COMPARISON ANALYSIS OF SHUNT ACTIVE
FILTER AND TRANSFORMERLESS PARALLEL
HYBRID ACTIVE FILTER
Sakshi Bangia1
, P.R.Sharma2
and Maneesha Garg3
1,2
Department of Electrical Engineering, YMCA University Of Science and
Technology, Faridabad
1
sakshibangia@gmail.com,2
prsharma1966@gmail.com
3
Department of Humanities and Applied Science , YMCA University Of
Science and Technology, Faridabad
Garg_maneesha@yahoo.com
ABSTRACT
This research work presents the comparison analysis of Shunt Active Filter (SAF) with Parallel
Hybrid Active Filter (PHAF). The performances of SAF and PHAF have been analyzed with PI
controllers based on Synchronous Reference Frame theory. In each case, simulation is carried
out for three phase unbalanced non liner load conditions. The advantages of the designed
system and the proposed current reference calculation methods are verified by simulations
using MATLAB Power system Toolbox.
KEYWORDS
Power quality, shunt active filter, transformer-less shunt hybrid active filter, Total Harmonic
Distortion
1. INTRODUCTION
Harmonics are injected in source current due to the application of non-linear load. These
harmonic currents influence the function of other equipment connected on the similar distribution
feeder, including the harmonic producing loads. Among number of solutions conventionally
passive filters offers a low cost solution. They generally offer high series impedance or low shunt
impedance to block the particular harmonic content. However there are certain disadvantages like
fixed compensation characteristics and resonances with the source impedance. Thus in orders to
prevail over the demerits associated with traditional passive filters, Active Power Filters (APF)
have been introduced in recent years. APF plays a vital role for controlling the amount of
harmonic pollution present in a distribution system. They can be connected in series, shunt or
combination of series and shunt with the supply impedance.
Typically shunt APF consists of a three phase voltage source inverter with capacitor on dc side.
For large power applications, it is difficult to implement a low loss and a low cost PWM
374 Computer Science & Information Technology (CS & IT)
converter. When this equipment is connected in shunt to the ac source impedance it is possible to
improve the compensation characteristics of the passive filters in parallel connection [1], [2].This
forms the transformerless Parallel Hybrid Active Filter The aim of PHAF is to mitigate the
problems associated with SAF and passive filters and to complement and enhance their
performance by adding active or passive components to their structure [3].Figure 1 shows the
block diagram of transformerless parallel hybrid filter.
Figure 1. Block Diagram of Parallel Hybrid Active Filter
2. PRINCIPLE OF OPERATION
Hybrid active filters effectively mitigate the problems of a passive and an active filter and provide
cost-effective harmonic compensation, particularly for high-power nonlinear loads [4].The
parallel hybrid filter consists of three phase voltage source inverter with capacitor on the dc side
connected in shunt with the tuned passive filter. Shunt passive filter is a series combination of a
capacitor and a reactor tuned to a specific harmonic frequency. Since nonlinear load contributes
the major contribution of harmonics in the source current mainly due to lower order harmonics
thus tuned filter provides low impedance trap to harmonic. Remaining higher order harmonics
only are to be filtered by shunt active filter; hence its power rating can be reduced The
compensation of harmonics in the source current through enhancement of the compensation
characteristics of the passive filters also eliminates the chances of resonance [5].
The performance of the PHAF depends on the computation of reference compensating signal.
Among many control strategies mentioned for estimating the reference compensating current
Instantaneous Reactive Power (IRP) theory [6, 7] and Synchronous Reference Frame (SRF) are
mostly used. [8].These schemes employ the computation of the reference components through
subtraction of positive sequence fundamental current component from the load/source current.
These control strategies are very attractive for their simplicity and ease of implementation, but
lack in providing adequate solution under extreme or severe condition of fault conditions in
Computer Science & Information Technology (CS & IT) 375
passive filter branch. SRF control technique using proportional integral (PI) type controller are is
implemented to strength the currents of the filter to follow their reference values.
3. SYSTEM CONFIGURATION
A three phase parallel hybrid active filter is implemented for unbalance nonlinear load. The test
system consists of shunt connected active filter with shunt passive LC elements tuned 5th
harmonic frequency which the most prominent frequency is causing the distortion in source
current. Passive filters are designed to result in minimum Root Mean Square (RMS) value of
supply current at full load [9,10]. Proposal of Synchronous Reference Frame theory is included
in [11].
4. DESIGN PARAMETERS OF SHUNT ACTIVE FILTER
A shunt active filter consists of three phase, 6 pulse voltage source inverter. The line-line voltage
is considered as 415V. The design for dc bus capacitor, dc bus voltage and ac inductor are as
follows.
4.1. DC Capacitor Voltage
The minimum dc bus voltage should be greater than twice of the peak of the phase voltage of the
system [13]. The dc bus voltage is calculated as
V dc
=
m
V LL−
3
22
(1)
where, m is the modulation index =1 and is considered as 1 and VLL is the ac line voltage of
three phase source.
4.2. DC Bus Capacitor
The value of dc bus capacitor (Cdc)is given by
taIVVVC dcdcdc
)(3)]()[(
2
1 2
1
2
=− (2)
where, Vdc is the reference dc voltage and Vdc1 is the minimum voltage level of dc bus, a is the
over loading factor taken as 1.2, V is the phase voltage, I is the phase current and t is time by
which the dc bus voltage is to be recovered.
4.3. AC Filter
The ac inductance (Lf) depends on the current ripple icr,p-p, switching frequency fs, dc bus voltage
(Vdc) .Thus Lf is given as
376 Computer Science & Information Technology (CS & IT)
Lf=
if
V
pcrps
dc
a
m
−
12
3
(3)
where, i crp-p ,= 5%
5. DESIGN PARAMETERS OF PASSIVE FILTER
The basic of shunt passive filter is to trap the tuned harmonic component in the source current
using LC circuit. At resonance frequency inductive reactance is equal to that of capacitive
reactance. Hence for single tuned filter, resonance frequency is given by
CL ff
f
π2
1
= (4)
Thus to design the size of capacitor, first step is to fixed the reactive power compensation .Hence
capacitance can be calculated by
filterkVAR
V
X LL
c
.
2
−
= (5)
where VL-L is line –line source voltage
kVAR is the fixed reactive power compensation
6. CONTROL STRATEGY
The main function of the SRF control strategy is to provide high resistance at the fundamental
frequency and also zero impedance is presented to harmonic current flowing in to the passive
filter. [12].The control diagram is shown in Fig 2.
Fig 2 Synchronous Reference Frame Control Scheme
Computer Science & Information Technology (CS & IT) 377
In this three phase load current is transformed into d-q stationary reference frame using Parks
Transformation. Using this fundamental component appears as DC quantities and all other
harmonics are transformed as non-DC quantities. These quantities are not required hence these
can be filter out using low pass filter. The extracted dc components and are transformed back into
a–b–c coordinates to obtain the fundamental components of source currents. To compensate for
the inverter losses PI controller is applied to regulate the DC bus voltage.
The output of PI controller at the dc bus voltage of active filter is considered as the current (iloss)
for meeting its losses.
vkvvkii ndeidndendepdnlossnloss )()1()()1()(
)( +−+= −−
(6)
where, vv ndede )1( −
− is the error between the reference(vdc*) and sensed (vdc) dc
voltage at the nth sampling instant. Kpd and Kid are the proportional and the integral gains of the
dc bus voltage PI controller.
The reference source current is therefore expressed as,
iii lossddd
+=
*
(7)
Similarly PI controller is used to regulate reactive power
vkvvkii nteiqntentepqnqrsnqr )()1()()1()(
)( +−+= −−
(8)
The reference supply quadrature axis current is as
iii qrqdq
+=
*
(9)
where, vvv nsnte )(
*
)(
−= denotes the error between reference (vs*) and actual(vs(n)) terminal
voltage amplitudes at the n sampling instant. Kpq and Kiq are the proportional and the integral
gains of the PI controller.
7. MATLAB IMPLEMENTATION
A three phase transformerless hybrid active filter is implemented using MATLAB Power system
Toolbox. Three phase input source voltage of 415V, 50 Hz frequency with source resistance of
0.2 ohms and inductance of 2mH is considered. A three phase unbalance nonlinear load drawing
5A is considered for simulation. Shunt active filter is constituted of 6 pulse VSI with 2200 e-6F
of capacitance attached to the DC side. A small-rated filter has been included to minimize the
switching ripples at the inverter output. Passive elements of the filter are calculated using the
mathematical relation s considering 50% of fixed reactive compensation. Table1 gives the
detailed parameters of the system.
378 Computer Science & Information Technology (CS & IT)
Table 1. Detailed Parameters of the System.
Parameters Values
Supply voltage 415V (L-L), 50 Hz
Loads: (i) Linear: phase a= 25
Phase b=10 and 80mH
Phase c =10 and 80 mH
(ii) Nonlinear: Three phase
full bridge rectifier drawing
15A
Shunt Active Filter:
Interfacing
Inductance
Lf = 5.5 mH
DC bus capacitance 22000e-6F.
Referenced Dc
voltage
750 V
Tuned Passive Filter C5=129.4e-6F ;L5=3.1mH
8. RESULTS AND DISCUSSION
The performance of the presented SRF control strategy is evaluated using by comparison of pure
shunt active power filter and parallel hybrid power filter. The three phase unbalance nonlinear
load considered here in the present system contains 5th harmonic content as the most prominent
factor which causes the distortion in the source current. Hence the passive elements of the hybrid
filter are tuned for the resonance frequency of 250Hz. The VA rating required for the inverter in
the hybrid filter is much lesser than that required in a pure shunt active filter.
The VA rating required of the inverter in parallel hybrid power active filter is given by
VA rating= 3
22
IV FMAXdc
××
Where I FMAX A13≅ is the maximum filter current.
Also the apparent power rating of nonlinear load is given by
VA rating= IV LrmsSrms
××3
Where VSrms and ILrms are the RMS value of source voltage taken as 415 V and load current taken
as 38A.
The apparent ratio of the parallel hybrid filter and nonlinear load is greatly reduced by 16%.
Another factor which determines the validation of active filters is Total Harmonic Distortion
(THD) is reduced from14.74 % to 2.65 % for phase a. Table II shows the THD for all three
phases for different types of filter. It can be seen from Fig 5 and Table III that parallel hybrid
filter system is able to reduce the 5th harmonic of supply current to 1.68% .The THD of the ac
supply current reduces to 3.27% with pure shunt active power filters alone as the major
component of the load current without any filter is composed of 5th harmonic.
Computer Science & Information Technology (CS & IT) 379
TABLE III Harmonic Current in Percentage of Fundamental Current
5th 7th 11th 13th 17th 19th
Load current 12.76 5.42 3.92 2.23 1.55 0.97
Source current
with Passive Filter
0.20 2.69 2.57 1.64 1.13 0.89
Source current
with Pure Shunt
Active Filter
1.83 0.54 0.64 0.65 0.83 0.05
Source current
with Shunt Hybrid
Active Filter
1.68 1.03 0.23 0.21 0.19 0.13
Figure 3 shows the waveform of load current without filter. Fig 4 and 5 shows the waveform of
source current with pure shunt active filter and parallel hybrid active filter respectively. These
waveforms clearly illustrates that load current is very distorted that implies source current at this
time without filtering is also very distorted . With the application of power filter source currents
can be made sinusoidal .Clearly with the application of parallel hybrid active filter source current
is less distorted and contains less harmonics content as compared to pure shunt active filter. Fig 6
shows the uncompensated and compensated reactive power using parallel hybrid active filter
.Since the passive elements are tuned at fixed 50% compensation, fig 6 clearly validates the
passive parameters of hybrid filter. Fig7 demonstrates the source voltage, source current, load
voltage, load current, DC bus voltage, and filter current for parallel hybrid active filter.
TABLE II THD For Different Phases (in percentage)
Phase
Phase a Phas
e b
Phase
cType of filter
Load current
without filter
14.74 16.27 19.66
Pure shunt active
filter
3.27 4.58 3.75
Parallel hybrid filter 2.65 3.15 2.64
380 Computer Science & Information Technology (CS & IT)
Figure 3 Load current
Figure 4 Source Current with Pure Active Filter
Figure 4 Source Current with Parallel Hybrid Active Filter
Figure 6 Load Reactive Power and Source Reactive power using parallel Hybrid Active Filter
Computer Science & Information Technology (CS & IT) 381
Figure 7 Source Voltage, Source Current, Load Voltage, Load Current, DC Bus Voltage, Filter Current.
9. CONCLUSIONS
In this work, concept of transformerless parallel hybrid active filter is defined and verified by
MATLAB simulation. Simulation results verify that presented method has good performance in
the elimination of selective harmonic content and Total Harmonic Distortion. It has much better
dynamic response with less rating compared with the pure shunt active filter.
REFERENCES
[1] B. Singh, K. Al-Haddad, and A. Chandra, “A review of active filters for power quality improvement,”
IEEE Trans. Ind. Electron., vol. 46, no. 5, pp. 960–971, Oct. 1999.
[2] J.W. Dixon, G. Venegas, and L. A.Moran, “A series active power filter based on a sinusoidal current-
controlled voltage-source inverter,” IEEE Trans. Ind. Electron., vol. 44, no. 5, pp. 612–620, Oct.
1997.
[3] Bhattacharya,Divan,”Synchronous Frame based controller implementation for a hybrid series active
filter,Confeence record of IEEE Industry Apllications Conference Vol, 3,pp. 2531-2540 October
1995.
[4] S. Srianthumrong and H. Akagi, “A medium-voltage transformerless AC/DC power conversion
system consisting of a diode rectifier and a shunt hybrid filter,” IEEE Trans. Ind. Appl., vol. 39, no. 3,
pp. 874–882, May/Jun. 2003.
[5] H. Fujita, T. Yamasaki and H. Akagi, "A hybrid active filter for damping of harmonic resonance in
industrial power systems," IEEE Trans. on Power Electronics, vol. 15, no. 2, pp. 215-222, March
2000.
382 Computer Science & Information Technology (CS & IT)
[6] H. Fujita, H. Akagi, "A Practical Approach to Harmonic Compensation in Power Systems-Series
Connection of Passive, Active Filters," IEEE Trans. on Ind.. Appl., vol.27, no.6, pp. 1020-1025,
Nov./Dec. 1991.
[7] F.B. Libano, J.A.Cobos, J. Uceda, "Simplified control strategy for Hybrid Active Filters", IEEE
PESC Record, 1 997, pp 1102-1108.
[8] P.T. Cheng, S. Bhattacharya and D. Divan, "Experimental Verification of Dominant Harmonic Active
Filter for High Power Applications",IEEE Trans. on Ind. Appl., vol. 36, pp.567-577, March/April,
2000.
[9] IEEE Guide for Application and Specification of Harmonic Filters IEEE Std 1531-2003.
[10] V, Verma, S. Shanker, B. Singh, A. Chandra, and Kamal Al- Haddad, "Genetic Algorithm Based
Design of Passive Filters for Offshore Applications," Proc. ofIEEE PCIC '04, 2004, pp 55-62.
[11] S. Bhattacharya, D. Divan and B. Banerjee, “Synchronous frame harmonic isolator using active series
filter,” EPE-Firenze, Vol. 3, pp. 30-35, 1991.
[12] V, Verma, S. Shanker, B. Singh,’Design and Implemention of Current Controlled Parallel Hybrid
Power Filter.
[13] B.N.Singh, P.Rastgoufard, B.Singh, A.Chandra and K.Al.Haddad, “Design,simulation and
implementation of three pole/ four pole topologies for active filters,” IEE Eletr. Power Appl., vol.
151, no. 4, pp. 467-476, July 2004.
Authors
Sakshi Bangia received the B.Tech degree in Instrumentation and Control from MDU
Rohtak and M.Tech degree in Electrical Engg. from YMCA UST in 2004 and 2006,
respectively. She is pursuing Ph.D in Power Quality from Maharishi Dayanand
University, India. Presently she is working as Assistant Professor in Electrical
Engineering Department at YMCA UST Faridabad.
Dr. P.R.Sharma was born in 1966 in India. He is currently working as Chairman of
the Department in Electrical Engg. in YMCA University Of Science and
Technology, Faridabad. He received his B.E Electrical Engineering in 1988 from
Punjab University Chandigarh, M.Tech in Electrical Engineering (Power System)
from Regional Engineering College Kurukshetra in 1990 and Ph.D from
M.D.University Rohtak in 2005. He started his carrier from industry. He has vast
experience in the industry and teaching. His area of interest is Optimal location and
coordinated control of FACTS devices ,power system stability and control
Dr. Maneesha Garg did her Ph.D(Physics) in 2002 from Kurukshetra University,
India. After that she worked as Research Associate granted by CSIR, in NIT
Kurukshetra for 4 years. She has 18 publications in national, international journals
and more than 30 papers in conferences to her credit. Presently she is working as
Assistant Professor in Humanities and Applied Science Department, YMCA UST,
Faridabad and guiding 4 scholars for their research work.

More Related Content

PDF
Cascaded Multilevel Inverter Based Active Power Filters: A Survey of Controls
PDF
International Journal of Engineering Research and Development
PDF
E04501041049
PDF
S25096101
PDF
Comparison of Two Compensation Control Strategies for Shunt Active Power Filt...
PDF
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
PDF
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
PDF
Welcome to International Journal of Engineering Research and Development (IJERD)
Cascaded Multilevel Inverter Based Active Power Filters: A Survey of Controls
International Journal of Engineering Research and Development
E04501041049
S25096101
Comparison of Two Compensation Control Strategies for Shunt Active Power Filt...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
Welcome to International Journal of Engineering Research and Development (IJERD)

What's hot (17)

PDF
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
PDF
Lr3421092114
PDF
Optimize Controlling of Active Filters Controlled by Pi Controller
PDF
Volume 2-issue-6-1950-1954
PDF
K1102016673
PDF
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
PDF
Predictive Approach for Power Quality Improvement Based Direct Power Control
PDF
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
PDF
REDUCTION IN THE TRANSIENT TIME OF SHUNT ACTIVE FILTERS USING INTELLIGENT CON...
PDF
Design of PI and Fuzzy Logic Controllers for Distribution Static Compensator
PDF
Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...
PDF
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
PDF
Comparison of Cascaded H-bridge Inverters for Harmonic Mitigation Considerin...
PDF
IRJET- Power Quality Improvement using Active Power Filter
PDF
Load Flow Analysis of Jamshoro Thermal Power Station (JTPS) Pakistan Using MA...
PPTX
Computer Application in Power system: Chapter two - load flow analysis
PDF
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
Lr3421092114
Optimize Controlling of Active Filters Controlled by Pi Controller
Volume 2-issue-6-1950-1954
K1102016673
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
Predictive Approach for Power Quality Improvement Based Direct Power Control
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
REDUCTION IN THE TRANSIENT TIME OF SHUNT ACTIVE FILTERS USING INTELLIGENT CON...
Design of PI and Fuzzy Logic Controllers for Distribution Static Compensator
Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Comparison of Cascaded H-bridge Inverters for Harmonic Mitigation Considerin...
IRJET- Power Quality Improvement using Active Power Filter
Load Flow Analysis of Jamshoro Thermal Power Station (JTPS) Pakistan Using MA...
Computer Application in Power system: Chapter two - load flow analysis
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
Ad

Similar to COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRID ACTIVE FILTER (20)

PDF
Performance analysis of three phase shunt hybrid active power filter
PDF
Performance analysis of three phase shunt hybrid active power filter
PDF
Pll based shunt active harmonic filter to compensate multiple non linear loads
PDF
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
PDF
Power System Harmonic Compensation Using Shunt Active Power Filter
PDF
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
PPTX
Performance Analysis of Three-phase Four-wire Shunt Active Power Filter
PDF
Performance Investigation of Shunt Active Power Filter Using Hysteresis Curre...
PDF
Harmonic Mitigation using Modified Synchronous Reference Frame Theory
PDF
Improvement of the electric power quality using
PDF
Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...
PDF
A011140104
PDF
IRJET-Shunt Hybrid Active Power Filter for Eradication of Current Harmonics
PDF
POWER QUALITY ENHANCEMENT USING HYBRID ACTIVE POWER FILTER UNDER NON-LINEAR L...
PDF
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
PDF
Mitigation of Harmonic Current through Hybrid Power Filter in Single Phase Re...
PDF
T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...
PDF
Power system harmonic reduction using shunt active filter
PDF
Experimental Comparative Study of Feedback Linearized Controller and Proporti...
PDF
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Performance analysis of three phase shunt hybrid active power filter
Performance analysis of three phase shunt hybrid active power filter
Pll based shunt active harmonic filter to compensate multiple non linear loads
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Power System Harmonic Compensation Using Shunt Active Power Filter
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
Performance Analysis of Three-phase Four-wire Shunt Active Power Filter
Performance Investigation of Shunt Active Power Filter Using Hysteresis Curre...
Harmonic Mitigation using Modified Synchronous Reference Frame Theory
Improvement of the electric power quality using
Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...
A011140104
IRJET-Shunt Hybrid Active Power Filter for Eradication of Current Harmonics
POWER QUALITY ENHANCEMENT USING HYBRID ACTIVE POWER FILTER UNDER NON-LINEAR L...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Mitigation of Harmonic Current through Hybrid Power Filter in Single Phase Re...
T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...
Power system harmonic reduction using shunt active filter
Experimental Comparative Study of Feedback Linearized Controller and Proporti...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Ad

More from cscpconf (20)

PDF
ANALYSIS OF LAND SURFACE DEFORMATION GRADIENT BY DINSAR
PDF
4D AUTOMATIC LIP-READING FOR SPEAKER'S FACE IDENTIFCATION
PDF
MOVING FROM WATERFALL TO AGILE PROCESS IN SOFTWARE ENGINEERING CAPSTONE PROJE...
PDF
PROMOTING STUDENT ENGAGEMENT USING SOCIAL MEDIA TECHNOLOGIES
PDF
A SURVEY ON QUESTION ANSWERING SYSTEMS: THE ADVANCES OF FUZZY LOGIC
PDF
DYNAMIC PHONE WARPING – A METHOD TO MEASURE THE DISTANCE BETWEEN PRONUNCIATIONS
PDF
INTELLIGENT ELECTRONIC ASSESSMENT FOR SUBJECTIVE EXAMS
PDF
TWO DISCRETE BINARY VERSIONS OF AFRICAN BUFFALO OPTIMIZATION METAHEURISTIC
PDF
DETECTION OF ALGORITHMICALLY GENERATED MALICIOUS DOMAIN
PDF
GLOBAL MUSIC ASSET ASSURANCE DIGITAL CURRENCY: A DRM SOLUTION FOR STREAMING C...
PDF
IMPORTANCE OF VERB SUFFIX MAPPING IN DISCOURSE TRANSLATION SYSTEM
PDF
EXACT SOLUTIONS OF A FAMILY OF HIGHER-DIMENSIONAL SPACE-TIME FRACTIONAL KDV-T...
PDF
AUTOMATED PENETRATION TESTING: AN OVERVIEW
PDF
CLASSIFICATION OF ALZHEIMER USING fMRI DATA AND BRAIN NETWORK
PDF
VALIDATION METHOD OF FUZZY ASSOCIATION RULES BASED ON FUZZY FORMAL CONCEPT AN...
PDF
PROBABILITY BASED CLUSTER EXPANSION OVERSAMPLING TECHNIQUE FOR IMBALANCED DATA
PDF
CHARACTER AND IMAGE RECOGNITION FOR DATA CATALOGING IN ECOLOGICAL RESEARCH
PDF
SOCIAL MEDIA ANALYTICS FOR SENTIMENT ANALYSIS AND EVENT DETECTION IN SMART CI...
PDF
SOCIAL NETWORK HATE SPEECH DETECTION FOR AMHARIC LANGUAGE
PDF
GENERAL REGRESSION NEURAL NETWORK BASED POS TAGGING FOR NEPALI TEXT
ANALYSIS OF LAND SURFACE DEFORMATION GRADIENT BY DINSAR
4D AUTOMATIC LIP-READING FOR SPEAKER'S FACE IDENTIFCATION
MOVING FROM WATERFALL TO AGILE PROCESS IN SOFTWARE ENGINEERING CAPSTONE PROJE...
PROMOTING STUDENT ENGAGEMENT USING SOCIAL MEDIA TECHNOLOGIES
A SURVEY ON QUESTION ANSWERING SYSTEMS: THE ADVANCES OF FUZZY LOGIC
DYNAMIC PHONE WARPING – A METHOD TO MEASURE THE DISTANCE BETWEEN PRONUNCIATIONS
INTELLIGENT ELECTRONIC ASSESSMENT FOR SUBJECTIVE EXAMS
TWO DISCRETE BINARY VERSIONS OF AFRICAN BUFFALO OPTIMIZATION METAHEURISTIC
DETECTION OF ALGORITHMICALLY GENERATED MALICIOUS DOMAIN
GLOBAL MUSIC ASSET ASSURANCE DIGITAL CURRENCY: A DRM SOLUTION FOR STREAMING C...
IMPORTANCE OF VERB SUFFIX MAPPING IN DISCOURSE TRANSLATION SYSTEM
EXACT SOLUTIONS OF A FAMILY OF HIGHER-DIMENSIONAL SPACE-TIME FRACTIONAL KDV-T...
AUTOMATED PENETRATION TESTING: AN OVERVIEW
CLASSIFICATION OF ALZHEIMER USING fMRI DATA AND BRAIN NETWORK
VALIDATION METHOD OF FUZZY ASSOCIATION RULES BASED ON FUZZY FORMAL CONCEPT AN...
PROBABILITY BASED CLUSTER EXPANSION OVERSAMPLING TECHNIQUE FOR IMBALANCED DATA
CHARACTER AND IMAGE RECOGNITION FOR DATA CATALOGING IN ECOLOGICAL RESEARCH
SOCIAL MEDIA ANALYTICS FOR SENTIMENT ANALYSIS AND EVENT DETECTION IN SMART CI...
SOCIAL NETWORK HATE SPEECH DETECTION FOR AMHARIC LANGUAGE
GENERAL REGRESSION NEURAL NETWORK BASED POS TAGGING FOR NEPALI TEXT

Recently uploaded (20)

PDF
Supply Chain Operations Speaking Notes -ICLT Program
PDF
LDMMIA Reiki Yoga Finals Review Spring Summer
PDF
medical_surgical_nursing_10th_edition_ignatavicius_TEST_BANK_pdf.pdf
PDF
A GUIDE TO GENETICS FOR UNDERGRADUATE MEDICAL STUDENTS
PDF
Chinmaya Tiranga quiz Grand Finale.pdf
PPTX
Introduction-to-Literarature-and-Literary-Studies-week-Prelim-coverage.pptx
PPTX
Final Presentation General Medicine 03-08-2024.pptx
PPTX
A powerpoint presentation on the Revised K-10 Science Shaping Paper
PDF
Black Hat USA 2025 - Micro ICS Summit - ICS/OT Threat Landscape
PDF
Indian roads congress 037 - 2012 Flexible pavement
PDF
SOIL: Factor, Horizon, Process, Classification, Degradation, Conservation
PPTX
CHAPTER IV. MAN AND BIOSPHERE AND ITS TOTALITY.pptx
PPTX
Orientation - ARALprogram of Deped to the Parents.pptx
PPTX
Digestion and Absorption of Carbohydrates, Proteina and Fats
PDF
Practical Manual AGRO-233 Principles and Practices of Natural Farming
PDF
Paper A Mock Exam 9_ Attempt review.pdf.
PDF
GENETICS IN BIOLOGY IN SECONDARY LEVEL FORM 3
PDF
A systematic review of self-coping strategies used by university students to ...
PDF
Empowerment Technology for Senior High School Guide
PDF
1_English_Language_Set_2.pdf probationary
Supply Chain Operations Speaking Notes -ICLT Program
LDMMIA Reiki Yoga Finals Review Spring Summer
medical_surgical_nursing_10th_edition_ignatavicius_TEST_BANK_pdf.pdf
A GUIDE TO GENETICS FOR UNDERGRADUATE MEDICAL STUDENTS
Chinmaya Tiranga quiz Grand Finale.pdf
Introduction-to-Literarature-and-Literary-Studies-week-Prelim-coverage.pptx
Final Presentation General Medicine 03-08-2024.pptx
A powerpoint presentation on the Revised K-10 Science Shaping Paper
Black Hat USA 2025 - Micro ICS Summit - ICS/OT Threat Landscape
Indian roads congress 037 - 2012 Flexible pavement
SOIL: Factor, Horizon, Process, Classification, Degradation, Conservation
CHAPTER IV. MAN AND BIOSPHERE AND ITS TOTALITY.pptx
Orientation - ARALprogram of Deped to the Parents.pptx
Digestion and Absorption of Carbohydrates, Proteina and Fats
Practical Manual AGRO-233 Principles and Practices of Natural Farming
Paper A Mock Exam 9_ Attempt review.pdf.
GENETICS IN BIOLOGY IN SECONDARY LEVEL FORM 3
A systematic review of self-coping strategies used by university students to ...
Empowerment Technology for Senior High School Guide
1_English_Language_Set_2.pdf probationary

COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRID ACTIVE FILTER

  • 1. Jan Zizka (Eds) : CCSIT, SIPP, AISC, PDCTA - 2013 pp. 373–382, 2013. © CS & IT-CSCP 2013 DOI : 10.5121/csit.2013.3642 COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRID ACTIVE FILTER Sakshi Bangia1 , P.R.Sharma2 and Maneesha Garg3 1,2 Department of Electrical Engineering, YMCA University Of Science and Technology, Faridabad 1 sakshibangia@gmail.com,2 prsharma1966@gmail.com 3 Department of Humanities and Applied Science , YMCA University Of Science and Technology, Faridabad Garg_maneesha@yahoo.com ABSTRACT This research work presents the comparison analysis of Shunt Active Filter (SAF) with Parallel Hybrid Active Filter (PHAF). The performances of SAF and PHAF have been analyzed with PI controllers based on Synchronous Reference Frame theory. In each case, simulation is carried out for three phase unbalanced non liner load conditions. The advantages of the designed system and the proposed current reference calculation methods are verified by simulations using MATLAB Power system Toolbox. KEYWORDS Power quality, shunt active filter, transformer-less shunt hybrid active filter, Total Harmonic Distortion 1. INTRODUCTION Harmonics are injected in source current due to the application of non-linear load. These harmonic currents influence the function of other equipment connected on the similar distribution feeder, including the harmonic producing loads. Among number of solutions conventionally passive filters offers a low cost solution. They generally offer high series impedance or low shunt impedance to block the particular harmonic content. However there are certain disadvantages like fixed compensation characteristics and resonances with the source impedance. Thus in orders to prevail over the demerits associated with traditional passive filters, Active Power Filters (APF) have been introduced in recent years. APF plays a vital role for controlling the amount of harmonic pollution present in a distribution system. They can be connected in series, shunt or combination of series and shunt with the supply impedance. Typically shunt APF consists of a three phase voltage source inverter with capacitor on dc side. For large power applications, it is difficult to implement a low loss and a low cost PWM
  • 2. 374 Computer Science & Information Technology (CS & IT) converter. When this equipment is connected in shunt to the ac source impedance it is possible to improve the compensation characteristics of the passive filters in parallel connection [1], [2].This forms the transformerless Parallel Hybrid Active Filter The aim of PHAF is to mitigate the problems associated with SAF and passive filters and to complement and enhance their performance by adding active or passive components to their structure [3].Figure 1 shows the block diagram of transformerless parallel hybrid filter. Figure 1. Block Diagram of Parallel Hybrid Active Filter 2. PRINCIPLE OF OPERATION Hybrid active filters effectively mitigate the problems of a passive and an active filter and provide cost-effective harmonic compensation, particularly for high-power nonlinear loads [4].The parallel hybrid filter consists of three phase voltage source inverter with capacitor on the dc side connected in shunt with the tuned passive filter. Shunt passive filter is a series combination of a capacitor and a reactor tuned to a specific harmonic frequency. Since nonlinear load contributes the major contribution of harmonics in the source current mainly due to lower order harmonics thus tuned filter provides low impedance trap to harmonic. Remaining higher order harmonics only are to be filtered by shunt active filter; hence its power rating can be reduced The compensation of harmonics in the source current through enhancement of the compensation characteristics of the passive filters also eliminates the chances of resonance [5]. The performance of the PHAF depends on the computation of reference compensating signal. Among many control strategies mentioned for estimating the reference compensating current Instantaneous Reactive Power (IRP) theory [6, 7] and Synchronous Reference Frame (SRF) are mostly used. [8].These schemes employ the computation of the reference components through subtraction of positive sequence fundamental current component from the load/source current. These control strategies are very attractive for their simplicity and ease of implementation, but lack in providing adequate solution under extreme or severe condition of fault conditions in
  • 3. Computer Science & Information Technology (CS & IT) 375 passive filter branch. SRF control technique using proportional integral (PI) type controller are is implemented to strength the currents of the filter to follow their reference values. 3. SYSTEM CONFIGURATION A three phase parallel hybrid active filter is implemented for unbalance nonlinear load. The test system consists of shunt connected active filter with shunt passive LC elements tuned 5th harmonic frequency which the most prominent frequency is causing the distortion in source current. Passive filters are designed to result in minimum Root Mean Square (RMS) value of supply current at full load [9,10]. Proposal of Synchronous Reference Frame theory is included in [11]. 4. DESIGN PARAMETERS OF SHUNT ACTIVE FILTER A shunt active filter consists of three phase, 6 pulse voltage source inverter. The line-line voltage is considered as 415V. The design for dc bus capacitor, dc bus voltage and ac inductor are as follows. 4.1. DC Capacitor Voltage The minimum dc bus voltage should be greater than twice of the peak of the phase voltage of the system [13]. The dc bus voltage is calculated as V dc = m V LL− 3 22 (1) where, m is the modulation index =1 and is considered as 1 and VLL is the ac line voltage of three phase source. 4.2. DC Bus Capacitor The value of dc bus capacitor (Cdc)is given by taIVVVC dcdcdc )(3)]()[( 2 1 2 1 2 =− (2) where, Vdc is the reference dc voltage and Vdc1 is the minimum voltage level of dc bus, a is the over loading factor taken as 1.2, V is the phase voltage, I is the phase current and t is time by which the dc bus voltage is to be recovered. 4.3. AC Filter The ac inductance (Lf) depends on the current ripple icr,p-p, switching frequency fs, dc bus voltage (Vdc) .Thus Lf is given as
  • 4. 376 Computer Science & Information Technology (CS & IT) Lf= if V pcrps dc a m − 12 3 (3) where, i crp-p ,= 5% 5. DESIGN PARAMETERS OF PASSIVE FILTER The basic of shunt passive filter is to trap the tuned harmonic component in the source current using LC circuit. At resonance frequency inductive reactance is equal to that of capacitive reactance. Hence for single tuned filter, resonance frequency is given by CL ff f π2 1 = (4) Thus to design the size of capacitor, first step is to fixed the reactive power compensation .Hence capacitance can be calculated by filterkVAR V X LL c . 2 − = (5) where VL-L is line –line source voltage kVAR is the fixed reactive power compensation 6. CONTROL STRATEGY The main function of the SRF control strategy is to provide high resistance at the fundamental frequency and also zero impedance is presented to harmonic current flowing in to the passive filter. [12].The control diagram is shown in Fig 2. Fig 2 Synchronous Reference Frame Control Scheme
  • 5. Computer Science & Information Technology (CS & IT) 377 In this three phase load current is transformed into d-q stationary reference frame using Parks Transformation. Using this fundamental component appears as DC quantities and all other harmonics are transformed as non-DC quantities. These quantities are not required hence these can be filter out using low pass filter. The extracted dc components and are transformed back into a–b–c coordinates to obtain the fundamental components of source currents. To compensate for the inverter losses PI controller is applied to regulate the DC bus voltage. The output of PI controller at the dc bus voltage of active filter is considered as the current (iloss) for meeting its losses. vkvvkii ndeidndendepdnlossnloss )()1()()1()( )( +−+= −− (6) where, vv ndede )1( − − is the error between the reference(vdc*) and sensed (vdc) dc voltage at the nth sampling instant. Kpd and Kid are the proportional and the integral gains of the dc bus voltage PI controller. The reference source current is therefore expressed as, iii lossddd += * (7) Similarly PI controller is used to regulate reactive power vkvvkii nteiqntentepqnqrsnqr )()1()()1()( )( +−+= −− (8) The reference supply quadrature axis current is as iii qrqdq += * (9) where, vvv nsnte )( * )( −= denotes the error between reference (vs*) and actual(vs(n)) terminal voltage amplitudes at the n sampling instant. Kpq and Kiq are the proportional and the integral gains of the PI controller. 7. MATLAB IMPLEMENTATION A three phase transformerless hybrid active filter is implemented using MATLAB Power system Toolbox. Three phase input source voltage of 415V, 50 Hz frequency with source resistance of 0.2 ohms and inductance of 2mH is considered. A three phase unbalance nonlinear load drawing 5A is considered for simulation. Shunt active filter is constituted of 6 pulse VSI with 2200 e-6F of capacitance attached to the DC side. A small-rated filter has been included to minimize the switching ripples at the inverter output. Passive elements of the filter are calculated using the mathematical relation s considering 50% of fixed reactive compensation. Table1 gives the detailed parameters of the system.
  • 6. 378 Computer Science & Information Technology (CS & IT) Table 1. Detailed Parameters of the System. Parameters Values Supply voltage 415V (L-L), 50 Hz Loads: (i) Linear: phase a= 25 Phase b=10 and 80mH Phase c =10 and 80 mH (ii) Nonlinear: Three phase full bridge rectifier drawing 15A Shunt Active Filter: Interfacing Inductance Lf = 5.5 mH DC bus capacitance 22000e-6F. Referenced Dc voltage 750 V Tuned Passive Filter C5=129.4e-6F ;L5=3.1mH 8. RESULTS AND DISCUSSION The performance of the presented SRF control strategy is evaluated using by comparison of pure shunt active power filter and parallel hybrid power filter. The three phase unbalance nonlinear load considered here in the present system contains 5th harmonic content as the most prominent factor which causes the distortion in the source current. Hence the passive elements of the hybrid filter are tuned for the resonance frequency of 250Hz. The VA rating required for the inverter in the hybrid filter is much lesser than that required in a pure shunt active filter. The VA rating required of the inverter in parallel hybrid power active filter is given by VA rating= 3 22 IV FMAXdc ×× Where I FMAX A13≅ is the maximum filter current. Also the apparent power rating of nonlinear load is given by VA rating= IV LrmsSrms ××3 Where VSrms and ILrms are the RMS value of source voltage taken as 415 V and load current taken as 38A. The apparent ratio of the parallel hybrid filter and nonlinear load is greatly reduced by 16%. Another factor which determines the validation of active filters is Total Harmonic Distortion (THD) is reduced from14.74 % to 2.65 % for phase a. Table II shows the THD for all three phases for different types of filter. It can be seen from Fig 5 and Table III that parallel hybrid filter system is able to reduce the 5th harmonic of supply current to 1.68% .The THD of the ac supply current reduces to 3.27% with pure shunt active power filters alone as the major component of the load current without any filter is composed of 5th harmonic.
  • 7. Computer Science & Information Technology (CS & IT) 379 TABLE III Harmonic Current in Percentage of Fundamental Current 5th 7th 11th 13th 17th 19th Load current 12.76 5.42 3.92 2.23 1.55 0.97 Source current with Passive Filter 0.20 2.69 2.57 1.64 1.13 0.89 Source current with Pure Shunt Active Filter 1.83 0.54 0.64 0.65 0.83 0.05 Source current with Shunt Hybrid Active Filter 1.68 1.03 0.23 0.21 0.19 0.13 Figure 3 shows the waveform of load current without filter. Fig 4 and 5 shows the waveform of source current with pure shunt active filter and parallel hybrid active filter respectively. These waveforms clearly illustrates that load current is very distorted that implies source current at this time without filtering is also very distorted . With the application of power filter source currents can be made sinusoidal .Clearly with the application of parallel hybrid active filter source current is less distorted and contains less harmonics content as compared to pure shunt active filter. Fig 6 shows the uncompensated and compensated reactive power using parallel hybrid active filter .Since the passive elements are tuned at fixed 50% compensation, fig 6 clearly validates the passive parameters of hybrid filter. Fig7 demonstrates the source voltage, source current, load voltage, load current, DC bus voltage, and filter current for parallel hybrid active filter. TABLE II THD For Different Phases (in percentage) Phase Phase a Phas e b Phase cType of filter Load current without filter 14.74 16.27 19.66 Pure shunt active filter 3.27 4.58 3.75 Parallel hybrid filter 2.65 3.15 2.64
  • 8. 380 Computer Science & Information Technology (CS & IT) Figure 3 Load current Figure 4 Source Current with Pure Active Filter Figure 4 Source Current with Parallel Hybrid Active Filter Figure 6 Load Reactive Power and Source Reactive power using parallel Hybrid Active Filter
  • 9. Computer Science & Information Technology (CS & IT) 381 Figure 7 Source Voltage, Source Current, Load Voltage, Load Current, DC Bus Voltage, Filter Current. 9. CONCLUSIONS In this work, concept of transformerless parallel hybrid active filter is defined and verified by MATLAB simulation. Simulation results verify that presented method has good performance in the elimination of selective harmonic content and Total Harmonic Distortion. It has much better dynamic response with less rating compared with the pure shunt active filter. REFERENCES [1] B. Singh, K. Al-Haddad, and A. Chandra, “A review of active filters for power quality improvement,” IEEE Trans. Ind. Electron., vol. 46, no. 5, pp. 960–971, Oct. 1999. [2] J.W. Dixon, G. Venegas, and L. A.Moran, “A series active power filter based on a sinusoidal current- controlled voltage-source inverter,” IEEE Trans. Ind. Electron., vol. 44, no. 5, pp. 612–620, Oct. 1997. [3] Bhattacharya,Divan,”Synchronous Frame based controller implementation for a hybrid series active filter,Confeence record of IEEE Industry Apllications Conference Vol, 3,pp. 2531-2540 October 1995. [4] S. Srianthumrong and H. Akagi, “A medium-voltage transformerless AC/DC power conversion system consisting of a diode rectifier and a shunt hybrid filter,” IEEE Trans. Ind. Appl., vol. 39, no. 3, pp. 874–882, May/Jun. 2003. [5] H. Fujita, T. Yamasaki and H. Akagi, "A hybrid active filter for damping of harmonic resonance in industrial power systems," IEEE Trans. on Power Electronics, vol. 15, no. 2, pp. 215-222, March 2000.
  • 10. 382 Computer Science & Information Technology (CS & IT) [6] H. Fujita, H. Akagi, "A Practical Approach to Harmonic Compensation in Power Systems-Series Connection of Passive, Active Filters," IEEE Trans. on Ind.. Appl., vol.27, no.6, pp. 1020-1025, Nov./Dec. 1991. [7] F.B. Libano, J.A.Cobos, J. Uceda, "Simplified control strategy for Hybrid Active Filters", IEEE PESC Record, 1 997, pp 1102-1108. [8] P.T. Cheng, S. Bhattacharya and D. Divan, "Experimental Verification of Dominant Harmonic Active Filter for High Power Applications",IEEE Trans. on Ind. Appl., vol. 36, pp.567-577, March/April, 2000. [9] IEEE Guide for Application and Specification of Harmonic Filters IEEE Std 1531-2003. [10] V, Verma, S. Shanker, B. Singh, A. Chandra, and Kamal Al- Haddad, "Genetic Algorithm Based Design of Passive Filters for Offshore Applications," Proc. ofIEEE PCIC '04, 2004, pp 55-62. [11] S. Bhattacharya, D. Divan and B. Banerjee, “Synchronous frame harmonic isolator using active series filter,” EPE-Firenze, Vol. 3, pp. 30-35, 1991. [12] V, Verma, S. Shanker, B. Singh,’Design and Implemention of Current Controlled Parallel Hybrid Power Filter. [13] B.N.Singh, P.Rastgoufard, B.Singh, A.Chandra and K.Al.Haddad, “Design,simulation and implementation of three pole/ four pole topologies for active filters,” IEE Eletr. Power Appl., vol. 151, no. 4, pp. 467-476, July 2004. Authors Sakshi Bangia received the B.Tech degree in Instrumentation and Control from MDU Rohtak and M.Tech degree in Electrical Engg. from YMCA UST in 2004 and 2006, respectively. She is pursuing Ph.D in Power Quality from Maharishi Dayanand University, India. Presently she is working as Assistant Professor in Electrical Engineering Department at YMCA UST Faridabad. Dr. P.R.Sharma was born in 1966 in India. He is currently working as Chairman of the Department in Electrical Engg. in YMCA University Of Science and Technology, Faridabad. He received his B.E Electrical Engineering in 1988 from Punjab University Chandigarh, M.Tech in Electrical Engineering (Power System) from Regional Engineering College Kurukshetra in 1990 and Ph.D from M.D.University Rohtak in 2005. He started his carrier from industry. He has vast experience in the industry and teaching. His area of interest is Optimal location and coordinated control of FACTS devices ,power system stability and control Dr. Maneesha Garg did her Ph.D(Physics) in 2002 from Kurukshetra University, India. After that she worked as Research Associate granted by CSIR, in NIT Kurukshetra for 4 years. She has 18 publications in national, international journals and more than 30 papers in conferences to her credit. Presently she is working as Assistant Professor in Humanities and Applied Science Department, YMCA UST, Faridabad and guiding 4 scholars for their research work.