Dedicated VFDs for HVAC/R and Pumps
H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
General specifications
• Drive capacity
- 230V, Three-phase, 1~25hp(5~69A, ND)
- 480V, Three-phase, 1~125hp(2.5~169A, ND)
• Overload capacity
- 120% for 60sec. (up to 90kW)
- 110% for 60sec. (above 110kW)
• Input voltage range
- 200~240V Three-phase (-15%/+10%)
- 380~480V Three-phase (-15%/+10%)
• Communication
- Built-in BACnet(MS/TP, B-ASC), Metasys N2
LS Bus, Modbus-RTU
- LonWorks as optional
• Control meothod
- V/f
• Output frequency
- 0~400Hz
• Carrier frequency
- Normal Duty: 1~15kHz
• Protection degree
- Standard: IP20, Optional: NEMA1
• Global Certificated
- CE, UL, cUL, RoHS, *Plenum Rated (UL1995)
- UL Pollution type 3 Conformal Coating on PCB
1 25 125
HP
IP20 400V/3Φ
IP20 200V/3Φ
800
Built In EMC Filter, DC Reactor as optional (IP20)
40
H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
H100 Hardware specification
• Flange mountable with kit
- IP54 Heat sink out the back design
(above 150HP)
• Universal conduit box
1~15hp 20hp 25hp240V
480V 1~15hp 20~25hp 30~40hp 50hp 60~75hp 100~125hp
• 11 frame size
- 1 though 25HP (240V)
- 1 though 800HP (480V)
- UL single rating up to 125HP
150~200hp 250~300hp
350~400hp480V 500~650hp 800hp
H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
H100 Hardware specification
*‘MULTI’ key: One touch allows to access to user group that can be registered up to 64 parameters by user.
 HAND Mode (Local Control Mode) or AUTO Mode (Remote Control Mode) can be selected.
 Standard functions for HVAC/R
- Hand key: Operation via keypad.
- Hand key  up/down: changes speed. V/F only (PID is disabled)
- Off key: Functions as Stop or Reset button.
- Auto key: Operation as preset functions.
HAND AUTO
OFF
Push HAND ①
Push AUTO ②
H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
H100 Hardware specification
EMC Filter
- Built-in C3
Capacitor Bank
- Long Life Span
FAN
- Suction Type
- Removable
Heat Sink
- Pin bonding type:
Down size
- Press Body
Wiring Bracket
- Removable Wire Guide
*‘Even thought EMC filter is not built in the 75~90kW models, it meets the EMC Directive Category C3
H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
H100 Hardware specification
Switch Description LEFT RIGHT
SW1 Termination Resistor ON OFF
SW2 NPN / PNP NPN PNP
SW3 Analog Input-1 Select V1 T1(PTC)
SW4 Analog Input-2 Select I2 V2
SW5 Analog Output-1 Select Voltage Current
Standard
I/O
No. of Pins 34 pins
Relay output
A1,B1,C1
A2, C2
A3, C3
A4, C4
A5, C5
24V output 24
Analog input voltage (+12V) VR
Analog voltage input /
PTC input
V1
Analog voltage/Current input /
PTC input
I2
Analog voltage/Current output AO1
Analog voltage output AO2
RS485 signal / Ground S+,S- / SG
I/O Ground(Except for comm.) CM
Programmable TR output /
Pulse train output(0~32kHz)
Q1,EG
Programmable digital input
(PNP/NPN)
P1~P7
Pulse train input (0~32kHz) TI
Terminal pitch 5mm
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
0 Basic
1 Compressor
2 Supply Fan
3 Exhaust Fan
4 Cooling Tower
5 Circulating Pump
6 Vacuum Pump
7 Constant Torque
7 Selectable Macros Example of Compressor(MC1) Macro
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Sunday Monday Tuesday Wednesday Thursday Friday Saturday
00:00
08:00
04:00
12:00
02:00
06:00
10:00
14:00
22:00
18:00
16:00
20:00
24:00
Pre-Heat
Fx
Speed-L
Speed-H
 4 time period modules (Weekly)
 8 exception date modules (Day)
 8 time event modules
 30 functions available (Fx, Rx, Step Freq, PID, etc.)
 Day Light Savings available (Start/End date setting)
 3 types of date displays available (EU / USA / ASIA)
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
*
f
출력전압지령
출력 주파수
기저 주파수
60.00Hz
시작 주파수
(0.5Hz)
4729
132
DQ
Transformation
PWM Input
Voltage Reference
cba iii ,,
compV
DQ
Transformation
di
qi
Compensation
Voltage Regulator
ATB Filt Gain
CON_21
Rated Slip
Motor Capacitiy
ATB Volt Gain
CON_22
PWMAVR
Voltage Reference
Regulator
LPF
Motor
Test
condition
Cmd
Freq.
Load
Rate
ACC
Time
Auto torque boost 1 (Existing) Auto torque boost 2 (New)
20hp-480V 100hp-480V 20hp-480V 100hp-480V
Starting 3Hz
100%
0sec ○ ○ ○ ○
10sec ○ ○ ○ ○
120%
0sec ○ ○ ○ ○
10sec ○ ○ ○ ○
adjust load
3Hz
Variable -
X
(50%->100%)
○ ○ ○
5Hz
X
(0%->120%)
X
(50%->100%)
○ ○
Starting 60Hz
100% 10sec ○ X ○ ○
120% 10sec △(Unstable) X ○ ○
adjust load 60Hz Variable - ○ ○ ○ ○
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Fire Mode Signal
Direction command
Fire Mode Freq
Ignored Trip Retry Trip
Fault
FWD
FWD
Fire Mode Direction
Fire Mode
Signal Input
On
Off
Output Frequency
Fire mode sequence
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Soft Fill sequence
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Pump clean Sequence
*’Load tune’ function should be conducted before activating ‘Pump clean’ function.
Pump clean operationForeign debris stuck in impeller
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Under load operation
*’Load tune’ function should be conducted before activating ‘Pump clean’ function.
Under load sequence
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Soft Fill sequence
Pre-PID
Soft Fill
Normal PID
PID-04
PID Ref Value
PID Reference
Soft Fill Set
AP-22
Pre-PID Delay
AP-21
Pre-PID Freq
AP-25
Soft Step Time
AP-24
Fill Step Set
t
t
PID-05
PID Fdb Value
Frequency
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Pipe broken operation
PID Reference
Feedback
PID Reference*PRT-61(Pipe Broken Dev)
PRT-62(Pipe Broken DT)
Time
Time
PID Unit
PID Output(MAX)
or Max Freq
Time
PID Reference
FeedBack
Min(PID Limit, Max Freq)
PID Reference*PRT-61(PipeBroken Dev)
A
PID Unit
Frequency
PRT-62
Pipe Broken DT
B
C
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Flow compensation operation
Pressure
LengthSensor
position
Pressure Reference Setpoint
Pressure1 Pressure Loss
Pipe Outlet
Pressure2
Flo
w
Pressure
Compensated Pressure Reference
Pressure Reference at “no flow”
Compensation amount
𝐎𝐮𝐭 𝐅𝐫𝐞𝐪 − 𝐒𝐭𝐚𝐫𝐭 𝐅𝐫𝐞𝐪
𝐌𝐚𝐱𝐅𝐫𝐞𝐪 − 𝐒𝐭𝐚𝐫𝐭 𝐅𝐫𝐞𝐪
∗ 𝐔𝐧𝐢𝐭 𝐑𝐞𝐟𝐞𝐫𝐞𝐧𝐜𝐞 𝐌𝐚𝐱 ∗
𝐌𝐚𝐱 𝐂𝐨𝐦𝐩 𝐕𝐚𝐥𝐮𝐞 %
𝟏𝟎𝟎%
Flow Compensation Value
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Aux PID compensation sequence
PID Reference
AUX1
AUX2
AUX3
AUX4
AUX5
t
A
B
C
D
E
A B C D E
PID Final ReferencePID Reference without
Aux PID Compensation
PID Ref Set
AUX1
Ref Comp
AUX2
Ref Comp
AUX3
Ref Comp
AUX4
Ref Comp
AUX5
Ref Comp
t
PID Reference
Compensation
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Start Ramp & End Ramp sequence
ADV-25
Freq Limit Low
Frequency
Time
DRV-03
ACC Time
DRV-04
DEC Time
AP2-41
Start Ramp
ACC
AP2-42
END Ramp DEC
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Dec Valve Ramp sequence
ADV-25
Freq Limit Low
Frequency
Time
AP2-38
Dec Valve Freq
AP2-39 Dec Valve Time
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Damper control sequence
t1
Output
Frequency
Trip
Run Cmd
Damper Open
(input)
t1
t1 >= Damper DTt1< Damper DTt1 t1< Damper DT
time
t2
t2< Damper DT
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Lubrication control sequence
Run Cmd
Lubrication
(Relay Output)
Frequency
Lub Op Time
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Pre Heat sequence
Time
P1(Fx)
Pre Heat
Signal
AP2-48
Pre Heat Level
AP2-49
Pre Heat Duty
10s
AP2-49
Pre Heat Duty
10s
Frequency
10s 10s
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Level detection sequence
Level Detect Source
0 : Output Current
1 : DCLink Voltage
2 : Output Voltage
3 : kW
4 : HP
5 : V1
6 : V2
7 : I2
8 : PID Ref Value
9 : PID Fdb Value
10 : PID Output
11 : EPID1 Fdb Val
12 : EPID2 Fdb Val
LDT Freq
Feed Back
PID Fdb
Frequency
LDT Dly Time
Realy1
(LDT)
Realy2
(Trip)
LDT Restart DT
LDT Level+LDT Band Width
LDT Level
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
CODE Keypad Display Setting Range Factory Default Units Edit Mode
AP2-87 M1 AVG PWR 0.1 ~ 90 Inv Cap kW Δ
AP2-88 M2 AVG PWR 0.1 ~ 90 Inv Cap kW Δ
AP2-89 Cost per kWh 0.0 ~ 1000.0 0 O
AP2-90 Saved kWh -999.9~999.9 0 kWh X
AP2-91 Saved MWh -32000~32000 0 MWh X
AP2-92 Saved Cost1 -999.9~999.9 0 X
AP2-93 Saved Cost2 -32000~32000 0 X
AP2-94 CO2 Factor 0.0 ~ 5.0 0.5 O
AP2-95 Saved CO2 - 1 -999.9~999.9 0 Ton X
AP2-96 Saved CO2 - 2 -160~160 0 kTon X
AP2-97 Reset Energy
0 : No
1 : YES
0 Msg O
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Time
Ready
Signal
Frequency
Power
On
Power-On
Delay Time
Power On Run Delay sequence
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
 Process PID: 2 Reference Calculator, 8 Step Reference Selection, 1 Feedback Calculator.
 Process PID Mode: [PID out], [PID+Main Freq], [PID+EPID Out], [PID+EPID+Main].
Normal PID: [PID out]
Process PID: [PID+Main Freq]
Dual PID: [PID+EPID Out]
Process PID + Dual PID : [PID+EPID Out+Main Freq]
 External PID 1: +Process PID or Analog Output
 External PID 2: Analog Output Only
0 : CUST
1 : %
2 : PSI
3 : ˚F
4 : ˚C
5 : inWC
6 : inM
7 : Bar
8 : mBar
9 : Pa
10 : kPa
11 : Hz
12 : rpm
13 : V
14 : I
15 : kW
16 :HP
17 : mpm
18 : ft
19 : m/s
20 : m3/s (m3/S)
21 : m3/m (m3/min)
22 : m3/h (m3/h)
23 : l/s
24 : l/m
25 : l/h
26 : kg/s
27 : kg/m
28 : kg/h
29 : gl/s
30 : gl/m
31 : gl/h
32 : ft/s
33 : f3/s (ft3/s)
34 : f3/m (ft3/min)
35 : f3/h (ft3/h)
40 : pps
36 : lb/s
37 : lb/m
38 : lb/h
39 : ppm
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Power loss case
t t
Vdc
Vdc
Frequency
Power Loss Power Restore
CON-79 KEB Stop Level
CON-78 KEB Start Level
CON-79 KEB Stop Level
CON-78 KEB Start Level
Acceleration by “KEB Acc Time”
t
t
ONRelay
Output
ON
OFF
OFF
LV Trip Level LV Trip Level
Relay
Output
t t
Frequency
Power recover case
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
 Interlock, Auto Change (Main Exchange, Aux Exchange), Regular Bypass with feedback value)
 Only possible in PID operation (except regular bypass)
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
 Sleep boost, Sleep mode, Wake-up delay, Wake-up mode
PID Reference
Time
Time
AP1-10 Wake Up Dev
Sleep Boost
Sleep Mode
Wake-up Mode
AP1-05 Sleep Bst Set
Feedback
Out Freq
AP1-08 PID Sleep1 Freq
AP1-06 Sleep Bst Freq
dt < AP-07
AP-07
PID Sleep1 DT
dt dt
AP-09
PID Wake Up1 DT
Sleep & Wake-up sequence
Features [S/W]H100
Dedicated VFDs for HVAC/R
2] Applications
3] H100 Overview
4] Features [H/W]
5] Features [S/W]
7] LSIS Company
1] Benefits
6] H100 Bypass
Value Description
0 None
1 Fx
2 Rx
3 RST
4 External Trip
5 BX
6 JOG
7 Speed-L
8 Speed-M
9 Speed-H
11 XCEL-L
12 XCEL-M
13 XCEL-H
14 XCEL Stop
15 RUN Enable
16 3-Wire
17 2nd Source
18 Exchange
19 Up
20 Down
22 U/D Clear
23 Analog Hold
24 I-Term Clear
25 PID Openloop
26 PID Gain2
Value Description
27 PID Ref Change
28 2nd Motor
29 Interlock 1
30 Interlock 2
31 Interlock 3
32 Interlock 4
33 Interlock 5
34 Pre Excite
35 Timer In
37 dis Aux Ref
38 FWD JOG
39 REV JOG
40 Fire Mode
41 EPID1 Run
42 EPID1 ItermClr
43 Time Event En
44 Pre Heat
45 Damper Open
46 PumpClean
47 EPID2 Run
48 EPID2 ItermClr
49 Sleep Wake Chg
50 PID Step Ref L
51 PID Step Ref M
52 PID Step Ref H
Value Description
20 Ready
21 MMC
22 Timer Out
23 Trip
25 DB Warn%ED
26 On/Off Control
27 Fire Mode
28 Pipe Broken
29 Damper Err
30 Lubrication
31 Pump Clean
32 Level Detect
33 Damper Control
34 CAP.Warning
35 Fan Exchange
36 AUTO State
37 Hand State
38 TO
39 Except Date
40 KEB Operating
Value Description
0 None
1 FDT-1
2 FDT-2
3 FDT-3
4 FDT-4
5 Over Load
6 IOL
7 Under Load
8 Fan Warning
9 Stall
10 Over Voltage
11 Low Voltage
12 Over Heat
13 Lost Command
14 Run
15 Stop
16 Steady
17 Inverter Line
18 Comm Line
19 Speed Search
Multi-functional Digital Input Multi-functional Digital Output

More Related Content

PDF
Liebherr A 914 C Litronic EDC Hydraulic Excavator Service Repair Manual SN:35...
DOCX
550 ICA AS-550-900 Rev A
PDF
Project #3 - A Class Treatment Plant - AMIAD Micro-Strainers
PDF
MITSUBISHI ELECTRIC SPLIT-TYPE
PDF
Compressed Coalescing Filters for Industrial Use
PPTX
Operation of hydro power plants
PDF
Technical Data 2468 Pitot Primary Standard
PPTX
P and Id
Liebherr A 914 C Litronic EDC Hydraulic Excavator Service Repair Manual SN:35...
550 ICA AS-550-900 Rev A
Project #3 - A Class Treatment Plant - AMIAD Micro-Strainers
MITSUBISHI ELECTRIC SPLIT-TYPE
Compressed Coalescing Filters for Industrial Use
Operation of hydro power plants
Technical Data 2468 Pitot Primary Standard
P and Id

What's hot (12)

PPTX
PDF
ASCO Numatics Valve Redundant Control System, RCS, Pilot Valve System, Sil 3
PDF
Emergency Shutdown System - Worldwide Oilfield Machine
PDF
Integrated control valve, sensors, actuator, and controller
PPTX
Presentazione Navim VRCS Cruise 2015- Rev.1
DOC
Basheervs C&I Engineer
PDF
Seminar58 castro presentation_3
PDF
SFCXX1 - SFCXX2 Air Flow Testing Report
PDF
P&id+abbreviation
PDF
Гидромоторы серии PSP Berarma Srl
PDF
Microtrans differential pressure and airflow signal processor
PDF
Thermal dispersion switch for flow, level, interface, or temperature
ASCO Numatics Valve Redundant Control System, RCS, Pilot Valve System, Sil 3
Emergency Shutdown System - Worldwide Oilfield Machine
Integrated control valve, sensors, actuator, and controller
Presentazione Navim VRCS Cruise 2015- Rev.1
Basheervs C&I Engineer
Seminar58 castro presentation_3
SFCXX1 - SFCXX2 Air Flow Testing Report
P&id+abbreviation
Гидромоторы серии PSP Berarma Srl
Microtrans differential pressure and airflow signal processor
Thermal dispersion switch for flow, level, interface, or temperature
Ad

Similar to LSIS H100 Engineering Introduction (20)

PPTX
FRENIC-Eco Product Presentation__r1.pptx
PPT
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
PPT
Varaible Speed Drives for Motor Driven Fire Pumps
PPT
Amiri Guard Starter panels Presentation Rev-1 Dt16-11-2014
PDF
Automation Solution With Energy Optimisation By Technosoft Consultancy & Serv...
PDF
Quick guide aqua fc 200
PPT
H Max Presentation For Sales(Dr)
PDF
HFW-135 T5 EN
PDF
Vfd 130221061349-phpapp02
PDF
Mitsubishi inverter freqrol-f700 series
PDF
Mitsubishi inverter freqrol-f700 series dienhathe.vn
PDF
Mitsubishi inverter freqrol-f700 series
PDF
LHB coach TL AC systems of indian railway
PDF
Variable speed fire pump controllers
PDF
Advanced motion controls dpeaniu c100a400
PDF
Advanced motion controls dpeaniu c100a400
PDF
D1401 e 3.2
PDF
Advanced motion controls dpqnnie 100a400
FRENIC-Eco Product Presentation__r1.pptx
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
Varaible Speed Drives for Motor Driven Fire Pumps
Amiri Guard Starter panels Presentation Rev-1 Dt16-11-2014
Automation Solution With Energy Optimisation By Technosoft Consultancy & Serv...
Quick guide aqua fc 200
H Max Presentation For Sales(Dr)
HFW-135 T5 EN
Vfd 130221061349-phpapp02
Mitsubishi inverter freqrol-f700 series
Mitsubishi inverter freqrol-f700 series dienhathe.vn
Mitsubishi inverter freqrol-f700 series
LHB coach TL AC systems of indian railway
Variable speed fire pump controllers
Advanced motion controls dpeaniu c100a400
Advanced motion controls dpeaniu c100a400
D1401 e 3.2
Advanced motion controls dpqnnie 100a400
Ad

Recently uploaded (20)

PDF
August 2025 - Top 10 Read Articles in Network Security & Its Applications
PPTX
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
PDF
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
PPTX
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
PDF
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
PPTX
Management Information system : MIS-e-Business Systems.pptx
PDF
Abrasive, erosive and cavitation wear.pdf
PPTX
CyberSecurity Mobile and Wireless Devices
PDF
Applications of Equal_Area_Criterion.pdf
PDF
Computer organization and architecuture Digital Notes....pdf
PPTX
Sorting and Hashing in Data Structures with Algorithms, Techniques, Implement...
PPTX
A Brief Introduction to IoT- Smart Objects: The "Things" in IoT
PPTX
Module 8- Technological and Communication Skills.pptx
PDF
August -2025_Top10 Read_Articles_ijait.pdf
PPTX
Principal presentation for NAAC (1).pptx
PDF
Unit I -OPERATING SYSTEMS_SRM_KATTANKULATHUR.pptx.pdf
PDF
UEFA_Embodied_Carbon_Emissions_Football_Infrastructure.pdf
PPTX
Building constraction Conveyance of water.pptx
PPTX
tack Data Structure with Array and Linked List Implementation, Push and Pop O...
PDF
Soil Improvement Techniques Note - Rabbi
August 2025 - Top 10 Read Articles in Network Security & Its Applications
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
Management Information system : MIS-e-Business Systems.pptx
Abrasive, erosive and cavitation wear.pdf
CyberSecurity Mobile and Wireless Devices
Applications of Equal_Area_Criterion.pdf
Computer organization and architecuture Digital Notes....pdf
Sorting and Hashing in Data Structures with Algorithms, Techniques, Implement...
A Brief Introduction to IoT- Smart Objects: The "Things" in IoT
Module 8- Technological and Communication Skills.pptx
August -2025_Top10 Read_Articles_ijait.pdf
Principal presentation for NAAC (1).pptx
Unit I -OPERATING SYSTEMS_SRM_KATTANKULATHUR.pptx.pdf
UEFA_Embodied_Carbon_Emissions_Football_Infrastructure.pdf
Building constraction Conveyance of water.pptx
tack Data Structure with Array and Linked List Implementation, Push and Pop O...
Soil Improvement Techniques Note - Rabbi

LSIS H100 Engineering Introduction

  • 1. Dedicated VFDs for HVAC/R and Pumps
  • 2. H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass General specifications • Drive capacity - 230V, Three-phase, 1~25hp(5~69A, ND) - 480V, Three-phase, 1~125hp(2.5~169A, ND) • Overload capacity - 120% for 60sec. (up to 90kW) - 110% for 60sec. (above 110kW) • Input voltage range - 200~240V Three-phase (-15%/+10%) - 380~480V Three-phase (-15%/+10%) • Communication - Built-in BACnet(MS/TP, B-ASC), Metasys N2 LS Bus, Modbus-RTU - LonWorks as optional • Control meothod - V/f • Output frequency - 0~400Hz • Carrier frequency - Normal Duty: 1~15kHz • Protection degree - Standard: IP20, Optional: NEMA1 • Global Certificated - CE, UL, cUL, RoHS, *Plenum Rated (UL1995) - UL Pollution type 3 Conformal Coating on PCB 1 25 125 HP IP20 400V/3Φ IP20 200V/3Φ 800 Built In EMC Filter, DC Reactor as optional (IP20) 40
  • 3. H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass H100 Hardware specification • Flange mountable with kit - IP54 Heat sink out the back design (above 150HP) • Universal conduit box 1~15hp 20hp 25hp240V 480V 1~15hp 20~25hp 30~40hp 50hp 60~75hp 100~125hp • 11 frame size - 1 though 25HP (240V) - 1 though 800HP (480V) - UL single rating up to 125HP 150~200hp 250~300hp 350~400hp480V 500~650hp 800hp
  • 4. H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass H100 Hardware specification *‘MULTI’ key: One touch allows to access to user group that can be registered up to 64 parameters by user.  HAND Mode (Local Control Mode) or AUTO Mode (Remote Control Mode) can be selected.  Standard functions for HVAC/R - Hand key: Operation via keypad. - Hand key  up/down: changes speed. V/F only (PID is disabled) - Off key: Functions as Stop or Reset button. - Auto key: Operation as preset functions. HAND AUTO OFF Push HAND ① Push AUTO ②
  • 5. H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass H100 Hardware specification EMC Filter - Built-in C3 Capacitor Bank - Long Life Span FAN - Suction Type - Removable Heat Sink - Pin bonding type: Down size - Press Body Wiring Bracket - Removable Wire Guide *‘Even thought EMC filter is not built in the 75~90kW models, it meets the EMC Directive Category C3
  • 6. H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass H100 Hardware specification Switch Description LEFT RIGHT SW1 Termination Resistor ON OFF SW2 NPN / PNP NPN PNP SW3 Analog Input-1 Select V1 T1(PTC) SW4 Analog Input-2 Select I2 V2 SW5 Analog Output-1 Select Voltage Current Standard I/O No. of Pins 34 pins Relay output A1,B1,C1 A2, C2 A3, C3 A4, C4 A5, C5 24V output 24 Analog input voltage (+12V) VR Analog voltage input / PTC input V1 Analog voltage/Current input / PTC input I2 Analog voltage/Current output AO1 Analog voltage output AO2 RS485 signal / Ground S+,S- / SG I/O Ground(Except for comm.) CM Programmable TR output / Pulse train output(0~32kHz) Q1,EG Programmable digital input (PNP/NPN) P1~P7 Pulse train input (0~32kHz) TI Terminal pitch 5mm
  • 7. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass 0 Basic 1 Compressor 2 Supply Fan 3 Exhaust Fan 4 Cooling Tower 5 Circulating Pump 6 Vacuum Pump 7 Constant Torque 7 Selectable Macros Example of Compressor(MC1) Macro
  • 8. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Sunday Monday Tuesday Wednesday Thursday Friday Saturday 00:00 08:00 04:00 12:00 02:00 06:00 10:00 14:00 22:00 18:00 16:00 20:00 24:00 Pre-Heat Fx Speed-L Speed-H  4 time period modules (Weekly)  8 exception date modules (Day)  8 time event modules  30 functions available (Fx, Rx, Step Freq, PID, etc.)  Day Light Savings available (Start/End date setting)  3 types of date displays available (EU / USA / ASIA)
  • 9. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass * f 출력전압지령 출력 주파수 기저 주파수 60.00Hz 시작 주파수 (0.5Hz) 4729 132 DQ Transformation PWM Input Voltage Reference cba iii ,, compV DQ Transformation di qi Compensation Voltage Regulator ATB Filt Gain CON_21 Rated Slip Motor Capacitiy ATB Volt Gain CON_22 PWMAVR Voltage Reference Regulator LPF Motor Test condition Cmd Freq. Load Rate ACC Time Auto torque boost 1 (Existing) Auto torque boost 2 (New) 20hp-480V 100hp-480V 20hp-480V 100hp-480V Starting 3Hz 100% 0sec ○ ○ ○ ○ 10sec ○ ○ ○ ○ 120% 0sec ○ ○ ○ ○ 10sec ○ ○ ○ ○ adjust load 3Hz Variable - X (50%->100%) ○ ○ ○ 5Hz X (0%->120%) X (50%->100%) ○ ○ Starting 60Hz 100% 10sec ○ X ○ ○ 120% 10sec △(Unstable) X ○ ○ adjust load 60Hz Variable - ○ ○ ○ ○
  • 10. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Fire Mode Signal Direction command Fire Mode Freq Ignored Trip Retry Trip Fault FWD FWD Fire Mode Direction Fire Mode Signal Input On Off Output Frequency Fire mode sequence
  • 11. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Soft Fill sequence
  • 12. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Pump clean Sequence *’Load tune’ function should be conducted before activating ‘Pump clean’ function. Pump clean operationForeign debris stuck in impeller
  • 13. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Under load operation *’Load tune’ function should be conducted before activating ‘Pump clean’ function. Under load sequence
  • 14. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Soft Fill sequence Pre-PID Soft Fill Normal PID PID-04 PID Ref Value PID Reference Soft Fill Set AP-22 Pre-PID Delay AP-21 Pre-PID Freq AP-25 Soft Step Time AP-24 Fill Step Set t t PID-05 PID Fdb Value Frequency
  • 15. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Pipe broken operation PID Reference Feedback PID Reference*PRT-61(Pipe Broken Dev) PRT-62(Pipe Broken DT) Time Time PID Unit PID Output(MAX) or Max Freq Time PID Reference FeedBack Min(PID Limit, Max Freq) PID Reference*PRT-61(PipeBroken Dev) A PID Unit Frequency PRT-62 Pipe Broken DT B C
  • 16. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Flow compensation operation Pressure LengthSensor position Pressure Reference Setpoint Pressure1 Pressure Loss Pipe Outlet Pressure2 Flo w Pressure Compensated Pressure Reference Pressure Reference at “no flow” Compensation amount 𝐎𝐮𝐭 𝐅𝐫𝐞𝐪 − 𝐒𝐭𝐚𝐫𝐭 𝐅𝐫𝐞𝐪 𝐌𝐚𝐱𝐅𝐫𝐞𝐪 − 𝐒𝐭𝐚𝐫𝐭 𝐅𝐫𝐞𝐪 ∗ 𝐔𝐧𝐢𝐭 𝐑𝐞𝐟𝐞𝐫𝐞𝐧𝐜𝐞 𝐌𝐚𝐱 ∗ 𝐌𝐚𝐱 𝐂𝐨𝐦𝐩 𝐕𝐚𝐥𝐮𝐞 % 𝟏𝟎𝟎% Flow Compensation Value
  • 17. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Aux PID compensation sequence PID Reference AUX1 AUX2 AUX3 AUX4 AUX5 t A B C D E A B C D E PID Final ReferencePID Reference without Aux PID Compensation PID Ref Set AUX1 Ref Comp AUX2 Ref Comp AUX3 Ref Comp AUX4 Ref Comp AUX5 Ref Comp t PID Reference Compensation
  • 18. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Start Ramp & End Ramp sequence ADV-25 Freq Limit Low Frequency Time DRV-03 ACC Time DRV-04 DEC Time AP2-41 Start Ramp ACC AP2-42 END Ramp DEC
  • 19. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Dec Valve Ramp sequence ADV-25 Freq Limit Low Frequency Time AP2-38 Dec Valve Freq AP2-39 Dec Valve Time
  • 20. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Damper control sequence t1 Output Frequency Trip Run Cmd Damper Open (input) t1 t1 >= Damper DTt1< Damper DTt1 t1< Damper DT time t2 t2< Damper DT
  • 21. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Lubrication control sequence Run Cmd Lubrication (Relay Output) Frequency Lub Op Time
  • 22. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Pre Heat sequence Time P1(Fx) Pre Heat Signal AP2-48 Pre Heat Level AP2-49 Pre Heat Duty 10s AP2-49 Pre Heat Duty 10s Frequency 10s 10s
  • 23. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Level detection sequence Level Detect Source 0 : Output Current 1 : DCLink Voltage 2 : Output Voltage 3 : kW 4 : HP 5 : V1 6 : V2 7 : I2 8 : PID Ref Value 9 : PID Fdb Value 10 : PID Output 11 : EPID1 Fdb Val 12 : EPID2 Fdb Val LDT Freq Feed Back PID Fdb Frequency LDT Dly Time Realy1 (LDT) Realy2 (Trip) LDT Restart DT LDT Level+LDT Band Width LDT Level
  • 24. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass CODE Keypad Display Setting Range Factory Default Units Edit Mode AP2-87 M1 AVG PWR 0.1 ~ 90 Inv Cap kW Δ AP2-88 M2 AVG PWR 0.1 ~ 90 Inv Cap kW Δ AP2-89 Cost per kWh 0.0 ~ 1000.0 0 O AP2-90 Saved kWh -999.9~999.9 0 kWh X AP2-91 Saved MWh -32000~32000 0 MWh X AP2-92 Saved Cost1 -999.9~999.9 0 X AP2-93 Saved Cost2 -32000~32000 0 X AP2-94 CO2 Factor 0.0 ~ 5.0 0.5 O AP2-95 Saved CO2 - 1 -999.9~999.9 0 Ton X AP2-96 Saved CO2 - 2 -160~160 0 kTon X AP2-97 Reset Energy 0 : No 1 : YES 0 Msg O
  • 25. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Time Ready Signal Frequency Power On Power-On Delay Time Power On Run Delay sequence
  • 26. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass  Process PID: 2 Reference Calculator, 8 Step Reference Selection, 1 Feedback Calculator.  Process PID Mode: [PID out], [PID+Main Freq], [PID+EPID Out], [PID+EPID+Main]. Normal PID: [PID out] Process PID: [PID+Main Freq] Dual PID: [PID+EPID Out] Process PID + Dual PID : [PID+EPID Out+Main Freq]  External PID 1: +Process PID or Analog Output  External PID 2: Analog Output Only 0 : CUST 1 : % 2 : PSI 3 : ˚F 4 : ˚C 5 : inWC 6 : inM 7 : Bar 8 : mBar 9 : Pa 10 : kPa 11 : Hz 12 : rpm 13 : V 14 : I 15 : kW 16 :HP 17 : mpm 18 : ft 19 : m/s 20 : m3/s (m3/S) 21 : m3/m (m3/min) 22 : m3/h (m3/h) 23 : l/s 24 : l/m 25 : l/h 26 : kg/s 27 : kg/m 28 : kg/h 29 : gl/s 30 : gl/m 31 : gl/h 32 : ft/s 33 : f3/s (ft3/s) 34 : f3/m (ft3/min) 35 : f3/h (ft3/h) 40 : pps 36 : lb/s 37 : lb/m 38 : lb/h 39 : ppm
  • 27. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Power loss case t t Vdc Vdc Frequency Power Loss Power Restore CON-79 KEB Stop Level CON-78 KEB Start Level CON-79 KEB Stop Level CON-78 KEB Start Level Acceleration by “KEB Acc Time” t t ONRelay Output ON OFF OFF LV Trip Level LV Trip Level Relay Output t t Frequency Power recover case
  • 28. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass  Interlock, Auto Change (Main Exchange, Aux Exchange), Regular Bypass with feedback value)  Only possible in PID operation (except regular bypass)
  • 29. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass  Sleep boost, Sleep mode, Wake-up delay, Wake-up mode PID Reference Time Time AP1-10 Wake Up Dev Sleep Boost Sleep Mode Wake-up Mode AP1-05 Sleep Bst Set Feedback Out Freq AP1-08 PID Sleep1 Freq AP1-06 Sleep Bst Freq dt < AP-07 AP-07 PID Sleep1 DT dt dt AP-09 PID Wake Up1 DT Sleep & Wake-up sequence
  • 30. Features [S/W]H100 Dedicated VFDs for HVAC/R 2] Applications 3] H100 Overview 4] Features [H/W] 5] Features [S/W] 7] LSIS Company 1] Benefits 6] H100 Bypass Value Description 0 None 1 Fx 2 Rx 3 RST 4 External Trip 5 BX 6 JOG 7 Speed-L 8 Speed-M 9 Speed-H 11 XCEL-L 12 XCEL-M 13 XCEL-H 14 XCEL Stop 15 RUN Enable 16 3-Wire 17 2nd Source 18 Exchange 19 Up 20 Down 22 U/D Clear 23 Analog Hold 24 I-Term Clear 25 PID Openloop 26 PID Gain2 Value Description 27 PID Ref Change 28 2nd Motor 29 Interlock 1 30 Interlock 2 31 Interlock 3 32 Interlock 4 33 Interlock 5 34 Pre Excite 35 Timer In 37 dis Aux Ref 38 FWD JOG 39 REV JOG 40 Fire Mode 41 EPID1 Run 42 EPID1 ItermClr 43 Time Event En 44 Pre Heat 45 Damper Open 46 PumpClean 47 EPID2 Run 48 EPID2 ItermClr 49 Sleep Wake Chg 50 PID Step Ref L 51 PID Step Ref M 52 PID Step Ref H Value Description 20 Ready 21 MMC 22 Timer Out 23 Trip 25 DB Warn%ED 26 On/Off Control 27 Fire Mode 28 Pipe Broken 29 Damper Err 30 Lubrication 31 Pump Clean 32 Level Detect 33 Damper Control 34 CAP.Warning 35 Fan Exchange 36 AUTO State 37 Hand State 38 TO 39 Except Date 40 KEB Operating Value Description 0 None 1 FDT-1 2 FDT-2 3 FDT-3 4 FDT-4 5 Over Load 6 IOL 7 Under Load 8 Fan Warning 9 Stall 10 Over Voltage 11 Low Voltage 12 Over Heat 13 Lost Command 14 Run 15 Stop 16 Steady 17 Inverter Line 18 Comm Line 19 Speed Search Multi-functional Digital Input Multi-functional Digital Output

Editor's Notes

  • #2: Good morning, My name is Cho Kyu Seong and I’m working for LSIS, Korea in charge of Low and Medium voltage drives for Indonesian market. First of all, thank you very much to give a chance to introduce our company, LSIS. My presentation should last about 5 minutes. After my presentation, you will watch our company profile video to know better about our company. So, let’s start.