Neural network based shunt active filter for harmonic reduction:
                   A technological review
               V.V.Appalanaidu Menda1, B Sankaraprasad2, Kotyada Kalyani3
                    1
                      Department of Electrical Engineering, st.Theresa Inst .of Engg &Tech, Garividi-535101
      2,3
            Associate Professor,Department of Electrical Engineering, st.Theresa Inst .of Engg &Tech, Garividi-535101
                                                        AndhraPradesh.



Abstract––The paper attempts to improve shunt active power filter performance using neural networks. Shunt Active
Power Filters (SAPF) are one of the viable solutions to eliminate the power line harmonic/reactive currents generated by
nonlinear loads and improve the power factor. Design and implementation are studied for a neural-network-based
controller to govern the dynamics of non-linear processes. The advantages of using neural networks for modeling non-
linear processes are shown together resulting implementation of the neural controller is able to eliminate the most
significant obstacles encountered in non-linear systems.

Keywords––Active power filter, Artificial neural networks, Harmonics mitigation, Power electronics, Power quality,
Voltage source inverter.

                                              I.        INTRODUCTION
           Power electronics based electronics based devices/equipments are a major key component of today’s modern
power processing, at the transmission as well as the distribution level because of the numerous advantages offered by them.
These devices, equipments, nonlinear load including saturated transformers, arc furnaces and semiconductor switches and so
on, draw non-sinusoidal currents from the utility. Although these power electronics devices have benefited the electrical and
electronics industry, these devices are also the main source of power harmonics in the power system. These power
harmonics are called electrical pollution which will degrade the quality of the power supply. As a result, filtering process for
these harmonics is needed in order to improve the quality of the power supply. Thus, active power filter seems to be a viable
alternative for power conditioning to control the harmonics level in the power system nowadays.
           Harmonics have a number of undesirable effects on the distribution system. They fall into two basic categories:
short-term and long-term. Short-term effects are usually the most noticeable and are related to excessive voltage distortion.
On the other hand, long-term effects often go undetected and are usually related to increased resistive losses or voltage
stresses. In addition, the harmonic currents produced by nonlinear loads can interact adversely with a wide range of power
system equipment, most notably capacitors, transformers, and motors, causing additional losses, overheating, and
overloading. These harmonic currents can also cause interferences

                                             II.       ACTIVE FILTERS
          The basic principle of APF is to utilize power electronics technologies to produce specific currents components
that cancel the harmonic currents components caused by the nonlinear load. Figure2.1 shows the components of a typical
APF system and their connections. The information regarding the harmonic currents and other system variables are passed to
the compensation current/voltage reference signal estimator [11]. The compensation reference signal from the estimator
drives the overall system controller. This in turn provides the control for the gating signal generator.




                                        Fig 2.1. Generalized block diagram for APF

                                                              32
Neural network based shunt active filter for harmonic reduction: A technological review

           A three-phase shunt APF is typically composed of a three-phase bridge converter and control circuitry. Most of
the previous control approaches need to sense the load current and calculate its harmonics and reactive components in order
to generate the reference for controlling the current of a bridge converter. Those control methods require fast and real-time
calculation; therefore, a high-speed digital microprocessor and high-performance A/D converters are necessary, which yields
high cost, complexity, and low stability.

2.1 Classification of Active Power Filters
           An unfavorable but inseparable feature of APF is the necessity of fast switching of high currents in the power
circuit of the APF. This results in a high frequency noise that may cause an electromagnetic interference (EMI) in the power
distribution systems [11]. APF can be connected in several power circuit configurations as illustrated in the block diagram
shown in Figure2.2 In general, they are divided into three main categories, namely shunt APF, series APF and hybrid APF.




                                        Fig2.2 classification of active power filters

2.2 Shunt Active Power Filter
          Shunt active power filter (SAPF) is commonly used as an effective method in compensating harmonic components
in non-linear loads[10]. Fig. 2.1 shows the basic principle of SAPF in which APF is connected in parallel to the power
system at a point of common coupling (PCC) between metropolitan electricity authority (MEA) and power users. The
objective of SAPF is to minimize the distortion in power supply using four main components – harmonic detection,
compensating current control, DC bus voltage control, and active power filter – as shown in Fig.2.2




                                     Fig. 2.1 The system using shunt active power filter




                                      Fig. 2.2 Three – phase shunt active power filter

          In the harmonic detection component, the distorted signal can be detected by several harmonic detection
techniques, i.e., the instantaneous reactive power theory (PQ), the synchronous reference frame (SRF), the d-q axis with
Fourier (DQF), and the synchronous detection (SD) etc. Then, APF injects the compensating currents into the power system.
The current control techniques are hysteresis current control, Pulse Width Modulation (PWM), and Space Vector
Modulation (SVM) etc. For dc bus voltage control, proportional integral (PI) is employed[10].
                                                            33
Neural network based shunt active filter for harmonic reduction: A technological review

                    III.      AN APPLICATION OF NEURAL NETWORK IN APF
          There are many conventional techniques to detect and compensate harmonic current. ANN is one of the modern
techniques which are used in many areas of application including harmonic eliminations [1][10]. Fig. 3.1 shows an
architecture of three-phase diagram of neural network controlled SAPF. A NN is used to control the compensating current
injection with SAPF.




                               Fig. 3.1 the active power filter control using NN approaches

        From the review several IEEE papers, it shows that neural network is employed to substitute a harmonic detection
component for the following reasons [10]:
    1. To increase the processing speed, response speed, and convergence speed.
    2. To increase the robustness.
    3. To increase the efficiency and performance of the algorithm.
    4. To increase the steady-state stability.
    5. To increase an accuracy, precision, and validity of the evaluation process.
    6. To increase an adaptive ability, so that it can response in real time.
    7. To increase tracking ability.
    8. To provide the optimal solution.

          NN is easy and convenient to use as a substitution of the current control component. Furthermore, the following
reasons are also given as the merit of the NN for current control process[10].
     1. To increase the performance and efficiency of the algorithm in order to improve power factor.
     2. To increase an accuracy, precision, and validity of the process.
     3. To eliminate the threat of resonance.
     4. To increase processing speed, response speed.
     5. To increase the steady-state stability.
     6. To reduce the switching frequency.

                  IV.        DESIGN CONSIDERATION FOR APF CONTROLLERS
         The block diagram of the proposed power line conditioner using active power filter is shown in Fig.4.1. The
proposed Modular Active power filter connected to the electric Distribution system. The line current signal is obtained and
fed to an ADALINE which extracts the fundamental components of the line current signal. In the controller block,
fundamental component is compared with distorted line current to generate modulating signal. This modulating signal is
used to generate Pulse-Width Modulated (PWM) switching pattern for the switches of the active line conditioner module.
The output current of the active filter is injected into the power line.




                                     Fig. 4.1: Block Diagram of the Proposed Scheme

                                                           34
Neural network based shunt active filter for harmonic reduction: A technological review

          The injected current, equal-but opposite to the harmonic components to be eliminated. Harmonics are suppressed
by connecting the active filter modules to the electric grid [3][4].
          Fig.4.2 consists of a single phase fully controlled converter feeding RL load, Active filter and its ANN based
control circuit. Fig.6 shows the details of control block using ANN. In the control block an improved scheme is proposed in
which only the actual Load current is given to adaptive neural network and the reference current is obtained [5][6]. The load
voltage is given to a DC regulator with a simple PI controller which gives the actual filter current and which is compared
with reference current the gating pulses to IGBTs are provided through a hysteresis band comparator




                 Fig 4.2: Simulated circuit diagram of ANN based active filter connected to non-linear load

4.1.1 Design of Low Pass Filter for Reference Current calculation
The reference current calculation for low pass filter for balanced load is




The d-axis current for balanced load can be written as.




Similarly for unbalanced load




          It can be seen from equations (4.4) and (4.5) that the first are the fundamental component of the load current and
both are of DC values [7]. The lowest frequency in the d-axis current is the third harmonic for the balanced load and the
fundamental frequency for the case of unbalanced load. Thus, to obtain the fundamental component for both the cases of
balanced and unbalanced loads, the cutoff frequency          a    must lie between the DC frequency (0 rad/sec) and the

fundamental frequency (377 rad/sec). In this paper,        a =100 rad/sec is chosen. This yields a delay time constant T a of
10ms.




                                                                35
Neural network based shunt active filter for harmonic reduction: A technological review

4.1.2 Design of Current Regulators
            The choice of cutoff frequency      f       in the simplified analytical model will influence the line current tracking
capability of the active power filter. To obtain a fast response and low overshoot for the current of an active power filter, a
higher value of   f   must be chosen. Unfortunately, the maximum value is limited by the maximum IGBT device switching
frequency.

4.1.3 Design of DC-link Voltage Regulator
            For the sake of simplicity in the design of a DC-link voltage regulator, the cutoff frequency        dc   of a low -pass

filter in the voltage detection block is equal to    a this gives


Thus, the delay time constant    Tdc is equal to 10 ms and equation can be written as.




For design convenience of controller parameters, reduced-order operation is exercised for equation (4.7) to obtain the
following standard second-order transfer function.




To obtain low overshoot for the DC-link voltage, the damping coefficient = 0.707 is chosen. The corresponding proportional
gain of a DC-link voltage controller is




Equation (4.11) reveals the dependence of the proportional gain on the DC-link capacitance           C2   DC-link voltage command
    *
V   dc 2
           peak value of phase voltage   Vm   and delay times     Tf   and   Tdc    .


                  1
n                           ----------------- (4.12)
             2 (T f  Tdc )
Finally, substitution of the system parameters yields          K pdc = 0.381 and  n =70.15 rad/sec. The value of K pdc =0.381 is
reasonable because the limiting value for     K pdc      for stable operation is 96.71.

4.2 Design Consideration for APF Controller
4.2.1 DC-Link Capacitor Design
          The output dc-link capacitor of voltage source converter is determined by the output voltage ripple. The equation
is given by




                                                                            -------------- (4.13)



                                                                       36
Neural network based shunt active filter for harmonic reduction: A technological review

Where Vomax , Vomin is the peak to peak of the output dc-link voltage ripple.

4.2.2 Selection of APF Inductance
          The concept of the proposed control is using one-cycle control to implement the control key equation as follows:
 Rs.ieq =Vm. (1-d) ---------------- (4.14)
Where
 ieq = (2ip + in) (OR) (ip +2 in)
Similar to the peak current model control, there is the convergence condition.

The stability condition is given by




                                            ----------------- (4.15)
Where m1 is the ON slope of the input current and m2 is the OFF slope of the input current; mc is the equivalent slope of
the carrier signal, which is implemented by integrator with reset.
Considering that the load current is low frequency and the influence of load current can be neglected, we only concern the
inductor current in the stability analysis, we have




Where



Therefore




The convergence condition is dependent on the angular angle of input voltage wt and the Vm, which is related to the output
power and input voltage. When the convergency condition is satisfied partially, the system will still be stable.

According to (4.17), convergence condition for region 0o~360o is given by




But Vm is related to input voltage and output power through (4.19) . It can be rewritten as




where η is the estimated efficiency.

Combination of the above equations yields




                                                              37
Neural network based shunt active filter for harmonic reduction: A technological review




4.2.3 Design of the Control stage:
          The large-signal model for a single-phase APF in line cycle can be derived based on energy balance. Suppose the
efficiency is 100%. The input power equal to the output power, that is




Where Re is emulated resistance and Pload is the load power and ic is the current flowing into the dc-link capacitor.
By definition, we have




Combination of the above equation yields




Considering the small ac signal disturbation, that is




 Neglecting the influence of load power, substitution of the (4.26) equation into (4.27) and linearize by considering the
following conditions
In addition, we can neglect the influence of input voltage disturbation by setting,
then we can get simplified solution as




The transfer function from capacitor current to output voltage is given by




Therefore, combination of the above equations (4.27) &(4.28) yields the following transfer function:




Equation (4.27) can be used to determine the design of the output feedback compensator.


                                                              38
Neural network based shunt active filter for harmonic reduction: A technological review

                                   V.        SIMULATION AND RESULTS
          Simulations have been conducted for balanced and unbalanced loads using SIMULINK for different controller
configurations. Switching frequency of the inverter is set at 10 kHz, and the dead time of the inverter is set at 2 μs. The
controller took 36 and 42 ms to converge in simulations. The controller is found to operate satisfactorily. Finally, the
performance of the proposed controller is compared with that of a traditional controller (such as synchronous reference
frame based). The synchronous reference frame controller is simulated (using the cutoff frequency of the low-pass filter as
10 Hz). A 110-V 50-Hz main supplying a load of 3 kVA is considered.




                                            Fig.5.1 three phase source currents




                            Fig 5.2 load currents of Phase a wave, Phase b wave, Phase c wave




                                                           39
Neural network based shunt active filter for harmonic reduction: A technological review




                              Fig 5.3 compensated source current of phase a, phase b, phase c




 Fig 5.4 Performance of the APF with ADALINE (simulation results). Top waveform: Source current of phase A (scale: 5
 A/div). Middle waveform: Load current of phase A (scale: 5 A/div). Bottom waveform: Compensating current of phase A
                                                   (scale: 5 A/div).

                                               VI.       CONCLUSION
           Different power harmonic sources exist mainly due to nonlinear loads made up of power electronics devices.
Active filters main principle of operation is injecting harmonic current into the ac system, of the same amplitude and reverse


                                                             40
Neural network based shunt active filter for harmonic reduction: A technological review

phase to that of the load current harmonics.. This will thus result in sinusoidal line currents and unity power factor in the
input power system.
          An integration of ANN-based controller for a shunt-type APF has been presented in this paper to improve the
convergence and reduce the computational requirement. The algorithm is derived from an ANN based PWM controller used
to regulate the dc-link voltage in the APF. This is followed by an adaline-based THD minimization technique. The results
from Experiments match well with the simulation, confirming the usefulness of proposed technique.

                                                    REFERENCES
[1].     Avik Bhattacharya, and Chandan Chakraborty, “A Shunt Active Power Filter With Enhanced Performance Using
         ANN-Based Predictive and Adaptive Controllers” IEEE Transactions On Industrial Electronics, Vol. 58, No. 2,
         February 2011.
[2].     Yang Han and Lin Xu “Design and Implementation of a Robust Predictive Control Scheme for Active Power
         Filters”. JPE 11-5-16
[3].     Chongming Qiao and Keyue Ma Smedley; “Three-Phase Bipolar Mode Active Power Filters”, IEEE Transactions
         on Industry Applications, vol. 38, no. 1, January/February 2002
[4].     Chongming Qiao ,Keyue M. Smedley and Franco Maddaleno; “A Single-Phase Active Power Filter With One-
         CycleControl Under Unipolar Operationn”, IEEE Transactions on Circuits and systems vol. 51, no. 8, august
         2004.
[5].     J. Sebastian Tepper, Juan W. Dixon,Gustavo Venegas, and Luis Morh; “A Simple Frequency-Independent Method
         for Calculating the Reactive and Harmonic Current in a Nonlinear Load”, IEEE Transactions on Industrial
         Electronics, vol. 43, no. 6, December 1996.
[6].     Chongming Qiao, Taotao Jin and Keyue M. Smedley; “Unified Constant-frequency Integration Control of Three-
         phase Active-Power-Filter with Vector Operation”, 2001 IEEE.
[7].     Wang Yong, Shen Songhua, Guan Miao; “Three-phase Active Power Filter Based on Space Vector and One-cycle
         Control”, IEEE IPEMC 2006.
[8].     H.-H.Kuo, S.-N.Yeh and J.-C.Hwang; “Novel analytical model for design and implementation of three-phase
         active power filter controller”, IEE Proc.-Electr. Power Appl.. Vol. 148, No. 4, July 2001.
 [9].     Mircea Lazar and Octavian Pastravanu “A Neural Predictive Controller For Non-linear Systems”
[10].    S. Janpong, K-L. Areerak and K-N. Areerak “A Literature Survey of Neural Network Applications for Shunt
         Active Power Filters”, World Academy of Science, Engineering and Technology 60 2011.
[11].    Zainal Salam, Tan Perng Cheng and Awang Jusoh Harmonics Mitigation Using Active Power Filter: A
         Technological Review




                                                            41

More Related Content

PDF
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
PDF
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
PDF
Battery energy storage and power electronics based voltage and frequency cont...
PDF
Kw2519001905
PDF
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
PDF
Improved Power Quality by using STATCOM Under Various Loading Conditions
PDF
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
PDF
Grid-Connection Control and Simulation of PMSG Wind Power System Based on Mul...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
Battery energy storage and power electronics based voltage and frequency cont...
Kw2519001905
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
Improved Power Quality by using STATCOM Under Various Loading Conditions
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
Grid-Connection Control and Simulation of PMSG Wind Power System Based on Mul...

What's hot (19)

PDF
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
PDF
MICROCONTROLLER BASED SOLAR POWER INVERTER
PDF
I010416376
PDF
A New Approach to Powerflow Management in Transmission System Using Interline...
PDF
A1103030111
PDF
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
PDF
Simulation of a 13-Level Inverter with Facts Capability for Distributed Energ...
PDF
Performance Analysis of DC Micro Grid with PV-Fuel Cell Hybrid Generation
PDF
IRJET - Optimal Scheduling of Solar Wind Bio-Mass Systems and Evaluating the ...
PDF
LOAD FREQUENCY CONTROL IN TWO AREA NETWORK INCLUDING DG
PDF
Integration of Unified Power Quality Controller with DG
PDF
J010417781
PDF
Grid Connected Distributed Generation System with High Voltage Gain Cascaded ...
PDF
Fractional Order PID Controlled Cascaded Re-boost Seven Level Inverter Fed In...
PDF
M0104198105
PDF
Dw33741745
PDF
K010418290
PDF
Hysteresis SVM for Coupled Inductor Z Source Diode Clamped 3-Level Inverter B...
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
MICROCONTROLLER BASED SOLAR POWER INVERTER
I010416376
A New Approach to Powerflow Management in Transmission System Using Interline...
A1103030111
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Simulation of a 13-Level Inverter with Facts Capability for Distributed Energ...
Performance Analysis of DC Micro Grid with PV-Fuel Cell Hybrid Generation
IRJET - Optimal Scheduling of Solar Wind Bio-Mass Systems and Evaluating the ...
LOAD FREQUENCY CONTROL IN TWO AREA NETWORK INCLUDING DG
Integration of Unified Power Quality Controller with DG
J010417781
Grid Connected Distributed Generation System with High Voltage Gain Cascaded ...
Fractional Order PID Controlled Cascaded Re-boost Seven Level Inverter Fed In...
M0104198105
Dw33741745
K010418290
Hysteresis SVM for Coupled Inductor Z Source Diode Clamped 3-Level Inverter B...
Ad

Viewers also liked (20)

PDF
Living Longer, Living Better: Reform Report #2 - GT review Australia
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PDF
Thomas Piesch - intrduction “Making the Connection” – Practical Experiences o...
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PPTX
James Herbert Willams - Disaster, Risk and Human Security
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PPTX
Security and safety of cross-border infrastructure
PPTX
Seven elements for capacity development for disaster risk reduction
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
ODT
Science 1
PPT
A regional multi-risk assessment approach to support the definition public mi...
PDF
Spatio-temporal analyses of the impacts of extreme weather events on renewabl...
PPS
FASTID project - FAST and efficient international disaster victim IDentification
PDF
Scores.schoenberg pianopierrot
PDF
Success and rest don't sleep together.
PDF
GT IBR 2012 - focus on Ireland
PPT
Weather aware, climate prepared.
Living Longer, Living Better: Reform Report #2 - GT review Australia
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
Thomas Piesch - intrduction “Making the Connection” – Practical Experiences o...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
James Herbert Willams - Disaster, Risk and Human Security
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
Security and safety of cross-border infrastructure
Seven elements for capacity development for disaster risk reduction
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
Science 1
A regional multi-risk assessment approach to support the definition public mi...
Spatio-temporal analyses of the impacts of extreme weather events on renewabl...
FASTID project - FAST and efficient international disaster victim IDentification
Scores.schoenberg pianopierrot
Success and rest don't sleep together.
GT IBR 2012 - focus on Ireland
Weather aware, climate prepared.
Ad

Similar to IJERD (www.ijerd.com) International Journal of Engineering Research and Development (20)

PDF
Advanced Techniques in Harmonic Suppression via Active Power Filter: A Review
PDF
Power Quality Improvement in Distribution System using ANN Based Shunt Active...
PDF
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
PDF
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
PDF
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
PDF
Power System Harmonic Compensation Using Shunt Active Power Filter
PDF
Harmonic Mitigation using Modified Synchronous Reference Frame Theory
PDF
Power system harmonic reduction using shunt active filter
PDF
Design of shunt active power filter to mitigate harmonic
PDF
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
PDF
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
PDF
Neuro fuzzy control technique in hybrid power filter for power quality improv...
PPTX
Prateek PPT.pptx
PDF
A new fuzzy based control strategy for three phase shunt active power filters
PDF
Optimize Controlling of Active Filters Controlled by Pi Controller
PDF
Shunt active power filters based on diode clamped multilevel inverter and hys...
PDF
Shunt active power filters based on diode clamped multilevel inverter and hys...
PDF
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
PDF
Simulation and Hardware Implementation of Shunt Active Power Filter Based on ...
PDF
A011140104
Advanced Techniques in Harmonic Suppression via Active Power Filter: A Review
Power Quality Improvement in Distribution System using ANN Based Shunt Active...
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
Power System Harmonic Compensation Using Shunt Active Power Filter
Harmonic Mitigation using Modified Synchronous Reference Frame Theory
Power system harmonic reduction using shunt active filter
Design of shunt active power filter to mitigate harmonic
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
Neuro fuzzy control technique in hybrid power filter for power quality improv...
Prateek PPT.pptx
A new fuzzy based control strategy for three phase shunt active power filters
Optimize Controlling of Active Filters Controlled by Pi Controller
Shunt active power filters based on diode clamped multilevel inverter and hys...
Shunt active power filters based on diode clamped multilevel inverter and hys...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Simulation and Hardware Implementation of Shunt Active Power Filter Based on ...
A011140104

More from IJERD Editor (20)

PDF
A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
PDF
MEMS MICROPHONE INTERFACE
PDF
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
PDF
Gold prospecting using Remote Sensing ‘A case study of Sudan’
PDF
Reducing Corrosion Rate by Welding Design
PDF
Router 1X3 – RTL Design and Verification
PDF
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
PDF
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
PDF
Study on the Fused Deposition Modelling In Additive Manufacturing
PDF
Spyware triggering system by particular string value
PDF
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
PDF
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
PDF
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
PDF
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
PDF
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
PDF
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
PDF
Moon-bounce: A Boon for VHF Dxing
PDF
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
PDF
Importance of Measurements in Smart Grid
PDF
Study of Macro level Properties of SCC using GGBS and Lime stone powder
A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
MEMS MICROPHONE INTERFACE
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Reducing Corrosion Rate by Welding Design
Router 1X3 – RTL Design and Verification
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Study on the Fused Deposition Modelling In Additive Manufacturing
Spyware triggering system by particular string value
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Moon-bounce: A Boon for VHF Dxing
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
Importance of Measurements in Smart Grid
Study of Macro level Properties of SCC using GGBS and Lime stone powder

Recently uploaded (20)

PDF
Unlocking AI with Model Context Protocol (MCP)
PDF
Encapsulation theory and applications.pdf
PPTX
Big Data Technologies - Introduction.pptx
PDF
Encapsulation_ Review paper, used for researhc scholars
PDF
Network Security Unit 5.pdf for BCA BBA.
DOCX
The AUB Centre for AI in Media Proposal.docx
PDF
Spectral efficient network and resource selection model in 5G networks
PDF
Architecting across the Boundaries of two Complex Domains - Healthcare & Tech...
PPTX
Cloud computing and distributed systems.
PPT
Teaching material agriculture food technology
PPTX
Understanding_Digital_Forensics_Presentation.pptx
PDF
The Rise and Fall of 3GPP – Time for a Sabbatical?
PDF
Electronic commerce courselecture one. Pdf
PDF
Blue Purple Modern Animated Computer Science Presentation.pdf.pdf
PDF
Chapter 3 Spatial Domain Image Processing.pdf
PDF
Review of recent advances in non-invasive hemoglobin estimation
PPTX
Detection-First SIEM: Rule Types, Dashboards, and Threat-Informed Strategy
PDF
KodekX | Application Modernization Development
PPTX
Effective Security Operations Center (SOC) A Modern, Strategic, and Threat-In...
PPTX
PA Analog/Digital System: The Backbone of Modern Surveillance and Communication
Unlocking AI with Model Context Protocol (MCP)
Encapsulation theory and applications.pdf
Big Data Technologies - Introduction.pptx
Encapsulation_ Review paper, used for researhc scholars
Network Security Unit 5.pdf for BCA BBA.
The AUB Centre for AI in Media Proposal.docx
Spectral efficient network and resource selection model in 5G networks
Architecting across the Boundaries of two Complex Domains - Healthcare & Tech...
Cloud computing and distributed systems.
Teaching material agriculture food technology
Understanding_Digital_Forensics_Presentation.pptx
The Rise and Fall of 3GPP – Time for a Sabbatical?
Electronic commerce courselecture one. Pdf
Blue Purple Modern Animated Computer Science Presentation.pdf.pdf
Chapter 3 Spatial Domain Image Processing.pdf
Review of recent advances in non-invasive hemoglobin estimation
Detection-First SIEM: Rule Types, Dashboards, and Threat-Informed Strategy
KodekX | Application Modernization Development
Effective Security Operations Center (SOC) A Modern, Strategic, and Threat-In...
PA Analog/Digital System: The Backbone of Modern Surveillance and Communication

IJERD (www.ijerd.com) International Journal of Engineering Research and Development

  • 1. International Journal of Engineering Research and Development e-ISSN: 2278-067X, p-ISSN: 2278-800X, www.ijerd.com Volume 2, Issue 11 (August 2012), PP. 32-41 Neural network based shunt active filter for harmonic reduction: A technological review V.V.Appalanaidu Menda1, B Sankaraprasad2, Kotyada Kalyani3 1 Department of Electrical Engineering, st.Theresa Inst .of Engg &Tech, Garividi-535101 2,3 Associate Professor,Department of Electrical Engineering, st.Theresa Inst .of Engg &Tech, Garividi-535101 AndhraPradesh. Abstract––The paper attempts to improve shunt active power filter performance using neural networks. Shunt Active Power Filters (SAPF) are one of the viable solutions to eliminate the power line harmonic/reactive currents generated by nonlinear loads and improve the power factor. Design and implementation are studied for a neural-network-based controller to govern the dynamics of non-linear processes. The advantages of using neural networks for modeling non- linear processes are shown together resulting implementation of the neural controller is able to eliminate the most significant obstacles encountered in non-linear systems. Keywords––Active power filter, Artificial neural networks, Harmonics mitigation, Power electronics, Power quality, Voltage source inverter. I. INTRODUCTION Power electronics based electronics based devices/equipments are a major key component of today’s modern power processing, at the transmission as well as the distribution level because of the numerous advantages offered by them. These devices, equipments, nonlinear load including saturated transformers, arc furnaces and semiconductor switches and so on, draw non-sinusoidal currents from the utility. Although these power electronics devices have benefited the electrical and electronics industry, these devices are also the main source of power harmonics in the power system. These power harmonics are called electrical pollution which will degrade the quality of the power supply. As a result, filtering process for these harmonics is needed in order to improve the quality of the power supply. Thus, active power filter seems to be a viable alternative for power conditioning to control the harmonics level in the power system nowadays. Harmonics have a number of undesirable effects on the distribution system. They fall into two basic categories: short-term and long-term. Short-term effects are usually the most noticeable and are related to excessive voltage distortion. On the other hand, long-term effects often go undetected and are usually related to increased resistive losses or voltage stresses. In addition, the harmonic currents produced by nonlinear loads can interact adversely with a wide range of power system equipment, most notably capacitors, transformers, and motors, causing additional losses, overheating, and overloading. These harmonic currents can also cause interferences II. ACTIVE FILTERS The basic principle of APF is to utilize power electronics technologies to produce specific currents components that cancel the harmonic currents components caused by the nonlinear load. Figure2.1 shows the components of a typical APF system and their connections. The information regarding the harmonic currents and other system variables are passed to the compensation current/voltage reference signal estimator [11]. The compensation reference signal from the estimator drives the overall system controller. This in turn provides the control for the gating signal generator. Fig 2.1. Generalized block diagram for APF 32
  • 2. Neural network based shunt active filter for harmonic reduction: A technological review A three-phase shunt APF is typically composed of a three-phase bridge converter and control circuitry. Most of the previous control approaches need to sense the load current and calculate its harmonics and reactive components in order to generate the reference for controlling the current of a bridge converter. Those control methods require fast and real-time calculation; therefore, a high-speed digital microprocessor and high-performance A/D converters are necessary, which yields high cost, complexity, and low stability. 2.1 Classification of Active Power Filters An unfavorable but inseparable feature of APF is the necessity of fast switching of high currents in the power circuit of the APF. This results in a high frequency noise that may cause an electromagnetic interference (EMI) in the power distribution systems [11]. APF can be connected in several power circuit configurations as illustrated in the block diagram shown in Figure2.2 In general, they are divided into three main categories, namely shunt APF, series APF and hybrid APF. Fig2.2 classification of active power filters 2.2 Shunt Active Power Filter Shunt active power filter (SAPF) is commonly used as an effective method in compensating harmonic components in non-linear loads[10]. Fig. 2.1 shows the basic principle of SAPF in which APF is connected in parallel to the power system at a point of common coupling (PCC) between metropolitan electricity authority (MEA) and power users. The objective of SAPF is to minimize the distortion in power supply using four main components – harmonic detection, compensating current control, DC bus voltage control, and active power filter – as shown in Fig.2.2 Fig. 2.1 The system using shunt active power filter Fig. 2.2 Three – phase shunt active power filter In the harmonic detection component, the distorted signal can be detected by several harmonic detection techniques, i.e., the instantaneous reactive power theory (PQ), the synchronous reference frame (SRF), the d-q axis with Fourier (DQF), and the synchronous detection (SD) etc. Then, APF injects the compensating currents into the power system. The current control techniques are hysteresis current control, Pulse Width Modulation (PWM), and Space Vector Modulation (SVM) etc. For dc bus voltage control, proportional integral (PI) is employed[10]. 33
  • 3. Neural network based shunt active filter for harmonic reduction: A technological review III. AN APPLICATION OF NEURAL NETWORK IN APF There are many conventional techniques to detect and compensate harmonic current. ANN is one of the modern techniques which are used in many areas of application including harmonic eliminations [1][10]. Fig. 3.1 shows an architecture of three-phase diagram of neural network controlled SAPF. A NN is used to control the compensating current injection with SAPF. Fig. 3.1 the active power filter control using NN approaches From the review several IEEE papers, it shows that neural network is employed to substitute a harmonic detection component for the following reasons [10]: 1. To increase the processing speed, response speed, and convergence speed. 2. To increase the robustness. 3. To increase the efficiency and performance of the algorithm. 4. To increase the steady-state stability. 5. To increase an accuracy, precision, and validity of the evaluation process. 6. To increase an adaptive ability, so that it can response in real time. 7. To increase tracking ability. 8. To provide the optimal solution. NN is easy and convenient to use as a substitution of the current control component. Furthermore, the following reasons are also given as the merit of the NN for current control process[10]. 1. To increase the performance and efficiency of the algorithm in order to improve power factor. 2. To increase an accuracy, precision, and validity of the process. 3. To eliminate the threat of resonance. 4. To increase processing speed, response speed. 5. To increase the steady-state stability. 6. To reduce the switching frequency. IV. DESIGN CONSIDERATION FOR APF CONTROLLERS The block diagram of the proposed power line conditioner using active power filter is shown in Fig.4.1. The proposed Modular Active power filter connected to the electric Distribution system. The line current signal is obtained and fed to an ADALINE which extracts the fundamental components of the line current signal. In the controller block, fundamental component is compared with distorted line current to generate modulating signal. This modulating signal is used to generate Pulse-Width Modulated (PWM) switching pattern for the switches of the active line conditioner module. The output current of the active filter is injected into the power line. Fig. 4.1: Block Diagram of the Proposed Scheme 34
  • 4. Neural network based shunt active filter for harmonic reduction: A technological review The injected current, equal-but opposite to the harmonic components to be eliminated. Harmonics are suppressed by connecting the active filter modules to the electric grid [3][4]. Fig.4.2 consists of a single phase fully controlled converter feeding RL load, Active filter and its ANN based control circuit. Fig.6 shows the details of control block using ANN. In the control block an improved scheme is proposed in which only the actual Load current is given to adaptive neural network and the reference current is obtained [5][6]. The load voltage is given to a DC regulator with a simple PI controller which gives the actual filter current and which is compared with reference current the gating pulses to IGBTs are provided through a hysteresis band comparator Fig 4.2: Simulated circuit diagram of ANN based active filter connected to non-linear load 4.1.1 Design of Low Pass Filter for Reference Current calculation The reference current calculation for low pass filter for balanced load is The d-axis current for balanced load can be written as. Similarly for unbalanced load It can be seen from equations (4.4) and (4.5) that the first are the fundamental component of the load current and both are of DC values [7]. The lowest frequency in the d-axis current is the third harmonic for the balanced load and the fundamental frequency for the case of unbalanced load. Thus, to obtain the fundamental component for both the cases of balanced and unbalanced loads, the cutoff frequency a must lie between the DC frequency (0 rad/sec) and the fundamental frequency (377 rad/sec). In this paper,  a =100 rad/sec is chosen. This yields a delay time constant T a of 10ms. 35
  • 5. Neural network based shunt active filter for harmonic reduction: A technological review 4.1.2 Design of Current Regulators The choice of cutoff frequency f in the simplified analytical model will influence the line current tracking capability of the active power filter. To obtain a fast response and low overshoot for the current of an active power filter, a higher value of f must be chosen. Unfortunately, the maximum value is limited by the maximum IGBT device switching frequency. 4.1.3 Design of DC-link Voltage Regulator For the sake of simplicity in the design of a DC-link voltage regulator, the cutoff frequency  dc of a low -pass filter in the voltage detection block is equal to  a this gives Thus, the delay time constant Tdc is equal to 10 ms and equation can be written as. For design convenience of controller parameters, reduced-order operation is exercised for equation (4.7) to obtain the following standard second-order transfer function. To obtain low overshoot for the DC-link voltage, the damping coefficient = 0.707 is chosen. The corresponding proportional gain of a DC-link voltage controller is Equation (4.11) reveals the dependence of the proportional gain on the DC-link capacitance C2 DC-link voltage command * V dc 2 peak value of phase voltage Vm and delay times Tf and Tdc . 1 n  ----------------- (4.12) 2 (T f  Tdc ) Finally, substitution of the system parameters yields K pdc = 0.381 and  n =70.15 rad/sec. The value of K pdc =0.381 is reasonable because the limiting value for K pdc for stable operation is 96.71. 4.2 Design Consideration for APF Controller 4.2.1 DC-Link Capacitor Design The output dc-link capacitor of voltage source converter is determined by the output voltage ripple. The equation is given by -------------- (4.13) 36
  • 6. Neural network based shunt active filter for harmonic reduction: A technological review Where Vomax , Vomin is the peak to peak of the output dc-link voltage ripple. 4.2.2 Selection of APF Inductance The concept of the proposed control is using one-cycle control to implement the control key equation as follows: Rs.ieq =Vm. (1-d) ---------------- (4.14) Where ieq = (2ip + in) (OR) (ip +2 in) Similar to the peak current model control, there is the convergence condition. The stability condition is given by ----------------- (4.15) Where m1 is the ON slope of the input current and m2 is the OFF slope of the input current; mc is the equivalent slope of the carrier signal, which is implemented by integrator with reset. Considering that the load current is low frequency and the influence of load current can be neglected, we only concern the inductor current in the stability analysis, we have Where Therefore The convergence condition is dependent on the angular angle of input voltage wt and the Vm, which is related to the output power and input voltage. When the convergency condition is satisfied partially, the system will still be stable. According to (4.17), convergence condition for region 0o~360o is given by But Vm is related to input voltage and output power through (4.19) . It can be rewritten as where η is the estimated efficiency. Combination of the above equations yields 37
  • 7. Neural network based shunt active filter for harmonic reduction: A technological review 4.2.3 Design of the Control stage: The large-signal model for a single-phase APF in line cycle can be derived based on energy balance. Suppose the efficiency is 100%. The input power equal to the output power, that is Where Re is emulated resistance and Pload is the load power and ic is the current flowing into the dc-link capacitor. By definition, we have Combination of the above equation yields Considering the small ac signal disturbation, that is Neglecting the influence of load power, substitution of the (4.26) equation into (4.27) and linearize by considering the following conditions In addition, we can neglect the influence of input voltage disturbation by setting, then we can get simplified solution as The transfer function from capacitor current to output voltage is given by Therefore, combination of the above equations (4.27) &(4.28) yields the following transfer function: Equation (4.27) can be used to determine the design of the output feedback compensator. 38
  • 8. Neural network based shunt active filter for harmonic reduction: A technological review V. SIMULATION AND RESULTS Simulations have been conducted for balanced and unbalanced loads using SIMULINK for different controller configurations. Switching frequency of the inverter is set at 10 kHz, and the dead time of the inverter is set at 2 μs. The controller took 36 and 42 ms to converge in simulations. The controller is found to operate satisfactorily. Finally, the performance of the proposed controller is compared with that of a traditional controller (such as synchronous reference frame based). The synchronous reference frame controller is simulated (using the cutoff frequency of the low-pass filter as 10 Hz). A 110-V 50-Hz main supplying a load of 3 kVA is considered. Fig.5.1 three phase source currents Fig 5.2 load currents of Phase a wave, Phase b wave, Phase c wave 39
  • 9. Neural network based shunt active filter for harmonic reduction: A technological review Fig 5.3 compensated source current of phase a, phase b, phase c Fig 5.4 Performance of the APF with ADALINE (simulation results). Top waveform: Source current of phase A (scale: 5 A/div). Middle waveform: Load current of phase A (scale: 5 A/div). Bottom waveform: Compensating current of phase A (scale: 5 A/div). VI. CONCLUSION Different power harmonic sources exist mainly due to nonlinear loads made up of power electronics devices. Active filters main principle of operation is injecting harmonic current into the ac system, of the same amplitude and reverse 40
  • 10. Neural network based shunt active filter for harmonic reduction: A technological review phase to that of the load current harmonics.. This will thus result in sinusoidal line currents and unity power factor in the input power system. An integration of ANN-based controller for a shunt-type APF has been presented in this paper to improve the convergence and reduce the computational requirement. The algorithm is derived from an ANN based PWM controller used to regulate the dc-link voltage in the APF. This is followed by an adaline-based THD minimization technique. The results from Experiments match well with the simulation, confirming the usefulness of proposed technique. REFERENCES [1]. Avik Bhattacharya, and Chandan Chakraborty, “A Shunt Active Power Filter With Enhanced Performance Using ANN-Based Predictive and Adaptive Controllers” IEEE Transactions On Industrial Electronics, Vol. 58, No. 2, February 2011. [2]. Yang Han and Lin Xu “Design and Implementation of a Robust Predictive Control Scheme for Active Power Filters”. JPE 11-5-16 [3]. Chongming Qiao and Keyue Ma Smedley; “Three-Phase Bipolar Mode Active Power Filters”, IEEE Transactions on Industry Applications, vol. 38, no. 1, January/February 2002 [4]. Chongming Qiao ,Keyue M. Smedley and Franco Maddaleno; “A Single-Phase Active Power Filter With One- CycleControl Under Unipolar Operationn”, IEEE Transactions on Circuits and systems vol. 51, no. 8, august 2004. [5]. J. Sebastian Tepper, Juan W. Dixon,Gustavo Venegas, and Luis Morh; “A Simple Frequency-Independent Method for Calculating the Reactive and Harmonic Current in a Nonlinear Load”, IEEE Transactions on Industrial Electronics, vol. 43, no. 6, December 1996. [6]. Chongming Qiao, Taotao Jin and Keyue M. Smedley; “Unified Constant-frequency Integration Control of Three- phase Active-Power-Filter with Vector Operation”, 2001 IEEE. [7]. Wang Yong, Shen Songhua, Guan Miao; “Three-phase Active Power Filter Based on Space Vector and One-cycle Control”, IEEE IPEMC 2006. [8]. H.-H.Kuo, S.-N.Yeh and J.-C.Hwang; “Novel analytical model for design and implementation of three-phase active power filter controller”, IEE Proc.-Electr. Power Appl.. Vol. 148, No. 4, July 2001. [9]. Mircea Lazar and Octavian Pastravanu “A Neural Predictive Controller For Non-linear Systems” [10]. S. Janpong, K-L. Areerak and K-N. Areerak “A Literature Survey of Neural Network Applications for Shunt Active Power Filters”, World Academy of Science, Engineering and Technology 60 2011. [11]. Zainal Salam, Tan Perng Cheng and Awang Jusoh Harmonics Mitigation Using Active Power Filter: A Technological Review 41