SlideShare a Scribd company logo
IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163
__________________________________________________________________________________________
Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 504
INTEGRATION OF ARTIFICIAL INTELLIGENCE CONTROL TO THE
UNIFIED POWER QUALITY CONDITIONER
T.Madhurantaka1
, S. Muni Sekhar2
, P.Lokesh3
tarasimadhu@gmail.com, munisekhar1980@gmail.com, lokesh.parukuru@live.com
Abstract
Modernization of the Industrial world is completely accompanied with growing power demands. It is very necessary to utilize the
available power efficiently with as much less issues as possible rather than focusing on the excessive generation to meet the demand.
UPQC consist of combined series active power filter that compensates voltage harmonics of the power supply, and shunt active power
filter that compensates harmonic currents of a non-linear load. We need to focus on the control of UPQC to achieve the best results.
Artificial Neural Networks is now considered as a tool for the design of controller for the Power Quality devices. In this paper, the
ANN-based controller is designed for the current control of the shunt active power filter and trained offline using data from the
conventional PI controller. An exhaustive simulation study is carried out to investigate the performance of the ANN controller and
compare its performance with the conventional PI controller results.
Index Terms: Power Quality, Unified Power Quality Conditioner, Artificial Neural Networks, Proportional Integral, CSI,
VSI, Harmonics.
-----------------------------------------------------------------------***-----------------------------------------------------------------------
1. INTRODUCTION
With the usage of more sensitive loads such as Automation
Equipment in the Industrial operation, Communication
Equipment, Medical equipment, and military equipment
power quality has become a significant issue to both
customers and the Utility companies. For the effective
utilization of the available power, the elimination or mitigation
of disturbances propagated from the supply system is
absolutely required to improve the operational reliability of all
the connected loads. To meet the requirements of Harmonic
regulation, Power quality enhancement passive and active
power filters are being used in combination with the
conventional converters. Availability of power semiconductor
devices made the usage of Active Power Filters more
compared to the Passive filters. Besides it, the APF also
provides multiple functions like Harmonic filtering, Damping,
Isolation and termination , Load balancing, Voltage
regulation, Power factor correction, Voltage flicker reduction
etc.,. UPQC has been widely studied in order to improve
Universal power quality by many researchers. The
performance of UPQC mainly depends upon how accurately
and quickly reference signals are derived. After efficient
extraction of the distorted signal, a suitable dc-link current
regulator is used to derive the actual reference signals. Various
control approaches, such as the PI, PID, fuzzy-logic, sliding-
mode, predictive, unified constant frequency (UCF)
controllers, etc., are in use. The frequency converter is
achieved by matrix converter. The main advantage of
frequency converter is as follow. Matrix converter can only
increase or decrease the frequency instead of cyclo converter.
Here there is no dc storage element. So losses are minimized
and Harmonics also minimized UPQC has the potential
drawbacks in the hybrid filtering performance as its filter in
characteristics depends on load impedance and supply
frequency. PI and PID controllers need a precise mathematical
model to be derived for their design and there is a major
drawback that they fail to operate under parameter variation
and load disturbances etc.
There has been a continuous research effort taken to develop
new and unconventional control techniques that can
effectively the drawbacks of the conventional controllers and
take an effective position in the control center. A Large
number of modern techniques have evolved, offering solutions
to many difficult control problems in industry and
manufacturing sectors. Unlike their conventional counter-
parts, these unconventional controllers (intelligent controllers)
can learn, remember, and make decisions. Artificial-
intelligence (AI) techniques, particularly the NNs, are having
a significant impact on the power electronics applications.
Neural-network-based controllers provide fast dynamic
response while maintaining the stability of the converter
system over a wide operating range and are considered as a
new tool to design control circuits for PQ devices. With the
motive of designing the controller for the UPQC for the
effective control, obtain the reliable control algorithms, and
faster response to produce the output signals. In this paper, for
improving the performance of a UPQC, a multilayer feed
forward-type ANN-based controller is designed for the current
control of the shunt active filter instead of the conventional PI
controller. An algorithm for training the ANN controller is
IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163
__________________________________________________________________________________________
Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 505
developed and trained offline. Various simulation results are
presented and are compared with the results that are obtained
with the conventional PI Controller. A DSP based
microcontroller is used for the real time simulation and
implementation of the control algorithm. The system
configuration is described in Section II, while PI and ANN
controller design are explained in Sections III and IV,
respectively. Simulation results are discussed in Sections V
with relevant waveforms and tabular column of simulated
parameter values.
2. SYSTEM CONFIGURATION
The configuration of a general UPQC consists of the
combination of a series active power filter and shunt active
power filter. The main aim of the series active power filter is
harmonic isolation between a sub-transmission system and a
distribution system; it has the capability of voltage flicker/
imbalance compensation as well as voltage regulation and
harmonic compensation at the utility-consumer point of
common coupling (PCC). The shunt active power filter is used
to absorb current harmonics, compensate for reactive power
and negative-sequence current, and regulate the dc-link
voltage between both active power filters. It can be configured
either with voltage-source converters or current source
converters in single phase, three-phase three wire, or three-
phase four-wire configurations. The block diagram of the
UPQC is as shown in the fig. 1.
Fig: 1 Block diagram of UPQC.
Although the Voltage Sourced configuration is the most
common practice, the VSI topology has slow control of the
converter (LC filter) output voltage and no short-
circuit/overcurrent protection. When the active rectifier inside
the UPQC is used as a power factor corrector, dc bus voltage
oscillations appear which makes the control of the series filter
output voltage more difficult. The CSI-based UPQC has
advantages of excellent current control capability, easy
protection, and high reliability over VSI-based UPQC. The
main drawback of the CSI-based UPQC has been so far the
lack of proper switching devices and large dc-side filter. The
new insulated-gate bipolar transistors (IGBTs) with reverse
blocking capability are being launched in the markets which
are suitable for the CSI-based UPQC. With the use of SMES
coils, the size and losses can be reduced considerably. A
configuration of UPQC using two current-source converters
connected back to back through a large dc-link reactor is
shown in Fig.
Fig: 2 MATLAB Simulation Circuit of the UPQC integrated
into the simple power system network.
3. DESIGN OF PI CONTROLLER
Since the dc-link current is controlled by the shunt filter, we
need to design the Controller for the shunt filter. The
following basic equations are used for designing the control
system:
Is = Il – iinj (1)
Iinj = d2idc (2)
Lsh
diinj
dt
= Vl – iinjRsh = Vl - Vsh (3)
In order to control the filter current (iinj), the only control
variable is the duty cycle of the PWM converter. The problem
of control is to determine the duty cycle (d2) in such a way
that the dc-link current remains constant and to produce
suitable filter current to cancel the load current harmonics.
This filter current should be opposite of the harmonic current,
which is split into two components (i.e., one loss component
plus the reactive component and another harmonic
component). The energy transfer to the continuous side takes
place only at the fundamental frequency to compensate all of
the losses in the PWM converter). Thus, it is required to
control two outputs, namely idc and iinj from one control
variable (i.e., the duty cycle of the PWM converter). However,
the main objective is to control the filter current, and the
control strategy must lead to precise compensation of the
harmonic component. The value of needs to only be
approximately constant and there is no dynamic performance
to be attained. The more it is constant, the more linear the
system will be. Hence, Iinjis controlled indirectly by
processing the actual source current and estimated reference
current in a hysteresis current controller. These reference
IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163
__________________________________________________________________________________________
Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 506
currents are estimated by regulating dc-link current. In order
to estimate the steady-state error in the dc-link current, a PI
controller is used. Although the dynamic response of the dc-
link inductor has no effect on the compensation feature of the
scheme, a mathematical model is required for the stability
analysis and, hence, for determining the parameters of the PI
controller. The following assumptions are made for deriving
the mathematical model of the system.
1) The voltage at PCC is sinusoidal and balanced.
2) Since the harmonic component does not affect the average
power balance expressions, only the fundamental component
of currents is considered.
3) Losses of the system are lumped and represented by an
Equivalent resistance Rshconnected in series with the filter
inductor Lsh.
4) Ripples in the dc-link current are neglected.
The block diagram of the current control loop is shown in Fig.
3,
Fig: 3 Block diagram of the current control loop
Where,
‗G‘ is the gain of the PI Controller, ‗Kc‘ is the transfer
function of the PWM converter.
Linear model of the PWM converter can be derived by
applying a small-signal perturbation technique to obtain its
transfer function. In this method of deriving a linear model,
the system is assumed to operate in the steady state, and the
defining equations are linearized for small-signal perturbation.
The relation between the input (ac side) and output (dc-link
side) quantities of the PWM converter are obtained by
equating the rate of change of energy associated.
1) The average rate at which energy being absorbed by the
inductor is
Pind =
𝑑
𝑑𝑡
(
1
2
LDCIDC
2
) = LDCIDC(
𝑑
𝑑𝑡
IDC) (4)
2) The power input to the PWM Converter
Pconv = 3 VshIinj (5)
3) The average rate of change of energy associated with the
capacitor filter is
Pcap = 3
𝑑
𝑑𝑡
(
1
2
CshVsh
2
) (6)
Power loss in the resistor Rsh is Ploss = 3Ish2Rsh (7)
Equating the average rate of change of the change of energy,
Pind = Pconv – Ploss – Pcap (8)
On substituting values from 4 to 8,
LdcIdc
dIdc
dt
=3(VshIinj– Iinj2Rsh – d/dt (1/2 CshVsh2 ))
Or
LdcIdc
dIdc
dt
= 3VshIijn – Iinj2Rsh - VshCsh
dVsh
dt
(9)
In order to linearize the power equation, a small perturbation
is applied in the input current of converter. The average dc-
link current will also get perturbed by a small amount.
Hence by substituting
Iinj = Iinj0 + ∆Iinj and Idc = Idc0 +∆ Idc in equation 9 and
archiving the higher order terms,
The transfer function of the PWM converter for a particular
operating point can be obtained as follows:
Kc = ∆Idc/∆Iinj = 3(
Vsh −CshVshS −2Iinj 0Rsh
LdcIdc 0S
) (10)
The characteristic equation of the current control loop is used
to obtain the constants of the PI regulator which can be written
as,
1 + (Kp + Ki/s)
3(Vsh −CshVshS −2Iinj 0Rsh )
LdcIdc 0S
(11)
The controller parameters are designed on the basis of 5%
overshoot to step change in the amplitude of current reference.
For the selected system with the following variables, a second
order characteristic equation is found for the closed-loop
system.
Vsh = 230 V, Iinj0 = 5A, Rsh = 0.4 Ω, Csh = 24 µF
Ldc = 160 mH and Idc0 = 5 A.
This characteristic equation is used to determine the
components of the PI regulator. The analysis of this
characteristic equation shows thatKp determines the current
response and Ki defines the damping factor of the current
loop.
IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163
__________________________________________________________________________________________
Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 507
By substituting the above values in eq 11, we obtain
0.8s2 + Kp( 678s – 0.165s2) + Ki (678 – 0.0165s) = 0---- (12)
Using Routh–Hurwitz criteria for system stability, the limit of
the stability region is found out for the characteristic equation
shown in equation 12. The parameters obtained for the PI
Controller are as Kp = 0.5 and Ki = 10. For the selected values
of Kpand Ki in the most stable region, the transient response
of the current control loop for the step change is plotted as
given in the table 1.
With the careful observation at the Fig 4, we can deduce the
optimal values of the proportional gain Kp and Ki. We need to
have the overshoot as minimum as possible and the settling
time as optimal as possible. For such kind of requirements, the
values of Kp and Ki are selected and the same values are
being applied while designing the Proportional Integral
controller. The so designed PI Shunt controller is integrated as
shown below.
Fig: 4 MATLAB Design of the Proportional Integral Shunt
Controller generating the controlling pulses.
4. DESIGN OF ANN CONTROLLER
An Artificial neural network (ANN), often just called a Neural
Network, is a mathematical model inspired by biological
neural networks. A neural network consists of an
interconnected group of artificial neurons, and it processes
information using a connectionist approach to computation. It
resembles the brain in two aspects: 1) The knowledge is
acquired by the network through the learning process and 2)
Interneuron connection strengths are used to store the
knowledge. These networks are characterized by their
topology, the way in which they communicate with their
environment, the manner in which they are trained, and their
ability to process information. ANNs are being used to solve
AI problems without necessarily creating a model of a real
dynamic system.
The rapid detection of the disturbance signal with high
accuracy, fast processing of the reference signal, and high
dynamic response of the controller are the prime requirements
for desired compensation in case of UPQC. The conventional
controller fails to perform satisfactorily under parameter
variations nonlinearity load disturbance, etc. A recent study
shows that NN-based controllers provide fast dynamic
response while maintaining stability of the converter system
over a wide operating range.
For improving the performance of the considered Unified
Power Quality conditioner, a multilayer feed forward network
is considered. This network consists of ‗3‘ layers and their
corresponding neuron interconnections. Input layer with ‗2‘
neurons to receive the inputs ‗Idc‘ and ‗dIdc‘ where‗d‘ is a
constant. Hidden layer consists of ‗21‘ neurons to which each
of the processed input is fed. Output layer consists of ‗1‘
neuron whose output is the computed Ploss. We need to assign
the activation functions for each of the layers in order to train
them. Input is layer is given the Log-Sigmoidal function as
activation function. Hidden layer is also assigned the same and
the output layer is being given the Pure-Linear activation
function as activation function. The corresponding exploded
diagram of the designed Neural Network is as shown in the fig
5 below.
Fig: 5 Exploded diagram of the Neural network.
The large data of the dc-link current for ‗n‘ and ‗n-1‘ intervals
from the conventional method are collected and are stored in
the Matlab workspace. These data are used for training the
NN. The workspace stored data is being retrieved using the
training algorithm used. The hidden layer is the Intermediate
layer that performs many computations and is the most typical
one with large number of neurons and their interconnections.
The neurons in the input and output layers is almost a fixed
quantity to receive the provided input. The accuracy of the
ANN operation is mostly depends on the number of hidden
neurons. The hidden layer interconnections can be configured
as follows.
IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163
__________________________________________________________________________________________
Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 508
Fig: 6.Hidden layer Interconnections
The training algorithm used is BFGS Quasi-Newton (BFG).
The MATLAB programming of the ANN training is as given
below.
net=newff(minmax(P),[2,21,1],{'logsig','logsig','purelin'},'train
bfg');
net.trainParam.show=50;
net.trainParam.lr=0.08;
net.trainParam.mc=0.815;
net.trainParam.lr_inc=1.87;
net.trainParam.epochs=900;
net.trainParam.goal=1e-6;
[net,tr]=train(net,P,T);
a=sim(net,P);
gensim(net,-1);
In the above algorithm, the Neural Network is created with the
specified number of neurons in the each layer. There are 900
iterations done in each training session and 6 such a validation
checks are carried out in order to minimize the scope of error
occurrence. The aim is to bring the Performance to 10-6. For
each 50 iterations (epochs), the corresponding values of
Gradient, Mu and the performance parameters during training
session are being displayed. Learning rate is the major
consideration in the training of the Artificial Neural Network
(change of interconnection weights). It should not be too low
that the training gets too delayed. It should not be too high
because the oscillations occur about the target values and the
time taken to converge is too high and the training gets
delayed. For the considered controller, Neural Network is
trained at a learning rate of 0.08. The compensator output
depends on the input and its evolution.The NN is trained for
outputting fundamental referencecurrents. The signals thus
obtained are compared in a hysteresisband current controller
to provide switching signals.The so generated shunt controller
is integrated as shown below.
Fig: 7 MATLAB Design of the Neural Network based shunt
controller.
5. SIMULATION RESULTS
In this section, the performance of the PI and ANN controllers
in controlling the DC Link current of Unified Power Quality
Conditioner is performed. The designed Artificial Neural
Network is integrated into the circuit and the resulting power
quality solution is compared with the result obtained with the
PI Controller. In this comparison, the time required for stable
operation at initial and load change conditions as well as the
changein load current performance are studied. ANN Based
compensator is represented in the Fig 7. The performance of
theshunt active filter of the UPQC with the PI controller and
ANN Controller are given in Fig 8 and Fig 9 respectively.
Fig: 8 Block diagram of the ANN based compensator for
offline-training.
The signal extractor is fed the signals source voltages and
currents. ANN block acts as the compensation signal generator
and sends the corresponding controlling signal to the signal
extractor. With the coordinated control of these loops, the
gating signal is generated and is sent to the shunt controller for
the controlling action. The simulation results with the
IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163
__________________________________________________________________________________________
Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 509
Conventional and Unconventional controller actions can be as
shown below.
Fig: 9 Performance of the shunt active filter of the UPQC with
the PI controller for load perturbations.
Fig: 10Performance of the shunt active filter of the UPQC
with an ANN controller for load perturbations.
From the above simulation results,it is observed that in case of
the PI controller,the shunt filter takes almost two-and-a-half
cycles to stabilizethe dc-link current at the initial
condition.Also at the load change from 7.5A to 12.5A, it
almost takes a similar amount oftime to reach a stable state. In
case of the ANN controller, thedc-link current stabilizes
within a half cycle after the start of theshunt filter, and at the
load change, it takes almost one cycle toreach its mean value,
thus improving system performance.
The performance of harmonic current filtration is shown
inFigs. 10 and 11.
Fig: 11 Frequency spectrum of the source current at different
loading conditions with the PI controller.
Fig: 12 Frequency spectrum of the source current at different
loading conditions with the ANN controller.
TABLE II COMPARISON OF THE PI AND ANN
CONTROLLER PERFORMANCE
Type of Controller PI ANN
Time for stabilization
at initial loading
50 ms 10 ms
Time for stabilization
at load change
50 ms 35 ms
Load Current
Harmonics
16.21% 13.28%
Source current
harmonics at 0.15 sec
0.75% 0.69%
Source current
harmonics at 0.25 sec
0.76% 0.66%
From the above table, it is clear that the load current in both
cases is found to be content of all odd harmonic minus triplen,
providing a total harmonic distortion (THD) of 16.21% with
PI Controller and 13.28% with the ANN Controller
respectively. From the figure 10 and 11, it is observed that
Total Harmonic Distortion of the source current at 0.15 sec is
0.75% with the PI Controller and 0.69% with the ANN
Controller scheme. Similarly, the THD of the source current at
0.25 sec is 0.76% with the PI and 0.66% in case of ANN
Controller respectively.
CONCLUSIONS
The performance of the UPQC mainly depends upon how
accurately and quickly reference signals are derived. It was
observed that the power conditioner compensates for voltage
as well as current harmonics. However, its performance using
the conventional PI controller was not satisfactory especially
with respect to transient conditions. It is very necessary in the
Power System network to detect the change of parameters as
soon as possible and then we can go for the solutions. Thus the
response time of the device applied to improve the power
quality should be optimal. In order to improve its response
time, the artificial-intelligence-based ANN controlleris
proposed, and its performance is analyzed by simulation. It is
found that the Artificial Intelligence technique for the
controlling of Unified Power Quality lead satisfactory results
in Improving the Power Quality and Power system
IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163
__________________________________________________________________________________________
Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 510
stabilization compared to the conventional Proportional
Integral controller.
REFERENCES
[1] E. W. Gunther and H. Mehta, ―A survey of distribution
system powerquality,‖ IEEE Trans. Power Del., vol. 10, no. 1,
pp. 322–329, Jan.1995.
[2] W. M. Grady, M. J. Samotyj, and A. A. Noyola, ―Survey
of activepower line conditioning methodologies,‖ IEEE Trans.
Power Del., vol.
5, no. 3, pp. 1536–1542, Jul. 1990.
[3] F. Kamron, ―Combined dead beat control of series—
Parallel convertercombination used as a universal power
filter,‖ in Proc. IEEE PowerElectronics Specialist Conf.,
1995, pp. 196–201.
[4] H. Fujita and H. Akagi, ―The unified power quality
conditioner: Theintegration of series active filter and shunt
active filters,‖ in Proc. IEEE/Power Eng. Soc. Power
Electronics Specialist Conf., Jun. 1996, pp.
491–501.
[5] V. S. C. Raviraj and P. C. Sen, ―Comparative study of
proportional integral,sliding mode and fuzzy logic controllers
for power converters,‖IEEE Trans. Ind. Appl., vol. 33, no. 2,
pp. 518–524, Mar./Apr. 1997.
[6] J.L. Flores Garrido and P. Salmerón Revuelta, ―Control of
an active power filter using dynamic neural networks‖,
Department of Electrical Engineering, Huelva University,
Huelva (Spain).
[7] N. Pecharanin, M. Sone, H. Mitsui, ―An application
ofneural network for harmonic detection in active filter‖,IEEE
World Congress on Computational Intelligence.,IEEE
International Conference on Neural Networks, Vol.6, pp.
3756-3760, 1994.
[8] M. Rukonuzzaman, M. Nakaoka, ―An advanced
activepower filter with neural network based harmonic
detectionscheme‖, Power Electronics Specialists Conference,
PESC2001 IEEE 32nd Annual, Vol. 3, pp 1602-1607, June
2001.
[9] A. Elmitwally, S. Abdelkader, and M. EL-Kateb, ―Neural
networkcontrolled three-phase four-wire shunt active power
filter,‖ Proc. Inst.Elect. Eng., Gen. Trans. Distrib. vol. 147,
no. 2, Mar. 2000.
BIOGRAPHIES:
T. Madhurantaka received the B.Tech
degree in Electrical and Electronics
Engineering from Sree Vidyanikethan
Engineering College, Tirupati, India in
2003, M.Tech degree in Power Electronics
from Sree Vidyanikethan Engineering
College, Tirupati, India in 2007. Currently
pursuing his Ph.D. degree in SV University.
S. MuniSekhar received the B.Tech
degree in Electrical and Electronics
Engineering from PBRVITS, Kavali,
India in 2002. He is currently pursuing
M.Tech degree from AITS, Rajampet,
India.
P. Lokesh is currently pursuing the final
year of his B.Tech degree in Electrical
and Electronics Engineering from Sri
Venkateswara College Of Engineering,
Tirupati, India.

More Related Content

PDF
IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PDF
AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...
PDF
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
PDF
Performance and Analysis of Reactive Power Compensation by Unified Power Flow...
PDF
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
PDF
IRJET-Static Voltage Stabilizer
PDF
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
Performance and Analysis of Reactive Power Compensation by Unified Power Flow...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
IRJET-Static Voltage Stabilizer
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...

What's hot (19)

PPTX
Abhishek seminar
PDF
Principle and Algorithm of Reactive Power Management for LLC Based Parlled MT...
PDF
D011122934
PDF
The compensatation of unbalanced 3 phase currents in transmission systems on ...
PPTX
V fuzzy logic applications to electrical systems
PDF
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
PDF
International Journal of Engineering Research and Development
PDF
International Journal of Engineering and Science Invention (IJESI)
PDF
International Journal of Engineering Research and Development (IJERD)
PDF
Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...
DOCX
Electrode regulation
PDF
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
PDF
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
PDF
Review of the Most Applicable Regulator Collections to Control the Parallel A...
PDF
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
PDF
The Intellectual Automated Substation
PDF
Optimize Controlling of Active Filters Controlled by Pi Controller
PDF
Load Frequency Control of Multi Area System using Integral-Fuzzy Controller
Abhishek seminar
Principle and Algorithm of Reactive Power Management for LLC Based Parlled MT...
D011122934
The compensatation of unbalanced 3 phase currents in transmission systems on ...
V fuzzy logic applications to electrical systems
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
International Journal of Engineering Research and Development
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering Research and Development (IJERD)
Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...
Electrode regulation
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
Review of the Most Applicable Regulator Collections to Control the Parallel A...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
The Intellectual Automated Substation
Optimize Controlling of Active Filters Controlled by Pi Controller
Load Frequency Control of Multi Area System using Integral-Fuzzy Controller
Ad

Viewers also liked (20)

PDF
Advisedly delayed packet attack on tcp based mobile
PDF
Computational study of a trailblazer multi reactor
PDF
Evaluation of topsoil iron oxide from visible
PDF
Transmission of cryptic text using rotational visual
PDF
Nonlinear fe modelling of anchorage bond in
PDF
Unravelling the molecular linkage of co morbid
PDF
Design and simulation of a tunable frequency
PDF
Pounding problems in urban areas
PDF
Design and development of a linear variable
PDF
Impact of inadvertent interchange pricing in
PDF
Fault detection and diagnosis ingears using wavelet
PDF
Development of pavement management strategies for
PDF
Root cause failure analysis of blanking device of strainer housing used in st...
PDF
Simulation of pedestrian at intersection in urban congested area
PDF
Beam steering in smart antennas by using low complex
PDF
Computational model to design circular runner
PDF
Factors affecting def and asr in the concrete dam at vrané nad vltavou
PDF
A new approach “ring” for restricting web pages from
PDF
Novel technique in charactarizing a pv module using
PDF
Use of cloud federation without need of identity federation using dynamic acc...
Advisedly delayed packet attack on tcp based mobile
Computational study of a trailblazer multi reactor
Evaluation of topsoil iron oxide from visible
Transmission of cryptic text using rotational visual
Nonlinear fe modelling of anchorage bond in
Unravelling the molecular linkage of co morbid
Design and simulation of a tunable frequency
Pounding problems in urban areas
Design and development of a linear variable
Impact of inadvertent interchange pricing in
Fault detection and diagnosis ingears using wavelet
Development of pavement management strategies for
Root cause failure analysis of blanking device of strainer housing used in st...
Simulation of pedestrian at intersection in urban congested area
Beam steering in smart antennas by using low complex
Computational model to design circular runner
Factors affecting def and asr in the concrete dam at vrané nad vltavou
A new approach “ring” for restricting web pages from
Novel technique in charactarizing a pv module using
Use of cloud federation without need of identity federation using dynamic acc...
Ad

Similar to Integration of artificial intelligence control to the unified power quality conditioner (20)

PDF
Review on Different Time Domain Controlling Technique for UPQC
PDF
Controlling power flow losses in upfc system using adaptive neuro fuzzy contr...
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PDF
The compensatation of unbalanced 3 phase currents in transmission systems on ...
PDF
Load flow analysis with upfc under unsymmetrical fault condition
PDF
IRJET- UPQC System for Improved Control Method
PDF
IRJET- Impact of UPQC on Protection of Distributed Generation Integrated Dist...
PDF
Unified power quality conditioner using generalized
PDF
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
PDF
www.ijerd.com
PDF
B04931120
PDF
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
PDF
A Power Control Scheme for UPQC for Power Quality Improvement
PDF
Voltage Sag and Harmonics Mitigation using Distributed Power Flow Controller
PDF
Pi controller based of multi level upqc using dq0 transformation to improve p...
PDF
B360614
PDF
IRJET- Generalized UPQC System with an Improved Control Method under Distorte...
PDF
Enhancement of upfc performance with matrix
PDF
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
Review on Different Time Domain Controlling Technique for UPQC
Controlling power flow losses in upfc system using adaptive neuro fuzzy contr...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
The compensatation of unbalanced 3 phase currents in transmission systems on ...
Load flow analysis with upfc under unsymmetrical fault condition
IRJET- UPQC System for Improved Control Method
IRJET- Impact of UPQC on Protection of Distributed Generation Integrated Dist...
Unified power quality conditioner using generalized
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
www.ijerd.com
B04931120
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
A Power Control Scheme for UPQC for Power Quality Improvement
Voltage Sag and Harmonics Mitigation using Distributed Power Flow Controller
Pi controller based of multi level upqc using dq0 transformation to improve p...
B360614
IRJET- Generalized UPQC System with an Improved Control Method under Distorte...
Enhancement of upfc performance with matrix
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW

More from eSAT Publishing House (20)

PDF
Likely impacts of hudhud on the environment of visakhapatnam
PDF
Impact of flood disaster in a drought prone area – case study of alampur vill...
PDF
Hudhud cyclone – a severe disaster in visakhapatnam
PDF
Groundwater investigation using geophysical methods a case study of pydibhim...
PDF
Flood related disasters concerned to urban flooding in bangalore, india
PDF
Enhancing post disaster recovery by optimal infrastructure capacity building
PDF
Effect of lintel and lintel band on the global performance of reinforced conc...
PDF
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
PDF
Wind damage to buildings, infrastrucuture and landscape elements along the be...
PDF
Shear strength of rc deep beam panels – a review
PDF
Role of voluntary teams of professional engineers in dissater management – ex...
PDF
Risk analysis and environmental hazard management
PDF
Review study on performance of seismically tested repaired shear walls
PDF
Monitoring and assessment of air quality with reference to dust particles (pm...
PDF
Low cost wireless sensor networks and smartphone applications for disaster ma...
PDF
Coastal zones – seismic vulnerability an analysis from east coast of india
PDF
Can fracture mechanics predict damage due disaster of structures
PDF
Assessment of seismic susceptibility of rc buildings
PDF
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
PDF
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Likely impacts of hudhud on the environment of visakhapatnam
Impact of flood disaster in a drought prone area – case study of alampur vill...
Hudhud cyclone – a severe disaster in visakhapatnam
Groundwater investigation using geophysical methods a case study of pydibhim...
Flood related disasters concerned to urban flooding in bangalore, india
Enhancing post disaster recovery by optimal infrastructure capacity building
Effect of lintel and lintel band on the global performance of reinforced conc...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Shear strength of rc deep beam panels – a review
Role of voluntary teams of professional engineers in dissater management – ex...
Risk analysis and environmental hazard management
Review study on performance of seismically tested repaired shear walls
Monitoring and assessment of air quality with reference to dust particles (pm...
Low cost wireless sensor networks and smartphone applications for disaster ma...
Coastal zones – seismic vulnerability an analysis from east coast of india
Can fracture mechanics predict damage due disaster of structures
Assessment of seismic susceptibility of rc buildings
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...

Recently uploaded (20)

PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
Sustainable Sites - Green Building Construction
PPTX
bas. eng. economics group 4 presentation 1.pptx
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
web development for engineering and engineering
PPTX
CH1 Production IntroductoryConcepts.pptx
PPTX
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
PPTX
OOP with Java - Java Introduction (Basics)
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PDF
Well-logging-methods_new................
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PDF
PPT on Performance Review to get promotions
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
Operating System & Kernel Study Guide-1 - converted.pdf
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
UNIT-1 - COAL BASED THERMAL POWER PLANTS
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
Sustainable Sites - Green Building Construction
bas. eng. economics group 4 presentation 1.pptx
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
web development for engineering and engineering
CH1 Production IntroductoryConcepts.pptx
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
OOP with Java - Java Introduction (Basics)
R24 SURVEYING LAB MANUAL for civil enggi
Automation-in-Manufacturing-Chapter-Introduction.pdf
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
Well-logging-methods_new................
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
Embodied AI: Ushering in the Next Era of Intelligent Systems
PPT on Performance Review to get promotions
CYBER-CRIMES AND SECURITY A guide to understanding

Integration of artificial intelligence control to the unified power quality conditioner

  • 1. IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163 __________________________________________________________________________________________ Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 504 INTEGRATION OF ARTIFICIAL INTELLIGENCE CONTROL TO THE UNIFIED POWER QUALITY CONDITIONER T.Madhurantaka1 , S. Muni Sekhar2 , P.Lokesh3 tarasimadhu@gmail.com, munisekhar1980@gmail.com, lokesh.parukuru@live.com Abstract Modernization of the Industrial world is completely accompanied with growing power demands. It is very necessary to utilize the available power efficiently with as much less issues as possible rather than focusing on the excessive generation to meet the demand. UPQC consist of combined series active power filter that compensates voltage harmonics of the power supply, and shunt active power filter that compensates harmonic currents of a non-linear load. We need to focus on the control of UPQC to achieve the best results. Artificial Neural Networks is now considered as a tool for the design of controller for the Power Quality devices. In this paper, the ANN-based controller is designed for the current control of the shunt active power filter and trained offline using data from the conventional PI controller. An exhaustive simulation study is carried out to investigate the performance of the ANN controller and compare its performance with the conventional PI controller results. Index Terms: Power Quality, Unified Power Quality Conditioner, Artificial Neural Networks, Proportional Integral, CSI, VSI, Harmonics. -----------------------------------------------------------------------***----------------------------------------------------------------------- 1. INTRODUCTION With the usage of more sensitive loads such as Automation Equipment in the Industrial operation, Communication Equipment, Medical equipment, and military equipment power quality has become a significant issue to both customers and the Utility companies. For the effective utilization of the available power, the elimination or mitigation of disturbances propagated from the supply system is absolutely required to improve the operational reliability of all the connected loads. To meet the requirements of Harmonic regulation, Power quality enhancement passive and active power filters are being used in combination with the conventional converters. Availability of power semiconductor devices made the usage of Active Power Filters more compared to the Passive filters. Besides it, the APF also provides multiple functions like Harmonic filtering, Damping, Isolation and termination , Load balancing, Voltage regulation, Power factor correction, Voltage flicker reduction etc.,. UPQC has been widely studied in order to improve Universal power quality by many researchers. The performance of UPQC mainly depends upon how accurately and quickly reference signals are derived. After efficient extraction of the distorted signal, a suitable dc-link current regulator is used to derive the actual reference signals. Various control approaches, such as the PI, PID, fuzzy-logic, sliding- mode, predictive, unified constant frequency (UCF) controllers, etc., are in use. The frequency converter is achieved by matrix converter. The main advantage of frequency converter is as follow. Matrix converter can only increase or decrease the frequency instead of cyclo converter. Here there is no dc storage element. So losses are minimized and Harmonics also minimized UPQC has the potential drawbacks in the hybrid filtering performance as its filter in characteristics depends on load impedance and supply frequency. PI and PID controllers need a precise mathematical model to be derived for their design and there is a major drawback that they fail to operate under parameter variation and load disturbances etc. There has been a continuous research effort taken to develop new and unconventional control techniques that can effectively the drawbacks of the conventional controllers and take an effective position in the control center. A Large number of modern techniques have evolved, offering solutions to many difficult control problems in industry and manufacturing sectors. Unlike their conventional counter- parts, these unconventional controllers (intelligent controllers) can learn, remember, and make decisions. Artificial- intelligence (AI) techniques, particularly the NNs, are having a significant impact on the power electronics applications. Neural-network-based controllers provide fast dynamic response while maintaining the stability of the converter system over a wide operating range and are considered as a new tool to design control circuits for PQ devices. With the motive of designing the controller for the UPQC for the effective control, obtain the reliable control algorithms, and faster response to produce the output signals. In this paper, for improving the performance of a UPQC, a multilayer feed forward-type ANN-based controller is designed for the current control of the shunt active filter instead of the conventional PI controller. An algorithm for training the ANN controller is
  • 2. IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163 __________________________________________________________________________________________ Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 505 developed and trained offline. Various simulation results are presented and are compared with the results that are obtained with the conventional PI Controller. A DSP based microcontroller is used for the real time simulation and implementation of the control algorithm. The system configuration is described in Section II, while PI and ANN controller design are explained in Sections III and IV, respectively. Simulation results are discussed in Sections V with relevant waveforms and tabular column of simulated parameter values. 2. SYSTEM CONFIGURATION The configuration of a general UPQC consists of the combination of a series active power filter and shunt active power filter. The main aim of the series active power filter is harmonic isolation between a sub-transmission system and a distribution system; it has the capability of voltage flicker/ imbalance compensation as well as voltage regulation and harmonic compensation at the utility-consumer point of common coupling (PCC). The shunt active power filter is used to absorb current harmonics, compensate for reactive power and negative-sequence current, and regulate the dc-link voltage between both active power filters. It can be configured either with voltage-source converters or current source converters in single phase, three-phase three wire, or three- phase four-wire configurations. The block diagram of the UPQC is as shown in the fig. 1. Fig: 1 Block diagram of UPQC. Although the Voltage Sourced configuration is the most common practice, the VSI topology has slow control of the converter (LC filter) output voltage and no short- circuit/overcurrent protection. When the active rectifier inside the UPQC is used as a power factor corrector, dc bus voltage oscillations appear which makes the control of the series filter output voltage more difficult. The CSI-based UPQC has advantages of excellent current control capability, easy protection, and high reliability over VSI-based UPQC. The main drawback of the CSI-based UPQC has been so far the lack of proper switching devices and large dc-side filter. The new insulated-gate bipolar transistors (IGBTs) with reverse blocking capability are being launched in the markets which are suitable for the CSI-based UPQC. With the use of SMES coils, the size and losses can be reduced considerably. A configuration of UPQC using two current-source converters connected back to back through a large dc-link reactor is shown in Fig. Fig: 2 MATLAB Simulation Circuit of the UPQC integrated into the simple power system network. 3. DESIGN OF PI CONTROLLER Since the dc-link current is controlled by the shunt filter, we need to design the Controller for the shunt filter. The following basic equations are used for designing the control system: Is = Il – iinj (1) Iinj = d2idc (2) Lsh diinj dt = Vl – iinjRsh = Vl - Vsh (3) In order to control the filter current (iinj), the only control variable is the duty cycle of the PWM converter. The problem of control is to determine the duty cycle (d2) in such a way that the dc-link current remains constant and to produce suitable filter current to cancel the load current harmonics. This filter current should be opposite of the harmonic current, which is split into two components (i.e., one loss component plus the reactive component and another harmonic component). The energy transfer to the continuous side takes place only at the fundamental frequency to compensate all of the losses in the PWM converter). Thus, it is required to control two outputs, namely idc and iinj from one control variable (i.e., the duty cycle of the PWM converter). However, the main objective is to control the filter current, and the control strategy must lead to precise compensation of the harmonic component. The value of needs to only be approximately constant and there is no dynamic performance to be attained. The more it is constant, the more linear the system will be. Hence, Iinjis controlled indirectly by processing the actual source current and estimated reference current in a hysteresis current controller. These reference
  • 3. IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163 __________________________________________________________________________________________ Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 506 currents are estimated by regulating dc-link current. In order to estimate the steady-state error in the dc-link current, a PI controller is used. Although the dynamic response of the dc- link inductor has no effect on the compensation feature of the scheme, a mathematical model is required for the stability analysis and, hence, for determining the parameters of the PI controller. The following assumptions are made for deriving the mathematical model of the system. 1) The voltage at PCC is sinusoidal and balanced. 2) Since the harmonic component does not affect the average power balance expressions, only the fundamental component of currents is considered. 3) Losses of the system are lumped and represented by an Equivalent resistance Rshconnected in series with the filter inductor Lsh. 4) Ripples in the dc-link current are neglected. The block diagram of the current control loop is shown in Fig. 3, Fig: 3 Block diagram of the current control loop Where, ‗G‘ is the gain of the PI Controller, ‗Kc‘ is the transfer function of the PWM converter. Linear model of the PWM converter can be derived by applying a small-signal perturbation technique to obtain its transfer function. In this method of deriving a linear model, the system is assumed to operate in the steady state, and the defining equations are linearized for small-signal perturbation. The relation between the input (ac side) and output (dc-link side) quantities of the PWM converter are obtained by equating the rate of change of energy associated. 1) The average rate at which energy being absorbed by the inductor is Pind = 𝑑 𝑑𝑡 ( 1 2 LDCIDC 2 ) = LDCIDC( 𝑑 𝑑𝑡 IDC) (4) 2) The power input to the PWM Converter Pconv = 3 VshIinj (5) 3) The average rate of change of energy associated with the capacitor filter is Pcap = 3 𝑑 𝑑𝑡 ( 1 2 CshVsh 2 ) (6) Power loss in the resistor Rsh is Ploss = 3Ish2Rsh (7) Equating the average rate of change of the change of energy, Pind = Pconv – Ploss – Pcap (8) On substituting values from 4 to 8, LdcIdc dIdc dt =3(VshIinj– Iinj2Rsh – d/dt (1/2 CshVsh2 )) Or LdcIdc dIdc dt = 3VshIijn – Iinj2Rsh - VshCsh dVsh dt (9) In order to linearize the power equation, a small perturbation is applied in the input current of converter. The average dc- link current will also get perturbed by a small amount. Hence by substituting Iinj = Iinj0 + ∆Iinj and Idc = Idc0 +∆ Idc in equation 9 and archiving the higher order terms, The transfer function of the PWM converter for a particular operating point can be obtained as follows: Kc = ∆Idc/∆Iinj = 3( Vsh −CshVshS −2Iinj 0Rsh LdcIdc 0S ) (10) The characteristic equation of the current control loop is used to obtain the constants of the PI regulator which can be written as, 1 + (Kp + Ki/s) 3(Vsh −CshVshS −2Iinj 0Rsh ) LdcIdc 0S (11) The controller parameters are designed on the basis of 5% overshoot to step change in the amplitude of current reference. For the selected system with the following variables, a second order characteristic equation is found for the closed-loop system. Vsh = 230 V, Iinj0 = 5A, Rsh = 0.4 Ω, Csh = 24 µF Ldc = 160 mH and Idc0 = 5 A. This characteristic equation is used to determine the components of the PI regulator. The analysis of this characteristic equation shows thatKp determines the current response and Ki defines the damping factor of the current loop.
  • 4. IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163 __________________________________________________________________________________________ Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 507 By substituting the above values in eq 11, we obtain 0.8s2 + Kp( 678s – 0.165s2) + Ki (678 – 0.0165s) = 0---- (12) Using Routh–Hurwitz criteria for system stability, the limit of the stability region is found out for the characteristic equation shown in equation 12. The parameters obtained for the PI Controller are as Kp = 0.5 and Ki = 10. For the selected values of Kpand Ki in the most stable region, the transient response of the current control loop for the step change is plotted as given in the table 1. With the careful observation at the Fig 4, we can deduce the optimal values of the proportional gain Kp and Ki. We need to have the overshoot as minimum as possible and the settling time as optimal as possible. For such kind of requirements, the values of Kp and Ki are selected and the same values are being applied while designing the Proportional Integral controller. The so designed PI Shunt controller is integrated as shown below. Fig: 4 MATLAB Design of the Proportional Integral Shunt Controller generating the controlling pulses. 4. DESIGN OF ANN CONTROLLER An Artificial neural network (ANN), often just called a Neural Network, is a mathematical model inspired by biological neural networks. A neural network consists of an interconnected group of artificial neurons, and it processes information using a connectionist approach to computation. It resembles the brain in two aspects: 1) The knowledge is acquired by the network through the learning process and 2) Interneuron connection strengths are used to store the knowledge. These networks are characterized by their topology, the way in which they communicate with their environment, the manner in which they are trained, and their ability to process information. ANNs are being used to solve AI problems without necessarily creating a model of a real dynamic system. The rapid detection of the disturbance signal with high accuracy, fast processing of the reference signal, and high dynamic response of the controller are the prime requirements for desired compensation in case of UPQC. The conventional controller fails to perform satisfactorily under parameter variations nonlinearity load disturbance, etc. A recent study shows that NN-based controllers provide fast dynamic response while maintaining stability of the converter system over a wide operating range. For improving the performance of the considered Unified Power Quality conditioner, a multilayer feed forward network is considered. This network consists of ‗3‘ layers and their corresponding neuron interconnections. Input layer with ‗2‘ neurons to receive the inputs ‗Idc‘ and ‗dIdc‘ where‗d‘ is a constant. Hidden layer consists of ‗21‘ neurons to which each of the processed input is fed. Output layer consists of ‗1‘ neuron whose output is the computed Ploss. We need to assign the activation functions for each of the layers in order to train them. Input is layer is given the Log-Sigmoidal function as activation function. Hidden layer is also assigned the same and the output layer is being given the Pure-Linear activation function as activation function. The corresponding exploded diagram of the designed Neural Network is as shown in the fig 5 below. Fig: 5 Exploded diagram of the Neural network. The large data of the dc-link current for ‗n‘ and ‗n-1‘ intervals from the conventional method are collected and are stored in the Matlab workspace. These data are used for training the NN. The workspace stored data is being retrieved using the training algorithm used. The hidden layer is the Intermediate layer that performs many computations and is the most typical one with large number of neurons and their interconnections. The neurons in the input and output layers is almost a fixed quantity to receive the provided input. The accuracy of the ANN operation is mostly depends on the number of hidden neurons. The hidden layer interconnections can be configured as follows.
  • 5. IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163 __________________________________________________________________________________________ Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 508 Fig: 6.Hidden layer Interconnections The training algorithm used is BFGS Quasi-Newton (BFG). The MATLAB programming of the ANN training is as given below. net=newff(minmax(P),[2,21,1],{'logsig','logsig','purelin'},'train bfg'); net.trainParam.show=50; net.trainParam.lr=0.08; net.trainParam.mc=0.815; net.trainParam.lr_inc=1.87; net.trainParam.epochs=900; net.trainParam.goal=1e-6; [net,tr]=train(net,P,T); a=sim(net,P); gensim(net,-1); In the above algorithm, the Neural Network is created with the specified number of neurons in the each layer. There are 900 iterations done in each training session and 6 such a validation checks are carried out in order to minimize the scope of error occurrence. The aim is to bring the Performance to 10-6. For each 50 iterations (epochs), the corresponding values of Gradient, Mu and the performance parameters during training session are being displayed. Learning rate is the major consideration in the training of the Artificial Neural Network (change of interconnection weights). It should not be too low that the training gets too delayed. It should not be too high because the oscillations occur about the target values and the time taken to converge is too high and the training gets delayed. For the considered controller, Neural Network is trained at a learning rate of 0.08. The compensator output depends on the input and its evolution.The NN is trained for outputting fundamental referencecurrents. The signals thus obtained are compared in a hysteresisband current controller to provide switching signals.The so generated shunt controller is integrated as shown below. Fig: 7 MATLAB Design of the Neural Network based shunt controller. 5. SIMULATION RESULTS In this section, the performance of the PI and ANN controllers in controlling the DC Link current of Unified Power Quality Conditioner is performed. The designed Artificial Neural Network is integrated into the circuit and the resulting power quality solution is compared with the result obtained with the PI Controller. In this comparison, the time required for stable operation at initial and load change conditions as well as the changein load current performance are studied. ANN Based compensator is represented in the Fig 7. The performance of theshunt active filter of the UPQC with the PI controller and ANN Controller are given in Fig 8 and Fig 9 respectively. Fig: 8 Block diagram of the ANN based compensator for offline-training. The signal extractor is fed the signals source voltages and currents. ANN block acts as the compensation signal generator and sends the corresponding controlling signal to the signal extractor. With the coordinated control of these loops, the gating signal is generated and is sent to the shunt controller for the controlling action. The simulation results with the
  • 6. IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163 __________________________________________________________________________________________ Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 509 Conventional and Unconventional controller actions can be as shown below. Fig: 9 Performance of the shunt active filter of the UPQC with the PI controller for load perturbations. Fig: 10Performance of the shunt active filter of the UPQC with an ANN controller for load perturbations. From the above simulation results,it is observed that in case of the PI controller,the shunt filter takes almost two-and-a-half cycles to stabilizethe dc-link current at the initial condition.Also at the load change from 7.5A to 12.5A, it almost takes a similar amount oftime to reach a stable state. In case of the ANN controller, thedc-link current stabilizes within a half cycle after the start of theshunt filter, and at the load change, it takes almost one cycle toreach its mean value, thus improving system performance. The performance of harmonic current filtration is shown inFigs. 10 and 11. Fig: 11 Frequency spectrum of the source current at different loading conditions with the PI controller. Fig: 12 Frequency spectrum of the source current at different loading conditions with the ANN controller. TABLE II COMPARISON OF THE PI AND ANN CONTROLLER PERFORMANCE Type of Controller PI ANN Time for stabilization at initial loading 50 ms 10 ms Time for stabilization at load change 50 ms 35 ms Load Current Harmonics 16.21% 13.28% Source current harmonics at 0.15 sec 0.75% 0.69% Source current harmonics at 0.25 sec 0.76% 0.66% From the above table, it is clear that the load current in both cases is found to be content of all odd harmonic minus triplen, providing a total harmonic distortion (THD) of 16.21% with PI Controller and 13.28% with the ANN Controller respectively. From the figure 10 and 11, it is observed that Total Harmonic Distortion of the source current at 0.15 sec is 0.75% with the PI Controller and 0.69% with the ANN Controller scheme. Similarly, the THD of the source current at 0.25 sec is 0.76% with the PI and 0.66% in case of ANN Controller respectively. CONCLUSIONS The performance of the UPQC mainly depends upon how accurately and quickly reference signals are derived. It was observed that the power conditioner compensates for voltage as well as current harmonics. However, its performance using the conventional PI controller was not satisfactory especially with respect to transient conditions. It is very necessary in the Power System network to detect the change of parameters as soon as possible and then we can go for the solutions. Thus the response time of the device applied to improve the power quality should be optimal. In order to improve its response time, the artificial-intelligence-based ANN controlleris proposed, and its performance is analyzed by simulation. It is found that the Artificial Intelligence technique for the controlling of Unified Power Quality lead satisfactory results in Improving the Power Quality and Power system
  • 7. IJRET: International Journal of Research in Engineering and Technology ISSN: 2319-1163 __________________________________________________________________________________________ Volume: 02 Issue: 04 | Apr-2013, Available @ http://www.ijret.org 510 stabilization compared to the conventional Proportional Integral controller. REFERENCES [1] E. W. Gunther and H. Mehta, ―A survey of distribution system powerquality,‖ IEEE Trans. Power Del., vol. 10, no. 1, pp. 322–329, Jan.1995. [2] W. M. Grady, M. J. Samotyj, and A. A. Noyola, ―Survey of activepower line conditioning methodologies,‖ IEEE Trans. Power Del., vol. 5, no. 3, pp. 1536–1542, Jul. 1990. [3] F. Kamron, ―Combined dead beat control of series— Parallel convertercombination used as a universal power filter,‖ in Proc. IEEE PowerElectronics Specialist Conf., 1995, pp. 196–201. [4] H. Fujita and H. Akagi, ―The unified power quality conditioner: Theintegration of series active filter and shunt active filters,‖ in Proc. IEEE/Power Eng. Soc. Power Electronics Specialist Conf., Jun. 1996, pp. 491–501. [5] V. S. C. Raviraj and P. C. Sen, ―Comparative study of proportional integral,sliding mode and fuzzy logic controllers for power converters,‖IEEE Trans. Ind. Appl., vol. 33, no. 2, pp. 518–524, Mar./Apr. 1997. [6] J.L. Flores Garrido and P. Salmerón Revuelta, ―Control of an active power filter using dynamic neural networks‖, Department of Electrical Engineering, Huelva University, Huelva (Spain). [7] N. Pecharanin, M. Sone, H. Mitsui, ―An application ofneural network for harmonic detection in active filter‖,IEEE World Congress on Computational Intelligence.,IEEE International Conference on Neural Networks, Vol.6, pp. 3756-3760, 1994. [8] M. Rukonuzzaman, M. Nakaoka, ―An advanced activepower filter with neural network based harmonic detectionscheme‖, Power Electronics Specialists Conference, PESC2001 IEEE 32nd Annual, Vol. 3, pp 1602-1607, June 2001. [9] A. Elmitwally, S. Abdelkader, and M. EL-Kateb, ―Neural networkcontrolled three-phase four-wire shunt active power filter,‖ Proc. Inst.Elect. Eng., Gen. Trans. Distrib. vol. 147, no. 2, Mar. 2000. BIOGRAPHIES: T. Madhurantaka received the B.Tech degree in Electrical and Electronics Engineering from Sree Vidyanikethan Engineering College, Tirupati, India in 2003, M.Tech degree in Power Electronics from Sree Vidyanikethan Engineering College, Tirupati, India in 2007. Currently pursuing his Ph.D. degree in SV University. S. MuniSekhar received the B.Tech degree in Electrical and Electronics Engineering from PBRVITS, Kavali, India in 2002. He is currently pursuing M.Tech degree from AITS, Rajampet, India. P. Lokesh is currently pursuing the final year of his B.Tech degree in Electrical and Electronics Engineering from Sri Venkateswara College Of Engineering, Tirupati, India.