contacts do not need to be able to interrupt the coil currents. Typical interposing relays A wide variety of relays are suitable for use in interposing relay applications. The most extensively-used relays over the decades are the GE type HFA and Westinghouse (ABB) type SG relays. These are older designs, and take somewhat more space than newer relays, but have a long record of success. More recently, a number of smaller relays have been used for interposing applications. Among these are relays from Potter Brumfield (KRP), Struthers Dunn (219) and even some of the miniature (“ice cube”) relays from several suppliers. Any of these relays are suitable provided they meet the voltage and current requirements of the application. Typical control scheme The basic elements of typical controls are shown in the schematic diagram. A few observations on the control scheme: Interposing relays are connected to the same control voltage supply as is used for the circuit breaker. Many contacts used to initiate remote closing or tripping, particularly PLC contacts, cannot handle the higher control voltages (e.g., 125 Vdc) used in the circuit breaker control scheme. In such cases, the interposing relay coil should be connected to the lower control voltage of the PLC (typically, 24 Vdc), and actuated by the contact from the PLC. The interposing relay output contact should be connected in the circuit breaker control circuit. Interposing relay contacts must provide a signal duration of at least 50 ms. Latched-type relays must not be used. Maintained contacts must never be used to actuate a circuit breaker close or trip circuit. The interposing relay coil should have a very low operating current, to minimize voltage drop in the control circuit from the remote actuating contact to the interposing relay coil. The minimum pickup voltage for the interposing relay must be compatible with the minimum control voltage specified in ANSI/IEEE standards for the switchgear. For dc tripping circuits, the control voltage range in ANSI/IEEE C37.06 is 56 percent to 112 percent of the rated voltage. For example, the range for 125 Vdc circuits is 70 to 140 Vdc. In contrast, the control voltage range given in ANSI/IEEE C37.90 for protective relays is 80 percent to 112 percent of rated voltage, or 100 to 140 Vdc for our example. In this scheme, the circuit includes truck-operated cell (TOC) contacts responsive to the position of the circuit breaker in the cell. These contacts are used to make the local control switch close contact (CS/C) operative only in the TEST position. The local control switch trip contact (CS/T) is operative in both the TEST and CONNECTED position. The TOC contacts are used to make the remote control contacts (201T and 201C) operative only in the CONNECTED position. Most users prefer that remote control contacts be operative only in the CONNECTED position. User preferences are less pronounced regarding local control circuits, with some users desiring that local circuits be operable only in the TEST position, and others desiring that local control circuits be operable in both CONNECTED and TEST positions.
  • 3. The information provided in this document contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners. Siemens Industry, Inc. 7000 Siemens Road Wendell, NC 27591 Subject to change without prior notice. Order No.: E50001-F710-A331-X-4A00 All rights reserved. © 2012 Siemens Industry, Inc. For more information, contact: +1 (800) 347-6659 www.usa.siemens.com/techtopics Symbols 52/a Aux switch (open when CB open) 52/b Aux switch (closed when CB open) 52SRC Close coil 52T Trip coil CS/C Control switch (local) close contact CS/T Control switch (local) trip contact RL Red indicating lamp GL Green indicating lamp 201C Interposing relay, close 201T Interposing relay, trip TOC/a Truck operated cell switch, closed when CB in connected position TOC/b Truck operated cell switch, open when CB in connected position LS Limit switch (spring charged)