PROJECT CONCEPT DRAWING (EX SYSTEM)
Ex 230/115KV Berri
230KV Side (Outdoor
S/S)
230KV Jubail Residential
SS# 40
230KV OHL
Ex 230/115KV Berri
115KV Side (Outdoor
S/S)
SS# 11
SS# 20
To Captive TFs
To Captive TFs
Diversions of Existing OHL Circuits is required with respect to location of new
Berri SS
115KV OHL
(Ex)
PROJECT CONCEPT DRAWING (NEW 230KV SYSTEM)
New 230/115KV Berri
230KV Side
230KV Jubail Residential
230KV OHL
(ex)
New 230KV UGC
(2Rx1600mm2)
RL=65M
To new
230/115KVTFs
New 230KV UGC
(2Rx1600mm2)
RL=90M
New
230KVGantries
PROJECT CONCEPT DRAWING (NEW 115KV SYSTEM)
Riyas NGL SS
New 230/115KV Berri
115KV Side
SS# 20
To Captive TFs
To Captive TFs
New OHL (28.54
KM)
New OHL (1.35
KM)
UGC 2500mm2
SS Sub-1
Ex OHL with Div / DISM
SS Sub-40
UGC 1600mm2
Ex OHL with Div
SS Sub-11
UGC 800mm2
Ex OHL Div
Ex OHL with Div
Ex OHL with Div
SCOPE OF WORK (230KV BSP)
EQUIPMENT LIST BERRI GAS PLANT 230KV GIS BSP
230KV, 3150A, HGIS INDOOR (SEC APPROVED) 2 C.B
with 2C/ph Cable Box at Each End
115KV, 3150A, GIS (SEC APPROVED) 7 DIA (21 C.B)
115KV, 3150A, HGIS INDOOR (SEC APPROVED)
1 C.B
with 2C/ph Cable Box at Each End
230KV/115/13.8KV, 500MVA Power Transformer (ARAMCO
APPROVED)
2 No’s
Grounding Transformer (SEC APPROVED) 2 No’s
13.8KV SWGR (ARAMCO APPROVED) 2 C.B
13.8/0.4KV, 3.125MVA (ARAMCO APPROVED) 2 No’s
Physical Security System (CCTV, ACS) Lot
Cyber Security System Lot
FO Cable (Direct Buried)
6 Circuits (RL=23.6KM, Total FOC-35.2 KM)
From New BGP SS to SS#11, SS#01, Berri DCO,
Berri CCR, SS#40, SS#20
SCOPE OF WORK (230KV BSP)
EQUIPMENT LIST BERRI GAS PLANT 230KV GIS BSP
115KV Cables
115KV, 1C - 2500 MM2 = 6,900 Mtr’s (6 CKT’s) –
SGT, Riyas NGL, SUB-1
115KV, 1C - 1600 MM2 = 6,720 Mtr’s (2 CKT’s) –
Sub-40
115KV, 1C – 800MM2 – 2,190 Mtr’s (2 CKT’s) –
Sub-11
115KV Cable Termination
115KV, 1C X 2500MM2 - SF6/XLPE - 30 No’s
115KV, 1C X 2500MM2 - XLPE/Air - 30 No’s
115KV, 1C X 1600MM2 - SF6/XLPE - 12 No’s
115KV, 1C X 1600MM2 - XLPE/Air - 12 No’s
115KV, 1C X 800MM2 - SF6/XLPE - 6 No’s
115KV, 1C X 800MM2 - XLPE/Air - 6 No’s
Link box = 28 No's
230KV Outdoor S.A
230KV S.A at Gantries - 6 No's
230KV S.A at TRF's - 6 No's
115KV S.A 48 No’s at gantries and at TRF
230KV Cables 230KV, 1C - 1600 MM2 = 2,076 Mtr's
230KV Cable Termination
230KV, 1C X 1600MM2 - SF6/XLPE - 24 No's
230KV, 1C X 1600MM2 - XLPE/Air - 24 No's
Link box = 12 No's
PROTECTION & SAS SCOPE
SN Scope
New 230kV
BGP SUB 30
230/115KV BSP
Jubail Res.
230KV - 2
Lines – OHL
RIYAS NGL
115KV
2 Feeders
Sub-40
115KV
2 Feeders
Sub-11
115KV
2 Feeders
Sub-20 115KV
2 Feeders
Sub-1 115KV
2 Feeders
1 Protection New Protection
New
Protection
New
Protection
New
Protection
New
Protection
New
Protection
New
Protection
2 SAS Modification NEW PSA
ABB Mod
SAS
NA SCADA SS SCADA SS SCADA SS SCADA SS
3 FR New TFR Qualitrol TFR mod. TFR mod. TFR mod. TFR mod. TFR mod.
4 DSM NA Qualitrol NA NA NA NA NA
5 SOE
New SOE in SEC
Room In SAS NA GE D20 NA NA NA
6 SCADA
New SCADA in
SEC Room
In SAS NA GE D20 GE D20 GE D20 GE D20
8 230KV FSCT NA NA NA NA NA NA NA
9 230KV Ring Core
CTs
NA NA NA NA NA NA NA
230KV Remote ends of Berri Gas Plant Sub-30 230/115KV BSP
- Jubail Residential 230KV - 2 Lines - OHL
115KV Remote ends of BGP Sub 30 230/115KV BSP
- RIYAS Line A & B - Sub 40 Line A & B - Sub 11 Line A & B - Sub 20 Line A & B
- Sub 1 Line A & B - Loads Feeders (Load M1, M2, M3, M4)
ISLANDING AND BACK SYNCHRONIZATION SYSTEM REQUIREMENTS FOR BGP
A) ISLANDING SYSTEM REQUIREMENTS:
Islanding System is required at BGP and extension / modification in existing system among existing SS/s Riyas NGL sub, WIP sub, Sub 30, Sub 40.
ISLANDING AND BACK SYNCHRONIZATION SYSTEM REQUIREMENTS FOR BGP
A) ISLANDING SYSTEM REQUIREMENTS:
NOTES:
1. Remote end line/breaker statuses (for SEC/Riyas) shall be interfaced to Islanding system for islanding detection logic.
2. Islanding panel housing, PLC/ automation controllers and I/Os to be installed in the P&C room of the new GIS building.
3. Temporary communication arrangement between new islanding system and existing islanding system.
4. Frequency Separation relays in separate panel. Additional frequency separation relays may be required at 115kV Riyas.
5. Interface with new PSA (for transfer signals to Dhahran PCC) over FO or hardwired (Redundant FO links)
7. Remote I/O interface panels at BGP, Riyas 115kV and WIP 115kV, I/Os (CBs status, MW measurements and load shedding)
8. Back Sync panel shall be installed in new GIS P&C room. Additional back synch panel at Riyas 115kV may be required
depending on system design and islanding scenarios. This will determine during design stage.
9. Back Synchronization FO link to remote I/O modules for back sync located in Cogen unit location.
10. Islanding system will monitor power in real time using accurate power meters. The data acquired will be used for plant
load calculations and load shedding calculations.
11. The Contractor shall propose reliable and robust communication network, for N-1 contingency.
ISLANDING AND BACK SYNCHRONIZATION SYSTEM REQUIREMENTS FOR BGP
The proposed Islanding system shall meet the following requirements
- The Islanding system requires 230kV/115kV CBs status and/or 230kV/115kV lines (open/close status), for islanding/ partial
islanding detection logic (separation of Saudi Aramco electrical network from SEC network).
- The Islanding detection logic shall cover all possible islanding and partial islanding scenarios. All
- The Islanding detection logic shall generate a separate islanding output signal for each unique islanding or partial
islanding scenario. There are four possible Islanding and partial islanding scenarios:
A- Complete Islanding BGP (Sub 30, Sub 40)
B- Complete Islanding BGP and RNGL (Sub 30, sub 40 and RNGL)
C- Partial Island sub 40 (Sub 40)
D- Complete Island RNGL
Note: Islanding scenarios b, c and d shall be discussed and agreed with process plant proponents to determine if
implementation of these scenarios is practical and feasible from process perspective.
PROJECT DRAWING – BERRI GAS PLANT S/S - SLD
PROJECT LAYOUT DRAWING (NEW S/S LAYOUT)
OVERALL LAYOUT WITH O/D S/S (TO BE DISMANTLED)
To be newly
constructed
To be Dismantled
SCOPE OF WORK
PART 1: SLD FOR NEW 115KV OHTL – 28.54 KM
New BGP
SUB-30
RIYAS NGLF
SUBSTATIO
N
ROUTE LENGTH 28.54 KM
GAP TYPE HEAT RESISTANT CONDUCTOR
GZTACSR EQUIVALENT TO ACSR DRAKE
CONDUCTOR (TWIN PER PHASE)
115KV XLPE CABLE,
ROUTE LENGTH: 530 M
TC WITH
SA & CSE
TC WITH
SA & CSE
SCOPE OF WORK
A: ROUTE DRAWING FOR NEW 115KV OHTL – 28.54 KM
BERRI
GAS
PLANT
S/S
RIYAS NGL
S/S
SCOPE OF WORK
SCOPE ITEM QTY REMARKS
ROUTE LENGTH 28.54 KM
TAPPING FOR LILO Not Applicable
CONDUCTOR GZTACSR EQUIVALENT TO ACSR “DRAKE” CONDUCTOR
TOTAL CONDUCTOR 342.48 KM D/C, TWIN CONDUCTOR PER PHASE
LATTICED STEEL TOWER 82 NOS “SEC FAMILY OF TOWERS”
SUSPENSION TOWERS 60 NOS
ANGLE TOWERS 18 NOS
DE TOWERS 04 NOS
U/C GANTRIES NOT REQUIRED
INSULATORS COMPOSITE LONG ROD 40mm/KV
RTV COATING NOT REQUIRED
TOWER PAINTING NOT REQUIRED
OPGW 57.08 KM 96C [ITU-T G652D]
SCOPE OF WORK FOR NEW 115KV OHTL BGP SUB-30 AND RIYAS NGLF
SCOPE OF WORK
SCOPE ITEM QTY REMARKS
OHTL CROSSINGS 01 LOT BETWEEN PI-14 AND PI-15
TRANSITION COMPOUNDS 02 NOS AT PI-14 & PI-15
CROSSING DETAILS FOR NEW 115KV OHTL BGP SUB-30 AND RIYAS NGLF
SCOPE OF WORK
PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30
[PORTION 1: SUB 1]
SCOPE OF WORK
SCOPE ITEM QTY REMARKS
ROUTE LENGTH 440 M
DIVERSION OF EXISTING 230KV OHTL BETWEEN JRSD AND
JUBAIL SUB-30 TO NEW BGP SUB-30 SUBSTATION
TAPPING FOR LILO Not Applicable
CONDUCTOR ACSR/AW “DRAKE”
TOTAL CONDUCTOR 5.280 KM D/C, TWIN CONDUCTOR PER PHASE
STEEL MONOPOLES 03 NOS “SEC FAMILY OF TOWERS”
SUSPENSION POLES 00 NOS
ANGLE POLES 01 NOS
DE POLES 01 NOS
S/C GANTRIES 02 NOS
INSULATORS COMPOSITE LONG ROD 40mm/KV
RTV COATING NOT REQUIRED
TOWER PAINTING NOT REQUIRED
OPGW 0.880 KM 96C [ITU-T G652D]
OHTL DISMANTLING 310 M EXISTING 230KV OHTL PORTION TO BE DISMANTLED
PART 2: SCOPE OF WORK FOR DIVERSION OF EXISTING 230KV OHTL JRSD TO BGP SUB-30
SCOPE OF WORK
PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30
[PORTION 1: SUB 1]
SCOPE OF WORK
SCOPE ITEM QTY REMARKS
ROUTE LENGTH 1.35 KM
DIVERSION OF EXISTING 115KV OHTL FROM POINT A1 TO
POINT A8 (GANTRY)
TAPPING FOR LILO Not Applicable
CONDUCTOR ACSR/AW “DRAKE”
TOTAL CONDUCTOR 8.10 KM D/C, SINGLE CONDUCTOR PER PHASE
STEEL MONOPOLES 07 NOS “SEC FAMILY OF TOWERS”
SUSPENSION POLES 01 NOS
ANGLE POLES 05 NOS
DE TOWERS 01 NOS
S/C GANTRY 02 NOS
INSULATORS COMPOSITE LONG ROD 40mm/KV
D/C GANTRY AT SUB-30 01 NOS EXISTING AT SUB-30
OPGW 2.7 KM 96C [ITU-T G652D]
CRITICAL POINT LIVE LINE CROSSING
THE NEW OHTL FROM SUB 1 TO AIS BGP S/S WILL CROSS THE
EXISTING SUB-40 OHTL LIVE
PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30
[PORTION 1: SUB 1 TO EXISTING AIS S/S]
SCOPE OF WORK
SCOPE ITEM QTY REMARKS
ROUTE LENGTH 320 M
DIVERSION OF EXISTING 115KV OHTL FROM POINT B1 TO
POINT B4 (GANTRY)
TAPPING FOR LILO Not Applicable
CONDUCTOR GZTACSR EQUIVALENT TO CONDUCTOR CODE CURLEW
TOTAL CONDUCTOR 1.920 KM D/C, SINGLE CONDUCTOR PER PHASE
STEEL MONOPOLES 03 NOS “SEC FAMILY OF TOWERS”
SUSPENSION POLES 00 NOS
ANGLE POLES 03 NOS
DE TOWERS 00 NOS
S/C GANTRY 02 NOS
INSULATORS COMPOSITE LONG ROD 40mm/KV
OPGW 0.640 KM 96C [ITU-T G652D]
OHTL DISMANTLING 400 M EXISTING 115KV OHTL PORTION TO BE DISMANTLED
PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30
[PORTION 2: SUB 40 TO EXISTING BGP AIS S/S]
SCOPE OF WORK
SCOPE ITEM QTY REMARKS
ROUTE LENGTH 320 M
DIVERSION OF EXISTING 115KV OHTL FROM POINT F1 TO
POINT F4 (GANTRY)
TAPPING FOR LILO Not Applicable
CONDUCTOR ACSR/AW “DRAKE”
TOTAL CONDUCTOR 1.920 KM D/C, SINGLE CONDUCTOR PER PHASE
STEEL MONOPOLES 03 NOS “SEC FAMILY OF TOWERS”
SUSPENSION POLES 00 NOS
ANGLE POLES 02 NOS
DE TOWERS 01 NOS
S/C GANTRY 02 NOS INCLUDED IN S/S PTS
INSULATORS COMPOSITE LONG ROD 40mm/KV
OPGW 0.640 KM 96C [ITU-T G652D]
OHTL DISMANTLING 120 M EXISTING 115KV OHTL PORTION TO BE DISMANTLED
PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30
[PORTION 3: M2/M1]
SCOPE OF WORK
SCOPE ITEM QTY REMARKS
ROUTE LENGTH 305 M
DIVERSION OF EXISTING 115KV OHTL FROM POINT E1 TO
POINT E4 (GANTRY)
TAPPING FOR LILO Not Applicable
CONDUCTOR ACSR/AW “DRAKE”
TOTAL CONDUCTOR 1.830 KM D/C, SINGLE CONDUCTOR PER PHASE
STEEL MONOPOLES 03 NOS “SEC FAMILY OF TOWERS”
SUSPENSION POLES 00 NOS
ANGLE POLES 02 NOS
DE TOWERS 01 NOS
S/C GANTRY 02 NOS INCLUDED IN S/S PTS
INSULATORS COMPOSITE LONG ROD 40mm/KV
OPGW 0.610 KM 96C [ITU-T G652D]
OHTL DISMANTLING 120 M EXISTING 115KV OHTL PORTION TO BE DISMANTLED
PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30
[PORTION 4: M4/M3]
SCOPE OF WORK
SCOPE ITEM QTY REMARKS
ROUTE LENGTH 300 M
DIVERSION OF EXISTING 115KV OHTL FROM POINT D1 TO
POINT D4 (GANTRY)
TAPPING FOR LILO Not Applicable
CONDUCTOR ACSR/AW “DRAKE”
TOTAL CONDUCTOR 1.800 KM D/C, SINGLE CONDUCTOR PER PHASE
STEEL MONOPOLES 03 NOS “SEC FAMILY OF TOWERS”
SUSPENSION POLES 00 NOS
ANGLE POLES 02 NOS
DE TOWERS 01 NOS
S/C GANTRY 02 NOS INCLUDED IN S/S PTS
INSULATORS COMPOSITE LONG ROD 40mm/KV
OPGW 0.600 KM 96C [ITU-T G652D]
OHTL DISMANTLING 120 M EXISTING 115KV OHTL PORTION TO BE DISMANTLED
PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30
[PORTION 5: SUB-20]
SCOPE OF WORK
SCOPE ITEM QTY REMARKS
ROUTE LENGTH 80 M
DIVERSION OF EXISTING 115KV OHTL FROM POINT D1 TO
POINT D4 (GANTRY)
TAPPING FOR LILO Not Applicable
CONDUCTOR ACSR/AW “DRAKE”
TOTAL CONDUCTOR 480 M D/C, SINGLE CONDUCTOR PER PHASE
STEEL MONOPOLES 01 NOS “SEC FAMILY OF TOWERS”
SUSPENSION POLES 00 NOS
ANGLE POLES 00 NOS
DE TOWERS 01 NOS
S/C GANTRY 02 NOS
INSULATORS COMPOSITE LONG ROD 40mm/KV
OPGW 160 M 96C [ITU-T G652D]
OHTL DISMANTLING 125 M EXISTING 115KV OHTL PORTION TO BE DISMANTLED
PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30
[PORTION 6: SUB-11]

More Related Content

PPTX
NMML1 Power supply and traction Presentation.pptx
PPT
Traction distribution
PPTX
CEA Regulations.pptx
PPTX
Distribution system 2
PDF
Electrical System Design - Industrial installations
PPTX
Proposal for Reduction of excessive CB tripping as on 31.03.2022.pptx
PDF
M. standard-stock-materials-for-33k v-system
DOCX
metro naveen
NMML1 Power supply and traction Presentation.pptx
Traction distribution
CEA Regulations.pptx
Distribution system 2
Electrical System Design - Industrial installations
Proposal for Reduction of excessive CB tripping as on 31.03.2022.pptx
M. standard-stock-materials-for-33k v-system
metro naveen

Similar to Data required for power system studies related to ETAP (20)

PPT
OPERATION & MAINTENANCE OF OF OVER HEADLINES.ppt
PDF
General condition-relating-to-electricity new
PDF
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)
PPT
122983136-Substation-wewwwwLayoutassss .ppt
PPT
transmission line
DOCX
132 KV GSS NPH jodhpur treaning report
XLS
Specifications
PDF
Industrial Training Presentation
PPTX
SERVICE CONNECTION, INSPECTION AND TESTING OF INSTALLATION
PPT
132kv Substation
PPTX
EEE Unit , electronic and electrical engineering
PDF
C0396824_REV_B_As_Issued
PDF
110KV Substation spec with AnnexuresR.pdf
DOC
PPT
Transmission Line presentation______.ppt
PPTX
ELECTRICAL POWER TRANSMISSION-3.pptx
PPTX
Electrical and Electronics engineering power point presentation.
PPTX
BEEE-UNIT 5.pptx
DOC
220 kv g.s.s, report
OPERATION & MAINTENANCE OF OF OVER HEADLINES.ppt
General condition-relating-to-electricity new
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)
122983136-Substation-wewwwwLayoutassss .ppt
transmission line
132 KV GSS NPH jodhpur treaning report
Specifications
Industrial Training Presentation
SERVICE CONNECTION, INSPECTION AND TESTING OF INSTALLATION
132kv Substation
EEE Unit , electronic and electrical engineering
C0396824_REV_B_As_Issued
110KV Substation spec with AnnexuresR.pdf
Transmission Line presentation______.ppt
ELECTRICAL POWER TRANSMISSION-3.pptx
Electrical and Electronics engineering power point presentation.
BEEE-UNIT 5.pptx
220 kv g.s.s, report
Ad

Recently uploaded (20)

PDF
advance database management system book.pdf
PDF
Hazard Identification & Risk Assessment .pdf
PDF
Supply Chain Operations Speaking Notes -ICLT Program
PPTX
Final Presentation General Medicine 03-08-2024.pptx
PPTX
UNIT III MENTAL HEALTH NURSING ASSESSMENT
PDF
LDMMIA Reiki Yoga Finals Review Spring Summer
PDF
Chinmaya Tiranga quiz Grand Finale.pdf
PDF
Classroom Observation Tools for Teachers
PPTX
History, Philosophy and sociology of education (1).pptx
PDF
RMMM.pdf make it easy to upload and study
PPTX
Onco Emergencies - Spinal cord compression Superior vena cava syndrome Febr...
PDF
SOIL: Factor, Horizon, Process, Classification, Degradation, Conservation
PPTX
Unit 4 Skeletal System.ppt.pptxopresentatiom
PDF
A GUIDE TO GENETICS FOR UNDERGRADUATE MEDICAL STUDENTS
PPTX
Chinmaya Tiranga Azadi Quiz (Class 7-8 )
PPTX
Radiologic_Anatomy_of_the_Brachial_plexus [final].pptx
PDF
RTP_AR_KS1_Tutor's Guide_English [FOR REPRODUCTION].pdf
PPTX
A powerpoint presentation on the Revised K-10 Science Shaping Paper
PDF
احياء السادس العلمي - الفصل الثالث (التكاثر) منهج متميزين/كلية بغداد/موهوبين
PPTX
Cell Types and Its function , kingdom of life
advance database management system book.pdf
Hazard Identification & Risk Assessment .pdf
Supply Chain Operations Speaking Notes -ICLT Program
Final Presentation General Medicine 03-08-2024.pptx
UNIT III MENTAL HEALTH NURSING ASSESSMENT
LDMMIA Reiki Yoga Finals Review Spring Summer
Chinmaya Tiranga quiz Grand Finale.pdf
Classroom Observation Tools for Teachers
History, Philosophy and sociology of education (1).pptx
RMMM.pdf make it easy to upload and study
Onco Emergencies - Spinal cord compression Superior vena cava syndrome Febr...
SOIL: Factor, Horizon, Process, Classification, Degradation, Conservation
Unit 4 Skeletal System.ppt.pptxopresentatiom
A GUIDE TO GENETICS FOR UNDERGRADUATE MEDICAL STUDENTS
Chinmaya Tiranga Azadi Quiz (Class 7-8 )
Radiologic_Anatomy_of_the_Brachial_plexus [final].pptx
RTP_AR_KS1_Tutor's Guide_English [FOR REPRODUCTION].pdf
A powerpoint presentation on the Revised K-10 Science Shaping Paper
احياء السادس العلمي - الفصل الثالث (التكاثر) منهج متميزين/كلية بغداد/موهوبين
Cell Types and Its function , kingdom of life
Ad

Data required for power system studies related to ETAP

  • 1. PROJECT CONCEPT DRAWING (EX SYSTEM) Ex 230/115KV Berri 230KV Side (Outdoor S/S) 230KV Jubail Residential SS# 40 230KV OHL Ex 230/115KV Berri 115KV Side (Outdoor S/S) SS# 11 SS# 20 To Captive TFs To Captive TFs Diversions of Existing OHL Circuits is required with respect to location of new Berri SS 115KV OHL (Ex)
  • 2. PROJECT CONCEPT DRAWING (NEW 230KV SYSTEM) New 230/115KV Berri 230KV Side 230KV Jubail Residential 230KV OHL (ex) New 230KV UGC (2Rx1600mm2) RL=65M To new 230/115KVTFs New 230KV UGC (2Rx1600mm2) RL=90M New 230KVGantries
  • 3. PROJECT CONCEPT DRAWING (NEW 115KV SYSTEM) Riyas NGL SS New 230/115KV Berri 115KV Side SS# 20 To Captive TFs To Captive TFs New OHL (28.54 KM) New OHL (1.35 KM) UGC 2500mm2 SS Sub-1 Ex OHL with Div / DISM SS Sub-40 UGC 1600mm2 Ex OHL with Div SS Sub-11 UGC 800mm2 Ex OHL Div Ex OHL with Div Ex OHL with Div
  • 4. SCOPE OF WORK (230KV BSP) EQUIPMENT LIST BERRI GAS PLANT 230KV GIS BSP 230KV, 3150A, HGIS INDOOR (SEC APPROVED) 2 C.B with 2C/ph Cable Box at Each End 115KV, 3150A, GIS (SEC APPROVED) 7 DIA (21 C.B) 115KV, 3150A, HGIS INDOOR (SEC APPROVED) 1 C.B with 2C/ph Cable Box at Each End 230KV/115/13.8KV, 500MVA Power Transformer (ARAMCO APPROVED) 2 No’s Grounding Transformer (SEC APPROVED) 2 No’s 13.8KV SWGR (ARAMCO APPROVED) 2 C.B 13.8/0.4KV, 3.125MVA (ARAMCO APPROVED) 2 No’s Physical Security System (CCTV, ACS) Lot Cyber Security System Lot FO Cable (Direct Buried) 6 Circuits (RL=23.6KM, Total FOC-35.2 KM) From New BGP SS to SS#11, SS#01, Berri DCO, Berri CCR, SS#40, SS#20
  • 5. SCOPE OF WORK (230KV BSP) EQUIPMENT LIST BERRI GAS PLANT 230KV GIS BSP 115KV Cables 115KV, 1C - 2500 MM2 = 6,900 Mtr’s (6 CKT’s) – SGT, Riyas NGL, SUB-1 115KV, 1C - 1600 MM2 = 6,720 Mtr’s (2 CKT’s) – Sub-40 115KV, 1C – 800MM2 – 2,190 Mtr’s (2 CKT’s) – Sub-11 115KV Cable Termination 115KV, 1C X 2500MM2 - SF6/XLPE - 30 No’s 115KV, 1C X 2500MM2 - XLPE/Air - 30 No’s 115KV, 1C X 1600MM2 - SF6/XLPE - 12 No’s 115KV, 1C X 1600MM2 - XLPE/Air - 12 No’s 115KV, 1C X 800MM2 - SF6/XLPE - 6 No’s 115KV, 1C X 800MM2 - XLPE/Air - 6 No’s Link box = 28 No's 230KV Outdoor S.A 230KV S.A at Gantries - 6 No's 230KV S.A at TRF's - 6 No's 115KV S.A 48 No’s at gantries and at TRF 230KV Cables 230KV, 1C - 1600 MM2 = 2,076 Mtr's 230KV Cable Termination 230KV, 1C X 1600MM2 - SF6/XLPE - 24 No's 230KV, 1C X 1600MM2 - XLPE/Air - 24 No's Link box = 12 No's
  • 6. PROTECTION & SAS SCOPE SN Scope New 230kV BGP SUB 30 230/115KV BSP Jubail Res. 230KV - 2 Lines – OHL RIYAS NGL 115KV 2 Feeders Sub-40 115KV 2 Feeders Sub-11 115KV 2 Feeders Sub-20 115KV 2 Feeders Sub-1 115KV 2 Feeders 1 Protection New Protection New Protection New Protection New Protection New Protection New Protection New Protection 2 SAS Modification NEW PSA ABB Mod SAS NA SCADA SS SCADA SS SCADA SS SCADA SS 3 FR New TFR Qualitrol TFR mod. TFR mod. TFR mod. TFR mod. TFR mod. 4 DSM NA Qualitrol NA NA NA NA NA 5 SOE New SOE in SEC Room In SAS NA GE D20 NA NA NA 6 SCADA New SCADA in SEC Room In SAS NA GE D20 GE D20 GE D20 GE D20 8 230KV FSCT NA NA NA NA NA NA NA 9 230KV Ring Core CTs NA NA NA NA NA NA NA 230KV Remote ends of Berri Gas Plant Sub-30 230/115KV BSP - Jubail Residential 230KV - 2 Lines - OHL 115KV Remote ends of BGP Sub 30 230/115KV BSP - RIYAS Line A & B - Sub 40 Line A & B - Sub 11 Line A & B - Sub 20 Line A & B - Sub 1 Line A & B - Loads Feeders (Load M1, M2, M3, M4)
  • 7. ISLANDING AND BACK SYNCHRONIZATION SYSTEM REQUIREMENTS FOR BGP A) ISLANDING SYSTEM REQUIREMENTS: Islanding System is required at BGP and extension / modification in existing system among existing SS/s Riyas NGL sub, WIP sub, Sub 30, Sub 40.
  • 8. ISLANDING AND BACK SYNCHRONIZATION SYSTEM REQUIREMENTS FOR BGP A) ISLANDING SYSTEM REQUIREMENTS: NOTES: 1. Remote end line/breaker statuses (for SEC/Riyas) shall be interfaced to Islanding system for islanding detection logic. 2. Islanding panel housing, PLC/ automation controllers and I/Os to be installed in the P&C room of the new GIS building. 3. Temporary communication arrangement between new islanding system and existing islanding system. 4. Frequency Separation relays in separate panel. Additional frequency separation relays may be required at 115kV Riyas. 5. Interface with new PSA (for transfer signals to Dhahran PCC) over FO or hardwired (Redundant FO links) 7. Remote I/O interface panels at BGP, Riyas 115kV and WIP 115kV, I/Os (CBs status, MW measurements and load shedding) 8. Back Sync panel shall be installed in new GIS P&C room. Additional back synch panel at Riyas 115kV may be required depending on system design and islanding scenarios. This will determine during design stage. 9. Back Synchronization FO link to remote I/O modules for back sync located in Cogen unit location. 10. Islanding system will monitor power in real time using accurate power meters. The data acquired will be used for plant load calculations and load shedding calculations. 11. The Contractor shall propose reliable and robust communication network, for N-1 contingency.
  • 9. ISLANDING AND BACK SYNCHRONIZATION SYSTEM REQUIREMENTS FOR BGP The proposed Islanding system shall meet the following requirements - The Islanding system requires 230kV/115kV CBs status and/or 230kV/115kV lines (open/close status), for islanding/ partial islanding detection logic (separation of Saudi Aramco electrical network from SEC network). - The Islanding detection logic shall cover all possible islanding and partial islanding scenarios. All - The Islanding detection logic shall generate a separate islanding output signal for each unique islanding or partial islanding scenario. There are four possible Islanding and partial islanding scenarios: A- Complete Islanding BGP (Sub 30, Sub 40) B- Complete Islanding BGP and RNGL (Sub 30, sub 40 and RNGL) C- Partial Island sub 40 (Sub 40) D- Complete Island RNGL Note: Islanding scenarios b, c and d shall be discussed and agreed with process plant proponents to determine if implementation of these scenarios is practical and feasible from process perspective.
  • 10. PROJECT DRAWING – BERRI GAS PLANT S/S - SLD
  • 11. PROJECT LAYOUT DRAWING (NEW S/S LAYOUT)
  • 12. OVERALL LAYOUT WITH O/D S/S (TO BE DISMANTLED) To be newly constructed To be Dismantled
  • 13. SCOPE OF WORK PART 1: SLD FOR NEW 115KV OHTL – 28.54 KM New BGP SUB-30 RIYAS NGLF SUBSTATIO N ROUTE LENGTH 28.54 KM GAP TYPE HEAT RESISTANT CONDUCTOR GZTACSR EQUIVALENT TO ACSR DRAKE CONDUCTOR (TWIN PER PHASE) 115KV XLPE CABLE, ROUTE LENGTH: 530 M TC WITH SA & CSE TC WITH SA & CSE
  • 14. SCOPE OF WORK A: ROUTE DRAWING FOR NEW 115KV OHTL – 28.54 KM BERRI GAS PLANT S/S RIYAS NGL S/S
  • 15. SCOPE OF WORK SCOPE ITEM QTY REMARKS ROUTE LENGTH 28.54 KM TAPPING FOR LILO Not Applicable CONDUCTOR GZTACSR EQUIVALENT TO ACSR “DRAKE” CONDUCTOR TOTAL CONDUCTOR 342.48 KM D/C, TWIN CONDUCTOR PER PHASE LATTICED STEEL TOWER 82 NOS “SEC FAMILY OF TOWERS” SUSPENSION TOWERS 60 NOS ANGLE TOWERS 18 NOS DE TOWERS 04 NOS U/C GANTRIES NOT REQUIRED INSULATORS COMPOSITE LONG ROD 40mm/KV RTV COATING NOT REQUIRED TOWER PAINTING NOT REQUIRED OPGW 57.08 KM 96C [ITU-T G652D] SCOPE OF WORK FOR NEW 115KV OHTL BGP SUB-30 AND RIYAS NGLF
  • 16. SCOPE OF WORK SCOPE ITEM QTY REMARKS OHTL CROSSINGS 01 LOT BETWEEN PI-14 AND PI-15 TRANSITION COMPOUNDS 02 NOS AT PI-14 & PI-15 CROSSING DETAILS FOR NEW 115KV OHTL BGP SUB-30 AND RIYAS NGLF
  • 17. SCOPE OF WORK PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30 [PORTION 1: SUB 1]
  • 18. SCOPE OF WORK SCOPE ITEM QTY REMARKS ROUTE LENGTH 440 M DIVERSION OF EXISTING 230KV OHTL BETWEEN JRSD AND JUBAIL SUB-30 TO NEW BGP SUB-30 SUBSTATION TAPPING FOR LILO Not Applicable CONDUCTOR ACSR/AW “DRAKE” TOTAL CONDUCTOR 5.280 KM D/C, TWIN CONDUCTOR PER PHASE STEEL MONOPOLES 03 NOS “SEC FAMILY OF TOWERS” SUSPENSION POLES 00 NOS ANGLE POLES 01 NOS DE POLES 01 NOS S/C GANTRIES 02 NOS INSULATORS COMPOSITE LONG ROD 40mm/KV RTV COATING NOT REQUIRED TOWER PAINTING NOT REQUIRED OPGW 0.880 KM 96C [ITU-T G652D] OHTL DISMANTLING 310 M EXISTING 230KV OHTL PORTION TO BE DISMANTLED PART 2: SCOPE OF WORK FOR DIVERSION OF EXISTING 230KV OHTL JRSD TO BGP SUB-30
  • 19. SCOPE OF WORK PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30 [PORTION 1: SUB 1]
  • 20. SCOPE OF WORK SCOPE ITEM QTY REMARKS ROUTE LENGTH 1.35 KM DIVERSION OF EXISTING 115KV OHTL FROM POINT A1 TO POINT A8 (GANTRY) TAPPING FOR LILO Not Applicable CONDUCTOR ACSR/AW “DRAKE” TOTAL CONDUCTOR 8.10 KM D/C, SINGLE CONDUCTOR PER PHASE STEEL MONOPOLES 07 NOS “SEC FAMILY OF TOWERS” SUSPENSION POLES 01 NOS ANGLE POLES 05 NOS DE TOWERS 01 NOS S/C GANTRY 02 NOS INSULATORS COMPOSITE LONG ROD 40mm/KV D/C GANTRY AT SUB-30 01 NOS EXISTING AT SUB-30 OPGW 2.7 KM 96C [ITU-T G652D] CRITICAL POINT LIVE LINE CROSSING THE NEW OHTL FROM SUB 1 TO AIS BGP S/S WILL CROSS THE EXISTING SUB-40 OHTL LIVE PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30 [PORTION 1: SUB 1 TO EXISTING AIS S/S]
  • 21. SCOPE OF WORK SCOPE ITEM QTY REMARKS ROUTE LENGTH 320 M DIVERSION OF EXISTING 115KV OHTL FROM POINT B1 TO POINT B4 (GANTRY) TAPPING FOR LILO Not Applicable CONDUCTOR GZTACSR EQUIVALENT TO CONDUCTOR CODE CURLEW TOTAL CONDUCTOR 1.920 KM D/C, SINGLE CONDUCTOR PER PHASE STEEL MONOPOLES 03 NOS “SEC FAMILY OF TOWERS” SUSPENSION POLES 00 NOS ANGLE POLES 03 NOS DE TOWERS 00 NOS S/C GANTRY 02 NOS INSULATORS COMPOSITE LONG ROD 40mm/KV OPGW 0.640 KM 96C [ITU-T G652D] OHTL DISMANTLING 400 M EXISTING 115KV OHTL PORTION TO BE DISMANTLED PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30 [PORTION 2: SUB 40 TO EXISTING BGP AIS S/S]
  • 22. SCOPE OF WORK SCOPE ITEM QTY REMARKS ROUTE LENGTH 320 M DIVERSION OF EXISTING 115KV OHTL FROM POINT F1 TO POINT F4 (GANTRY) TAPPING FOR LILO Not Applicable CONDUCTOR ACSR/AW “DRAKE” TOTAL CONDUCTOR 1.920 KM D/C, SINGLE CONDUCTOR PER PHASE STEEL MONOPOLES 03 NOS “SEC FAMILY OF TOWERS” SUSPENSION POLES 00 NOS ANGLE POLES 02 NOS DE TOWERS 01 NOS S/C GANTRY 02 NOS INCLUDED IN S/S PTS INSULATORS COMPOSITE LONG ROD 40mm/KV OPGW 0.640 KM 96C [ITU-T G652D] OHTL DISMANTLING 120 M EXISTING 115KV OHTL PORTION TO BE DISMANTLED PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30 [PORTION 3: M2/M1]
  • 23. SCOPE OF WORK SCOPE ITEM QTY REMARKS ROUTE LENGTH 305 M DIVERSION OF EXISTING 115KV OHTL FROM POINT E1 TO POINT E4 (GANTRY) TAPPING FOR LILO Not Applicable CONDUCTOR ACSR/AW “DRAKE” TOTAL CONDUCTOR 1.830 KM D/C, SINGLE CONDUCTOR PER PHASE STEEL MONOPOLES 03 NOS “SEC FAMILY OF TOWERS” SUSPENSION POLES 00 NOS ANGLE POLES 02 NOS DE TOWERS 01 NOS S/C GANTRY 02 NOS INCLUDED IN S/S PTS INSULATORS COMPOSITE LONG ROD 40mm/KV OPGW 0.610 KM 96C [ITU-T G652D] OHTL DISMANTLING 120 M EXISTING 115KV OHTL PORTION TO BE DISMANTLED PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30 [PORTION 4: M4/M3]
  • 24. SCOPE OF WORK SCOPE ITEM QTY REMARKS ROUTE LENGTH 300 M DIVERSION OF EXISTING 115KV OHTL FROM POINT D1 TO POINT D4 (GANTRY) TAPPING FOR LILO Not Applicable CONDUCTOR ACSR/AW “DRAKE” TOTAL CONDUCTOR 1.800 KM D/C, SINGLE CONDUCTOR PER PHASE STEEL MONOPOLES 03 NOS “SEC FAMILY OF TOWERS” SUSPENSION POLES 00 NOS ANGLE POLES 02 NOS DE TOWERS 01 NOS S/C GANTRY 02 NOS INCLUDED IN S/S PTS INSULATORS COMPOSITE LONG ROD 40mm/KV OPGW 0.600 KM 96C [ITU-T G652D] OHTL DISMANTLING 120 M EXISTING 115KV OHTL PORTION TO BE DISMANTLED PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30 [PORTION 5: SUB-20]
  • 25. SCOPE OF WORK SCOPE ITEM QTY REMARKS ROUTE LENGTH 80 M DIVERSION OF EXISTING 115KV OHTL FROM POINT D1 TO POINT D4 (GANTRY) TAPPING FOR LILO Not Applicable CONDUCTOR ACSR/AW “DRAKE” TOTAL CONDUCTOR 480 M D/C, SINGLE CONDUCTOR PER PHASE STEEL MONOPOLES 01 NOS “SEC FAMILY OF TOWERS” SUSPENSION POLES 00 NOS ANGLE POLES 00 NOS DE TOWERS 01 NOS S/C GANTRY 02 NOS INSULATORS COMPOSITE LONG ROD 40mm/KV OPGW 160 M 96C [ITU-T G652D] OHTL DISMANTLING 125 M EXISTING 115KV OHTL PORTION TO BE DISMANTLED PART 3: SCOPE OF WORK FOR DIVERSION OF EXISTING 115KV OHTLS TO NEW BGP SUB-30 [PORTION 6: SUB-11]