UNDER THE GUIDENCE OF
Prof. BASAVARAJ H TALIKOTI
Mechanical dept.
SPCE Bengaluru
SHRI PILLAPPA COLLEGE OF ENGINEERING
OVERVIEWOVERVIEW
 Abstract
 Introduction
 Literature Survey
 Layout of experimental set up
 Specifications
 Experimental Work
 Methodology
 Operating procedure
 Sample Reading
 Results And Discussion
 Graphs
 Conclusions
 Scope for future Work
 References
ABSTRACTABSTRACT
 In the present work the experimental setup for
convective heat transfer coefficient of air flowing
through a copper tube of circular cross section is
fabricated. This setup can be used to find out heat
transfer coefficient at different operating conditions.
 Using the experimental setup, convective heat transfer
coefficient of air passing through circular duct was
determined under the following conditions.
o By varying heat input.
o By varying blower valve position.
o By varying inclination of circular duct.
INTRODUCTIONINTRODUCTION
Heat transfer is defined as “transmission of energy from
one region to another as a result of temperature gradient”.
LITERATURE SURVEYLITERATURE SURVEY
 Hilpert was one of the earliest researchers in the area of forced
convection from heated pipe surfaces. He developed the correlation
Nu= hd/K) =C Re
m
Pr0.333.
 Fand and Keswani reviewed the work of Hilpert and recalculated
the values of the constants C and m in the above equation using
more accurate values for the thermo physical properties of air.
 Zukaukasz Another correlation proposed by Zukaukas for
convective heat transfer over a heated pipe is given by
Nuf =c Ref Prf
0.37
( Prf/ Prw)0.25
 Churchill and Bernstein Churchill and Bernstein proposed a
single comprehensive equation[5] that covered the entire range of
ReD for which data was available, as well as a wide range of Pr.
The equation was recommended for all ReD.Pr > 0.2 and has the
form
NuD= 0.3+ *[1+(ReD/282,000)5/8
]4/5
This correlation was based on semi-empirical work and all
properties were evaluated at the film temperature.
Contd…..Contd…..
 Dittus Boelter relation
The conventional expression for calculating the heat transfer
coefficient in fully developed turbulent flow in smooth pipes is the
Dittus Boelter equation
Nu = C Rem Prn
 where C, m and n are constant determined experimentally. these
values - C=0.023, m=0.8 and
 n = 0.4 for heating of the fluid
 n = 0.3 for cooling of the fluid
 Properties of this relation have been calculated at the average fluid
bulk temperatures. Equation is valid for single phase heat transfer
in fully developed turbulent flows in smooth pipes for fluids with
Prandtl number ranging from 0.6 to 100 at low heat fluxes. At high
fluxes the fluid properties changes resulting in higher errors.
LAYOUT OF EXPERIMENTALLAYOUT OF EXPERIMENTAL
SET UPSET UP
Where T1
= inlet temperature of air
T6
= outlet temperature of air
T ,T ,T ,T = Specimen surface temperature
SPECIFICATIONSSPECIFICATIONS
 Specimen : Copper circular Tube.
 Size of the Specimen : 33 mm x 33 mm x 500 mm long.
 Heater : Externally heated, Nichrome wire
Band Heater 500W.
 Ammeter : Digital type,0-20amps, AC.
 Voltmeter : Digital type, 0-300volts, AC.
 Dimmer stat for heating Coil : 0-230v, 2amps.
 Thermocouple Used : 6 no. k-type, range: 0 to 4000
c.
 Centrifugal Blower : Single Phase 230v, 50 Hz,
13000rpm.
 G. I pipe diameter : 33 mm.
 Outer duct : Aluminum
EXPERIMENTAL WORKEXPERIMENTAL WORK
Fig. 1Test section copper circular duct with
insulation and heater at 0º.º.
.
Fig 2: Experimental Setup of circular duct with
Insulation and Heater at 30º.
Fig 3: Experimental Set up of circular duct
with Insulation and Heater at 60º.
Fig 4: Experimental Setup of circular duct with
Insulation and Heater at 90º.
Contd….Contd….
Fig 5:Experimental Setup of Circular Cross
Section Duct at 1200
Fig 6:Experimental Setup of Circular Cross
Section Duct at 1500
 The above figure shows an experimental setup which comprises
of test specimen made up of copper having circular cross section
having dimensions 33x33x500mm, which is connected to a blower
through a GI pipe and bellows.
 The equipment is mounted on a 2ftX3ft rectangular table which
is made up of mild steel sheets and plane woods.
Contd….Contd….
 Angle of inclination can be varied in terms of 300,
600
,
90°,120° and 150° with the help of lever and nut-bolt
arrangement.
 Here five thermocouples of k-type, two for inlet and
outlet i.e. T4 and T5, rest of the three (i.e. T1,T2 andT3)
thermocouples are placed at equal distance on the
surface of test specimen.
 With the help of blower regulator, velocity of air can be
set.
 Heat input can be set with the help of variac provided on
control panel and same can be read out digitally with the
help of voltmeter and ammeter.
 Manometer is provided on the board to indicate the
level and hence velocity for different valve opening can
METHODOLOGYMETHODOLOGY
 The apparatus consists of a blower for forced
circulation.
 The air from the blower passes through a flow passage
at different valve positions, heater and then to the test
section.
 A heater placed around the tube heats the air, heat input
is controlled by a dimmer stat. Heat input is measured
with the help of voltmeter and ammeter.
 Temperature of the air at inlet and at outlet are measured
using thermocouples. The surface temperature of the
tube is measured at different sections using
thermocouples embedded on the circular duct.
 Test section is enclosed with wool and rope, where the
circulation of rope avoids the heat loss to outside.
 The entire test rig is mounted on a table as shown
OPERATING PROCEDUREOPERATING PROCEDURE
 Plug the 230 Volts AC mains to the main supply line and switch
ON mains.
 Put on the heater and adjust the voltage to a desired value by using
electronic voltage regulator and maintain it as constant
 Switch ON the Blower and regulate the flow for desired value by
using electronic regulator (First press the switch on the blower and
then control through the electronic regulator)
 Allow the system to stabilize (reach steady state).This may take
about 10-15 minutes.
 Note down all the temperatures T1 to T5, voltmeter, ammeter
readings and manometer readings.
 Repeat the experiment for different heat input and air flow rates.
SAMPLE READINGSSAMPLE READINGS
Readings for the velocity of 11.097 m/s and 40v heat input at 00
Procedure for calculation
Sl
No.
Manometer
reading in
cm
V
volts
I amps T1
0
c T2
0
c T3
0
c T4
0
c T5
0
c
h1 h2 hw
01 0.7 0 0.7 40 0.61 40.6 42.7 40.3 40.6 40
Contd….
 Note down all the parameters which are displayed on control
panel,which includes voltage, current & all temperatures.
 Calculate the surface temperature and ambient temperatures by
using the following formulae :
surface temp = (T1+T2+T3)/3
Ta= (T6+T5)/2
Tfilm =( Ts+Ta)/2
 Find the properties of air at film temperature like kinematic viscosity (ν),
prandtl number (Pr), thermal conductivity (K) from heat transfer data
hand book.
 Calculate the Reynolds number (Re), with the formula Re =
ρvD/μ
 Based on the Reynolds number, select the Hilpert’s constants like
C and m.
 Calculate Nusselt number using parameters Pr,C,m,ReD and the
formula is
Nu = C Rem
x
pr0.333
.
 Calculate the convective heat transfer coefficient by using the
formula.
h=( KxNu)/ D
Contd….
 Repeat the calculation part for following different situations.
 By keeping the valve openening and varying the heat input in
terms of 40,60,80,100,120 and 140 m/sec ,for various angle of
inclinations like 00
,300
,600
,900
,120° and 150°.
 And also varying the blower valve positions by 1/4th
,1/2,3/4th
and
full open, for various angle of inclinations like
00
,300
,600
,900
,120° and 150°.
 Tabulate all the calculations for separate angle of inclinations.
RESULTS AND DISCUSSIONRESULTS AND DISCUSSION
SL NO.
 
Inclination Valve
position
Velocity
(m/s)
Heat input
(W) Re Nu
H
(kW/m2 0
k)
01 00
1/4th
11.097 140.3 21369 81.02 64.98
1/2 12.578 140.3 25132.5 89.6 70.911
3/4th
12.58 140.3 24736.01 88.768 70.038
Full 11.094 140.3 22266.085 83.1905 65.237
02 300
1/4th
8.386 140.3 16052.12 68.052 54.533
1/2 12.58 140.3 24729.285 88.73 70.243
3/4th
12.58 140.3 24926.84 89.183 70.397
Full 11.86 140.3 23680.18 86.397 67.967
03 600
1/4th 9.375 140.3 17835.88 72.45 58.314
1/2 16.245 140.3 31869.22 103.637 81.99
3/4th
16.245 140.3 32268.645 104.615 82.49
Full 16.245 140.3 32191.638 104.498 82.45
SL NO. Inclination Valve
position
Velocity
(m/s)
Heat input
(W) Re Nu
h
(kW/m2 0
k)
04 900
1/4th 9.375 140.3 18026.91 72.92 120.86
1/2 20.54 140.3 40866.74 120.86 95.382
3/4th
22.966 140.3 46128.92 130.99 102.74
Full 23.72 140.3 47907.577 135.04 105.64
05 1200
1/4th
13.26 140.3 25766.61 90.988 72.51
1/2 21.787 140.3 43276.04 124.92 98.48
3/4th
23.345 140.3 46297.83 131.1 103.56
Full 23.34 140.3 46990.67 132.915 104.26
06 1500
1/4th
12.57 140.3 21042.95 81.36 70.12
1/2 19.66 140.3 39401.96 117.44 92.255
3/4th 24.08 140.3 48753.44 136.91 108.44
Full 23.34 140.3 46549.82 130.92 103.88
Variation of heat transfer coefficient withVariation of heat transfer coefficient with
inclination for different velocitiesinclination for different velocities
 As it seen from the above graph velocity of air flow influences the
heat transfer coefficient at a greater extent than the inclination.
GRAPHS
Variation of Reynolds number andVariation of Reynolds number and
Nusselts number at all inclinationsNusselts number at all inclinations
 From the above graph it is clear that, irrespective of angle of inclination
of duct, there is a direct proportionality between the Reynolds number
(Re) and Nusselts (Nu) number. i.e., by increasing the velocity of air there
must be an increase in the Reynolds number and Nusselts number, thus
increasing the heat transfer coefficient.
CONCLUSIONSCONCLUSIONS
 During the test it was found that convective heat transfer
coefficient increases in air stream velocity at constant heat input
and inclination.
 From the result it is evident that heat transfer coefficient is
maximum for a constant heat input of undergoes and 9.375 m/sec
velocity when the when the duct was inclined at 900
inclination.
 The minimum heat transfer coefficient was observed for heat input
of 292.6watts and air stream velocity of 8.386 m/sec with 300
inclinations.
 The decrease in heat transfer coefficient may be due to restriction
in the flow of air when the duct is above 900
.
SCOPE FOR FUTURE WORKSCOPE FOR FUTURE WORK
 The experimentation can be carried out for different fluids.
 The determination of variation of heat transfer coefficient for
varying cross section of the copper duct.
 The test rig can be computerized to obtain more accurate results.
 Fins can be attached on the specimen and the effect of fins on heat
transfer coefficient can be studied.
ReferencesReferences
 Krishpersad Manohar, Kimberly Ramroop. “A Comparison of Correlations for
Heat Transfer from Inclined Pipes” Volume 4, Issue 4, October 2010.
 2. Hilpert, R. “Heat Transfer from Cylinders,” Forsch. Geb. Ingenieurwes, 4:215,
1933.
 3. Fand, R. M. and K. K. Keswani. “A Continuous Correlation Equation for Heat
Transfer from
 Cylinders to Air in Crossflow for Reynold’s Numbers from 10-2 to 2(10)5,”
International Journal of Heat and Mass Transfer, 15:559-562, 1972.
 4.Zukauskas, A. “Heat Transfer From Tubes in Crossflow,” Advances in Heat
Transfer, 8:87-159, 1987.
 5. Churchill, S. W. and M. Bernstein. “A correlating Equation for Forced Convection
from Gases and Liquids to a Circular Cylinder in Crossflow,” J. Heat Transfer,
99:300-306, 1977.
 Sunil S and Basavaraj H Talikoti, “Fabrication Of Experimental Setup To Evaluate
The Convective Heat Transfer Coefficient Of Air Flowing Through An Inclined
Circular Cross Section Duct”. ISSN: 2278-0181 www.ijert.org IJERTV4IS020027
Vol. 4 Issue 02, February-2015.
THANK YOU

More Related Content

PDF
Heat transfer(HT) lab manual
DOCX
Manual tables all new
PDF
PDF
Lab%201
PPT
Se prod thermo_examples_compressor
PDF
Heat transfer experiment for chemical engineering student
PDF
Hmt lab manual (heat and mass transfer lab manual)
PDF
Heat transfer(HT) lab manual
Manual tables all new
Lab%201
Se prod thermo_examples_compressor
Heat transfer experiment for chemical engineering student
Hmt lab manual (heat and mass transfer lab manual)

What's hot (20)

PPT
Se prod thermo_examples_mst
PPT
Thermodynamics Problems Chapter 1
PDF
Thermal transfer Characteristics of TCM
PDF
Draught and chimney
PPTX
Thermodynamics - Experiment 2
PDF
Beikircher solar energy 1996 2
PDF
Cfd Simulation and Experimentalverification of Air Flow through Heated Pipe
PPT
Thermodynamics Examples and Class test
PDF
A046040105
PDF
Lab manuals Heat Transfer Manuals
DOCX
Isentropic Blow-Down Process and Discharge Coefficient
DOCX
To examine the temperature profile and to determine thermal conductor from ra...
PDF
Dana Gilbert - second year lab report
PPTX
heat pipe heat exchanger
PDF
Radial heat conduction
DOCX
To investigate Fourier’s Law for the linear conduction of heat along a homoge...
PDF
Boiler calculations
PDF
Maquinas y equipos termicos
PPTX
design and analysis of heat exchanger
PDF
Methods of handling Supply air in HVAC
Se prod thermo_examples_mst
Thermodynamics Problems Chapter 1
Thermal transfer Characteristics of TCM
Draught and chimney
Thermodynamics - Experiment 2
Beikircher solar energy 1996 2
Cfd Simulation and Experimentalverification of Air Flow through Heated Pipe
Thermodynamics Examples and Class test
A046040105
Lab manuals Heat Transfer Manuals
Isentropic Blow-Down Process and Discharge Coefficient
To examine the temperature profile and to determine thermal conductor from ra...
Dana Gilbert - second year lab report
heat pipe heat exchanger
Radial heat conduction
To investigate Fourier’s Law for the linear conduction of heat along a homoge...
Boiler calculations
Maquinas y equipos termicos
design and analysis of heat exchanger
Methods of handling Supply air in HVAC
Ad

Similar to FABRICATION OF EXPERIMENTAL SETUP TO EVALUATE CONVECTIVE HEAT TRANSFER COEFFICIENT OF AIR FLOWING THROUGH AN INCLINED CIRCULAR CROSS SECTION DUCT (20)

PDF
Evaluation of Convective Heat Transfer Coefficient of Air Flowing Through an ...
PDF
Prediction of friction factor and non dimensions numbers in force convection
PDF
EXPERIMENTAL INVESTIGATION OF CONVECTION HEAT TRANSFER FOR LAMINAR FLOW IN AN...
PDF
30120140504020
PDF
International Journal of Engineering Research and Development
PDF
IRJET- Experimental Investigation of Enhancement of Convective Heat Trans...
PDF
forced heat convection | HEAT TRANSFER Laboratory
PDF
Lect 9 Forced convection.pdf
PDF
IRJET- Study of Heat Transfer Coefficient in Natural and Forced Convection by...
PDF
Design of Heat Exchanger
PDF
NATURAL CONVECTION HEAT TRANSFER INSIDE INCLINED OPEN CYLINDER
PDF
Enhancement of Heat Transfer and Thermo-Hydraulic Performance Using Triangula...
PDF
Free and Forced Convection
PDF
Ld35191119013
PDF
Paper id 21201420
PDF
Natural convection heat transfer in inclined open annulus passege heated from...
PDF
Experimental analysis of heat transfer enhancementin circular
PDF
PERFORMANCE ENHANCEMENT OF HEAT EXCHANGERS USING VORTEX FLAPS
DOCX
Lab Report Conduction With Free Convection
Evaluation of Convective Heat Transfer Coefficient of Air Flowing Through an ...
Prediction of friction factor and non dimensions numbers in force convection
EXPERIMENTAL INVESTIGATION OF CONVECTION HEAT TRANSFER FOR LAMINAR FLOW IN AN...
30120140504020
International Journal of Engineering Research and Development
IRJET- Experimental Investigation of Enhancement of Convective Heat Trans...
forced heat convection | HEAT TRANSFER Laboratory
Lect 9 Forced convection.pdf
IRJET- Study of Heat Transfer Coefficient in Natural and Forced Convection by...
Design of Heat Exchanger
NATURAL CONVECTION HEAT TRANSFER INSIDE INCLINED OPEN CYLINDER
Enhancement of Heat Transfer and Thermo-Hydraulic Performance Using Triangula...
Free and Forced Convection
Ld35191119013
Paper id 21201420
Natural convection heat transfer in inclined open annulus passege heated from...
Experimental analysis of heat transfer enhancementin circular
PERFORMANCE ENHANCEMENT OF HEAT EXCHANGERS USING VORTEX FLAPS
Lab Report Conduction With Free Convection
Ad

Recently uploaded (20)

PPTX
Module 8- Technological and Communication Skills.pptx
PPTX
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
PDF
BIO-INSPIRED ARCHITECTURE FOR PARSIMONIOUS CONVERSATIONAL INTELLIGENCE : THE ...
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PPTX
Information Storage and Retrieval Techniques Unit III
PDF
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
PPTX
Artificial Intelligence
PDF
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
PPTX
Fundamentals of safety and accident prevention -final (1).pptx
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PPTX
Software Engineering and software moduleing
PPTX
Sorting and Hashing in Data Structures with Algorithms, Techniques, Implement...
PDF
Categorization of Factors Affecting Classification Algorithms Selection
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PPTX
communication and presentation skills 01
PPT
Occupational Health and Safety Management System
PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
PPTX
Feature types and data preprocessing steps
PDF
III.4.1.2_The_Space_Environment.p pdffdf
PDF
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
Module 8- Technological and Communication Skills.pptx
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
BIO-INSPIRED ARCHITECTURE FOR PARSIMONIOUS CONVERSATIONAL INTELLIGENCE : THE ...
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
Information Storage and Retrieval Techniques Unit III
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
Artificial Intelligence
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
Fundamentals of safety and accident prevention -final (1).pptx
Automation-in-Manufacturing-Chapter-Introduction.pdf
Software Engineering and software moduleing
Sorting and Hashing in Data Structures with Algorithms, Techniques, Implement...
Categorization of Factors Affecting Classification Algorithms Selection
R24 SURVEYING LAB MANUAL for civil enggi
communication and presentation skills 01
Occupational Health and Safety Management System
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
Feature types and data preprocessing steps
III.4.1.2_The_Space_Environment.p pdffdf
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...

FABRICATION OF EXPERIMENTAL SETUP TO EVALUATE CONVECTIVE HEAT TRANSFER COEFFICIENT OF AIR FLOWING THROUGH AN INCLINED CIRCULAR CROSS SECTION DUCT

  • 1. UNDER THE GUIDENCE OF Prof. BASAVARAJ H TALIKOTI Mechanical dept. SPCE Bengaluru SHRI PILLAPPA COLLEGE OF ENGINEERING
  • 2. OVERVIEWOVERVIEW  Abstract  Introduction  Literature Survey  Layout of experimental set up  Specifications  Experimental Work  Methodology  Operating procedure  Sample Reading  Results And Discussion  Graphs  Conclusions  Scope for future Work  References
  • 3. ABSTRACTABSTRACT  In the present work the experimental setup for convective heat transfer coefficient of air flowing through a copper tube of circular cross section is fabricated. This setup can be used to find out heat transfer coefficient at different operating conditions.  Using the experimental setup, convective heat transfer coefficient of air passing through circular duct was determined under the following conditions. o By varying heat input. o By varying blower valve position. o By varying inclination of circular duct.
  • 4. INTRODUCTIONINTRODUCTION Heat transfer is defined as “transmission of energy from one region to another as a result of temperature gradient”.
  • 5. LITERATURE SURVEYLITERATURE SURVEY  Hilpert was one of the earliest researchers in the area of forced convection from heated pipe surfaces. He developed the correlation Nu= hd/K) =C Re m Pr0.333.  Fand and Keswani reviewed the work of Hilpert and recalculated the values of the constants C and m in the above equation using more accurate values for the thermo physical properties of air.  Zukaukasz Another correlation proposed by Zukaukas for convective heat transfer over a heated pipe is given by Nuf =c Ref Prf 0.37 ( Prf/ Prw)0.25  Churchill and Bernstein Churchill and Bernstein proposed a single comprehensive equation[5] that covered the entire range of ReD for which data was available, as well as a wide range of Pr. The equation was recommended for all ReD.Pr > 0.2 and has the form NuD= 0.3+ *[1+(ReD/282,000)5/8 ]4/5 This correlation was based on semi-empirical work and all properties were evaluated at the film temperature.
  • 6. Contd…..Contd…..  Dittus Boelter relation The conventional expression for calculating the heat transfer coefficient in fully developed turbulent flow in smooth pipes is the Dittus Boelter equation Nu = C Rem Prn  where C, m and n are constant determined experimentally. these values - C=0.023, m=0.8 and  n = 0.4 for heating of the fluid  n = 0.3 for cooling of the fluid  Properties of this relation have been calculated at the average fluid bulk temperatures. Equation is valid for single phase heat transfer in fully developed turbulent flows in smooth pipes for fluids with Prandtl number ranging from 0.6 to 100 at low heat fluxes. At high fluxes the fluid properties changes resulting in higher errors.
  • 7. LAYOUT OF EXPERIMENTALLAYOUT OF EXPERIMENTAL SET UPSET UP Where T1 = inlet temperature of air T6 = outlet temperature of air T ,T ,T ,T = Specimen surface temperature
  • 8. SPECIFICATIONSSPECIFICATIONS  Specimen : Copper circular Tube.  Size of the Specimen : 33 mm x 33 mm x 500 mm long.  Heater : Externally heated, Nichrome wire Band Heater 500W.  Ammeter : Digital type,0-20amps, AC.  Voltmeter : Digital type, 0-300volts, AC.  Dimmer stat for heating Coil : 0-230v, 2amps.  Thermocouple Used : 6 no. k-type, range: 0 to 4000 c.  Centrifugal Blower : Single Phase 230v, 50 Hz, 13000rpm.  G. I pipe diameter : 33 mm.  Outer duct : Aluminum
  • 9. EXPERIMENTAL WORKEXPERIMENTAL WORK Fig. 1Test section copper circular duct with insulation and heater at 0º.º. . Fig 2: Experimental Setup of circular duct with Insulation and Heater at 30º. Fig 3: Experimental Set up of circular duct with Insulation and Heater at 60º. Fig 4: Experimental Setup of circular duct with Insulation and Heater at 90º.
  • 10. Contd….Contd…. Fig 5:Experimental Setup of Circular Cross Section Duct at 1200 Fig 6:Experimental Setup of Circular Cross Section Duct at 1500  The above figure shows an experimental setup which comprises of test specimen made up of copper having circular cross section having dimensions 33x33x500mm, which is connected to a blower through a GI pipe and bellows.  The equipment is mounted on a 2ftX3ft rectangular table which is made up of mild steel sheets and plane woods.
  • 11. Contd….Contd….  Angle of inclination can be varied in terms of 300, 600 , 90°,120° and 150° with the help of lever and nut-bolt arrangement.  Here five thermocouples of k-type, two for inlet and outlet i.e. T4 and T5, rest of the three (i.e. T1,T2 andT3) thermocouples are placed at equal distance on the surface of test specimen.  With the help of blower regulator, velocity of air can be set.  Heat input can be set with the help of variac provided on control panel and same can be read out digitally with the help of voltmeter and ammeter.  Manometer is provided on the board to indicate the level and hence velocity for different valve opening can
  • 12. METHODOLOGYMETHODOLOGY  The apparatus consists of a blower for forced circulation.  The air from the blower passes through a flow passage at different valve positions, heater and then to the test section.  A heater placed around the tube heats the air, heat input is controlled by a dimmer stat. Heat input is measured with the help of voltmeter and ammeter.  Temperature of the air at inlet and at outlet are measured using thermocouples. The surface temperature of the tube is measured at different sections using thermocouples embedded on the circular duct.  Test section is enclosed with wool and rope, where the circulation of rope avoids the heat loss to outside.  The entire test rig is mounted on a table as shown
  • 13. OPERATING PROCEDUREOPERATING PROCEDURE  Plug the 230 Volts AC mains to the main supply line and switch ON mains.  Put on the heater and adjust the voltage to a desired value by using electronic voltage regulator and maintain it as constant  Switch ON the Blower and regulate the flow for desired value by using electronic regulator (First press the switch on the blower and then control through the electronic regulator)  Allow the system to stabilize (reach steady state).This may take about 10-15 minutes.  Note down all the temperatures T1 to T5, voltmeter, ammeter readings and manometer readings.  Repeat the experiment for different heat input and air flow rates.
  • 14. SAMPLE READINGSSAMPLE READINGS Readings for the velocity of 11.097 m/s and 40v heat input at 00 Procedure for calculation Sl No. Manometer reading in cm V volts I amps T1 0 c T2 0 c T3 0 c T4 0 c T5 0 c h1 h2 hw 01 0.7 0 0.7 40 0.61 40.6 42.7 40.3 40.6 40 Contd….  Note down all the parameters which are displayed on control panel,which includes voltage, current & all temperatures.  Calculate the surface temperature and ambient temperatures by using the following formulae : surface temp = (T1+T2+T3)/3 Ta= (T6+T5)/2 Tfilm =( Ts+Ta)/2  Find the properties of air at film temperature like kinematic viscosity (ν), prandtl number (Pr), thermal conductivity (K) from heat transfer data hand book.
  • 15.  Calculate the Reynolds number (Re), with the formula Re = ρvD/μ  Based on the Reynolds number, select the Hilpert’s constants like C and m.  Calculate Nusselt number using parameters Pr,C,m,ReD and the formula is Nu = C Rem x pr0.333 .  Calculate the convective heat transfer coefficient by using the formula. h=( KxNu)/ D Contd….  Repeat the calculation part for following different situations.  By keeping the valve openening and varying the heat input in terms of 40,60,80,100,120 and 140 m/sec ,for various angle of inclinations like 00 ,300 ,600 ,900 ,120° and 150°.  And also varying the blower valve positions by 1/4th ,1/2,3/4th and full open, for various angle of inclinations like 00 ,300 ,600 ,900 ,120° and 150°.  Tabulate all the calculations for separate angle of inclinations.
  • 17. SL NO.   Inclination Valve position Velocity (m/s) Heat input (W) Re Nu H (kW/m2 0 k) 01 00 1/4th 11.097 140.3 21369 81.02 64.98 1/2 12.578 140.3 25132.5 89.6 70.911 3/4th 12.58 140.3 24736.01 88.768 70.038 Full 11.094 140.3 22266.085 83.1905 65.237 02 300 1/4th 8.386 140.3 16052.12 68.052 54.533 1/2 12.58 140.3 24729.285 88.73 70.243 3/4th 12.58 140.3 24926.84 89.183 70.397 Full 11.86 140.3 23680.18 86.397 67.967 03 600 1/4th 9.375 140.3 17835.88 72.45 58.314 1/2 16.245 140.3 31869.22 103.637 81.99 3/4th 16.245 140.3 32268.645 104.615 82.49 Full 16.245 140.3 32191.638 104.498 82.45
  • 18. SL NO. Inclination Valve position Velocity (m/s) Heat input (W) Re Nu h (kW/m2 0 k) 04 900 1/4th 9.375 140.3 18026.91 72.92 120.86 1/2 20.54 140.3 40866.74 120.86 95.382 3/4th 22.966 140.3 46128.92 130.99 102.74 Full 23.72 140.3 47907.577 135.04 105.64 05 1200 1/4th 13.26 140.3 25766.61 90.988 72.51 1/2 21.787 140.3 43276.04 124.92 98.48 3/4th 23.345 140.3 46297.83 131.1 103.56 Full 23.34 140.3 46990.67 132.915 104.26 06 1500 1/4th 12.57 140.3 21042.95 81.36 70.12 1/2 19.66 140.3 39401.96 117.44 92.255 3/4th 24.08 140.3 48753.44 136.91 108.44 Full 23.34 140.3 46549.82 130.92 103.88
  • 19. Variation of heat transfer coefficient withVariation of heat transfer coefficient with inclination for different velocitiesinclination for different velocities  As it seen from the above graph velocity of air flow influences the heat transfer coefficient at a greater extent than the inclination. GRAPHS
  • 20. Variation of Reynolds number andVariation of Reynolds number and Nusselts number at all inclinationsNusselts number at all inclinations  From the above graph it is clear that, irrespective of angle of inclination of duct, there is a direct proportionality between the Reynolds number (Re) and Nusselts (Nu) number. i.e., by increasing the velocity of air there must be an increase in the Reynolds number and Nusselts number, thus increasing the heat transfer coefficient.
  • 21. CONCLUSIONSCONCLUSIONS  During the test it was found that convective heat transfer coefficient increases in air stream velocity at constant heat input and inclination.  From the result it is evident that heat transfer coefficient is maximum for a constant heat input of undergoes and 9.375 m/sec velocity when the when the duct was inclined at 900 inclination.  The minimum heat transfer coefficient was observed for heat input of 292.6watts and air stream velocity of 8.386 m/sec with 300 inclinations.  The decrease in heat transfer coefficient may be due to restriction in the flow of air when the duct is above 900 .
  • 22. SCOPE FOR FUTURE WORKSCOPE FOR FUTURE WORK  The experimentation can be carried out for different fluids.  The determination of variation of heat transfer coefficient for varying cross section of the copper duct.  The test rig can be computerized to obtain more accurate results.  Fins can be attached on the specimen and the effect of fins on heat transfer coefficient can be studied.
  • 23. ReferencesReferences  Krishpersad Manohar, Kimberly Ramroop. “A Comparison of Correlations for Heat Transfer from Inclined Pipes” Volume 4, Issue 4, October 2010.  2. Hilpert, R. “Heat Transfer from Cylinders,” Forsch. Geb. Ingenieurwes, 4:215, 1933.  3. Fand, R. M. and K. K. Keswani. “A Continuous Correlation Equation for Heat Transfer from  Cylinders to Air in Crossflow for Reynold’s Numbers from 10-2 to 2(10)5,” International Journal of Heat and Mass Transfer, 15:559-562, 1972.  4.Zukauskas, A. “Heat Transfer From Tubes in Crossflow,” Advances in Heat Transfer, 8:87-159, 1987.  5. Churchill, S. W. and M. Bernstein. “A correlating Equation for Forced Convection from Gases and Liquids to a Circular Cylinder in Crossflow,” J. Heat Transfer, 99:300-306, 1977.  Sunil S and Basavaraj H Talikoti, “Fabrication Of Experimental Setup To Evaluate The Convective Heat Transfer Coefficient Of Air Flowing Through An Inclined Circular Cross Section Duct”. ISSN: 2278-0181 www.ijert.org IJERTV4IS020027 Vol. 4 Issue 02, February-2015.