Protection Relays & Controls
© 2014 Littelfuse Protection Relays & Controls
Littelfuse.com/ArcFlash
Rev: 4-G-032714
Based on Manual Rev 3-A-112913
Description
The PGR-8800 is a microprocessor-based relay that limits
arc-fault damage by detecting the light from an arc flash and
rapidly tripping. Phase-current-transformer inputs are provided
for current-constrained arc-flash protection and, when so
equipped, a programmable definite-time overcurrent function
can be enabled. An optical sensor on the PGR-8800 and
adjustable trip level reduce the chance of nuisance tripping
by setting a threshold for ambient light. Sensors, inputs, and
connections are monitored to ensure fail-safe operation. A
secondary solid-state trip circuit provides a redundant trip path.
A USB port is used for configuration and access to event logs
and graphs.
Optical Sensors
The PGR-8800 accepts both PGA-LS10 and PGA-LS20/PGA-
LS25/PGA-LS30 optical sensors, designed to collect light over
a wide angle and with high sensitivity. For fast fault location,
front-panel and sensor LED’s indicate sensor health and which
sensor detected an arc fault.
Sensor Placement
The PGR-8800 Arc-Flash Relay and sensors are easily
installed in retrofit projects and new switchgear with little or
no re-configuration. Even elaborate systems with multiple
power sources take minutes to configure using the relay’s
built-in USB interface software.
Generally, it is recommended to mount 1 or 2 sensors per
cubicle to cover all horizontal and vertical bus bars, breaker
compartments, drawers, and anywhere that there is potential
for an arc-fault. Threading a fiber-optic sensor through
the cabinets and in areas where point-sensor coverage is
uncertain results in complete coverage and an added level
of redundancy. Even if policy is to only work on de-energized
systems, all maintenance areas should be monitored to
prevent potential damage and additional cost. At least one
sensor should have visibility of an arc fault if a person blocks
the other sensor(s).
Simplified Circuit Diagram
PGA-LS10
(Point Sensor)
PGA-LS20/
PGA-LS25/
PGA-LS30
(Fiber-Optic Sensor)
PGA-1100
(Diode Logic Unit)
(Optional)
24 Vdc Battery
Backup
(Optional)
(Recommended)
(Arc-Flash Protection Relay)
PGR-8800
Trip
5-A-SECONDARY PHASE CT’s
L2
L1
A
B
C
A
B
Ordering Information
PGR-8800 SERIES (D1000)
Arc-Flash Relay
C
D
ORDERING NUMBER COMMUNICATIONS
PGR-8800-00 (UL, CE, C-tick) Multi-unit linking, Modbus®
RTU
ACCESSORIES REQUIREMENT
PGA-LS10 (A1000) Required*
PGA-LS20 (A2000)/
PGA-LS25 (A2000.0020)
PGA-LS30 (A2000.0030)
Required*
PGA-1100 (D1100) Optional
Current Transformer Optional
*At least one sensor is required. However, the exact number of sensors for proper coverage
depends on the application.
D D D
Local
Circuit Breaker
For detailed wiring diagram, see adjacent page.
Arc-Flash Monitoring
Protection Relays & Controls
© 2014 Littelfuse Protection Relays & Controls
Littelfuse.com/ArcFlash
Wiring Diagram
FEATURES BENEFITS
Arc-Flash trip time <1 ms Limits arc-flash damage and risk of injury
Multiple sensors (up to 24) Single module can monitor 6 sensors. Up to 4 PGR-8800 units can be linked into one system
Fail-safe system Continuous monitoring of optical sensors and inputs ensures protection
Redundant trip circuit Solid-state backup arc-detection circuit adds a second layer of safety
Adjustable light sensitivity Allows for operation in bright environments and maximum sensitivity in dark environments
LED indication (on unit and each sensor) 18 LEDs provide at-a glance status for module and I/O state
Current detection Phase-CT inputs provide overcurrent protection and prevent nuisance trips
Optical detection Point and fiber-optic sensors provide wide detection area with sensor health trip indication
Digital inputs (6) Two each: remote trip, inhibit, and reset inputs
Service mode Allows for system test without tripping
Trip coil contact Solid-state 24-300 Vdc/24-300 Vac IGBT
Indication contacts Form C and status outputs
USB interface Data logging and configuration software uses a USB interface with no drivers or software installation
Built-in sensor Can be used in single-sensor systems, as a seventh sensor, and for calibration
Universal power supply/Battery backup 100-240 Vac, 14-48 Vdc, or 110-250 Vdc supply accepted. Ability to charge and run off an external, user-supplied
24 Vdc battery.
Data logging On-board event recorder helps with system diagnostics
Modbus Remotely view measured values, event records & reset trips
Upstream Tripping Ability to trip upstream device if the local breaker fails to clear the fault
Features & Benefits
PGR-8800 SERIES (D1000)
Arc-Flash Relay
1
31 36 3937 45 46 47 48 49 50 51 52 53 54 55 56 57 59 6038
4
........
5 8
........
9 12
........
13 16
........
17 20
........
21 24
........
..................................
25 26 27 28 29 30
STATUS STATUS STATUS
TRIP COILTRIPPEDSERVICE
LINK
ONLINE
+ –
CONTROL POWER
and BATTERY
DIGITAL INPUTS
ARC-FLASH RELAY
PGR-8800 SERIES
ARC-FLASH RELAY
PGR-8800
(optional)
DIODE LOGIC
UNIT
PGA-1100
(optional)
ARC-FLASH RELAY
PGR-8800
(optional)
ARC-FLASH RELAY
PGR-8800
(optional)
PHASE CT
(recommended)
PHASE CT
(recommended)
PHASE CT
(recommended)
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
Specifications
IEEE Device Numbers	 Overcurrent (50), Arc Flash (AFD)
Input Voltage	 100-240 Vac, 14-48 Vdc, and 110-250 Vdc
Dimensions	H 130 mm (5.2”); W 200 mm (7.9”);
D 54 mm (2.2”)
Optical Trip Settings	 9-25 klux, 800 μs-20 s
Current Trip Setting (A)	 Programmable
Indication Contact Mode	 Fail-safe
Trip Coil Voltage(1)
	 24-300 Vdc, 24-300 Vac
Trip Coil Contact Mode	 Selectable fail-safe or non-fail-safe
Redundant Trip Circuit	 Standard feature
Input Monitoring	 Standard feature
USB Interface	 Standard feature
Trip, Reset,
Service Buttons	 Standard feature
Expandable System	 Link up to 4 PGR-8800 units
Warranty	 5 years
Mounting 	 DIN (with D0050 adapter clips), Surface
PGA-LS10 (A1000) Point Sensor
Line-of-sight light sensor detects an arc as small as 3 kA
within a 2-m half-sphere. Sensor health and trip indication.
Dimensions: See PGR-8800 Manual
PGA-LS20 (A2000)/PGA-LS25 (A2000.0020)/PGA-
LS30(A2000.0030) Fiber-Optic Sensor
360° light sensor for tricky installations with many shadows
or to run along bus bars. Sensor health and trip indication.
Dimensions: See PGR-8800 Manual
PGA-1100 (D1100) Diode Logic Unit
This module allows multiple PGR-8800 relays to trip the
same breaker, for example an upstream or a tie-breaker.
Dimensions: H 80mm (3.15”) W 20mm(.79”) D 70mm(2.76”)
CurrentTransformers
Eliminate nuisance arc-flash trips and use for
overcurrent protection.
Accessories
A
B
D
C
Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information.
NOTE (1) - Contact Littelfuse for trip coil voltages higher than 300 Vdc/Vac.
Rev: 4-F-012214
Based on Manual Rev 3-A-112913
Arc-Flash Monitoring

More Related Content

PDF
Littelfuse PGR-8800 D1000 Arc Flash Unit - DNV Marine Approval
PDF
Industrial Wireless Explosion Proof Antenna for Hazardous Area GPS/GLONASS/Ir...
PDF
Top Ten Advances In RTD Signal Conditioning
PPT
Medium Performance Gyroscopes
PDF
Datasheet Fluke CLKT Series. Hubungi PT. Siwali Swantika 021-45850618
PDF
How to design a Passive Infrared (PIR) Open Source Project
PDF
Ronan Intrinsic Safety Barriers
PDF
AFL Fiber Optic Test and Inspection Solutions 2017
Littelfuse PGR-8800 D1000 Arc Flash Unit - DNV Marine Approval
Industrial Wireless Explosion Proof Antenna for Hazardous Area GPS/GLONASS/Ir...
Top Ten Advances In RTD Signal Conditioning
Medium Performance Gyroscopes
Datasheet Fluke CLKT Series. Hubungi PT. Siwali Swantika 021-45850618
How to design a Passive Infrared (PIR) Open Source Project
Ronan Intrinsic Safety Barriers
AFL Fiber Optic Test and Inspection Solutions 2017

What's hot (20)

PDF
Magnetostrictive Liquid Level Transmitter for Process Measurement and Control
PDF
Brosur Fluke Insulation Resistance Testing. Hubungi PT. Siwali Swantika 021-4...
PDF
Isweek rps 409 a-is2 ultrasonic sensor certified safe for use in explosive en...
PDF
Raising the Bar: Foundry Expectations for Equipment Capability and Control
PDF
Flexim Americas - Non-Intrusive Liquid Flow Measurement
PPTX
Pinpoint the leading causes of downtime with LinkIQ Cable and Network Tester
PDF
Retractable Sensor Housings for Analytical Sensors
PDF
Datasheet Fluke CV Series. Hubungi PT. Siwali Swantika 021-45850618
PDF
Migration ux to windows - ICT i3070
PDF
Básicos de Functional Test Systems - Testing Days Tijuana
PDF
Andel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
PDF
Pulsar 7700-7900-datasheet
PDF
Pulsar 7000 safety manual
PDF
Drager REGARD-1 Fixed Gas Detector Control System - Spec Sheet
PDF
iRTU F: The RTU with Fault Detection
PDF
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
PDF
UE One Series Safety Transmitter
PDF
Seaward Catalog High Voltage Test Tools
PDF
2015 Katalog Fluke - Siwali 021 45850618
PDF
Process Control (Design Conference 2013)
Magnetostrictive Liquid Level Transmitter for Process Measurement and Control
Brosur Fluke Insulation Resistance Testing. Hubungi PT. Siwali Swantika 021-4...
Isweek rps 409 a-is2 ultrasonic sensor certified safe for use in explosive en...
Raising the Bar: Foundry Expectations for Equipment Capability and Control
Flexim Americas - Non-Intrusive Liquid Flow Measurement
Pinpoint the leading causes of downtime with LinkIQ Cable and Network Tester
Retractable Sensor Housings for Analytical Sensors
Datasheet Fluke CV Series. Hubungi PT. Siwali Swantika 021-45850618
Migration ux to windows - ICT i3070
Básicos de Functional Test Systems - Testing Days Tijuana
Andel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
Pulsar 7700-7900-datasheet
Pulsar 7000 safety manual
Drager REGARD-1 Fixed Gas Detector Control System - Spec Sheet
iRTU F: The RTU with Fault Detection
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
UE One Series Safety Transmitter
Seaward Catalog High Voltage Test Tools
2015 Katalog Fluke - Siwali 021 45850618
Process Control (Design Conference 2013)
Ad

Similar to Littelfuse PGR-8800 Arc-Flash Relay (20)

PDF
RCBU-2-Arc-Flash-Protection_Key_Considerations_for_Selection
PDF
Littelfuse protection relay_controls_catalog_may2012
PDF
Littelfuse - Protection Relays & Controls
PDF
20120504 LISAT slides Dube
PPTX
Protective Relay by Shamim Reza
PPT
Numerical protection 2
PDF
Arc_flash_mitigation_in_a_chemical_and_refining_facility_using_IEC_61850.pdf
PDF
Short Circuit, Protective Device Coordination
PDF
Selective Coodination
PDF
7SR220 Overcurrent Relay
PPTX
7SR10 Overcurrent Relay
PDF
Reducing Electrical Control Panel Size
PDF
Eng susol acb_ocr_p_stype_modbus_profile
PPTX
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
PDF
Evaluating the Arc-Flash Protection Benefits of IEC 61850 Communication
PPTX
Relay operation principles
PDF
7SR210 Overcurrent Relay
PDF
ETAP - Arcflash analysis & mitigation methods
PDF
7SR224 Overcurrent Protection Relay
RCBU-2-Arc-Flash-Protection_Key_Considerations_for_Selection
Littelfuse protection relay_controls_catalog_may2012
Littelfuse - Protection Relays & Controls
20120504 LISAT slides Dube
Protective Relay by Shamim Reza
Numerical protection 2
Arc_flash_mitigation_in_a_chemical_and_refining_facility_using_IEC_61850.pdf
Short Circuit, Protective Device Coordination
Selective Coodination
7SR220 Overcurrent Relay
7SR10 Overcurrent Relay
Reducing Electrical Control Panel Size
Eng susol acb_ocr_p_stype_modbus_profile
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
Evaluating the Arc-Flash Protection Benefits of IEC 61850 Communication
Relay operation principles
7SR210 Overcurrent Relay
ETAP - Arcflash analysis & mitigation methods
7SR224 Overcurrent Protection Relay
Ad

More from Thorne & Derrick International (20)

PDF
Isolation procedures for safe working on electrical systems and equipment by ...
PDF
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
PDF
The Children North East Annual Golf Day Wednesday 9th May 2018
PDF
3M Electrical Products Stocked By Thorne & Derrick International
PDF
CATU Electrical Safety Catalogue
PDF
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
PDF
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
PDF
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
PDF
Roxtec Cable Transit - B Frame Dimensional Drawing
PDF
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
PDF
T&D Experts In Equipment For Explosive Atmospheres
PDF
Ultrasonic Flow Meters - Customer Specification Demand
PDF
Emtelle Fibre Optic Cables - Product Catalogue 2016
PDF
Thorne & Derrick Process Heating Brochure 2016
PDF
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
PDF
Ripley Utility Tool Cable Preparation Tools
PDF
RIDGID micro CD100 Combustible Gas Detector
PDF
PDF
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
PDF
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Isolation procedures for safe working on electrical systems and equipment by ...
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
The Children North East Annual Golf Day Wednesday 9th May 2018
3M Electrical Products Stocked By Thorne & Derrick International
CATU Electrical Safety Catalogue
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Roxtec Cable Transit - B Frame Dimensional Drawing
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
T&D Experts In Equipment For Explosive Atmospheres
Ultrasonic Flow Meters - Customer Specification Demand
Emtelle Fibre Optic Cables - Product Catalogue 2016
Thorne & Derrick Process Heating Brochure 2016
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
Ripley Utility Tool Cable Preparation Tools
RIDGID micro CD100 Combustible Gas Detector
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet

Recently uploaded (20)

PDF
STKI Israel Market Study 2025 version august
PDF
NewMind AI Weekly Chronicles – August ’25 Week III
PPTX
Tartificialntelligence_presentation.pptx
PDF
Univ-Connecticut-ChatGPT-Presentaion.pdf
PDF
Enhancing emotion recognition model for a student engagement use case through...
PDF
A novel scalable deep ensemble learning framework for big data classification...
PDF
August Patch Tuesday
PPT
Module 1.ppt Iot fundamentals and Architecture
PDF
Taming the Chaos: How to Turn Unstructured Data into Decisions
DOCX
search engine optimization ppt fir known well about this
PPTX
Modernising the Digital Integration Hub
PDF
CloudStack 4.21: First Look Webinar slides
PPT
What is a Computer? Input Devices /output devices
PDF
Microsoft Solutions Partner Drive Digital Transformation with D365.pdf
PPTX
The various Industrial Revolutions .pptx
PDF
A Late Bloomer's Guide to GenAI: Ethics, Bias, and Effective Prompting - Boha...
PDF
Assigned Numbers - 2025 - Bluetooth® Document
PDF
Getting Started with Data Integration: FME Form 101
PPTX
Final SEM Unit 1 for mit wpu at pune .pptx
PDF
DASA ADMISSION 2024_FirstRound_FirstRank_LastRank.pdf
STKI Israel Market Study 2025 version august
NewMind AI Weekly Chronicles – August ’25 Week III
Tartificialntelligence_presentation.pptx
Univ-Connecticut-ChatGPT-Presentaion.pdf
Enhancing emotion recognition model for a student engagement use case through...
A novel scalable deep ensemble learning framework for big data classification...
August Patch Tuesday
Module 1.ppt Iot fundamentals and Architecture
Taming the Chaos: How to Turn Unstructured Data into Decisions
search engine optimization ppt fir known well about this
Modernising the Digital Integration Hub
CloudStack 4.21: First Look Webinar slides
What is a Computer? Input Devices /output devices
Microsoft Solutions Partner Drive Digital Transformation with D365.pdf
The various Industrial Revolutions .pptx
A Late Bloomer's Guide to GenAI: Ethics, Bias, and Effective Prompting - Boha...
Assigned Numbers - 2025 - Bluetooth® Document
Getting Started with Data Integration: FME Form 101
Final SEM Unit 1 for mit wpu at pune .pptx
DASA ADMISSION 2024_FirstRound_FirstRank_LastRank.pdf

Littelfuse PGR-8800 Arc-Flash Relay

  • 1. Protection Relays & Controls © 2014 Littelfuse Protection Relays & Controls Littelfuse.com/ArcFlash Rev: 4-G-032714 Based on Manual Rev 3-A-112913 Description The PGR-8800 is a microprocessor-based relay that limits arc-fault damage by detecting the light from an arc flash and rapidly tripping. Phase-current-transformer inputs are provided for current-constrained arc-flash protection and, when so equipped, a programmable definite-time overcurrent function can be enabled. An optical sensor on the PGR-8800 and adjustable trip level reduce the chance of nuisance tripping by setting a threshold for ambient light. Sensors, inputs, and connections are monitored to ensure fail-safe operation. A secondary solid-state trip circuit provides a redundant trip path. A USB port is used for configuration and access to event logs and graphs. Optical Sensors The PGR-8800 accepts both PGA-LS10 and PGA-LS20/PGA- LS25/PGA-LS30 optical sensors, designed to collect light over a wide angle and with high sensitivity. For fast fault location, front-panel and sensor LED’s indicate sensor health and which sensor detected an arc fault. Sensor Placement The PGR-8800 Arc-Flash Relay and sensors are easily installed in retrofit projects and new switchgear with little or no re-configuration. Even elaborate systems with multiple power sources take minutes to configure using the relay’s built-in USB interface software. Generally, it is recommended to mount 1 or 2 sensors per cubicle to cover all horizontal and vertical bus bars, breaker compartments, drawers, and anywhere that there is potential for an arc-fault. Threading a fiber-optic sensor through the cabinets and in areas where point-sensor coverage is uncertain results in complete coverage and an added level of redundancy. Even if policy is to only work on de-energized systems, all maintenance areas should be monitored to prevent potential damage and additional cost. At least one sensor should have visibility of an arc fault if a person blocks the other sensor(s). Simplified Circuit Diagram PGA-LS10 (Point Sensor) PGA-LS20/ PGA-LS25/ PGA-LS30 (Fiber-Optic Sensor) PGA-1100 (Diode Logic Unit) (Optional) 24 Vdc Battery Backup (Optional) (Recommended) (Arc-Flash Protection Relay) PGR-8800 Trip 5-A-SECONDARY PHASE CT’s L2 L1 A B C A B Ordering Information PGR-8800 SERIES (D1000) Arc-Flash Relay C D ORDERING NUMBER COMMUNICATIONS PGR-8800-00 (UL, CE, C-tick) Multi-unit linking, Modbus® RTU ACCESSORIES REQUIREMENT PGA-LS10 (A1000) Required* PGA-LS20 (A2000)/ PGA-LS25 (A2000.0020) PGA-LS30 (A2000.0030) Required* PGA-1100 (D1100) Optional Current Transformer Optional *At least one sensor is required. However, the exact number of sensors for proper coverage depends on the application. D D D Local Circuit Breaker For detailed wiring diagram, see adjacent page. Arc-Flash Monitoring
  • 2. Protection Relays & Controls © 2014 Littelfuse Protection Relays & Controls Littelfuse.com/ArcFlash Wiring Diagram FEATURES BENEFITS Arc-Flash trip time <1 ms Limits arc-flash damage and risk of injury Multiple sensors (up to 24) Single module can monitor 6 sensors. Up to 4 PGR-8800 units can be linked into one system Fail-safe system Continuous monitoring of optical sensors and inputs ensures protection Redundant trip circuit Solid-state backup arc-detection circuit adds a second layer of safety Adjustable light sensitivity Allows for operation in bright environments and maximum sensitivity in dark environments LED indication (on unit and each sensor) 18 LEDs provide at-a glance status for module and I/O state Current detection Phase-CT inputs provide overcurrent protection and prevent nuisance trips Optical detection Point and fiber-optic sensors provide wide detection area with sensor health trip indication Digital inputs (6) Two each: remote trip, inhibit, and reset inputs Service mode Allows for system test without tripping Trip coil contact Solid-state 24-300 Vdc/24-300 Vac IGBT Indication contacts Form C and status outputs USB interface Data logging and configuration software uses a USB interface with no drivers or software installation Built-in sensor Can be used in single-sensor systems, as a seventh sensor, and for calibration Universal power supply/Battery backup 100-240 Vac, 14-48 Vdc, or 110-250 Vdc supply accepted. Ability to charge and run off an external, user-supplied 24 Vdc battery. Data logging On-board event recorder helps with system diagnostics Modbus Remotely view measured values, event records & reset trips Upstream Tripping Ability to trip upstream device if the local breaker fails to clear the fault Features & Benefits PGR-8800 SERIES (D1000) Arc-Flash Relay 1 31 36 3937 45 46 47 48 49 50 51 52 53 54 55 56 57 59 6038 4 ........ 5 8 ........ 9 12 ........ 13 16 ........ 17 20 ........ 21 24 ........ .................................. 25 26 27 28 29 30 STATUS STATUS STATUS TRIP COILTRIPPEDSERVICE LINK ONLINE + – CONTROL POWER and BATTERY DIGITAL INPUTS ARC-FLASH RELAY PGR-8800 SERIES ARC-FLASH RELAY PGR-8800 (optional) DIODE LOGIC UNIT PGA-1100 (optional) ARC-FLASH RELAY PGR-8800 (optional) ARC-FLASH RELAY PGR-8800 (optional) PHASE CT (recommended) PHASE CT (recommended) PHASE CT (recommended) PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR Specifications IEEE Device Numbers Overcurrent (50), Arc Flash (AFD) Input Voltage 100-240 Vac, 14-48 Vdc, and 110-250 Vdc Dimensions H 130 mm (5.2”); W 200 mm (7.9”); D 54 mm (2.2”) Optical Trip Settings 9-25 klux, 800 μs-20 s Current Trip Setting (A) Programmable Indication Contact Mode Fail-safe Trip Coil Voltage(1) 24-300 Vdc, 24-300 Vac Trip Coil Contact Mode Selectable fail-safe or non-fail-safe Redundant Trip Circuit Standard feature Input Monitoring Standard feature USB Interface Standard feature Trip, Reset, Service Buttons Standard feature Expandable System Link up to 4 PGR-8800 units Warranty 5 years Mounting DIN (with D0050 adapter clips), Surface PGA-LS10 (A1000) Point Sensor Line-of-sight light sensor detects an arc as small as 3 kA within a 2-m half-sphere. Sensor health and trip indication. Dimensions: See PGR-8800 Manual PGA-LS20 (A2000)/PGA-LS25 (A2000.0020)/PGA- LS30(A2000.0030) Fiber-Optic Sensor 360° light sensor for tricky installations with many shadows or to run along bus bars. Sensor health and trip indication. Dimensions: See PGR-8800 Manual PGA-1100 (D1100) Diode Logic Unit This module allows multiple PGR-8800 relays to trip the same breaker, for example an upstream or a tie-breaker. Dimensions: H 80mm (3.15”) W 20mm(.79”) D 70mm(2.76”) CurrentTransformers Eliminate nuisance arc-flash trips and use for overcurrent protection. Accessories A B D C Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information. NOTE (1) - Contact Littelfuse for trip coil voltages higher than 300 Vdc/Vac. Rev: 4-F-012214 Based on Manual Rev 3-A-112913 Arc-Flash Monitoring