Performance Based Analysis of Concealed Beam in Reinforced Concrete
Structure
Chetan Talawar 1, Hemant Sonawadekar 2
1 Post-Graduate Student, Dept. of Civil Engineering, KLE Dr MSSCET, Belagavi-590008, India
2 Assistant Professor, Dept. of Civil Engineering, KLE Dr MSSCET, Belagavi-590008, India
---------------------------------------------------------------------***---------------------------------------------------------------------
Abstract- Beams are the structural elements and transfers
the load from slabs to columns. If the slab panels are very
large, the intermediate beams are used to convert them into
small panels. The dimensions of the beam depend on the load
from the slab. The HIDDEN BEAMS are widely used in
construction of multi-storey buildings because of the
advantages like, they provide more clearance between the
floor, they also save on formwork, labor and constructioncost.
In the present study the seismic behavior of the reinforced
concrete structure with and without concealed beam is
described. The various models of G+4 storey and G+6 storey
are modeled and analyzed in ETABS 09. The response
spectrum analysis is carried out as per IS 1893:2002 by
considering the seismic zone as ZONE II and medium soil.
Further the pushover analysis is carried out as per FEMA 356
and ATC-40. The parameters like Base Shear, Axial loads,
Natural period, Displacement are considered and comparison
is done between the models with and withoutconcealedbeam.
Key Words: ETABS 09, Concealed Beam, Response
Spectrum method, Pushover Analysis,PerformancePoint.
1. INTRODUCTION
The loads acting on the multi-story building are
Gravity loads (Dead load of the structure, Live load, Snow
load) and Lateral loads (earthquake and wind loads). In
earlier days only gravity loads are used to design the multi-
story buildings, but other than the gravity loads the
Horizontal loads are also act on the buildings. Now a day’s
design of the multi-story building is done by consideringthe
both Gravity loads and Lateral loads for the safety purpose.
The depth of the concealedbeamwill be equal tothe
thickness of the slab and it is hidden in the slab hence
Concealed beam is known as HIDDEN BEAM. The top levels
of the both slab and the hidden beam will be same. Concept
of concealed beam originated from flat slab. Thebeamrebar
is designed for the same depth of the slab. The concealed
beams are used to provide maximum clearance betweenthe
floors because of this hidden beams are widely used in
commercial buildings. When the concealed beams are
provided the beam-column joint is similar to the flat slab of
slab-column joint. Both buildings have the same appearance
but acts differently when considered resistance to gravity,
earthquake and wind loads.
Fig 1- Concealed Beam
2. MODELING AND BUILDING DATA
Fig 2- Building Plan
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056
Volume: 04 Issue: 06 | June -2017 www.irjet.net p-ISSN: 2395-0072
© 2017, IRJET | Impact Factor value: 5.181 | ISO 9001:2008 Certified Journal | Page 2194
Fig 3- Building elevation
2.1 Building Data
Plan 9mX9m
Slab panel 3mX3m
Floor Height 3m
Column 450mmX450mm
Normal Beam 300mmX300mm
Concealed Beam 250mmX300mm
Slab thickness 250 mm
Grade of Concrete M20
Grade of Steel Fe 415
Wall Load on Perimeter Beam 13.8 kN/m
Wall Load on Intermediate
Beams
9 kN/m
Parapet wall load 3kN/m
Floor Finish(FF) (Assumed) 1kN/m2
Floor Live Load 3kN/m2
Roof Live Load 1.5kN/m2
Type of soil Medium Soil
Type of Structure SMRF
Damping ratio 5% (RC Structure)
Importance Factor (I) 1 (Table 6)
Response Reduction Factor 5 (Table 7)
3 : Analysis of the Building
Response spectrummethodisusedintheanalysisof
multi-storey building with and without concealed beam. In
response spectrum method, dynamic characteristics are
considered. Base shear is calculated by multiplying total
seismic weight with acceleration spectrum coefficient. Base
shear is calculated according to IS 1893 (Part 1) -2002.
RS X – Response Spectrum in X direction,
RS Y – Response Spectrum in Y direction.
3.1 Results and Discussion
3.1.1 Base Shear
No of
Storeys
Type of model
Base Shear
(kN)
G+4
without concealed beam 311.38
with concealed beam 295.65
G+6
without concealed beam 314.83
with concealed beam 300.89
Fig 4-Base shear Comparison
The base shear of the model with normal beam is
more than the model with concealed beam.
3.1.2 Natural Period
No of
Storeys
Type of model
Natural
Period
(sec)
G+4
without concealed beam 0.648
with concealed beam 0.673
G+6
without concealed beam 0.89
with concealed beam 0.918
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056
Volume: 04 Issue: 06 | June -2017 www.irjet.net p-ISSN: 2395-0072
© 2017, IRJET | Impact Factor value: 5.181 | ISO 9001:2008 Certified Journal | Page 2195
Fig 5- Natural period Comparison
The Natural period of the model with concealed
beam is more than the model with the normal beam because
the stiffness of the concealed beam model is less than the
normal beam model.
3.1.3 Displacement
No of
Storeys
Type of model displacement
(mm)
G+4
without concealed beam 6.1
with concealed beam 6.2
G+6
without concealed beam 8.6
with concealed beam 8.8
Fig 6- Displacement Comparison
The depth of the concealed beam is less than that of
the normal beam because of this reason the weight of the
structure reduces. The stiffness of the whole structure
reduces in structure with concealed beam. Hence the
displacement of the top storey in models with concealed
beam is more than the models with normal beams.
3.2 Pushover Analysis
As the name pushover indicates, push the structure
with certain magnitude until itreachesmaximumcapacityto
deform. In this process the load on the structure is gradually
increased with certain pre-defined pattern. As the load on
the structure increases the yielding of the structure begins
and finally gets damaged and failure modes of the structure
becomes apparent. The effect of load reversal on the
structure during earthquake is analyzed by applying load
monotonically and deformation of the structureisestimated
with suitable damping. The aim ofthepushoveranalysisisto
understand the deformation andcrackingofthestructure.In
pushover analysis the plastic hinges are assigned to the
beams and columns at either ends. The hinges should be
studied carefully during the collapse mechanism and the
performance point may be observed. The hinges are
assigned to the beams and columns of the structure as per
the guidelines given in ASCE 41. For the beams the flexural
hinge (M3) and shear hinge (v2) are assigned at both the
ends at relative distance. Similarly, for the columns the
combination of axial and flexural hinges (P-M2-M3) are
assigned at both the ends with relative distance. At the
distance of 0.05 and 0.95, the hinges are assigned to the
beams and columns.
3.2.1 Performance point
The intersection of the capacity curve and the
demand curve is called as Performance point. The plotofthe
base shear of the structure to the roof displacement is called
as Capacity curve. and Capacity curve is also known as
Pushover curve.
Fig 7-Performane point fot G+4 model with concealed
beam
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056
Volume: 04 Issue: 06 | June -2017 www.irjet.net p-ISSN: 2395-0072
© 2017, IRJET | Impact Factor value: 5.181 | ISO 9001:2008 Certified Journal | Page 2196
Fig-8 Hinge formation in G+4 model with concealed beam
The first hinge formed in beams and as the load
increases the hinges started forming in columns. Thisshows
weak beam and strong column concept. By observing the
hinges, most of the hinges are in Life safety zone. In model
G+4 storey without concealed beam, the formation ofhinges
taken place in earlier steps than the model with concealed
beam. In both the models bottom storey columns are having
more number of life safety hinges hence retrofitting of
columns has to be done.
Fig 9-Performane point fot G+6 model with concealed
beam
Fig-10 Hinge formation in G+4 model with concealed
beam
The base shear of the model without concealed
beam is more than the model with concealed beam. The roof
displacement, Spectral displacement,effectivetimeperiodof
the model with concealed beam is more and Spectral
acceleration is more for the model without concealed beam.
In model G+6 with concealed beam, the formation of hinges
took place in later steps than the model without concealed
beam. The retrofitting is required for the bottom storey
columns of the both the models since life safety hinges are
formed more.
5. CONCLUSIONS
Following conclusions are drawn from the present study
 The base shear of the concealed beam structure is less as
compare to normal beam structure. Since lesserthemass
lesser will be the seismic force. Hence it is concludedthat
concealed beam structure is better than normal beam
structure during earthquake.
 The influence of concealed beam in a structure increases
the natural period as compared to normal beam
structure.
 In multi-storey structures, if long spanslabsareprovided
the deflection will be more. The concealed beams are
provided in order to decrease the deflectionandincrease
the stiffness of the slab.
 In multi-storey building provision of concealedbeamcan
act as a flat slab and provides large clearance in between
the floors.
 As the damping value increases, the inelastic
displacement of the structure decreases due overall
increase in the structural stiffness. As the damping
increases, the capacity of the structure increases.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056
Volume: 04 Issue: 06 | June -2017 www.irjet.net p-ISSN: 2395-0072
© 2017, IRJET | Impact Factor value: 5.181 | ISO 9001:2008 Certified Journal | Page 2197
 The more number of life safety (LS) hinges are formed in
model with concealed beams as compared to model with
normal beams. hence performance of the model with
concealed beams is better than model with normal
beams.
ACKNOWLEDGEMENT
The authors would like to thank Shri S. C. Metagud
Chairman Governing council, K.L.E.M.S.S.C.ET and Dr.
Basavaraj G. Katageri principal of K.L.E.M.S.S.C.ET, Belagavi
for their kind support and providing good infrastructure.
The authors are grateful to Prof. (Smt) Bharati Chiniwalar,
Head of Civil Department, for encouragement and support.
REFERENCES
 Akash.C. Arakere, Tejas D. Doshi, “Comparison of Multi-
Storey Building with Normal Beams and Concealed
Beams”, International Research Journal of Engineering
and Technology (IRJET) e-ISSN: 2395 -0056, | June-2015
 Samir H. Riyaj Awad, “Performance based analysis of
Hidden Beams in Reinforced Concrete Structure”, An-
Najah National University, Nablus, Palestine.
 Samir H. Helou, Munther M. Diab, “Slabs with Hidden
Beams”, An-Najah National University, Nablus, Palestine.
 Navyashree K, Sahana T.S, “Use of flat slabs in multi-
storey commercial buildingsituatedinhighseismiczone”,
International Journal of Research in Engineering
and Technology, eISSN: 2319-1163, August, 2014.
 M. Altus ERBERIK, Amr S. ELNASHAI, “Vulnerability
analysis of flat slab structures”, 13th World Conference
on Earthquake Engineering, August, 2014.
 Sumit Pahwa, Vivek Tiwari and Madhavi Prajapati,
“Comparative Study of Flat
Slab with Old Traditional Two-way slab”, International
Journal of Latest Trends
 Federal Emergency ManagementAgency,FEMA-356:Pre
standard and Commentary for the Seismic Rehabilitation
of Buildings, 2000: Washington DC.
 Federal Emergency Management Agency, FEMA-440:
Improvement of Non-linear Static Seismic Analysis
Procedures, June-2005: Washington DC.
 ATC -40, ‘Seismic Evaluation and Retrofit of Concrete
Buildings’, Vol. 1&2, Applied Technology Council,
California, 1996
BIOGRAPHIES
Chetan Talawar
Post-Graduate Student,
Department of Civil Engineering,
K.L.E. Dr.M.S.Sheshigiri College of
Engineering and Technology,
Belagavi, India- 590008
Prof. Hemant Sonawadekar
M.Tech (Structural Engineering),
B.E (Civil),
Assistant Professor,
Department of Civil Engineering,
K.L.E. Dr.M.S.Sheshigiri College of
Engineering and Technology,
Belagavi, India- 50008

More Related Content

PDF
IRJET- Effective Location of Shear Wall, its Significance and Displacement An...
PDF
IRJET-Conversion of MDOF System into SDOF System of RC Waffle Slab Structure ...
PDF
IRJET- Comparison of Seismic Response of RCC Framed Structure with FPB & HDRB...
PDF
Deflection control in rcc beams by using mild steel strips (an experimental i...
PDF
IRJET- Multi Cornered Thin Wall Sections for Crashworthiness and Occupant Pro...
PDF
Dynamic Analysis of Soft Storey Frame with Isolators
PDF
Structural Analysis and Design of Castellated Beam in Fixed Action
PDF
IRJET- Effect of Relative Stiffness of Beam-Column Joint on Internal Forces i...
IRJET- Effective Location of Shear Wall, its Significance and Displacement An...
IRJET-Conversion of MDOF System into SDOF System of RC Waffle Slab Structure ...
IRJET- Comparison of Seismic Response of RCC Framed Structure with FPB & HDRB...
Deflection control in rcc beams by using mild steel strips (an experimental i...
IRJET- Multi Cornered Thin Wall Sections for Crashworthiness and Occupant Pro...
Dynamic Analysis of Soft Storey Frame with Isolators
Structural Analysis and Design of Castellated Beam in Fixed Action
IRJET- Effect of Relative Stiffness of Beam-Column Joint on Internal Forces i...

What's hot (20)

PDF
Analysis of rc frame with and without masonry infill wall with different stif...
PDF
effect of non seismic walls
PDF
IRJET-Effective Location Of Shear Walls and Bracings for Multistoried Building
PDF
Study on Concentric Steel Bracing at Soft Storey During Earthquake
PDF
The Study on Behaviour of Outriggers for Tall Buildings Subjected to Lateral ...
PDF
Economical placement of shear walls in a moment resisting frame for earthquak...
PDF
Comparison of performance of lateral load resisting systems in multi storey f...
PDF
Numerical modeling on behaviour of reinforced concrete exterior beam column j...
PDF
Evaluation of Seismic Behaviour of RCC Building using Coupled Shear wall
PDF
seismic response of multi storey building equipped with steel bracing
PDF
Coupling beams design كمرات وجوائز ربط بجدران القص
PDF
Research Inventy : International Journal of Engineering and Science
PDF
Street Light Automatic Intensity Controller
PDF
Modern strengthening strategies for steel moment resisting frames
PDF
IRJET - Effect of Seismic Pounding between Adjacent Irregular Buildings a...
PDF
Structural Design
PDF
Study of Steel Moment Resisting Frame with Reduced Beam Section
PDF
Seismic rehabilitation of beam column joint using gfrp sheets-2002
PDF
A Study of Reduced Beam Section Profiles using Finite Element Analysis
PDF
Effect of User Defined Plastic Hinges on Nonlinear Modelling of Reinforced Co...
Analysis of rc frame with and without masonry infill wall with different stif...
effect of non seismic walls
IRJET-Effective Location Of Shear Walls and Bracings for Multistoried Building
Study on Concentric Steel Bracing at Soft Storey During Earthquake
The Study on Behaviour of Outriggers for Tall Buildings Subjected to Lateral ...
Economical placement of shear walls in a moment resisting frame for earthquak...
Comparison of performance of lateral load resisting systems in multi storey f...
Numerical modeling on behaviour of reinforced concrete exterior beam column j...
Evaluation of Seismic Behaviour of RCC Building using Coupled Shear wall
seismic response of multi storey building equipped with steel bracing
Coupling beams design كمرات وجوائز ربط بجدران القص
Research Inventy : International Journal of Engineering and Science
Street Light Automatic Intensity Controller
Modern strengthening strategies for steel moment resisting frames
IRJET - Effect of Seismic Pounding between Adjacent Irregular Buildings a...
Structural Design
Study of Steel Moment Resisting Frame with Reduced Beam Section
Seismic rehabilitation of beam column joint using gfrp sheets-2002
A Study of Reduced Beam Section Profiles using Finite Element Analysis
Effect of User Defined Plastic Hinges on Nonlinear Modelling of Reinforced Co...
Ad

Similar to Performance Based Analysis of Concealed Beam in Reinforced Concrete Structure (20)

PDF
“Analysis of a Multistorey Building with Grid slab in Different Seismic Zones...
PDF
IRJET- Seismic Behaviour of Steel Structures with Bracings Having Seismic Irr...
PDF
Effect of Positioning and Configuration of Shear Walls on Seismic Performance...
PDF
Effectiveness of Shear Wall-Frame Structure Subjected to Wind Loading in Mult...
PDF
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...
PDF
IRJET- A Review on Response Spectrum Analysis over Flat Slab-Shear Wall Inter...
PDF
IRJET- A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...
PDF
IRJET-Performance Improvement of Split Air Conditioner using Evaporative Cool...
PDF
IRJET- Comparative Study of Framed Structure with and without Shear Wall ...
PDF
Optimization of Seismic Response by Steel Framed Structures on Sloping Ground
PDF
IRJET- A Technical Approach to Flat Slab Multistorey Building under Wind Spee...
PDF
Effect of Backstay on Tall Structures with Podium
PDF
IRJET- Seismic Response of Flat Slab Buildings with Shear Wall
PDF
IRJET- Comparative Study of Different Bracing Systems in RCC Buildings using ...
PDF
Seismic Analysis of Multistorey Building with Different Slab Types on Plain a...
PDF
IRJET- Significance of Shear Wall in Multistory Building with Seismic Ana...
PDF
IRJET-Analysis of G+25 RCC Bare Framed Structure with Shear Wall Under the Ef...
PDF
IRJET- Parametric Study on Multistoried Diagrid Structure
PDF
Analyzing Utility of Component Elements of Outrigger System
PDF
STUDY OF PUSHOVER ANALYSIS OF G+10 RCC BUILDING WITH SHEAR WALL
“Analysis of a Multistorey Building with Grid slab in Different Seismic Zones...
IRJET- Seismic Behaviour of Steel Structures with Bracings Having Seismic Irr...
Effect of Positioning and Configuration of Shear Walls on Seismic Performance...
Effectiveness of Shear Wall-Frame Structure Subjected to Wind Loading in Mult...
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...
IRJET- A Review on Response Spectrum Analysis over Flat Slab-Shear Wall Inter...
IRJET- A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...
IRJET-Performance Improvement of Split Air Conditioner using Evaporative Cool...
IRJET- Comparative Study of Framed Structure with and without Shear Wall ...
Optimization of Seismic Response by Steel Framed Structures on Sloping Ground
IRJET- A Technical Approach to Flat Slab Multistorey Building under Wind Spee...
Effect of Backstay on Tall Structures with Podium
IRJET- Seismic Response of Flat Slab Buildings with Shear Wall
IRJET- Comparative Study of Different Bracing Systems in RCC Buildings using ...
Seismic Analysis of Multistorey Building with Different Slab Types on Plain a...
IRJET- Significance of Shear Wall in Multistory Building with Seismic Ana...
IRJET-Analysis of G+25 RCC Bare Framed Structure with Shear Wall Under the Ef...
IRJET- Parametric Study on Multistoried Diagrid Structure
Analyzing Utility of Component Elements of Outrigger System
STUDY OF PUSHOVER ANALYSIS OF G+10 RCC BUILDING WITH SHEAR WALL
Ad

More from IRJET Journal (20)

PDF
Enhanced heart disease prediction using SKNDGR ensemble Machine Learning Model
PDF
Utilizing Biomedical Waste for Sustainable Brick Manufacturing: A Novel Appro...
PDF
Kiona – A Smart Society Automation Project
PDF
DESIGN AND DEVELOPMENT OF BATTERY THERMAL MANAGEMENT SYSTEM USING PHASE CHANG...
PDF
Invest in Innovation: Empowering Ideas through Blockchain Based Crowdfunding
PDF
SPACE WATCH YOUR REAL-TIME SPACE INFORMATION HUB
PDF
A Review on Influence of Fluid Viscous Damper on The Behaviour of Multi-store...
PDF
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...
PDF
Explainable AI(XAI) using LIME and Disease Detection in Mango Leaf by Transfe...
PDF
BRAIN TUMOUR DETECTION AND CLASSIFICATION
PDF
The Project Manager as an ambassador of the contract. The case of NEC4 ECC co...
PDF
"Enhanced Heat Transfer Performance in Shell and Tube Heat Exchangers: A CFD ...
PDF
Advancements in CFD Analysis of Shell and Tube Heat Exchangers with Nanofluid...
PDF
Breast Cancer Detection using Computer Vision
PDF
Auto-Charging E-Vehicle with its battery Management.
PDF
Analysis of high energy charge particle in the Heliosphere
PDF
A Novel System for Recommending Agricultural Crops Using Machine Learning App...
PDF
Auto-Charging E-Vehicle with its battery Management.
PDF
Analysis of high energy charge particle in the Heliosphere
PDF
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...
Enhanced heart disease prediction using SKNDGR ensemble Machine Learning Model
Utilizing Biomedical Waste for Sustainable Brick Manufacturing: A Novel Appro...
Kiona – A Smart Society Automation Project
DESIGN AND DEVELOPMENT OF BATTERY THERMAL MANAGEMENT SYSTEM USING PHASE CHANG...
Invest in Innovation: Empowering Ideas through Blockchain Based Crowdfunding
SPACE WATCH YOUR REAL-TIME SPACE INFORMATION HUB
A Review on Influence of Fluid Viscous Damper on The Behaviour of Multi-store...
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...
Explainable AI(XAI) using LIME and Disease Detection in Mango Leaf by Transfe...
BRAIN TUMOUR DETECTION AND CLASSIFICATION
The Project Manager as an ambassador of the contract. The case of NEC4 ECC co...
"Enhanced Heat Transfer Performance in Shell and Tube Heat Exchangers: A CFD ...
Advancements in CFD Analysis of Shell and Tube Heat Exchangers with Nanofluid...
Breast Cancer Detection using Computer Vision
Auto-Charging E-Vehicle with its battery Management.
Analysis of high energy charge particle in the Heliosphere
A Novel System for Recommending Agricultural Crops Using Machine Learning App...
Auto-Charging E-Vehicle with its battery Management.
Analysis of high energy charge particle in the Heliosphere
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...

Recently uploaded (20)

PDF
Soil Improvement Techniques Note - Rabbi
PDF
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
PPTX
Module 8- Technological and Communication Skills.pptx
PPTX
Feature types and data preprocessing steps
PPTX
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
PPT
Total quality management ppt for engineering students
PDF
distributed database system" (DDBS) is often used to refer to both the distri...
PPTX
Information Storage and Retrieval Techniques Unit III
PPTX
Fundamentals of safety and accident prevention -final (1).pptx
PDF
August 2025 - Top 10 Read Articles in Network Security & Its Applications
PDF
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
PPTX
Fundamentals of Mechanical Engineering.pptx
PPTX
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
PDF
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
PPTX
Management Information system : MIS-e-Business Systems.pptx
PDF
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
PPTX
Sorting and Hashing in Data Structures with Algorithms, Techniques, Implement...
PDF
Visual Aids for Exploratory Data Analysis.pdf
PPT
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
PPTX
Safety Seminar civil to be ensured for safe working.
Soil Improvement Techniques Note - Rabbi
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
Module 8- Technological and Communication Skills.pptx
Feature types and data preprocessing steps
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
Total quality management ppt for engineering students
distributed database system" (DDBS) is often used to refer to both the distri...
Information Storage and Retrieval Techniques Unit III
Fundamentals of safety and accident prevention -final (1).pptx
August 2025 - Top 10 Read Articles in Network Security & Its Applications
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
Fundamentals of Mechanical Engineering.pptx
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
Management Information system : MIS-e-Business Systems.pptx
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
Sorting and Hashing in Data Structures with Algorithms, Techniques, Implement...
Visual Aids for Exploratory Data Analysis.pdf
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
Safety Seminar civil to be ensured for safe working.

Performance Based Analysis of Concealed Beam in Reinforced Concrete Structure

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056 Volume: 04 Issue: 06 | June -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 5.181 | ISO 9001:2008 Certified Journal | Page 2193 Performance Based Analysis of Concealed Beam in Reinforced Concrete Structure Chetan Talawar 1, Hemant Sonawadekar 2 1 Post-Graduate Student, Dept. of Civil Engineering, KLE Dr MSSCET, Belagavi-590008, India 2 Assistant Professor, Dept. of Civil Engineering, KLE Dr MSSCET, Belagavi-590008, India ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract- Beams are the structural elements and transfers the load from slabs to columns. If the slab panels are very large, the intermediate beams are used to convert them into small panels. The dimensions of the beam depend on the load from the slab. The HIDDEN BEAMS are widely used in construction of multi-storey buildings because of the advantages like, they provide more clearance between the floor, they also save on formwork, labor and constructioncost. In the present study the seismic behavior of the reinforced concrete structure with and without concealed beam is described. The various models of G+4 storey and G+6 storey are modeled and analyzed in ETABS 09. The response spectrum analysis is carried out as per IS 1893:2002 by considering the seismic zone as ZONE II and medium soil. Further the pushover analysis is carried out as per FEMA 356 and ATC-40. The parameters like Base Shear, Axial loads, Natural period, Displacement are considered and comparison is done between the models with and withoutconcealedbeam. Key Words: ETABS 09, Concealed Beam, Response Spectrum method, Pushover Analysis,PerformancePoint. 1. INTRODUCTION The loads acting on the multi-story building are Gravity loads (Dead load of the structure, Live load, Snow load) and Lateral loads (earthquake and wind loads). In earlier days only gravity loads are used to design the multi- story buildings, but other than the gravity loads the Horizontal loads are also act on the buildings. Now a day’s design of the multi-story building is done by consideringthe both Gravity loads and Lateral loads for the safety purpose. The depth of the concealedbeamwill be equal tothe thickness of the slab and it is hidden in the slab hence Concealed beam is known as HIDDEN BEAM. The top levels of the both slab and the hidden beam will be same. Concept of concealed beam originated from flat slab. Thebeamrebar is designed for the same depth of the slab. The concealed beams are used to provide maximum clearance betweenthe floors because of this hidden beams are widely used in commercial buildings. When the concealed beams are provided the beam-column joint is similar to the flat slab of slab-column joint. Both buildings have the same appearance but acts differently when considered resistance to gravity, earthquake and wind loads. Fig 1- Concealed Beam 2. MODELING AND BUILDING DATA Fig 2- Building Plan
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056 Volume: 04 Issue: 06 | June -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 5.181 | ISO 9001:2008 Certified Journal | Page 2194 Fig 3- Building elevation 2.1 Building Data Plan 9mX9m Slab panel 3mX3m Floor Height 3m Column 450mmX450mm Normal Beam 300mmX300mm Concealed Beam 250mmX300mm Slab thickness 250 mm Grade of Concrete M20 Grade of Steel Fe 415 Wall Load on Perimeter Beam 13.8 kN/m Wall Load on Intermediate Beams 9 kN/m Parapet wall load 3kN/m Floor Finish(FF) (Assumed) 1kN/m2 Floor Live Load 3kN/m2 Roof Live Load 1.5kN/m2 Type of soil Medium Soil Type of Structure SMRF Damping ratio 5% (RC Structure) Importance Factor (I) 1 (Table 6) Response Reduction Factor 5 (Table 7) 3 : Analysis of the Building Response spectrummethodisusedintheanalysisof multi-storey building with and without concealed beam. In response spectrum method, dynamic characteristics are considered. Base shear is calculated by multiplying total seismic weight with acceleration spectrum coefficient. Base shear is calculated according to IS 1893 (Part 1) -2002. RS X – Response Spectrum in X direction, RS Y – Response Spectrum in Y direction. 3.1 Results and Discussion 3.1.1 Base Shear No of Storeys Type of model Base Shear (kN) G+4 without concealed beam 311.38 with concealed beam 295.65 G+6 without concealed beam 314.83 with concealed beam 300.89 Fig 4-Base shear Comparison The base shear of the model with normal beam is more than the model with concealed beam. 3.1.2 Natural Period No of Storeys Type of model Natural Period (sec) G+4 without concealed beam 0.648 with concealed beam 0.673 G+6 without concealed beam 0.89 with concealed beam 0.918
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056 Volume: 04 Issue: 06 | June -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 5.181 | ISO 9001:2008 Certified Journal | Page 2195 Fig 5- Natural period Comparison The Natural period of the model with concealed beam is more than the model with the normal beam because the stiffness of the concealed beam model is less than the normal beam model. 3.1.3 Displacement No of Storeys Type of model displacement (mm) G+4 without concealed beam 6.1 with concealed beam 6.2 G+6 without concealed beam 8.6 with concealed beam 8.8 Fig 6- Displacement Comparison The depth of the concealed beam is less than that of the normal beam because of this reason the weight of the structure reduces. The stiffness of the whole structure reduces in structure with concealed beam. Hence the displacement of the top storey in models with concealed beam is more than the models with normal beams. 3.2 Pushover Analysis As the name pushover indicates, push the structure with certain magnitude until itreachesmaximumcapacityto deform. In this process the load on the structure is gradually increased with certain pre-defined pattern. As the load on the structure increases the yielding of the structure begins and finally gets damaged and failure modes of the structure becomes apparent. The effect of load reversal on the structure during earthquake is analyzed by applying load monotonically and deformation of the structureisestimated with suitable damping. The aim ofthepushoveranalysisisto understand the deformation andcrackingofthestructure.In pushover analysis the plastic hinges are assigned to the beams and columns at either ends. The hinges should be studied carefully during the collapse mechanism and the performance point may be observed. The hinges are assigned to the beams and columns of the structure as per the guidelines given in ASCE 41. For the beams the flexural hinge (M3) and shear hinge (v2) are assigned at both the ends at relative distance. Similarly, for the columns the combination of axial and flexural hinges (P-M2-M3) are assigned at both the ends with relative distance. At the distance of 0.05 and 0.95, the hinges are assigned to the beams and columns. 3.2.1 Performance point The intersection of the capacity curve and the demand curve is called as Performance point. The plotofthe base shear of the structure to the roof displacement is called as Capacity curve. and Capacity curve is also known as Pushover curve. Fig 7-Performane point fot G+4 model with concealed beam
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056 Volume: 04 Issue: 06 | June -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 5.181 | ISO 9001:2008 Certified Journal | Page 2196 Fig-8 Hinge formation in G+4 model with concealed beam The first hinge formed in beams and as the load increases the hinges started forming in columns. Thisshows weak beam and strong column concept. By observing the hinges, most of the hinges are in Life safety zone. In model G+4 storey without concealed beam, the formation ofhinges taken place in earlier steps than the model with concealed beam. In both the models bottom storey columns are having more number of life safety hinges hence retrofitting of columns has to be done. Fig 9-Performane point fot G+6 model with concealed beam Fig-10 Hinge formation in G+4 model with concealed beam The base shear of the model without concealed beam is more than the model with concealed beam. The roof displacement, Spectral displacement,effectivetimeperiodof the model with concealed beam is more and Spectral acceleration is more for the model without concealed beam. In model G+6 with concealed beam, the formation of hinges took place in later steps than the model without concealed beam. The retrofitting is required for the bottom storey columns of the both the models since life safety hinges are formed more. 5. CONCLUSIONS Following conclusions are drawn from the present study  The base shear of the concealed beam structure is less as compare to normal beam structure. Since lesserthemass lesser will be the seismic force. Hence it is concludedthat concealed beam structure is better than normal beam structure during earthquake.  The influence of concealed beam in a structure increases the natural period as compared to normal beam structure.  In multi-storey structures, if long spanslabsareprovided the deflection will be more. The concealed beams are provided in order to decrease the deflectionandincrease the stiffness of the slab.  In multi-storey building provision of concealedbeamcan act as a flat slab and provides large clearance in between the floors.  As the damping value increases, the inelastic displacement of the structure decreases due overall increase in the structural stiffness. As the damping increases, the capacity of the structure increases.
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056 Volume: 04 Issue: 06 | June -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 5.181 | ISO 9001:2008 Certified Journal | Page 2197  The more number of life safety (LS) hinges are formed in model with concealed beams as compared to model with normal beams. hence performance of the model with concealed beams is better than model with normal beams. ACKNOWLEDGEMENT The authors would like to thank Shri S. C. Metagud Chairman Governing council, K.L.E.M.S.S.C.ET and Dr. Basavaraj G. Katageri principal of K.L.E.M.S.S.C.ET, Belagavi for their kind support and providing good infrastructure. The authors are grateful to Prof. (Smt) Bharati Chiniwalar, Head of Civil Department, for encouragement and support. REFERENCES  Akash.C. Arakere, Tejas D. Doshi, “Comparison of Multi- Storey Building with Normal Beams and Concealed Beams”, International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056, | June-2015  Samir H. Riyaj Awad, “Performance based analysis of Hidden Beams in Reinforced Concrete Structure”, An- Najah National University, Nablus, Palestine.  Samir H. Helou, Munther M. Diab, “Slabs with Hidden Beams”, An-Najah National University, Nablus, Palestine.  Navyashree K, Sahana T.S, “Use of flat slabs in multi- storey commercial buildingsituatedinhighseismiczone”, International Journal of Research in Engineering and Technology, eISSN: 2319-1163, August, 2014.  M. Altus ERBERIK, Amr S. ELNASHAI, “Vulnerability analysis of flat slab structures”, 13th World Conference on Earthquake Engineering, August, 2014.  Sumit Pahwa, Vivek Tiwari and Madhavi Prajapati, “Comparative Study of Flat Slab with Old Traditional Two-way slab”, International Journal of Latest Trends  Federal Emergency ManagementAgency,FEMA-356:Pre standard and Commentary for the Seismic Rehabilitation of Buildings, 2000: Washington DC.  Federal Emergency Management Agency, FEMA-440: Improvement of Non-linear Static Seismic Analysis Procedures, June-2005: Washington DC.  ATC -40, ‘Seismic Evaluation and Retrofit of Concrete Buildings’, Vol. 1&2, Applied Technology Council, California, 1996 BIOGRAPHIES Chetan Talawar Post-Graduate Student, Department of Civil Engineering, K.L.E. Dr.M.S.Sheshigiri College of Engineering and Technology, Belagavi, India- 590008 Prof. Hemant Sonawadekar M.Tech (Structural Engineering), B.E (Civil), Assistant Professor, Department of Civil Engineering, K.L.E. Dr.M.S.Sheshigiri College of Engineering and Technology, Belagavi, India- 50008