The Intellectual Automated Substation
Zhalilov Rashid
Ph.D, Associate Professor,
Department of Electrical Engineering
Bukhara engineering – Technological institute, Uzbekistan
ABSTRACT
The article is devoted to the study and introduction of
modern technologies in electro-technical branch
of the industry for the purpose of increasing
reliability of electric supply. Appling the latest
technical developments marketed in automatic
breakers Compact NS and Master pact of the
company "Schneider Electric", for modernization
distributing device 0,4 kV applied transformer
substation is offered in it .
Keywords: Schneider Electric, Compact NS , Master-
pact, SCADA, the programmed logic controller ,
reliability of electrical supply,cases the low-voltage
transformer,four wire electric network TN-C,
recommended IEC three-phase five-wire network TN-
S, microcontacts OF, SDE, PF, CH, Modbus, SCADA,
Batibus.
INTRODUCTION
Introduction of systems of automation and dispatching
management on the modern digital techniques radical
raises in the image quality and reliability of processes
of manufacture, transfer and distribution electric
power [1]. As a result of equipment of power objects
by systems automations , microprocessor means
emergency-preventive automatics and relay
protection reach essential economic benefit at the
expense of optimization of modes of transfer and
distribution of energy, prevention of emergencies and
minimization of a damage in case of their occurrence
[1,2,3] .
At present the begun transition in abroad to the next
generation of microprocessor (digital) device of relay
protection and automatics (DRPA) with integration
within the limits of a uniform complex functions of
relay protection, measurement processor complexes
which have received wide applicated and commercial
account electric power, regulation and management of
electrical installation it is directed on maintenance of
increase of reliability of electrical supply of
consumers and conformity to modern safety
requirements on IEC [2]. Frequent relay protection
terminals carry out function of controllers of the
bottom level of the automated management systems
(AMS), providing complex protection of management
of substations at modern level. In this case they
provide management in a place or from remote
control offices, control of position of the primary
equipment, measurement, the alarm system,
record and transfer of oscillograms. Besides, the AMS
information system al lows to make to the user
record/change date with use the pass word, to receive
reports and to conduct archive of events, to execute
conditions of diagnostics of the primary equip
ment and etc.[4]. Wide use in electrical installations
of consumers of servers of control systems of real
time ( SCADA) provides [2,4]:
 teleinformation reception/transfer in any reports;
 reception / data transmission of the daily
dispatching sheet (DS);
 processing of the arriving information,
formation date bases (DB) of real time
(DBRT), to condense;
 management of a dispatching board (digital
devices, symbols, mnemonic schemes,
information displays);
 the cyclic copying DBRT on files-servers of a
local network (LN) and etc.
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470
@ IJTSRD | Available Online @ www.ijtsrd.com | Volume – 2 | Issue – 3 | Mar-Apr 2018 Page: 1653
As it is marked in [1-3], in the report 34-108 СIGRE
are answered to Dews of a combination of traditional
control facilities, relay protection and automatics
(DRРА) with the new microprocessor complexes
which have received wide application in the world.
Creation is thus provided: microprocessor systems of
registration of emergency events, gathering and data
processing about work RРА; systems of
communications of new complexes with computer
"kernel" of the integrated monitoring system and
management, and also systems of display of the
information on workplaces of operation personnel and
the personnel of services RРА.
Distinctive feature developed by us distributing
device -DD-0,4 kV for complete transformer
substation (CTS) is the modern design, an openness
for AMS for the account of presence of ports and the
applications of the software that allows to realize
flexible technical and economic solving for an
electrical supply of consumers of any category. The
device carries out functions local or remote control,
relay are sewn up, alarm systems, automatics,
registration, control of harmonics in a voltages curve
(in cells of input from a reserve source), diagnostics
automatic breakers, and also necessary blocking
various blockings CTS. The switching centre- DD-0,4
kV CTS gathers from low-voltage cases of
type Cases low-voltage transformer (CLVT). For
assemblage of sections of tires DD-0,4 kV CTS
separate CLVT, two party service, rigidly fasten
among themselves the folding connections.
In cells CLVT in the main chain following devices are
established:
 in cells of departing joining - automatic breakers
(АВ) manufactures Schneider Electric Compact
NS 400 N on 400 A to roll out executions with
the electric drive;
 in section and cells of input from the transformer -
automatic breakers manufactures Schneider
Electric Master pact NT 16 H1 on 1600 A to roll
out execution with the electric drive;
 in cells of input from a reserve source - automatic
breakers of manufacture Schneider Electric
Master pact NT 10 H1 on 1000 A to roll out
execution with the electric drive;
 a source of an uninterrupted food (UPS) (UPS
NetPro 19) capacity 1кVt.) with time of support of
capacity of consumers not less 5 minutes.
In cell RРА of the section breakers are established
various microprocessor blocks of relay protection, or
program- med logic controllers (PLC) at will of the
customer, for example S7-300 (the manufactures
Siemens). On fig. 1 basic one-linear scheme CTS with
it is developed us DD-0,4 kV.
In DD-0,4 kV the following algorithm of automatics
CTS is realized (fig. 1):
 on the section breakers (SВ) it is executed
automatic input of a reserve food (AIRBF) - a
normal mode - both introduction breakers from
transformers are included, SВ it is disconnected.
On voltage disappearance on one of inputs (voltage
control is carried out directly on tires CTS) - through
the set endurance of time the breakers is disconnected
corresponding introduction.
Upon switching-off of input, absence of voltage on
the disconnected section of tires and voltage presence
on the second section, joins SB. At switching-off of
the introduction breakers on currents protection the
signal on a start-up interdiction is given of AIRBF.
The algorithm of start of a reserve source (is carried
out by the independent automatical Diesel power
station (АDPS):
In a starting position both introduction breakers from
a transformers one of the introduction breakers is
included, the generating switch in van АDPS is
disconnected.
At voltage disappearance on two sections CTS
(voltage control it is made directly on tires) the signal
on start АDPS is formed, at occurrence of voltage
from АDPS, both introduction breakers are
disconnected CTS, upon their switching-off the signal
is formed on inclusions generating breakers are
ADPS.
 For realization of automatic and manual return
transition to a food Automatic return transition»,
having two position: "Auto" and «The manual.».
Algorithm of return transition.
At voltage occurrence on one of inputs, with set date
time (1-30 minutes), are formed a signal normal to
stopping АDPS. Thus is disconnected generating
breakers ADPS, upon its switching-off, presence
voltage on input to the introduction switch of one of
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470
@ IJTSRD | Available Online @ www.ijtsrd.com | Volume – 2 | Issue – 3 | Mar-Apr 2018 Page: 1654
section of tires (ST), to the absence fact voltage on
ST, to the fact of the disconnected condition of the
introduction switch adjacent section without
endurance of time the switch of that joins introduction
ST on which input there was voltage. At voltage
occurrence on other input, with set date time (1-30
minutes), upon presence of voltage to the introduction
switch of this ST, the included condition of the
introduction switch and voltage presence on adjacent
ST, it is disconnected SВ and the switch of the second
joins introduction Input. Thus scheme АIRВ comes
back in a starting position.
The choice of a priority of inclusion of the
introduction breaker is carried out with set date time
on inclusion. At voltage occurrence simultaneously on
both inputs - by the first input with smaller date time
joins.
One more feature developed DD-0,4 kV is that taps
«The automatic breakers - a departing cable to
consumers» are deduced in the bottom part of a case.
On the ends tires (each all taps and the ends are
marked (a phase, № the cells, a departing feeder). For
safety of attendants cases CLVT are divided into the
isolated compartments: the tires a compartment,
compartment with breakers, compartment of relay
protection and automatics. In the tires a compartment
the equipment of the main chains settles down: the
power the tires departing to consumers and a reserve
source power cables and transformers of a current.
Power automatic switches and switches of chains of
management are established in corresponding cells.
In cells of input from the transformer (cell № 1 in a
case №1 and cell № 2 in a case №5) under a
compartment for power switches it is allocated the
special sector for installation of a source of an
uninterrupted food (UPS) (UPS NetPro 19 capacity
of 1 kVt.) with time of support of capacity of
consumers not less minutes.
In is the requirement on maintenance of speed of
switching-off of the damages connected with
influence on the person. In a compartment of relay
protection are established: the interface relays of the
alarm system, blocking and automatics, PLC, devices
of control and the account of the electric power and
other. Cells inside CLVT are separated from each
other metal a partitions. For carrying out of repair
work and maintenance service the power to roll out
executions automatic breakers are established in cells
on not-mobile the chassis fixed in working position
bolt connection supported on the basis of a cell.
1
3
2
14
10
11
6 98
4
5
12
13
7
Fig-1: One-linear the principle scheme CTS.
Symbols are accepted, on the scheme the following : 1
high-voltage input- 1 from the closed distributing
device of voltage 6-10 кV ; 2- the transformer №1 of
voltage 6-10 /0.4 кV, capacity 1000 кVА; 3- input- 1
0.4 кV from transformer In = 1600 A; 4- high-voltage
input- 2 from transformer In = 1600 A; 5-the
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470
@ IJTSRD | Available Online @ www.ijtsrd.com | Volume – 2 | Issue – 3 | Mar-Apr 2018 Page: 1655
transformer №2 of voltage 6-10 /0.4 кV, capacity
1000 кVА; 6- input- 2 0.4 кV from transformer In
= 1600 A; 7- section automatic breakers In = 1600 A
; 8- section of tires № 1; 9- Section of tires № 2; 10-
automatic diesel power station (АDPS) rated current
of In = 1250 A; 11- automatic breakers the generating
of АDPS; 12- input- 1 0.4 кV from the АDPS; 13-
input- 2 0.4 кV from the АDPS; 14- bunch of power
cables 4х (КВБШв - 3х150+1х50).
CLVT on the back party has two doors: top – closing
access in compartment of modular tires and bottom
closes a zone of departing power cables and bottom
closes a zone of departing power cables.
For possibility of control over a power consumption,
management electrical Consumption, accumulation of
the information on loadings of sections of tires CTS,
integration of automatic switch Master pact NT H1
into scheduling systems uses additional function of data
transmission (communication Bus) COM, realized in
section, cells of
input from the transformer and from a reserve source,
АВ Master pact NT [5]. For these to roll out devices
additional function of data transmission is provided
(fig. 2)
The module of communication established in the
device, delivered together with group of contacts
(micro- contacts OF, SDE, PF, CH) and the complete
set of communication with electromagnets of
management XF and MX
 the module of communication established in the
chassis, delivered together with group of contacts
(contacts CE,CD, CT).
Each established device has the address which is
appropriated to it by means of the keyboard of the
block of control and management Micrologic
(Modbus) or remotely (Batibus). Thus at creation
automated management systems of the enterprise it is
possible from Information operating system of top
level , for example from mini enterprise COMPUTER
scheduling office , management (or through PLC, or
passing it) established on feeding substations AV, to
transfer in top level of the data of measurement, the
alarm system, automatics, registration, control of
harmonics in a pressure curve, and also other
necessary information, for example condition АВ of
switches in various joining CTS, voltage presence on
inputs and sections of tires CTS etc.
Fig. 2. The scheme of connection of additional function of data transmission COM .
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470
@ IJTSRD | Available Online @ www.ijtsrd.com | Volume – 2 | Issue – 3 | Mar-Apr 2018 Page: 1656
Conclusion
1. With a view of creation of the automated control
systems by industrial power supply, in particular an
electrical supply, workings out more perfection
methods of optimization of power modes, increases
adequacy and security of electrical supplies etc. it is
necessary to expand use sphere in of electrical
installations consumers of servers of control systems
of real time (SCADA).
2. DD-0,4 kV CTS, equipped with PLC, automatic
breakers the manufactures Schneider Electric Master
pact with block of the control and management
Micrologic A/P/H can carry out function of bottom
level automated management systems of electric
power, complex protection of management of
substations at modern level. In this case they provide
automatic control in a place or with the removed
control offices, control of position primary
installations, measurements, the alarm system, record
and transfer of oscillograms etc.
3. In development of the theory and perfection of
methodology of designing of systems electrical
supplies industrial company the important place
occupies the account in such workings out available in
present time in electrical installations of consumers
and introduced in practice of operation of modern
devices DRPA, micro-processor systems of
registration of emergency events, gathering and data
processing about work DRPA; systems of
communications of new complexes with computer
"kernel" of the integrated monitoring system and
management, and also systems of display of the
information on workplaces of operation personnel and
a personnel of services RPA
4. And necessary for such workings out conformity to
modern safety requirements on IEC, IEE is important.
At reconstruction maintained, and also designing of
new electric networks it is necessary to aspire to pass
on three-phase five-wire network TN-S recommended
to СIGRE, IEC.
REFERENCES:
1) Design of a digital protection scheme for power
transformers using optimal state observers/ Y.V.
Multy et al.// IEE Proceedings- C, N 3, pp.224-
230, 1988.
2) Rudenko J.N., Semenov V. A/Automation of
dispatching management in electrical power. М:
Publishing house MEI. pp. 648, 2000.
3) Zhalilov R. B. Preconditions of creation of the
automated control systems of industrial power
supply.// The chief electrical engineer, release 6,
pp. 41-43, 2006.
4) Zhalilov R. B. Preconditions to creation of the
intellectual automated substation..//Industrial
power, release 4, pp. 15-18, 2008 .
5) Merlin Gerin. Automatic switches and switches of
loading for capacities transfer in low voltage
networks. Masterpact NT and NW. The catalogue.
М: the centre of information support, 2007.

More Related Content

PDF
Case study - Elektro Gorenjska
PDF
IRJET- Phase Changer Mechanism in Abnormal Conditions for Single Phase Applic...
PPTX
AUTOMATIC WIRELESS POWER GRID CONTROL
PDF
Crouzet Aerospace - Electrical Protection & Distribution
PDF
Weg automation-drives-and-controls-usa804-brochure-english
PDF
7SK81 Motor Protection Relay
PDF
ABB Relay
PDF
Eaton ats automatic transfer switch ats pwr
Case study - Elektro Gorenjska
IRJET- Phase Changer Mechanism in Abnormal Conditions for Single Phase Applic...
AUTOMATIC WIRELESS POWER GRID CONTROL
Crouzet Aerospace - Electrical Protection & Distribution
Weg automation-drives-and-controls-usa804-brochure-english
7SK81 Motor Protection Relay
ABB Relay
Eaton ats automatic transfer switch ats pwr

What's hot (20)

DOC
Scada
PDF
Design of embedded based three phase preventor and selector system for indust...
PDF
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
PPTX
Liebert RG UPS for Regenerative Load Applications
PPTX
Scada for remote industrial plant
PPTX
Transformer protection using microcontroller and gsm technology
PDF
Iskra Marine Programme 2016
PPT
Scada monitoring system
PPTX
Traffic light controller
PDF
IRJET- Transformer Monitoring and Protection System using AVR Atmega16 Mi...
PPTX
Grid synchronisation
PDF
Automated water head controller for domestic application
PDF
Automated water head controller for domestic application
PDF
An automatic wave probe reference setting mechanism in a high speed towing tank
PPTX
Abhishek seminar
PDF
AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...
PDF
An automatic wave probe reference setting mechanism
PDF
Design and Construction of Automatic Three Phase Power System Selector
PDF
Nidec asi service infrared termography
DOCX
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...
Scada
Design of embedded based three phase preventor and selector system for indust...
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
Liebert RG UPS for Regenerative Load Applications
Scada for remote industrial plant
Transformer protection using microcontroller and gsm technology
Iskra Marine Programme 2016
Scada monitoring system
Traffic light controller
IRJET- Transformer Monitoring and Protection System using AVR Atmega16 Mi...
Grid synchronisation
Automated water head controller for domestic application
Automated water head controller for domestic application
An automatic wave probe reference setting mechanism in a high speed towing tank
Abhishek seminar
AUTOMATIC METHOD OF PROTECTING TRANSFORMER USING PIC MICROCONTROLLER AS AN AL...
An automatic wave probe reference setting mechanism
Design and Construction of Automatic Three Phase Power System Selector
Nidec asi service infrared termography
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...
Ad

Similar to The Intellectual Automated Substation (20)

PDF
Wind Turbine programme
PPTX
NMRC Summer Tanning/Internship PPT(Anand Mohan )
PDF
Using Alternative Energy Sources Way to Intellectualization and Greater Energ...
PDF
IRJET - Monitoring and Protection of Distribution Transformer using GSM Module
PDF
IRJET- Monitoring and Protection of Distribution Transformer using GSM Module
DOC
Applications of microcontroller
PPTX
Madan mohan malaviya
PDF
IRJET- PLC Based Intelligent Control of Substation
PPTX
Assam Electricity Grid Corporation PRESENTATION.pptx
PDF
Centralized Monitoring and Control of Process Plants using PLC
PDF
A DAPTIVE S UPPLY V OLTAGE M ANAGEMENT F OR L OW P OWER L OGIC C IRCU...
PDF
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
PDF
A low cost short range wireless embedded system for multiple parameter control
PDF
A low cost short range wireless embedded system for multiple parameter control
PDF
MISSILE DETECT AND DESTROY SYSTEM
PDF
IRJET- Solar Powered Transmission Line Inspection Robot
PPTX
safrety project ILCDFIS for diploma students.pptx
PPTX
INTELLIGENT HELMET FOR COAL MINERS
PPTX
Numerical-Relay-PPT-1-convvffverted.pptx
PPTX
Measurement and Relay Indications.pptx
Wind Turbine programme
NMRC Summer Tanning/Internship PPT(Anand Mohan )
Using Alternative Energy Sources Way to Intellectualization and Greater Energ...
IRJET - Monitoring and Protection of Distribution Transformer using GSM Module
IRJET- Monitoring and Protection of Distribution Transformer using GSM Module
Applications of microcontroller
Madan mohan malaviya
IRJET- PLC Based Intelligent Control of Substation
Assam Electricity Grid Corporation PRESENTATION.pptx
Centralized Monitoring and Control of Process Plants using PLC
A DAPTIVE S UPPLY V OLTAGE M ANAGEMENT F OR L OW P OWER L OGIC C IRCU...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
A low cost short range wireless embedded system for multiple parameter control
A low cost short range wireless embedded system for multiple parameter control
MISSILE DETECT AND DESTROY SYSTEM
IRJET- Solar Powered Transmission Line Inspection Robot
safrety project ILCDFIS for diploma students.pptx
INTELLIGENT HELMET FOR COAL MINERS
Numerical-Relay-PPT-1-convvffverted.pptx
Measurement and Relay Indications.pptx
Ad

More from ijtsrd (20)

PDF
A Study of School Dropout in Rural Districts of Darjeeling and Its Causes
PDF
Pre extension Demonstration and Evaluation of Soybean Technologies in Fedis D...
PDF
Pre extension Demonstration and Evaluation of Potato Technologies in Selected...
PDF
Pre extension Demonstration and Evaluation of Animal Drawn Potato Digger in S...
PDF
Pre extension Demonstration and Evaluation of Drought Tolerant and Early Matu...
PDF
Pre extension Demonstration and Evaluation of Double Cropping Practice Legume...
PDF
Pre extension Demonstration and Evaluation of Common Bean Technology in Low L...
PDF
Enhancing Image Quality in Compression and Fading Channels A Wavelet Based Ap...
PDF
Manpower Training and Employee Performance in Mellienium Ltdawka, Anambra State
PDF
A Statistical Analysis on the Growth Rate of Selected Sectors of Nigerian Eco...
PDF
Automatic Accident Detection and Emergency Alert System using IoT
PDF
Corporate Social Responsibility Dimensions and Corporate Image of Selected Up...
PDF
The Role of Media in Tribal Health and Educational Progress of Odisha
PDF
Advancements and Future Trends in Advanced Quantum Algorithms A Prompt Scienc...
PDF
A Study on Seismic Analysis of High Rise Building with Mass Irregularities, T...
PDF
Descriptive Study to Assess the Knowledge of B.Sc. Interns Regarding Biomedic...
PDF
Performance of Grid Connected Solar PV Power Plant at Clear Sky Day
PDF
Vitiligo Treated Homoeopathically A Case Report
PDF
Vitiligo Treated Homoeopathically A Case Report
PDF
Uterine Fibroids Homoeopathic Perspectives
A Study of School Dropout in Rural Districts of Darjeeling and Its Causes
Pre extension Demonstration and Evaluation of Soybean Technologies in Fedis D...
Pre extension Demonstration and Evaluation of Potato Technologies in Selected...
Pre extension Demonstration and Evaluation of Animal Drawn Potato Digger in S...
Pre extension Demonstration and Evaluation of Drought Tolerant and Early Matu...
Pre extension Demonstration and Evaluation of Double Cropping Practice Legume...
Pre extension Demonstration and Evaluation of Common Bean Technology in Low L...
Enhancing Image Quality in Compression and Fading Channels A Wavelet Based Ap...
Manpower Training and Employee Performance in Mellienium Ltdawka, Anambra State
A Statistical Analysis on the Growth Rate of Selected Sectors of Nigerian Eco...
Automatic Accident Detection and Emergency Alert System using IoT
Corporate Social Responsibility Dimensions and Corporate Image of Selected Up...
The Role of Media in Tribal Health and Educational Progress of Odisha
Advancements and Future Trends in Advanced Quantum Algorithms A Prompt Scienc...
A Study on Seismic Analysis of High Rise Building with Mass Irregularities, T...
Descriptive Study to Assess the Knowledge of B.Sc. Interns Regarding Biomedic...
Performance of Grid Connected Solar PV Power Plant at Clear Sky Day
Vitiligo Treated Homoeopathically A Case Report
Vitiligo Treated Homoeopathically A Case Report
Uterine Fibroids Homoeopathic Perspectives

Recently uploaded (20)

PDF
FOISHS ANNUAL IMPLEMENTATION PLAN 2025.pdf
PPTX
Virtual and Augmented Reality in Current Scenario
PDF
David L Page_DCI Research Study Journey_how Methodology can inform one's prac...
PPTX
History, Philosophy and sociology of education (1).pptx
PDF
CISA (Certified Information Systems Auditor) Domain-Wise Summary.pdf
PDF
LDMMIA Reiki Yoga Finals Review Spring Summer
PDF
Uderstanding digital marketing and marketing stratergie for engaging the digi...
PDF
Environmental Education MCQ BD2EE - Share Source.pdf
PDF
BP 704 T. NOVEL DRUG DELIVERY SYSTEMS (UNIT 1)
PDF
advance database management system book.pdf
PDF
Vision Prelims GS PYQ Analysis 2011-2022 www.upscpdf.com.pdf
PDF
Paper A Mock Exam 9_ Attempt review.pdf.
PPTX
Share_Module_2_Power_conflict_and_negotiation.pptx
PPTX
Onco Emergencies - Spinal cord compression Superior vena cava syndrome Febr...
PDF
HVAC Specification 2024 according to central public works department
PPTX
TNA_Presentation-1-Final(SAVE)) (1).pptx
PDF
1.3 FINAL REVISED K-10 PE and Health CG 2023 Grades 4-10 (1).pdf
PDF
IGGE1 Understanding the Self1234567891011
PDF
International_Financial_Reporting_Standa.pdf
PDF
Weekly quiz Compilation Jan -July 25.pdf
FOISHS ANNUAL IMPLEMENTATION PLAN 2025.pdf
Virtual and Augmented Reality in Current Scenario
David L Page_DCI Research Study Journey_how Methodology can inform one's prac...
History, Philosophy and sociology of education (1).pptx
CISA (Certified Information Systems Auditor) Domain-Wise Summary.pdf
LDMMIA Reiki Yoga Finals Review Spring Summer
Uderstanding digital marketing and marketing stratergie for engaging the digi...
Environmental Education MCQ BD2EE - Share Source.pdf
BP 704 T. NOVEL DRUG DELIVERY SYSTEMS (UNIT 1)
advance database management system book.pdf
Vision Prelims GS PYQ Analysis 2011-2022 www.upscpdf.com.pdf
Paper A Mock Exam 9_ Attempt review.pdf.
Share_Module_2_Power_conflict_and_negotiation.pptx
Onco Emergencies - Spinal cord compression Superior vena cava syndrome Febr...
HVAC Specification 2024 according to central public works department
TNA_Presentation-1-Final(SAVE)) (1).pptx
1.3 FINAL REVISED K-10 PE and Health CG 2023 Grades 4-10 (1).pdf
IGGE1 Understanding the Self1234567891011
International_Financial_Reporting_Standa.pdf
Weekly quiz Compilation Jan -July 25.pdf

The Intellectual Automated Substation

  • 1. @ IJTSRD | Available Online @ www.ijtsrd.com | Volume – 2 | Issue – 3 | Mar-Apr 2018 Page: 1652 ISSN No: 2456 - 6470 | www.ijtsrd.com | Volume - 2 | Issue – 3 International Journal of Trend in Scientific Research and Development (IJTSRD) International Open Access Journal The Intellectual Automated Substation Zhalilov Rashid Ph.D, Associate Professor, Department of Electrical Engineering Bukhara engineering – Technological institute, Uzbekistan ABSTRACT The article is devoted to the study and introduction of modern technologies in electro-technical branch of the industry for the purpose of increasing reliability of electric supply. Appling the latest technical developments marketed in automatic breakers Compact NS and Master pact of the company "Schneider Electric", for modernization distributing device 0,4 kV applied transformer substation is offered in it . Keywords: Schneider Electric, Compact NS , Master- pact, SCADA, the programmed logic controller , reliability of electrical supply,cases the low-voltage transformer,four wire electric network TN-C, recommended IEC three-phase five-wire network TN- S, microcontacts OF, SDE, PF, CH, Modbus, SCADA, Batibus. INTRODUCTION Introduction of systems of automation and dispatching management on the modern digital techniques radical raises in the image quality and reliability of processes of manufacture, transfer and distribution electric power [1]. As a result of equipment of power objects by systems automations , microprocessor means emergency-preventive automatics and relay protection reach essential economic benefit at the expense of optimization of modes of transfer and distribution of energy, prevention of emergencies and minimization of a damage in case of their occurrence [1,2,3] . At present the begun transition in abroad to the next generation of microprocessor (digital) device of relay protection and automatics (DRPA) with integration within the limits of a uniform complex functions of relay protection, measurement processor complexes which have received wide applicated and commercial account electric power, regulation and management of electrical installation it is directed on maintenance of increase of reliability of electrical supply of consumers and conformity to modern safety requirements on IEC [2]. Frequent relay protection terminals carry out function of controllers of the bottom level of the automated management systems (AMS), providing complex protection of management of substations at modern level. In this case they provide management in a place or from remote control offices, control of position of the primary equipment, measurement, the alarm system, record and transfer of oscillograms. Besides, the AMS information system al lows to make to the user record/change date with use the pass word, to receive reports and to conduct archive of events, to execute conditions of diagnostics of the primary equip ment and etc.[4]. Wide use in electrical installations of consumers of servers of control systems of real time ( SCADA) provides [2,4]:  teleinformation reception/transfer in any reports;  reception / data transmission of the daily dispatching sheet (DS);  processing of the arriving information, formation date bases (DB) of real time (DBRT), to condense;  management of a dispatching board (digital devices, symbols, mnemonic schemes, information displays);  the cyclic copying DBRT on files-servers of a local network (LN) and etc.
  • 2. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470 @ IJTSRD | Available Online @ www.ijtsrd.com | Volume – 2 | Issue – 3 | Mar-Apr 2018 Page: 1653 As it is marked in [1-3], in the report 34-108 СIGRE are answered to Dews of a combination of traditional control facilities, relay protection and automatics (DRРА) with the new microprocessor complexes which have received wide application in the world. Creation is thus provided: microprocessor systems of registration of emergency events, gathering and data processing about work RРА; systems of communications of new complexes with computer "kernel" of the integrated monitoring system and management, and also systems of display of the information on workplaces of operation personnel and the personnel of services RРА. Distinctive feature developed by us distributing device -DD-0,4 kV for complete transformer substation (CTS) is the modern design, an openness for AMS for the account of presence of ports and the applications of the software that allows to realize flexible technical and economic solving for an electrical supply of consumers of any category. The device carries out functions local or remote control, relay are sewn up, alarm systems, automatics, registration, control of harmonics in a voltages curve (in cells of input from a reserve source), diagnostics automatic breakers, and also necessary blocking various blockings CTS. The switching centre- DD-0,4 kV CTS gathers from low-voltage cases of type Cases low-voltage transformer (CLVT). For assemblage of sections of tires DD-0,4 kV CTS separate CLVT, two party service, rigidly fasten among themselves the folding connections. In cells CLVT in the main chain following devices are established:  in cells of departing joining - automatic breakers (АВ) manufactures Schneider Electric Compact NS 400 N on 400 A to roll out executions with the electric drive;  in section and cells of input from the transformer - automatic breakers manufactures Schneider Electric Master pact NT 16 H1 on 1600 A to roll out execution with the electric drive;  in cells of input from a reserve source - automatic breakers of manufacture Schneider Electric Master pact NT 10 H1 on 1000 A to roll out execution with the electric drive;  a source of an uninterrupted food (UPS) (UPS NetPro 19) capacity 1кVt.) with time of support of capacity of consumers not less 5 minutes. In cell RРА of the section breakers are established various microprocessor blocks of relay protection, or program- med logic controllers (PLC) at will of the customer, for example S7-300 (the manufactures Siemens). On fig. 1 basic one-linear scheme CTS with it is developed us DD-0,4 kV. In DD-0,4 kV the following algorithm of automatics CTS is realized (fig. 1):  on the section breakers (SВ) it is executed automatic input of a reserve food (AIRBF) - a normal mode - both introduction breakers from transformers are included, SВ it is disconnected. On voltage disappearance on one of inputs (voltage control is carried out directly on tires CTS) - through the set endurance of time the breakers is disconnected corresponding introduction. Upon switching-off of input, absence of voltage on the disconnected section of tires and voltage presence on the second section, joins SB. At switching-off of the introduction breakers on currents protection the signal on a start-up interdiction is given of AIRBF. The algorithm of start of a reserve source (is carried out by the independent automatical Diesel power station (АDPS): In a starting position both introduction breakers from a transformers one of the introduction breakers is included, the generating switch in van АDPS is disconnected. At voltage disappearance on two sections CTS (voltage control it is made directly on tires) the signal on start АDPS is formed, at occurrence of voltage from АDPS, both introduction breakers are disconnected CTS, upon their switching-off the signal is formed on inclusions generating breakers are ADPS.  For realization of automatic and manual return transition to a food Automatic return transition», having two position: "Auto" and «The manual.». Algorithm of return transition. At voltage occurrence on one of inputs, with set date time (1-30 minutes), are formed a signal normal to stopping АDPS. Thus is disconnected generating breakers ADPS, upon its switching-off, presence voltage on input to the introduction switch of one of
  • 3. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470 @ IJTSRD | Available Online @ www.ijtsrd.com | Volume – 2 | Issue – 3 | Mar-Apr 2018 Page: 1654 section of tires (ST), to the absence fact voltage on ST, to the fact of the disconnected condition of the introduction switch adjacent section without endurance of time the switch of that joins introduction ST on which input there was voltage. At voltage occurrence on other input, with set date time (1-30 minutes), upon presence of voltage to the introduction switch of this ST, the included condition of the introduction switch and voltage presence on adjacent ST, it is disconnected SВ and the switch of the second joins introduction Input. Thus scheme АIRВ comes back in a starting position. The choice of a priority of inclusion of the introduction breaker is carried out with set date time on inclusion. At voltage occurrence simultaneously on both inputs - by the first input with smaller date time joins. One more feature developed DD-0,4 kV is that taps «The automatic breakers - a departing cable to consumers» are deduced in the bottom part of a case. On the ends tires (each all taps and the ends are marked (a phase, № the cells, a departing feeder). For safety of attendants cases CLVT are divided into the isolated compartments: the tires a compartment, compartment with breakers, compartment of relay protection and automatics. In the tires a compartment the equipment of the main chains settles down: the power the tires departing to consumers and a reserve source power cables and transformers of a current. Power automatic switches and switches of chains of management are established in corresponding cells. In cells of input from the transformer (cell № 1 in a case №1 and cell № 2 in a case №5) under a compartment for power switches it is allocated the special sector for installation of a source of an uninterrupted food (UPS) (UPS NetPro 19 capacity of 1 kVt.) with time of support of capacity of consumers not less minutes. In is the requirement on maintenance of speed of switching-off of the damages connected with influence on the person. In a compartment of relay protection are established: the interface relays of the alarm system, blocking and automatics, PLC, devices of control and the account of the electric power and other. Cells inside CLVT are separated from each other metal a partitions. For carrying out of repair work and maintenance service the power to roll out executions automatic breakers are established in cells on not-mobile the chassis fixed in working position bolt connection supported on the basis of a cell. 1 3 2 14 10 11 6 98 4 5 12 13 7 Fig-1: One-linear the principle scheme CTS. Symbols are accepted, on the scheme the following : 1 high-voltage input- 1 from the closed distributing device of voltage 6-10 кV ; 2- the transformer №1 of voltage 6-10 /0.4 кV, capacity 1000 кVА; 3- input- 1 0.4 кV from transformer In = 1600 A; 4- high-voltage input- 2 from transformer In = 1600 A; 5-the
  • 4. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470 @ IJTSRD | Available Online @ www.ijtsrd.com | Volume – 2 | Issue – 3 | Mar-Apr 2018 Page: 1655 transformer №2 of voltage 6-10 /0.4 кV, capacity 1000 кVА; 6- input- 2 0.4 кV from transformer In = 1600 A; 7- section automatic breakers In = 1600 A ; 8- section of tires № 1; 9- Section of tires № 2; 10- automatic diesel power station (АDPS) rated current of In = 1250 A; 11- automatic breakers the generating of АDPS; 12- input- 1 0.4 кV from the АDPS; 13- input- 2 0.4 кV from the АDPS; 14- bunch of power cables 4х (КВБШв - 3х150+1х50). CLVT on the back party has two doors: top – closing access in compartment of modular tires and bottom closes a zone of departing power cables and bottom closes a zone of departing power cables. For possibility of control over a power consumption, management electrical Consumption, accumulation of the information on loadings of sections of tires CTS, integration of automatic switch Master pact NT H1 into scheduling systems uses additional function of data transmission (communication Bus) COM, realized in section, cells of input from the transformer and from a reserve source, АВ Master pact NT [5]. For these to roll out devices additional function of data transmission is provided (fig. 2) The module of communication established in the device, delivered together with group of contacts (micro- contacts OF, SDE, PF, CH) and the complete set of communication with electromagnets of management XF and MX  the module of communication established in the chassis, delivered together with group of contacts (contacts CE,CD, CT). Each established device has the address which is appropriated to it by means of the keyboard of the block of control and management Micrologic (Modbus) or remotely (Batibus). Thus at creation automated management systems of the enterprise it is possible from Information operating system of top level , for example from mini enterprise COMPUTER scheduling office , management (or through PLC, or passing it) established on feeding substations AV, to transfer in top level of the data of measurement, the alarm system, automatics, registration, control of harmonics in a pressure curve, and also other necessary information, for example condition АВ of switches in various joining CTS, voltage presence on inputs and sections of tires CTS etc. Fig. 2. The scheme of connection of additional function of data transmission COM .
  • 5. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470 @ IJTSRD | Available Online @ www.ijtsrd.com | Volume – 2 | Issue – 3 | Mar-Apr 2018 Page: 1656 Conclusion 1. With a view of creation of the automated control systems by industrial power supply, in particular an electrical supply, workings out more perfection methods of optimization of power modes, increases adequacy and security of electrical supplies etc. it is necessary to expand use sphere in of electrical installations consumers of servers of control systems of real time (SCADA). 2. DD-0,4 kV CTS, equipped with PLC, automatic breakers the manufactures Schneider Electric Master pact with block of the control and management Micrologic A/P/H can carry out function of bottom level automated management systems of electric power, complex protection of management of substations at modern level. In this case they provide automatic control in a place or with the removed control offices, control of position primary installations, measurements, the alarm system, record and transfer of oscillograms etc. 3. In development of the theory and perfection of methodology of designing of systems electrical supplies industrial company the important place occupies the account in such workings out available in present time in electrical installations of consumers and introduced in practice of operation of modern devices DRPA, micro-processor systems of registration of emergency events, gathering and data processing about work DRPA; systems of communications of new complexes with computer "kernel" of the integrated monitoring system and management, and also systems of display of the information on workplaces of operation personnel and a personnel of services RPA 4. And necessary for such workings out conformity to modern safety requirements on IEC, IEE is important. At reconstruction maintained, and also designing of new electric networks it is necessary to aspire to pass on three-phase five-wire network TN-S recommended to СIGRE, IEC. REFERENCES: 1) Design of a digital protection scheme for power transformers using optimal state observers/ Y.V. Multy et al.// IEE Proceedings- C, N 3, pp.224- 230, 1988. 2) Rudenko J.N., Semenov V. A/Automation of dispatching management in electrical power. М: Publishing house MEI. pp. 648, 2000. 3) Zhalilov R. B. Preconditions of creation of the automated control systems of industrial power supply.// The chief electrical engineer, release 6, pp. 41-43, 2006. 4) Zhalilov R. B. Preconditions to creation of the intellectual automated substation..//Industrial power, release 4, pp. 15-18, 2008 . 5) Merlin Gerin. Automatic switches and switches of loading for capacities transfer in low voltage networks. Masterpact NT and NW. The catalogue. М: the centre of information support, 2007.