Automatic Transfer Switch (ATS)
EE 50 – ELECTRICAL EQUIPMENT
AND DEVICE

MARK ANTHONY B. ENOY
BS EE - V

ENGR. KARRLOU C. RODA
INSTRUCTOR
Transfer Switch
A transfer switch is an electrical
switch that switches a load
between two sources.
Manual transfer switch
Automatic Transfer
Switch
Manual transfer switch
- an operator affects the
transfer by throwing a switch.
 Automatic Transfer Switch
- An ATS is a device designed to
Automatically switch (transfer)
between (2 or 3) sources of power to
improve the reliability of the
electrical supply to a connected
load.

- It automatically switches when
it senses one of the sources has
lost or gained power. Current
range up to 4000 Amperes.
Automatic Transfer Switch
Automatic transfer switch (ats)
Automatic transfer switch (ats)
Automatic transfer switch (ats)
Automatic transfer switch (ats)
Automatic transfer switch (ats)
Automatic transfer switch (ats)
Automatic transfer switch (ats)
Automatic transfer switch (ats)
Automatic transfer switch (ats)
Automatic transfer switch (ats)
Operation of an Automatic Transfer Switch

Not only does ATS transfer the
load to the backup generator but
also it commands the backup
generator to start, based on the
voltage monitored on the primary
supply.
Example: ATS installed in homes

In a home equipped with a backup
generator and an ATS, when an electric
utility outage occurs, the ATS will tell
the backup generator to start. Once the
ATS sees that the generator is ready to
provide electric power, the ATS breaks
the home's connection to the electric
utility and connects the generator to the
home's main electrical panel.
Example: ATS installed in homes
Example: ATS installed in homes

The generator supplies power to the
home's electric load, but is not
connected to the electric utility
lines. It is necessary to isolate the
generator from the distribution
system to protect the generator
from overload in powering loads
beyond the house and for safety, as
utility workers expect the lines to
be dead.
Example: ATS installed in homes

When utility power returns for a
minimum time, the ATS will
automatically transfer the house
back to utility power and
command the generator to turn
off, after another specified
amount of "cool down" time
with no load on the generator.
Typical Applications of ATS
 Utility and Engine Generator
- Single unit standby applications
are very common
For facilities with a standby power
system and a single utility feed. The
transfer switch senses when utility
power has been lost, sends a start
signal to the standby generator and
transfers the load.
Utility and Engine Generator
 Utility and Utility
- Dual utility applications are
becoming more common

For use in facilities with redundant
utility feeds but no standby
generator. If one utility feed fails,
the transfer switch automatically
connects the load to the second
utility feed.
Utility and Utility
 Generator and Generator
- Prime power / standby application
For facilities with a prime power
system
using
multiple
on-site
generators. If the primary generator
fails, the transfer switch sends a start
signal to the second generator and then
transfers the load.
Generator and Generator
 Three-source system
For facilities with a standby power
system and two utility feeds. The
utility transfer switch controls the
feeds from the two utilities based on a
pre-established priority. If both utility
feeds fail, the generator transfer
switch sends a start signal to the
standby generator and transfers the
load.
ONE STANDBY POWER SYSTEM AND TWO UTILITY FEEDS
Three-source system :

Another three source system uses a
standby generator in place of the
second utility (dual standby). If the
utility fails, the first transfer switch
sends a start signal to the primary
standby generator and transfers the
load. If the primary standby generator
fails, the transfer switch sends a start
signal to the second generator set and
transfers the load.
TWO STANDBY POWER SYSTEM AND ONE UTILITY FEEDS
Types of ATS Transition
Open transition TS
Closed transition TS
Soft loading TS
Static TS
Open transition TS
An open transition transfer
switch is also called a break
before make transfer switch.
A break before make transfer
switch breaks contact with one
source of power before it makes
contact with another.
It prevents backfeeding from an emergency
generator back into the utility line
Backfeeding occurs when electric power is
being induced into the power grid. Power
flows in an opposite direction.
It can cause utility lineman to be
electrocuted as they work in power lines.
Reverse- power relay opens if backfeeding
occurs in the power lines.
Applications: Emergency, coderequired and optional standby
systems; resistive loads; small
motor loads
Automatic transfer switch (ats)
Open transition TS:

o Knife Blade Switch





Typically Non-Load breaking
Usually Manually Operated
Sometimes motor operated - Is a method of
arc suppression
Low withstand ratings – no
that extinguishes
arc chutes or vents
arcs by
 Low endurance ratings
channeling them
limited life
into chambers
- arc flash happens when electric current
flows through an air gap between
conductors.

above the
contacts.
Closed transition TS
A closed transition transfer switch is
also called a make before break
transfer switch.

A make before break transfer
switch makes contact with another
source before it breaks contact with
the interrupted source.
There are some loads, however,
that are affected by even the
slightest loss of power. There
are also operational conditions
where it may be desirable to
transfer loads with zero
interruption of power when
conditions permit.
For
these
applications,
closed transition transfer
switches can be provided.
With
closed
transition
transfer, the on-site engine
generator set is momentarily
connected in parallel with
the utility source.
This
requires
getting
approval from the local
utility company. The switch
will operate in a makebefore-break mode provided
both sources are acceptable
and synchronized.
Typical parameters determining
synchronization are:
•voltage difference less than 5%
•frequency difference less than 0.2 Hz
- Frequency counter is used to measure frequency

•maximum phase angle between the
sources of 5 electrical degrees
- Is the difference between the phase of a
sinusoidally varying quantity and the phase
of a second quantity which varies
sinusoidally at the same quantity.
Analog Voltage & frequency meter

Digital Generator Frequency & Voltage meter
Closed
Transition
(Make-BeforeBreak Operation)
NOTE: “P” Position indicates
both sources paralleled for 5
cycles

Applications:
Critical power
requirements,
including
hospitals and
data centers
Delayed Transition (center off)
- The delayed transition (center off) switch is
especially suited to applications in which large
inductive loads result in large inrush currents.
The delayed transition allows magnetic fields to
completely collapse before reconnection.
- A time delay between the opening of the
closed contacts and the closing of the open
contacts allows large motor loads to
demagnetize before transfer. This prevents the
severe “bump” caused by switching a rotating
motor (which momentarily acts as a
generator) from one source to another source
that is not in synchronism.
Types of ATS
Construction &
Design
Knife
Blade
Type

Twin
Contactor
Type

Twin
MCCB
Type

Power
Contactor
Type

Static
Transfer
Type
Knife Blade
Closed transition TS

o Twin Contactor
- contactor type is simpler design that is electrically operated
and mechanically held. It operates faster than circuit breaker
transfer switches, which reduces transfer time.








Switching device having 1 position of rest
Returns to position of rest @ loss power (un-latched type) or
add’l latching arrangement to hold position on loss of power
Built using 1 of up to 12 types of contactors under, from
basic contactor to high-capacity motor starters.
Often very basic controller
Mechanical/safety interlock often not available or optional
Variety of operators, from motor to electromagnets
Not a True double throw device - possible to close into both
Sources
Twin Contactor
Closed transition TS
o Twin MCCB (Molded Case Circuit Breaker)
- circuit breaker type has two interlocked circuit breakers,
so only one breaker can be closed any anytime.







2 Position device, typically operated from add-on motors
Built using 1 of up to 2 types of breaker under, from basic
instantaneous-trip type to short-time rated devices.
Mechanical/safety interlock is an add-on, sometimes
optional
Motor operators usually slow, often unreliable for high duty.
Wide range of manf-assigned withstand ratings (low, med,
or high)
Not a True double throw device - possible to close into both
Sources
Twin MCCB (Molded Case Circuit Breaker)
o Power Contactor Type
 Std. Double Throw mechanism - Inherent
mechanical interlock against closing to
both sources
 No add-on interlocks required
 Fewer moving parts
 High Withstand Current ratings to allow
fault clearing coordination
 Integrated Arc quenching components
 Solenoid Operated (very fast)
Power Contactor Type
o Power Contactor ATS - Composition
•
•
•
•

•

•

Arc quenching grids & enclosed arc chutes
Movable contact assembly has 2 pieces, arcing contact
and main current carrying contact.
Arcing contacts make first, break last
Silver alloy contacts
 Resists welding
 Enhanced withstand ratings
“Over center” switching principal to achieve a
mechanically locked position in either Source 1 or 2
High speed solenoid actuated drive assures contact
transfer in 30-50 msec
Power Contactor ATS - Composition
Static/ Solid-State Transfer Type
The static/solid-state ATS lacks the traditional
mechanical transfer switch. Because this unit relies
on SCR or transistor technology, sub-cycle transfers
are possible. Although there is technically a "break"
in load current, the speed of these units prevents
adverse effects to sensitive equipment.
Static Transfer Type









Two live sources required. Solid-state
switching >> no moving parts
Extremely FAST operation, transfer in
less than ¼ cycle.
SCR technology
Typically used on critical loads where 2
reliable and independent power
supplies available, or switching 2 x UPS
Outputs.
Both sources must be in sync
Often cost prohibitive for Standby
applications

E

N
2

1

L
Static Transfer Type
Bypass Isolation Transfer
Allows maintenance to the main
ATS without disconnecting the
load. By having two transfer
switches connected in parallel, the
bypass transfer switch adds
redundancy to the system.
Applications: Critical power and maintenance
requirements, including healthcare and data
center
Bypass Isolation ATS
• Essentially (2) ATS in Parallel, (1)
Automatic Switch (ATS) & (1) Manual
Switch (MTS).
• ATS is withdrawable, similar to
withdrawable CB’s
• (2) redundant paths from each source
to load.
• ATS & MTS are mechanically and
electrically interlocked
– To prevents accidental closure of
both sources
• Bypassing power from Source to Load
permits testing or maintenance of ATS
without interruption to load.
• Available in Open, Delayed, and
Closed Transition
• If power fails while bypassed, Genset
is auto started to permit fast transfer
using MTS.

TWO PATHS FROM
SOURCE TO LOAD

WITHDRAWABLE
ATS

MECHANICAL
INTERLOCKS

FIXED MOUNT MTS
Thank You!
Automatic transfer switch (ats)
CREATIVE MAKER:

MARK ANTHONY B. ENOY
BS EE – 5
SPECIAL THANKS TO MY SPONSORS:

More Related Content

PPT
Grounding systems
PDF
UPS Working, UPS Types
PPTX
Circuit breakers
PPTX
Circuit Breakers for Low Voltage Applications
PDF
EE6702 Protection and Switchgear notes R2013
PDF
Alternator (AC Generator) Synchronizing Panel
PPT
PPTX
switchgear and protection by vala kamlesh
Grounding systems
UPS Working, UPS Types
Circuit breakers
Circuit Breakers for Low Voltage Applications
EE6702 Protection and Switchgear notes R2013
Alternator (AC Generator) Synchronizing Panel
switchgear and protection by vala kamlesh

What's hot (20)

PPTX
PPT ON 33/11KV SUBSTATION
PPTX
Reactive power compensation
PPTX
UNSYMMETRICAL FAULTS IN POWER SYSTEM
PPTX
PPT on 33/11 sub-station uppcl
PPTX
PPTX
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
PPTX
Unit 01 electrical wiring diagrams
PPTX
Power system protection
DOCX
Synchronous condensers
PPTX
Facts devices
PPTX
Line commutated converters
PPTX
Power factor
PPTX
Presentation on substations
DOCX
Switchgear Equipment in a Substation
PPTX
PDF
PPTX
Directional relay & Differential relay.pptx
PDF
Inplant training about 110kv/11kv substation
PPTX
GENERATING OF HIGH ALTERNATING VOLTAGE
PPT ON 33/11KV SUBSTATION
Reactive power compensation
UNSYMMETRICAL FAULTS IN POWER SYSTEM
PPT on 33/11 sub-station uppcl
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
Unit 01 electrical wiring diagrams
Power system protection
Synchronous condensers
Facts devices
Line commutated converters
Power factor
Presentation on substations
Switchgear Equipment in a Substation
Directional relay & Differential relay.pptx
Inplant training about 110kv/11kv substation
GENERATING OF HIGH ALTERNATING VOLTAGE
Ad

Similar to Automatic transfer switch (ats) (20)

DOC
Ats brochure
PPTX
Automatic transfer switch (ats)
PDF
Switch Seamlessly Automatic Transfer Switch Explained.pdf
PDF
Osung catalogue osung-ats
PDF
Switch Seamlessly Automatic Transfer Switch Explained.pdf
PPTX
Automatic Transfer Switches for Critical Infrastructure
PDF
RK Engineering ATS.pdf
PDF
HANCESS ATB CATALOGUE
PPTX
Critical power: Transfer switches and switchgear
PDF
Here’s Why You Can Rely on Automatic Changeover Switches..
PPTX
ATS circuit
PPTX
Group 34 fyp_presentation
PDF
Development and Performance Evaluation of an Intelligent Electric Power Switc...
PDF
Ls catalog thiet bi dien tri mec_alts_catalog_e_0807_dienhathe.vn
PDF
Eaton ats automatic transfer switch ats pwr
PDF
Eaton ATS Automatic Transfer Switch ATS-PWR
PPTX
Substation_equipment_ (1).pptx
PDF
Overview of custom power devices
PDF
Implementation of a Microcontroller Base Single Phase Automatic Changeover
PDF
Fast changeover switch
Ats brochure
Automatic transfer switch (ats)
Switch Seamlessly Automatic Transfer Switch Explained.pdf
Osung catalogue osung-ats
Switch Seamlessly Automatic Transfer Switch Explained.pdf
Automatic Transfer Switches for Critical Infrastructure
RK Engineering ATS.pdf
HANCESS ATB CATALOGUE
Critical power: Transfer switches and switchgear
Here’s Why You Can Rely on Automatic Changeover Switches..
ATS circuit
Group 34 fyp_presentation
Development and Performance Evaluation of an Intelligent Electric Power Switc...
Ls catalog thiet bi dien tri mec_alts_catalog_e_0807_dienhathe.vn
Eaton ats automatic transfer switch ats pwr
Eaton ATS Automatic Transfer Switch ATS-PWR
Substation_equipment_ (1).pptx
Overview of custom power devices
Implementation of a Microcontroller Base Single Phase Automatic Changeover
Fast changeover switch
Ad

More from Mark Anthony Enoy (12)

PPTX
Power quality & demand side management
PPTX
Protective relaying
PDF
CHEMICAL HAZARDS
PDF
The italian physicist alessandro volta 0
PPTX
Zaneco presentation
PPTX
Automatic Transfer Switch (ATS) using Two- Magnetic Contactors With Power- Delay
PDF
PDF
PDF
Transformer Design
PDF
Apartment design
PDF
Wireless electrical power transmission using atmospheric conduction method
PPT
Magnetic materials final
Power quality & demand side management
Protective relaying
CHEMICAL HAZARDS
The italian physicist alessandro volta 0
Zaneco presentation
Automatic Transfer Switch (ATS) using Two- Magnetic Contactors With Power- Delay
Transformer Design
Apartment design
Wireless electrical power transmission using atmospheric conduction method
Magnetic materials final

Recently uploaded (20)

PPTX
SOPHOS-XG Firewall Administrator PPT.pptx
PDF
A novel scalable deep ensemble learning framework for big data classification...
PDF
A comparative analysis of optical character recognition models for extracting...
PDF
NewMind AI Weekly Chronicles - August'25-Week II
PPTX
1. Introduction to Computer Programming.pptx
PDF
Getting Started with Data Integration: FME Form 101
PDF
A comparative study of natural language inference in Swahili using monolingua...
PDF
7 ChatGPT Prompts to Help You Define Your Ideal Customer Profile.pdf
PPTX
OMC Textile Division Presentation 2021.pptx
PDF
Agricultural_Statistics_at_a_Glance_2022_0.pdf
PDF
Building Integrated photovoltaic BIPV_UPV.pdf
PPTX
TechTalks-8-2019-Service-Management-ITIL-Refresh-ITIL-4-Framework-Supports-Ou...
PDF
Approach and Philosophy of On baking technology
PDF
Zenith AI: Advanced Artificial Intelligence
PDF
gpt5_lecture_notes_comprehensive_20250812015547.pdf
PDF
WOOl fibre morphology and structure.pdf for textiles
PDF
Univ-Connecticut-ChatGPT-Presentaion.pdf
PPTX
Tartificialntelligence_presentation.pptx
PPTX
cloud_computing_Infrastucture_as_cloud_p
PDF
Profit Center Accounting in SAP S/4HANA, S4F28 Col11
SOPHOS-XG Firewall Administrator PPT.pptx
A novel scalable deep ensemble learning framework for big data classification...
A comparative analysis of optical character recognition models for extracting...
NewMind AI Weekly Chronicles - August'25-Week II
1. Introduction to Computer Programming.pptx
Getting Started with Data Integration: FME Form 101
A comparative study of natural language inference in Swahili using monolingua...
7 ChatGPT Prompts to Help You Define Your Ideal Customer Profile.pdf
OMC Textile Division Presentation 2021.pptx
Agricultural_Statistics_at_a_Glance_2022_0.pdf
Building Integrated photovoltaic BIPV_UPV.pdf
TechTalks-8-2019-Service-Management-ITIL-Refresh-ITIL-4-Framework-Supports-Ou...
Approach and Philosophy of On baking technology
Zenith AI: Advanced Artificial Intelligence
gpt5_lecture_notes_comprehensive_20250812015547.pdf
WOOl fibre morphology and structure.pdf for textiles
Univ-Connecticut-ChatGPT-Presentaion.pdf
Tartificialntelligence_presentation.pptx
cloud_computing_Infrastucture_as_cloud_p
Profit Center Accounting in SAP S/4HANA, S4F28 Col11

Automatic transfer switch (ats)

  • 1. Automatic Transfer Switch (ATS) EE 50 – ELECTRICAL EQUIPMENT AND DEVICE MARK ANTHONY B. ENOY BS EE - V ENGR. KARRLOU C. RODA INSTRUCTOR
  • 2. Transfer Switch A transfer switch is an electrical switch that switches a load between two sources.
  • 4. Manual transfer switch - an operator affects the transfer by throwing a switch.
  • 5.  Automatic Transfer Switch - An ATS is a device designed to Automatically switch (transfer) between (2 or 3) sources of power to improve the reliability of the electrical supply to a connected load. - It automatically switches when it senses one of the sources has lost or gained power. Current range up to 4000 Amperes.
  • 17. Operation of an Automatic Transfer Switch Not only does ATS transfer the load to the backup generator but also it commands the backup generator to start, based on the voltage monitored on the primary supply.
  • 18. Example: ATS installed in homes In a home equipped with a backup generator and an ATS, when an electric utility outage occurs, the ATS will tell the backup generator to start. Once the ATS sees that the generator is ready to provide electric power, the ATS breaks the home's connection to the electric utility and connects the generator to the home's main electrical panel.
  • 20. Example: ATS installed in homes The generator supplies power to the home's electric load, but is not connected to the electric utility lines. It is necessary to isolate the generator from the distribution system to protect the generator from overload in powering loads beyond the house and for safety, as utility workers expect the lines to be dead.
  • 21. Example: ATS installed in homes When utility power returns for a minimum time, the ATS will automatically transfer the house back to utility power and command the generator to turn off, after another specified amount of "cool down" time with no load on the generator.
  • 23.  Utility and Engine Generator - Single unit standby applications are very common For facilities with a standby power system and a single utility feed. The transfer switch senses when utility power has been lost, sends a start signal to the standby generator and transfers the load.
  • 24. Utility and Engine Generator
  • 25.  Utility and Utility - Dual utility applications are becoming more common For use in facilities with redundant utility feeds but no standby generator. If one utility feed fails, the transfer switch automatically connects the load to the second utility feed.
  • 27.  Generator and Generator - Prime power / standby application For facilities with a prime power system using multiple on-site generators. If the primary generator fails, the transfer switch sends a start signal to the second generator and then transfers the load.
  • 29.  Three-source system For facilities with a standby power system and two utility feeds. The utility transfer switch controls the feeds from the two utilities based on a pre-established priority. If both utility feeds fail, the generator transfer switch sends a start signal to the standby generator and transfers the load.
  • 30. ONE STANDBY POWER SYSTEM AND TWO UTILITY FEEDS
  • 31. Three-source system : Another three source system uses a standby generator in place of the second utility (dual standby). If the utility fails, the first transfer switch sends a start signal to the primary standby generator and transfers the load. If the primary standby generator fails, the transfer switch sends a start signal to the second generator set and transfers the load.
  • 32. TWO STANDBY POWER SYSTEM AND ONE UTILITY FEEDS
  • 33. Types of ATS Transition Open transition TS Closed transition TS Soft loading TS Static TS
  • 34. Open transition TS An open transition transfer switch is also called a break before make transfer switch. A break before make transfer switch breaks contact with one source of power before it makes contact with another.
  • 35. It prevents backfeeding from an emergency generator back into the utility line Backfeeding occurs when electric power is being induced into the power grid. Power flows in an opposite direction. It can cause utility lineman to be electrocuted as they work in power lines. Reverse- power relay opens if backfeeding occurs in the power lines.
  • 36. Applications: Emergency, coderequired and optional standby systems; resistive loads; small motor loads
  • 38. Open transition TS: o Knife Blade Switch     Typically Non-Load breaking Usually Manually Operated Sometimes motor operated - Is a method of arc suppression Low withstand ratings – no that extinguishes arc chutes or vents arcs by  Low endurance ratings channeling them limited life into chambers - arc flash happens when electric current flows through an air gap between conductors. above the contacts.
  • 39. Closed transition TS A closed transition transfer switch is also called a make before break transfer switch. A make before break transfer switch makes contact with another source before it breaks contact with the interrupted source.
  • 40. There are some loads, however, that are affected by even the slightest loss of power. There are also operational conditions where it may be desirable to transfer loads with zero interruption of power when conditions permit.
  • 41. For these applications, closed transition transfer switches can be provided. With closed transition transfer, the on-site engine generator set is momentarily connected in parallel with the utility source.
  • 42. This requires getting approval from the local utility company. The switch will operate in a makebefore-break mode provided both sources are acceptable and synchronized.
  • 43. Typical parameters determining synchronization are: •voltage difference less than 5% •frequency difference less than 0.2 Hz - Frequency counter is used to measure frequency •maximum phase angle between the sources of 5 electrical degrees - Is the difference between the phase of a sinusoidally varying quantity and the phase of a second quantity which varies sinusoidally at the same quantity.
  • 44. Analog Voltage & frequency meter Digital Generator Frequency & Voltage meter
  • 45. Closed Transition (Make-BeforeBreak Operation) NOTE: “P” Position indicates both sources paralleled for 5 cycles Applications: Critical power requirements, including hospitals and data centers
  • 46. Delayed Transition (center off) - The delayed transition (center off) switch is especially suited to applications in which large inductive loads result in large inrush currents. The delayed transition allows magnetic fields to completely collapse before reconnection. - A time delay between the opening of the closed contacts and the closing of the open contacts allows large motor loads to demagnetize before transfer. This prevents the severe “bump” caused by switching a rotating motor (which momentarily acts as a generator) from one source to another source that is not in synchronism.
  • 50. Closed transition TS o Twin Contactor - contactor type is simpler design that is electrically operated and mechanically held. It operates faster than circuit breaker transfer switches, which reduces transfer time.        Switching device having 1 position of rest Returns to position of rest @ loss power (un-latched type) or add’l latching arrangement to hold position on loss of power Built using 1 of up to 12 types of contactors under, from basic contactor to high-capacity motor starters. Often very basic controller Mechanical/safety interlock often not available or optional Variety of operators, from motor to electromagnets Not a True double throw device - possible to close into both Sources
  • 52. Closed transition TS o Twin MCCB (Molded Case Circuit Breaker) - circuit breaker type has two interlocked circuit breakers, so only one breaker can be closed any anytime.       2 Position device, typically operated from add-on motors Built using 1 of up to 2 types of breaker under, from basic instantaneous-trip type to short-time rated devices. Mechanical/safety interlock is an add-on, sometimes optional Motor operators usually slow, often unreliable for high duty. Wide range of manf-assigned withstand ratings (low, med, or high) Not a True double throw device - possible to close into both Sources
  • 53. Twin MCCB (Molded Case Circuit Breaker)
  • 54. o Power Contactor Type  Std. Double Throw mechanism - Inherent mechanical interlock against closing to both sources  No add-on interlocks required  Fewer moving parts  High Withstand Current ratings to allow fault clearing coordination  Integrated Arc quenching components  Solenoid Operated (very fast)
  • 56. o Power Contactor ATS - Composition • • • • • • Arc quenching grids & enclosed arc chutes Movable contact assembly has 2 pieces, arcing contact and main current carrying contact. Arcing contacts make first, break last Silver alloy contacts  Resists welding  Enhanced withstand ratings “Over center” switching principal to achieve a mechanically locked position in either Source 1 or 2 High speed solenoid actuated drive assures contact transfer in 30-50 msec
  • 57. Power Contactor ATS - Composition
  • 58. Static/ Solid-State Transfer Type The static/solid-state ATS lacks the traditional mechanical transfer switch. Because this unit relies on SCR or transistor technology, sub-cycle transfers are possible. Although there is technically a "break" in load current, the speed of these units prevents adverse effects to sensitive equipment.
  • 59. Static Transfer Type       Two live sources required. Solid-state switching >> no moving parts Extremely FAST operation, transfer in less than ¼ cycle. SCR technology Typically used on critical loads where 2 reliable and independent power supplies available, or switching 2 x UPS Outputs. Both sources must be in sync Often cost prohibitive for Standby applications E N 2 1 L
  • 61. Bypass Isolation Transfer Allows maintenance to the main ATS without disconnecting the load. By having two transfer switches connected in parallel, the bypass transfer switch adds redundancy to the system. Applications: Critical power and maintenance requirements, including healthcare and data center
  • 62. Bypass Isolation ATS • Essentially (2) ATS in Parallel, (1) Automatic Switch (ATS) & (1) Manual Switch (MTS). • ATS is withdrawable, similar to withdrawable CB’s • (2) redundant paths from each source to load. • ATS & MTS are mechanically and electrically interlocked – To prevents accidental closure of both sources • Bypassing power from Source to Load permits testing or maintenance of ATS without interruption to load. • Available in Open, Delayed, and Closed Transition • If power fails while bypassed, Genset is auto started to permit fast transfer using MTS. TWO PATHS FROM SOURCE TO LOAD WITHDRAWABLE ATS MECHANICAL INTERLOCKS FIXED MOUNT MTS