Introduction
1.0 Introduction
• Case study location: Subang Parade, SS16, Subang Jaya
• 4 storey high 1,169,038 sq ft mall
Mechanical Ventilation and
Air Conditioning System
AIR CONDITIONING SYSTEM
• Achieve thermal comfort and better
indoor air quality
• Subang Parade Shopping Centre : 4
leveled with over 200 stores
• Requires large amount of cooling
load to distribute the stores evenly
• Centralized air-conditioning system
OPERATING SYSTEM
Cooling Tower Chiller
Air Handling Unit
(AHU)
AirductDiffuserReturn Airduct
ROOFTOP - COOLING TOWER
• Function : to cool the warm
water pumped up by the
condenser
• Using the evaporation of water
to remove process heat
• Located at the rooftop level of
the shopping mall
• To fully utilize the natural
convection
ROOFTOP - COOLING TOWER
• Packaged cooling tower
• Pre-assembled in the factory by
Nihon Spindle
• Design is shaped like a box
• Subang Parade : 6 cooling towers
• Each cooling tower can hold up
to 800 tons of water
bs slides
ROOFTOP - COOLING TOWER
• According to MS 1525 code 8.8 :
“The system design should provide means for balancing the air and water
system such as but not limited to dampers. Temperature and pressure test
connection and balancing valves.”
Fan Stack
CDWR (Condensed
Water Return), from
chilled water loop
CDWS (Condensed
Water), ready to re-
circulate
ROOFTOP - WATER TANK
• Positioned across/opposite of the
cooling tower
• Connected together, installed in case
of water shortage
• To add on/make up the amount of
water lost
PLANT ROOM
• Located outside of the shopping mall
• Includes chillers, compressors, distributor
pumps, condenser pumps, and chiller pumps
• There is a control room inside the plant room
Control Room
Plant Room
Entrance
Door
PLANT ROOM
PLANT ROOM - CHILLED WATER SYSTEM
• Chiller - Condenser (grey), Evaporater (black)
• Back-up tanks for evaporator
• 7 chillers altogether - 4 small (400 tons),
1 medium (800 tons), 2 large (1500 tons)
• According to MS 1525 code 8.11.1 :
“Chiller water pumps circulating chilled water through the
piping system external to the package, and cooling tower
pumps and fans circulating water or air through the condenser
and cooling tower are not to be included in the consideration
of the CDP for the component.”
PLANT ROOM - CHILLED WATER SYSTEM
• Connected with the evaporator
• Piping system that pumps to the
Air Handling Unit (AHU)
• Is covered/wrapped thick - hot
PLANT ROOM
Chilled Water Distribution Pump Condenser Water Pump
CONTROL ROOM - CONTROL PANELS
• Main air-conditioning control desk
• Manually controlled
• Shows the location of each system
• Able to detect which system is not
operating or damaged
bs slides
AIR HANDLING UNIT (AHU) ROOM
• Device that regulates and
circulates air as part of heating,
ventilation, and air-conditioning
system
• Function : supplies cooled air
into the building
• Main components : Air Filters,
Coils, Dampers, Fans, Mixing
Chamber, and Humidifiers
AHU ROOM
• Locations of AHU in lower ground floor
• 67 units of manually operated AHU
• Each AHU controls the air-conditioning
of 5 shops
• The air supplied and return is
approximately 23℃
• AHU will shut down automatically
when fire emergency or manually
stopped by pressing a release button
located in the control room
AHU ROOM - THERMOSTAT
• The supplied air temperature is controlled
by a thermostat
• According to MS 155 code 8.6, Air handling
duct system insulation :
“All ducts, plenums and enclosures installed in or on
buildings should be adequately insulated to prevent
excessive energy losses. Additional insulation with
vapour barriers may be required to prevent
condensation under some conditions.”
AHU ROOM - AIR FILTERS
• Removes impurities (allergens,
dust, dirt particles etc.)
• Prevent damage to coils and fan
AHU ROOM - COOLING COILS
• Coils are made of copper tubes,
copper/aluminium fins (to aid heat
transfer)
• Connected to chiller where water is
supplied through Chilled Water Supply
(CHWS) from chiller
• Warm water returned to chiller
through Chilled Water Return (CHWR)
DIFFUSERS - SUPPLY AIR DIFFUSERS
• Distributes equal amount of air
into the building
• Subang Parade uses 3 types
• Found on the ceiling of offices
and corridors
Multi-direction Diffuser
Linear Slot Diffuser
Cone Diffuser
RETURN AIR GRILLES
• Transports the air back to AHU room
• Covered with metallic grill to cover
the duct behind
• Prevent big objects from entering
the duct that causes damage to AHU
• Larger and lesser in numbers
compared with diffusers
Fire Protection System
Fire Protection System
-Active Fire Protection
• A component that detects and prevents fire by reacting to action or
motion efficiently
-Passive Fire Protection
• A group of systems that helps in contain or slow down the spread of
fire.
Active Fire Protection
-Smoke Detector
• Photoelectric smoke detector functions to
detect fire and sends off warning
• Located at the corridor within the mall
-Fire control room
• Functions to monitor actual situations and
controlling fire alarm system
• Located at ground floor of the mall
Fire Alarm System
-Manual Call Point
• Designed to function by raising the alarm bell manually
• Located at lift lobbies
-Alarm Bell
• Functions to give off warning during events of fire
• Located at lift lobbies
-Fireman’s Switch
• Functions to disengage power from electrical equipment
• Located at staircase and corridor of the mall
Fire Protection System
-Fireman Intercom Station
• Provides communication during emergency incidents
• Located at the emergency staircase and fire control room
-Sprinkler Pump Room
• Functions as main control room for water sprinkler system
• Sprinkler box consisting switches in pump room
-Water Sprinkler System
• Functions to suppress fire in buildings
• Two types which are pendent sprinkler and upright sprinkler
• Located within the corridor of the mall and fire escape stairway
Fire Protection System
-Smoke Extraction Fan
• Functions to extract smoke produced during the events of fire
• Located at the rooftop
-Portable Fire Extinguisher
• Functions to extinguish fires produced in small areas
• ABC dry powder fire extinguishers are being used
• Located at lift lobbies, electrical and machinery rooms, and corridor
within the mall
-Fire Hose Reel
• Functions to extinguish fire by ensuring supply of water
• Located at lift lobbies
Fire Protection System
-Fire Pump Room
• Consists of jockey pump, duty pump, and standby pump
-Jockey Pump
• Functions to control the pressure in sprinkler pipes
-Duty Pump
• Functions to generate enough pressure of water to
maintain the water pumping process
-Standby Pump
• Functions as the same as duty pump
Passive Fire Protection
-Fire Escape Plan
• Functions to show the location of
emergency staircases to provide
faster evacuation
• Located at lift lobbies.
Passive Fire Protection
-Emergency Exit Signage
• Assist occupants within the building to find the
emergency escape route
• Located above every fire door within the mall
-Fire Emergency Staircase
• A special exit that provides faster evacuation
when events of fire occurs
Mechanical Transportation
System
3.1 Escalators
• In Subang Parade, there are 4 floors not
including roof top
• Two types of escalators in Subang Parade:
Crisscross and Parallel escalators
Location of traction elevator
Location of escalators
FIRST FLOOR
BASEMENT FLOOR
3.1 Escalators
1. Crisscross
• 7 crisscross escalators in Subang Parade
• Minimize structural space requirements by “stacking“ escalators that
go in one direction
3.1 Escalators
2. Parallel
• 2 parallel escalators in Subang Parade
• Required more floor space than the crisscross arrangement (less often
used)
3.2 Elevators
-Gear traction elevator is used in Subang Parade
• Function: Carry passengers in a building with
more than 4 storeys
• Total 9 groups serving the whole mall (7 groups
connected directly to car park, 2 groups
connected floors in the mall)
• The major components: Motor (Machine Room),
Lift Car, Landing, Hoistway and Pit
• Travel speed: Up to 500 feet per minute
• Load carrying: Up to 30,000 pound (13,600 Kgs)
3.3 Motor Room (Machine Room)
(a) Geared traction machine
• Function: Ensure high quality, accurate,
smooth ride for the elevator with an
appropriate drive and control system
3.3 Motor Room (Machine Room)
(b) Controller / Control Panel
• Function: Controls and monitor the
operation of the lift which receive signals
from users through car operating panels
• Mounted against the wall
3.3 Motor Room (Machine Room)
( c ) Overspeed Governor
• Function: Bring the car to stop when
car exceeding 40% of the rated
speed
3.4 Lift cars
(a) Door Safety Devices
• It is the passenger detection
devices for the safety and
comfort of users
• 2 types of door safety
devices: Laser and touch
panel
• In Subang Parade, they are
using both devices for their
elevators
3.4 Lift cars
(b) Door Operator
3.4 Lift cars
( c ) Operating Panels
• A panel mounted in the car containing the car
operating control, such as call register buttons,
door open and close, alarm emergency stop and
whatever other buttons or key switches are
required for operation
3.5 LIFT DOOR (LANDING DOOR)
The type of lift door used in Subang Parade is two speed, centre opening.
The elevator in Subang Parade.
3.5 LIFT DOOR (LANDING DOOR)
-Key Switch Panel
• Located at the control room of Subang Parade
• Function: Control the car of the lift when there is an emergency or lift
breakdown occurs
• The passengers can contact the control room through the ring button
in the lift in case of emergency
• Technicians are able to know clearly when emergency or lift
breakdown occurs through the key switch panel
3.5 LIFT DOOR (LANDING DOOR)
Key Switch Panel
Electric Supply System
Blue = High Voltage Room
Green = Transformer Room
Red = Low Voltage Room
Electricity Supply System
 The TNB Power Station then receives electricity flow then transfer to the Vacuum Circuit Breaker
in High Voltage Room.
 Vacuum Circuit Breaker helps to protect the three phase transformer when it is overloaded
 The transformers received 11kV voltage of power and further steps down to 415V before it
transferred to the Low Voltage Room.
 The main switch board in Low Voltage Room received power supply and further distributed to
the rest of sub-switchboard in Subang Parade through riser.
Electricity Distribution
Plan view of High Voltage Room, Transformer Room & Low Voltage Room
High Tension Switchgear
 Switch and control the flow of electricity
within the electrical system.
 Provide protection electrical circuit and
equipment from current overloading,
short circuit current and insulation
failure.
 Receive electricity from TNB and transfer
to Transformers Room
Vacuum Circuit Breaker
 A device that interrupts and electric
circuit to prevent unwarranted
current, caused by a short circuit
 27 set of Vacuum Circuit Breaker
High Voltage Room
Step- down transformers
 stepped down high voltage current from 11kV
to 415V.
 17 transformer in Subang Parade.
 Receive voltage current from High Voltage
Room and distribute lower voltage current to
next room, Low Voltage Room.
 Current temperature is 42˚c, had reached 60˚c
before. Once reach 80˚c the transformer will
start make noise and straight power trip once
reach 90˚c.
Transformers Room
Main Switch Board
 A large assembly of panels which an
incoming-power supply divides into
separate circuits
 Control the entire electricity supply
of the building, distribute power to
sub- switchboard and other system.
 Contains switches, fuses, metering,
air circuit breaker and other
instrumentation.
 Having 3 set of Main Switch Board
Low Voltage Room
Backup System
 Provide sufficient electricity to the building
when there are power failure.
 Using diesel fuel to run.
 Repair once every 2 year
 Maintenance cost about Rm22,000.00 each
time
 For safety purpose, technician are
required to wear protective clothing
before maintenance.
Safety Issue in Electrical System Room
 Fire protection system is
installed in each room with
using a bank of high pressure
spun steel cylinders contained
CO² .
Sub-switch board
 Similar functionality of the main
switch board which is to connect
and disconnect the electric supply
from the main switchboard.
 Located in lower ground level and
distribute electricity to each level
of building through electrical riser.
Red= AHU, 9 nos
Green= A/C, 3 nos
Blue= Elevator, 7 nos
Location of sub-switchboard in lower ground floor
Electrical Components: Electrical conductor(1), Electrical Conduit(2),
Raceway(3) & Electrical riser(4)
(1): Are commonly round cross-section and are
usually made out of metals either copper or
aluminium.
(2): Used to protect the enclosed wiring from
mechanical injury and damage from
surrounding atmosphere
(3): Enclosed component that forms a physical
pathway for electrical wiring
(4): To carry electrical wiring to upper floors in
orderly and distribute them to each floor
Problems and
Recommendations
P1. Inappropriate Wire Installation
• The wiring in conductor pipe are
not sealed up and exposed to the
air
• It might cause rat gnawing the
insulating cover of electrical and
exposing the bare wires,
cockroaches and ants nesting inside
the place
P1. Inappropriate Wire Installation
• An excessive number of wires inside
the trunking make the wiring inside
trunking to be crowded
• The excessive wires in trunking will
build-up of heat inside the trunking
• Household pests and excessive wires
can harm the cabling, which can lead
to electrical faults, shocks or even
fires
R1: Inappropriate Wire Installation
• Connect back the exposed wire with using fire-proof flexible pipe to
protect the exposed wires
• Technician may need to inspect the condition of cable insulation before
connection
• Install additional trunking for the excessive wires in trunking
• Number of cables which drawn into a conduit or trunking should not
exceed 45% of space factor (less than half full of cable)
• The electrical systems require the periodic maintenance in addition to non-
scheduled maintenance in case there are some unpredictable events
• To keep the system operating at an acceptable level of service to the public
P2. Cleanliness of the HVAC System
• Low cleanliness level in HVAC systems will reduce
the life expectancy of the equipment
• Also impacting the indoor air quality and energy
efficiency of the HVAC systems.
• Cleaning should be undertaken whenever visual
inspections indicate that there is substantial visible
mold growth inside ducts
• Ducts are infested with rodents or insects
• They are clogged with excessive amounts of dust
and debris
Duct before cleaning
Duct after cleaning
R2: Cleanliness of the HVAC System
• Using a Rotobrush air duct cleaning
method combines physical scrubbing
to remove dust
• Sanitizing the ducts will help kill off
mold spores and bacteria
• Improve the indoor air quality and
the heating or cooling system is
more efficient
Rotobrush
P3. Condenser Fan Motor
• When it goes bad, the HVAC unit will
often work initially then stop
• A bad motor that suddenly start
working again and if not bolted in
place will spin out of control causing
damage
R3. Condenser Fan Motor
• Check the resistance of it using a meter, if shows high resistance it
should be replaced
• Regular maintenance and checking at least yearly especially in hot
and humid climates, make sure that every bolts in tighten up before
turning it on
• Fans should be checked for alignment and to see whether they are in
a good condition and function well or not
• Request cleaner to clean the fan motors and fan blades
Thank you!

More Related Content

PPTX
Building services presentation subang parade
PPTX
Bs ii presentation finale
PDF
Bs2 presentation
PPTX
BC Comfort ASHRAE 90.1 2010 Envelope Highlights (Christopher Boyzk Architects...
DOCX
Building services report subang parade
PPT
Basic Pneumatics
PPTX
Screw Air Compressors
PPT
CPD Presentation: Pressurisation
Building services presentation subang parade
Bs ii presentation finale
Bs2 presentation
BC Comfort ASHRAE 90.1 2010 Envelope Highlights (Christopher Boyzk Architects...
Building services report subang parade
Basic Pneumatics
Screw Air Compressors
CPD Presentation: Pressurisation

What's hot (20)

PPTX
PPTX
Industrial component cleaning machines manufacturer,supplier in India
PDF
Industrial component cleaning machines manufacturer,supplier in India
PPTX
HVAC Sysems & AHU
PPTX
B&d air compressor promotion(2019)
PPTX
Module 1 heating - steam (wecompress.com)
PDF
Pneumatic 1
PPT
Pneumatic1day
PDF
150519 AS1668 Part 1 Presentation
PDF
CPD Presentation: Car Park Ventilation
PDF
Boiler ppt
PPTX
Classification of Pneumatic Elements Included Valves, Compressor
PPTX
Heat ventilation and air conditioning (hvac)
PDF
Bs ii
PPT
Chapter 49
PDF
Sabardairy Training Report
DOCX
Bs final report
PPTX
Pneumatic Control System & ITS Components
PDF
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
PDF
Building Services : Subang Parade
Industrial component cleaning machines manufacturer,supplier in India
Industrial component cleaning machines manufacturer,supplier in India
HVAC Sysems & AHU
B&d air compressor promotion(2019)
Module 1 heating - steam (wecompress.com)
Pneumatic 1
Pneumatic1day
150519 AS1668 Part 1 Presentation
CPD Presentation: Car Park Ventilation
Boiler ppt
Classification of Pneumatic Elements Included Valves, Compressor
Heat ventilation and air conditioning (hvac)
Bs ii
Chapter 49
Sabardairy Training Report
Bs final report
Pneumatic Control System & ITS Components
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
Building Services : Subang Parade
Ad

Similar to bs slides (20)

PDF
Bs ii presentation slides
PDF
Building Services II Presentation Slides
PDF
Building Services 2
PPTX
Bs ii-presentation
PDF
Building Service 2 Presentation
PPT
CURSO DE AIRE ACONDICIONADO FRÍO CALOR
PPT
copyofmarinepipingsystems-130208164457-phpapp01 (1).ppt
PPT
Jomaray Pulp Packaging, Ana's breeders.ppt
PPTX
hummudity test machine.pptx
PPTX
S3 Lec 6 (Air Distribution) Note
PDF
marine piping system and Pipe Design and Production
PPTX
BUILDING SERVICE GROUP ASSIGNMENT
PPT
Marine piping systems
PDF
6.-Sistem-HVAC (heating, ventilation, and ac).pdf
PDF
Hvac Equipment and Maintenance
PPTX
Hvac System option heat ventilation 1.pptx
PDF
8_fire-protection-systems-(inspection-and-testing)-final-v2c348e169d90f4a50a5...
PPTX
Air conditioning system
PPTX
Basic Concepts of Air Conditionings.pptx
PDF
Basics of HVAC.pdf
Bs ii presentation slides
Building Services II Presentation Slides
Building Services 2
Bs ii-presentation
Building Service 2 Presentation
CURSO DE AIRE ACONDICIONADO FRÍO CALOR
copyofmarinepipingsystems-130208164457-phpapp01 (1).ppt
Jomaray Pulp Packaging, Ana's breeders.ppt
hummudity test machine.pptx
S3 Lec 6 (Air Distribution) Note
marine piping system and Pipe Design and Production
BUILDING SERVICE GROUP ASSIGNMENT
Marine piping systems
6.-Sistem-HVAC (heating, ventilation, and ac).pdf
Hvac Equipment and Maintenance
Hvac System option heat ventilation 1.pptx
8_fire-protection-systems-(inspection-and-testing)-final-v2c348e169d90f4a50a5...
Air conditioning system
Basic Concepts of Air Conditionings.pptx
Basics of HVAC.pdf
Ad

More from kellyxc (20)

DOCX
Bs report
PDF
HE report
DOCX
Bs report final
PDF
building services 1 presentation slides
PPT
Social Psychology video presentation slides - fnbe0315
PPT
Social Psychology comic presentation slides - fnbe 0315
DOC
Ecn30205 course outline september 2015 semester
DOC
Acc30205 new course outline september 2015 semester
DOC
Business Course Outline
DOCX
Introduction to Business Final Assignment Report
DOC
Intro to Business Assignment 2 Charity Drive
DOC
Intro to Business Assignment 1 Business Plan
PDF
Principle of Economics Assignment 1 Report
DOC
Acc30205 basic accounting assignment september 2015
DOC
Ecn30205 economics assignment sept 2015 intake
PPTX
Introduction to Business Assignment 1 Powerpoint
PDF
Basic Accounting Assignment 1 Report
PPTX
Epc oral presentation individual -slides 0315
PDF
Oral presentation individual (september 2015) Brief
DOC
Fnbe march 2015 assignment 2
Bs report
HE report
Bs report final
building services 1 presentation slides
Social Psychology video presentation slides - fnbe0315
Social Psychology comic presentation slides - fnbe 0315
Ecn30205 course outline september 2015 semester
Acc30205 new course outline september 2015 semester
Business Course Outline
Introduction to Business Final Assignment Report
Intro to Business Assignment 2 Charity Drive
Intro to Business Assignment 1 Business Plan
Principle of Economics Assignment 1 Report
Acc30205 basic accounting assignment september 2015
Ecn30205 economics assignment sept 2015 intake
Introduction to Business Assignment 1 Powerpoint
Basic Accounting Assignment 1 Report
Epc oral presentation individual -slides 0315
Oral presentation individual (september 2015) Brief
Fnbe march 2015 assignment 2

Recently uploaded (20)

PPTX
PPT- ENG7_QUARTER1_LESSON1_WEEK1. IMAGERY -DESCRIPTIONS pptx.pptx
PDF
Anesthesia in Laparoscopic Surgery in India
PDF
STATICS OF THE RIGID BODIES Hibbelers.pdf
PDF
Physiotherapy_for_Respiratory_and_Cardiac_Problems WEBBER.pdf
PDF
BÀI TẬP BỔ TRỢ 4 KỸ NĂNG TIẾNG ANH 9 GLOBAL SUCCESS - CẢ NĂM - BÁM SÁT FORM Đ...
PDF
102 student loan defaulters named and shamed – Is someone you know on the list?
PDF
Saundersa Comprehensive Review for the NCLEX-RN Examination.pdf
PPTX
1st Inaugural Professorial Lecture held on 19th February 2020 (Governance and...
PDF
RMMM.pdf make it easy to upload and study
PPTX
Lesson notes of climatology university.
PDF
Complications of Minimal Access Surgery at WLH
PPTX
school management -TNTEU- B.Ed., Semester II Unit 1.pptx
PPTX
Final Presentation General Medicine 03-08-2024.pptx
PPTX
IMMUNITY IMMUNITY refers to protection against infection, and the immune syst...
PPTX
Microbial diseases, their pathogenesis and prophylaxis
PDF
Computing-Curriculum for Schools in Ghana
PDF
Chapter 2 Heredity, Prenatal Development, and Birth.pdf
PDF
The Lost Whites of Pakistan by Jahanzaib Mughal.pdf
PPTX
Introduction_to_Human_Anatomy_and_Physiology_for_B.Pharm.pptx
PDF
01-Introduction-to-Information-Management.pdf
PPT- ENG7_QUARTER1_LESSON1_WEEK1. IMAGERY -DESCRIPTIONS pptx.pptx
Anesthesia in Laparoscopic Surgery in India
STATICS OF THE RIGID BODIES Hibbelers.pdf
Physiotherapy_for_Respiratory_and_Cardiac_Problems WEBBER.pdf
BÀI TẬP BỔ TRỢ 4 KỸ NĂNG TIẾNG ANH 9 GLOBAL SUCCESS - CẢ NĂM - BÁM SÁT FORM Đ...
102 student loan defaulters named and shamed – Is someone you know on the list?
Saundersa Comprehensive Review for the NCLEX-RN Examination.pdf
1st Inaugural Professorial Lecture held on 19th February 2020 (Governance and...
RMMM.pdf make it easy to upload and study
Lesson notes of climatology university.
Complications of Minimal Access Surgery at WLH
school management -TNTEU- B.Ed., Semester II Unit 1.pptx
Final Presentation General Medicine 03-08-2024.pptx
IMMUNITY IMMUNITY refers to protection against infection, and the immune syst...
Microbial diseases, their pathogenesis and prophylaxis
Computing-Curriculum for Schools in Ghana
Chapter 2 Heredity, Prenatal Development, and Birth.pdf
The Lost Whites of Pakistan by Jahanzaib Mughal.pdf
Introduction_to_Human_Anatomy_and_Physiology_for_B.Pharm.pptx
01-Introduction-to-Information-Management.pdf

bs slides

  • 1. Building Services Group Assignment Group members: Elissa Chang 0326909 Boon Li Ying 0323839 Michelle Tung 0324175 Alan Chung JiaZen 0321487 Calvin Wong Ping Ket 0322481 Kiew Chee Yuan 0323297 Tan Jia San 0322406 Lettitia Lois Hiew 0323908 Chin Ke Ni 0324021 Gillian Chong 0323941
  • 3. 1.0 Introduction • Case study location: Subang Parade, SS16, Subang Jaya • 4 storey high 1,169,038 sq ft mall
  • 4. Mechanical Ventilation and Air Conditioning System
  • 5. AIR CONDITIONING SYSTEM • Achieve thermal comfort and better indoor air quality • Subang Parade Shopping Centre : 4 leveled with over 200 stores • Requires large amount of cooling load to distribute the stores evenly • Centralized air-conditioning system
  • 6. OPERATING SYSTEM Cooling Tower Chiller Air Handling Unit (AHU) AirductDiffuserReturn Airduct
  • 7. ROOFTOP - COOLING TOWER • Function : to cool the warm water pumped up by the condenser • Using the evaporation of water to remove process heat • Located at the rooftop level of the shopping mall • To fully utilize the natural convection
  • 8. ROOFTOP - COOLING TOWER • Packaged cooling tower • Pre-assembled in the factory by Nihon Spindle • Design is shaped like a box • Subang Parade : 6 cooling towers • Each cooling tower can hold up to 800 tons of water
  • 10. ROOFTOP - COOLING TOWER • According to MS 1525 code 8.8 : “The system design should provide means for balancing the air and water system such as but not limited to dampers. Temperature and pressure test connection and balancing valves.” Fan Stack CDWR (Condensed Water Return), from chilled water loop CDWS (Condensed Water), ready to re- circulate
  • 11. ROOFTOP - WATER TANK • Positioned across/opposite of the cooling tower • Connected together, installed in case of water shortage • To add on/make up the amount of water lost
  • 12. PLANT ROOM • Located outside of the shopping mall • Includes chillers, compressors, distributor pumps, condenser pumps, and chiller pumps • There is a control room inside the plant room Control Room Plant Room Entrance Door
  • 14. PLANT ROOM - CHILLED WATER SYSTEM • Chiller - Condenser (grey), Evaporater (black) • Back-up tanks for evaporator • 7 chillers altogether - 4 small (400 tons), 1 medium (800 tons), 2 large (1500 tons) • According to MS 1525 code 8.11.1 : “Chiller water pumps circulating chilled water through the piping system external to the package, and cooling tower pumps and fans circulating water or air through the condenser and cooling tower are not to be included in the consideration of the CDP for the component.”
  • 15. PLANT ROOM - CHILLED WATER SYSTEM • Connected with the evaporator • Piping system that pumps to the Air Handling Unit (AHU) • Is covered/wrapped thick - hot
  • 16. PLANT ROOM Chilled Water Distribution Pump Condenser Water Pump
  • 17. CONTROL ROOM - CONTROL PANELS • Main air-conditioning control desk • Manually controlled • Shows the location of each system • Able to detect which system is not operating or damaged
  • 19. AIR HANDLING UNIT (AHU) ROOM • Device that regulates and circulates air as part of heating, ventilation, and air-conditioning system • Function : supplies cooled air into the building • Main components : Air Filters, Coils, Dampers, Fans, Mixing Chamber, and Humidifiers
  • 20. AHU ROOM • Locations of AHU in lower ground floor • 67 units of manually operated AHU • Each AHU controls the air-conditioning of 5 shops • The air supplied and return is approximately 23℃ • AHU will shut down automatically when fire emergency or manually stopped by pressing a release button located in the control room
  • 21. AHU ROOM - THERMOSTAT • The supplied air temperature is controlled by a thermostat • According to MS 155 code 8.6, Air handling duct system insulation : “All ducts, plenums and enclosures installed in or on buildings should be adequately insulated to prevent excessive energy losses. Additional insulation with vapour barriers may be required to prevent condensation under some conditions.”
  • 22. AHU ROOM - AIR FILTERS • Removes impurities (allergens, dust, dirt particles etc.) • Prevent damage to coils and fan
  • 23. AHU ROOM - COOLING COILS • Coils are made of copper tubes, copper/aluminium fins (to aid heat transfer) • Connected to chiller where water is supplied through Chilled Water Supply (CHWS) from chiller • Warm water returned to chiller through Chilled Water Return (CHWR)
  • 24. DIFFUSERS - SUPPLY AIR DIFFUSERS • Distributes equal amount of air into the building • Subang Parade uses 3 types • Found on the ceiling of offices and corridors Multi-direction Diffuser Linear Slot Diffuser Cone Diffuser
  • 25. RETURN AIR GRILLES • Transports the air back to AHU room • Covered with metallic grill to cover the duct behind • Prevent big objects from entering the duct that causes damage to AHU • Larger and lesser in numbers compared with diffusers
  • 27. Fire Protection System -Active Fire Protection • A component that detects and prevents fire by reacting to action or motion efficiently -Passive Fire Protection • A group of systems that helps in contain or slow down the spread of fire.
  • 28. Active Fire Protection -Smoke Detector • Photoelectric smoke detector functions to detect fire and sends off warning • Located at the corridor within the mall -Fire control room • Functions to monitor actual situations and controlling fire alarm system • Located at ground floor of the mall
  • 29. Fire Alarm System -Manual Call Point • Designed to function by raising the alarm bell manually • Located at lift lobbies -Alarm Bell • Functions to give off warning during events of fire • Located at lift lobbies -Fireman’s Switch • Functions to disengage power from electrical equipment • Located at staircase and corridor of the mall
  • 30. Fire Protection System -Fireman Intercom Station • Provides communication during emergency incidents • Located at the emergency staircase and fire control room -Sprinkler Pump Room • Functions as main control room for water sprinkler system • Sprinkler box consisting switches in pump room -Water Sprinkler System • Functions to suppress fire in buildings • Two types which are pendent sprinkler and upright sprinkler • Located within the corridor of the mall and fire escape stairway
  • 31. Fire Protection System -Smoke Extraction Fan • Functions to extract smoke produced during the events of fire • Located at the rooftop -Portable Fire Extinguisher • Functions to extinguish fires produced in small areas • ABC dry powder fire extinguishers are being used • Located at lift lobbies, electrical and machinery rooms, and corridor within the mall -Fire Hose Reel • Functions to extinguish fire by ensuring supply of water • Located at lift lobbies
  • 32. Fire Protection System -Fire Pump Room • Consists of jockey pump, duty pump, and standby pump -Jockey Pump • Functions to control the pressure in sprinkler pipes -Duty Pump • Functions to generate enough pressure of water to maintain the water pumping process -Standby Pump • Functions as the same as duty pump
  • 33. Passive Fire Protection -Fire Escape Plan • Functions to show the location of emergency staircases to provide faster evacuation • Located at lift lobbies.
  • 34. Passive Fire Protection -Emergency Exit Signage • Assist occupants within the building to find the emergency escape route • Located above every fire door within the mall -Fire Emergency Staircase • A special exit that provides faster evacuation when events of fire occurs
  • 36. 3.1 Escalators • In Subang Parade, there are 4 floors not including roof top • Two types of escalators in Subang Parade: Crisscross and Parallel escalators
  • 37. Location of traction elevator Location of escalators FIRST FLOOR BASEMENT FLOOR
  • 38. 3.1 Escalators 1. Crisscross • 7 crisscross escalators in Subang Parade • Minimize structural space requirements by “stacking“ escalators that go in one direction
  • 39. 3.1 Escalators 2. Parallel • 2 parallel escalators in Subang Parade • Required more floor space than the crisscross arrangement (less often used)
  • 40. 3.2 Elevators -Gear traction elevator is used in Subang Parade • Function: Carry passengers in a building with more than 4 storeys • Total 9 groups serving the whole mall (7 groups connected directly to car park, 2 groups connected floors in the mall) • The major components: Motor (Machine Room), Lift Car, Landing, Hoistway and Pit • Travel speed: Up to 500 feet per minute • Load carrying: Up to 30,000 pound (13,600 Kgs)
  • 41. 3.3 Motor Room (Machine Room) (a) Geared traction machine • Function: Ensure high quality, accurate, smooth ride for the elevator with an appropriate drive and control system
  • 42. 3.3 Motor Room (Machine Room) (b) Controller / Control Panel • Function: Controls and monitor the operation of the lift which receive signals from users through car operating panels • Mounted against the wall
  • 43. 3.3 Motor Room (Machine Room) ( c ) Overspeed Governor • Function: Bring the car to stop when car exceeding 40% of the rated speed
  • 44. 3.4 Lift cars (a) Door Safety Devices • It is the passenger detection devices for the safety and comfort of users • 2 types of door safety devices: Laser and touch panel • In Subang Parade, they are using both devices for their elevators
  • 45. 3.4 Lift cars (b) Door Operator
  • 46. 3.4 Lift cars ( c ) Operating Panels • A panel mounted in the car containing the car operating control, such as call register buttons, door open and close, alarm emergency stop and whatever other buttons or key switches are required for operation
  • 47. 3.5 LIFT DOOR (LANDING DOOR) The type of lift door used in Subang Parade is two speed, centre opening. The elevator in Subang Parade.
  • 48. 3.5 LIFT DOOR (LANDING DOOR) -Key Switch Panel • Located at the control room of Subang Parade • Function: Control the car of the lift when there is an emergency or lift breakdown occurs • The passengers can contact the control room through the ring button in the lift in case of emergency • Technicians are able to know clearly when emergency or lift breakdown occurs through the key switch panel
  • 49. 3.5 LIFT DOOR (LANDING DOOR) Key Switch Panel
  • 51. Blue = High Voltage Room Green = Transformer Room Red = Low Voltage Room Electricity Supply System
  • 52.  The TNB Power Station then receives electricity flow then transfer to the Vacuum Circuit Breaker in High Voltage Room.  Vacuum Circuit Breaker helps to protect the three phase transformer when it is overloaded  The transformers received 11kV voltage of power and further steps down to 415V before it transferred to the Low Voltage Room.  The main switch board in Low Voltage Room received power supply and further distributed to the rest of sub-switchboard in Subang Parade through riser. Electricity Distribution
  • 53. Plan view of High Voltage Room, Transformer Room & Low Voltage Room
  • 54. High Tension Switchgear  Switch and control the flow of electricity within the electrical system.  Provide protection electrical circuit and equipment from current overloading, short circuit current and insulation failure.  Receive electricity from TNB and transfer to Transformers Room Vacuum Circuit Breaker  A device that interrupts and electric circuit to prevent unwarranted current, caused by a short circuit  27 set of Vacuum Circuit Breaker High Voltage Room
  • 55. Step- down transformers  stepped down high voltage current from 11kV to 415V.  17 transformer in Subang Parade.  Receive voltage current from High Voltage Room and distribute lower voltage current to next room, Low Voltage Room.  Current temperature is 42˚c, had reached 60˚c before. Once reach 80˚c the transformer will start make noise and straight power trip once reach 90˚c. Transformers Room
  • 56. Main Switch Board  A large assembly of panels which an incoming-power supply divides into separate circuits  Control the entire electricity supply of the building, distribute power to sub- switchboard and other system.  Contains switches, fuses, metering, air circuit breaker and other instrumentation.  Having 3 set of Main Switch Board Low Voltage Room
  • 57. Backup System  Provide sufficient electricity to the building when there are power failure.  Using diesel fuel to run.  Repair once every 2 year  Maintenance cost about Rm22,000.00 each time
  • 58.  For safety purpose, technician are required to wear protective clothing before maintenance. Safety Issue in Electrical System Room  Fire protection system is installed in each room with using a bank of high pressure spun steel cylinders contained CO² .
  • 59. Sub-switch board  Similar functionality of the main switch board which is to connect and disconnect the electric supply from the main switchboard.  Located in lower ground level and distribute electricity to each level of building through electrical riser.
  • 60. Red= AHU, 9 nos Green= A/C, 3 nos Blue= Elevator, 7 nos Location of sub-switchboard in lower ground floor
  • 61. Electrical Components: Electrical conductor(1), Electrical Conduit(2), Raceway(3) & Electrical riser(4) (1): Are commonly round cross-section and are usually made out of metals either copper or aluminium. (2): Used to protect the enclosed wiring from mechanical injury and damage from surrounding atmosphere (3): Enclosed component that forms a physical pathway for electrical wiring (4): To carry electrical wiring to upper floors in orderly and distribute them to each floor
  • 63. P1. Inappropriate Wire Installation • The wiring in conductor pipe are not sealed up and exposed to the air • It might cause rat gnawing the insulating cover of electrical and exposing the bare wires, cockroaches and ants nesting inside the place
  • 64. P1. Inappropriate Wire Installation • An excessive number of wires inside the trunking make the wiring inside trunking to be crowded • The excessive wires in trunking will build-up of heat inside the trunking • Household pests and excessive wires can harm the cabling, which can lead to electrical faults, shocks or even fires
  • 65. R1: Inappropriate Wire Installation • Connect back the exposed wire with using fire-proof flexible pipe to protect the exposed wires • Technician may need to inspect the condition of cable insulation before connection • Install additional trunking for the excessive wires in trunking • Number of cables which drawn into a conduit or trunking should not exceed 45% of space factor (less than half full of cable) • The electrical systems require the periodic maintenance in addition to non- scheduled maintenance in case there are some unpredictable events • To keep the system operating at an acceptable level of service to the public
  • 66. P2. Cleanliness of the HVAC System • Low cleanliness level in HVAC systems will reduce the life expectancy of the equipment • Also impacting the indoor air quality and energy efficiency of the HVAC systems. • Cleaning should be undertaken whenever visual inspections indicate that there is substantial visible mold growth inside ducts • Ducts are infested with rodents or insects • They are clogged with excessive amounts of dust and debris Duct before cleaning Duct after cleaning
  • 67. R2: Cleanliness of the HVAC System • Using a Rotobrush air duct cleaning method combines physical scrubbing to remove dust • Sanitizing the ducts will help kill off mold spores and bacteria • Improve the indoor air quality and the heating or cooling system is more efficient Rotobrush
  • 68. P3. Condenser Fan Motor • When it goes bad, the HVAC unit will often work initially then stop • A bad motor that suddenly start working again and if not bolted in place will spin out of control causing damage
  • 69. R3. Condenser Fan Motor • Check the resistance of it using a meter, if shows high resistance it should be replaced • Regular maintenance and checking at least yearly especially in hot and humid climates, make sure that every bolts in tighten up before turning it on • Fans should be checked for alignment and to see whether they are in a good condition and function well or not • Request cleaner to clean the fan motors and fan blades