SlideShare a Scribd company logo
A
PROJECT SYNOPSIS
ON
GRID SYNCHRONIZATION FAIL DETECTION WITH
UNDER VOLTAGE AND OVER VOLTAGE
SUBMITTED IN PARTIAL FULFILLMENT
FOR THE AWARD OF THE
DEGREE OF
BACHELOR OF TECHNOLOGY
IN
ELECTRICAL ENGINEERING
Submitted by
Karishma 1812018
Princy 1812020
Diksha 1812031
Under the guidance of
(2012 – 2016)
Haryana Engineering College
Jagadhri
(Kurukshetra University, Kurukshetra
INTRODUCTION
There is an Under/over voltage or under/over frequency, then the comparator will detect the
difference the actual power and reactive. If there is no failure of power grid synchronization then
the detectors will give the zero values. Based on the Under/over voltage and under/over
frequency values the power suppliers will be disconnected if any out of limitation values are
observed.
Synchronization means the minimization of difference in voltage, frequency and phase angle
between the corresponding phases of the generator output and grid supply. An alternating current
generator must be synchronized with the grid prior to connection. It can’t deliver the power
unless it is running at same frequency as the network. Synchronization must occur before
connecting the generator to a grid. Synchronization can be achieved manually or automatically.
The purpose of synchronization is to monitor, access, enable, and automatically take the control
action to prevent the abnormalities of voltage and frequency.
Rules must be followed for Synchronization:
Voltage Fluctuation:
When a generator is synchronized with a power grid, normally there is a voltage fluctuation on
the distribution line. During synchronization the voltage fluctuation should not exceed 3% at the
at the point of common coupling.
Synchronization Limits:
The limits allowing for synchronization are
1. Phase angle- +/-20 degrees
2. Maximum voltage difference – 7%
3. Maximum slip frequency – 0.44%
Relays:
For checking the synchronization “synch check relay” must be used. The usage of relays can’t
apply for induction generators. The use of synch check relay is to accept as a backup during
synchronization and to ensure a generator will not connect to a dead distribution line.
Synchronization of Induction Generators:
For the synchronization of induction generators it just needs to be run up to synchronization
speed and connected. For this purpose standard motor controllers will be used. To mechanically
drive the generators up to synchronization speed turbine shaft power will be used. The speed of
the motors depends on supplied frequency and number of poles on the generators.
Synchronization of Synchronous Machines:
For synchronous generators output waveform should be in phase with the grid voltage waveform
or with in specified limits. The rate of change of phase angle between the grid and the machine
(generator) must be with in the specified limits.
Some other rules are variable speed drive arrangement to maintain a constant output frequency,
inter connection protection between the generator and distribution system.
Failure of Synchronization:
Synchronization circuit may fail for responding to a received input pulse when the received input
pulse is shorted than the sampling period of the synchronizer. Then no synchronized
representation will take place. When the pulse rate of the input signal is higher than the
synchronization rate of the synchronizer then also it may fail to respond. Some times the
synchronizer it self may fail by ignoring input events. These all are the circumstances which
could create problems if not detected. There are various reasons for failure of power grid
synchronization.
Synchronization Failures and their Detections:
There are some situations where the generators and some local loads have become disconnected
from main distribution lines. Due to this reduction in quality of supply, and it may prevent
automatic reconnection of devices. This is called as islanding. For this reason islanding must be
detected immediately and producing power must be stopped immediately.
Due to Islanding following hazards may take place
1. Generally distributed lines are earthed only at the sub station. When the distributing lines and
generators are disconnected the line is not earthed. Due to this reason line voltages may
excessive.
2. The fault level contribution from the grid to sub-station may be lost. This will effect the
operation of protection on distributed lines. Due to this sufficient current may not be generated.
3. Due to Islanding synchronization can’t be maintained. When the grip attempts to reconnect with
distribution line it may be out of synchronization at the reconnection point. Due to this, suddenly
large power may flows which cause damage for generators, distribution units and consumer
products.
Some other disadvantages due to islanding are the voltage levels may go outside of normal
operating limits, and the quality of supply may be reduced.
Detection methods of Islanding:
Detection of islanding can be done through active and passive methods. Passive methods look
for transient events on the grid and active methods will probe the grid by sending signals from
the distribution point of grid. Loss of Mains Protection (LoM) will be designed to sense the
disconnection of generators and loads when an island has been created. The most utilized LoM
detection methods may fail to detect islanding when the production matches closely with the
consumption in the island zone. This blind area is called Non Detection Zone (NDZ). The size of
NDZ can be reduced by tightening the LoM setting relays.
Active Methods:
Impedance measurement, Detection of impedance at specific frequency, slip mode frequency
shift, Frequency bias, and frequency jump detection methods are some passive methods for
islanding detection. The advantage of impedance measurement method is an extremely small
NDZ for a single inverter. Slip mode frequency shift method is relatively easy to implement. It is
highly effective in islanding prevention when compared to other detection methods.
Passive Methods:
All grid-connected PV inverters are required to have Over/Under frequency protections methods
and Under/Over voltage protection methods that cause the inverter to stop supplying power to
the utility grid if the frequency or voltage of grid at the point of coupling.
Block Diagram
These protection methods protect consumer’s equipment and also servicing as anti-islanding
methods. Voltage Phase Jump detection, and Detection of voltage harmonics are some more
passive methods for detection islanding. The Under/Over voltage protection methods and the
Under/over frequency methods are required other than preventing islanding. Several islanding
prevention methods produce abnormal voltage, and frequency. Under/Over voltage protection
methods and Under/Over frequency protection methods are low cost methods for the detection
islanding.
Applications of Power grid failure Detection:
Lighting is one of the main causes for power system faults. The entire power system is consisting
electrically of power plants, sub-stations and transmission lines, distribution feeders and power
consumers. Detecting the synchronization failure between generators and power grid is the major
advantage such as saving the energy. Then we can avoid the loss of power consumption by
disconnecting from the power consumption devices.
When there is an Under/over voltage or under/over frequency, then the comparator will detect
the difference the actual power and reactive. If there is no failure of power grid synchronization
then the detectors will give the zero values. Based on the Under/over voltage and under/over
frequency values the power suppliers will be disconnected if any out of limitation values are
observed.

More Related Content

PPT
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUENCY
PPT
power grid synchronization failure detection
DOCX
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...
PDF
Power grid synchronization failure detection and recovery
PPTX
Detection of power grid synchronization failure on sensing of frequency and v...
PPTX
Power Grid Control System
PPTX
Detecting Power Grid Synchronization Failure on Sensing Frequency or Voltage ...
PPTX
Grid synchronisation
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUENCY
power grid synchronization failure detection
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...
Power grid synchronization failure detection and recovery
Detection of power grid synchronization failure on sensing of frequency and v...
Power Grid Control System
Detecting Power Grid Synchronization Failure on Sensing Frequency or Voltage ...
Grid synchronisation

What's hot (20)

PPTX
Three Phase Fault Analysis With Auto Reset On Temporary Fault And Permanent Trip
PDF
Fault analysis on three phase system by auto reclosing mechanism
PDF
three phase fault analysis with auto reset for temporary fault and trip for p...
PPTX
AUTOMATIC ACTIVE PHASE SELECTOR FOR SINGLE ...
PPTX
overview of grid structure and synchronization for distributed power generati...
PPT
SEMINAR TOPIC- 3 PHASE SELETOR AND PREVENTER FOR INDUSTRIAL APPS. 2007.ppt
PPT
ppt of Three phase fault analysis with auto reset for temporary fault and tri...
PPTX
Auto selection of any aviliable phase
PDF
Y R ENGG Company Profile 2
DOC
Automatic Phase Changer
PPTX
SELF SWITCHING POWER SUPLLY
PPTX
Digital phase selector
PDF
Design and Construction of Automatic Three Phase Power System Selector
PDF
7SR12 Directional Over Current Relay
PPT
Digital phase changer ppt
PPTX
distribution system fault mangement
PPTX
Relay & Protection
PPTX
Automated load shedding using microcontroller
PPTX
Ppt power grid design
PPT
Basic short circuit calculation procedure
Three Phase Fault Analysis With Auto Reset On Temporary Fault And Permanent Trip
Fault analysis on three phase system by auto reclosing mechanism
three phase fault analysis with auto reset for temporary fault and trip for p...
AUTOMATIC ACTIVE PHASE SELECTOR FOR SINGLE ...
overview of grid structure and synchronization for distributed power generati...
SEMINAR TOPIC- 3 PHASE SELETOR AND PREVENTER FOR INDUSTRIAL APPS. 2007.ppt
ppt of Three phase fault analysis with auto reset for temporary fault and tri...
Auto selection of any aviliable phase
Y R ENGG Company Profile 2
Automatic Phase Changer
SELF SWITCHING POWER SUPLLY
Digital phase selector
Design and Construction of Automatic Three Phase Power System Selector
7SR12 Directional Over Current Relay
Digital phase changer ppt
distribution system fault mangement
Relay & Protection
Automated load shedding using microcontroller
Ppt power grid design
Basic short circuit calculation procedure
Ad

Viewers also liked (20)

DOCX
DLD_SYNOPSIS
DOCX
Synopsis for Public Garden automation with solar tracker by Punith urs
DOCX
Project Synopsis sample
PDF
J. A. P. Lopes, "The MERGE control concept - Microgrids and EVs - Development...
PDF
18 b mather_pv_sys_symposium_san_jose_ca_160510
PDF
Modelling the system dynamics of islanding asynchronous generators / Telemark...
DOCX
Storage Area Networks Unit 3 Notes
DOC
47879104 automatic-stand-release
PPTX
PPT_Final_Presentation
DOCX
PROJECT Room envirment monitoring system synopsis
PDF
Anish Kumar (EEE)
PDF
Chap2coulomb law
PPTX
Van de graaff generator pp
PPT
Automatic side stand remover
DOCX
Sprocket -Side Stand Retrieve System
PPT
Ven de graaff generator 745
PPTX
Audio steganography project presentation
PPT
Synopsis or minor project ppt's (2)
PDF
Canteen automation system (updated) revised
DOCX
B. Tech. Minor Project Synopsis
DLD_SYNOPSIS
Synopsis for Public Garden automation with solar tracker by Punith urs
Project Synopsis sample
J. A. P. Lopes, "The MERGE control concept - Microgrids and EVs - Development...
18 b mather_pv_sys_symposium_san_jose_ca_160510
Modelling the system dynamics of islanding asynchronous generators / Telemark...
Storage Area Networks Unit 3 Notes
47879104 automatic-stand-release
PPT_Final_Presentation
PROJECT Room envirment monitoring system synopsis
Anish Kumar (EEE)
Chap2coulomb law
Van de graaff generator pp
Automatic side stand remover
Sprocket -Side Stand Retrieve System
Ven de graaff generator 745
Audio steganography project presentation
Synopsis or minor project ppt's (2)
Canteen automation system (updated) revised
B. Tech. Minor Project Synopsis
Ad

Similar to Power grid synopsis (20)

PDF
Detection of Power Grid Synchronization Failure by Sensing Bad Voltage and Fr...
PDF
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
PDF
Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...
PDF
Kenny samaroo methodology of selection, setting and analysis of anti-islandin...
PPTX
GENERATOR POLE SLIP AND OUT – OF – STEP PROTECTION.pptx
PPTX
GENERATOR POLE SLIP AND OUT – OF – STEP PROTECTION.pptx
PDF
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
PDF
Fi25986990
PPT
seminar1.ppt
PPTX
Final presentation [Autosaved].pptxFinal presentation [Autosaved].pptxFinal p...
PDF
Hybrid islanding detection method based on the rate of change of frequency an...
PDF
G42022933
PDF
Auto synch considerations methods
PDF
A practical primer for paralleling electric systems
DOC
(4) synch
PPTX
Islands in power systems
PPT
Protection and Switch Gear Chapter I.ppt
PDF
lecture1423723756.pdf
PPTX
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
PDF
ANALYTICAL STUDY OF DIFFERENT TECHNIQUES FOR ISLANDING DETECTION OF PV GRID-T...
Detection of Power Grid Synchronization Failure by Sensing Bad Voltage and Fr...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...
Kenny samaroo methodology of selection, setting and analysis of anti-islandin...
GENERATOR POLE SLIP AND OUT – OF – STEP PROTECTION.pptx
GENERATOR POLE SLIP AND OUT – OF – STEP PROTECTION.pptx
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
Fi25986990
seminar1.ppt
Final presentation [Autosaved].pptxFinal presentation [Autosaved].pptxFinal p...
Hybrid islanding detection method based on the rate of change of frequency an...
G42022933
Auto synch considerations methods
A practical primer for paralleling electric systems
(4) synch
Islands in power systems
Protection and Switch Gear Chapter I.ppt
lecture1423723756.pdf
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
ANALYTICAL STUDY OF DIFFERENT TECHNIQUES FOR ISLANDING DETECTION OF PV GRID-T...

Recently uploaded (20)

PDF
Level 2 – IBM Data and AI Fundamentals (1)_v1.1.PDF
PDF
Abrasive, erosive and cavitation wear.pdf
PPTX
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
PDF
BIO-INSPIRED ARCHITECTURE FOR PARSIMONIOUS CONVERSATIONAL INTELLIGENCE : THE ...
PDF
distributed database system" (DDBS) is often used to refer to both the distri...
PPT
Occupational Health and Safety Management System
PPTX
Information Storage and Retrieval Techniques Unit III
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
PDF
Soil Improvement Techniques Note - Rabbi
PDF
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
PPTX
Feature types and data preprocessing steps
PPTX
Module 8- Technological and Communication Skills.pptx
PDF
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
PDF
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
PDF
Exploratory_Data_Analysis_Fundamentals.pdf
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PPTX
Sorting and Hashing in Data Structures with Algorithms, Techniques, Implement...
PPT
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
Level 2 – IBM Data and AI Fundamentals (1)_v1.1.PDF
Abrasive, erosive and cavitation wear.pdf
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
BIO-INSPIRED ARCHITECTURE FOR PARSIMONIOUS CONVERSATIONAL INTELLIGENCE : THE ...
distributed database system" (DDBS) is often used to refer to both the distri...
Occupational Health and Safety Management System
Information Storage and Retrieval Techniques Unit III
Automation-in-Manufacturing-Chapter-Introduction.pdf
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
Soil Improvement Techniques Note - Rabbi
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
Feature types and data preprocessing steps
Module 8- Technological and Communication Skills.pptx
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
Exploratory_Data_Analysis_Fundamentals.pdf
R24 SURVEYING LAB MANUAL for civil enggi
Sorting and Hashing in Data Structures with Algorithms, Techniques, Implement...
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt

Power grid synopsis

  • 1. A PROJECT SYNOPSIS ON GRID SYNCHRONIZATION FAIL DETECTION WITH UNDER VOLTAGE AND OVER VOLTAGE SUBMITTED IN PARTIAL FULFILLMENT FOR THE AWARD OF THE DEGREE OF BACHELOR OF TECHNOLOGY IN ELECTRICAL ENGINEERING Submitted by Karishma 1812018 Princy 1812020 Diksha 1812031 Under the guidance of (2012 – 2016) Haryana Engineering College Jagadhri (Kurukshetra University, Kurukshetra
  • 2. INTRODUCTION There is an Under/over voltage or under/over frequency, then the comparator will detect the difference the actual power and reactive. If there is no failure of power grid synchronization then the detectors will give the zero values. Based on the Under/over voltage and under/over frequency values the power suppliers will be disconnected if any out of limitation values are observed. Synchronization means the minimization of difference in voltage, frequency and phase angle between the corresponding phases of the generator output and grid supply. An alternating current generator must be synchronized with the grid prior to connection. It can’t deliver the power unless it is running at same frequency as the network. Synchronization must occur before connecting the generator to a grid. Synchronization can be achieved manually or automatically. The purpose of synchronization is to monitor, access, enable, and automatically take the control action to prevent the abnormalities of voltage and frequency. Rules must be followed for Synchronization: Voltage Fluctuation: When a generator is synchronized with a power grid, normally there is a voltage fluctuation on the distribution line. During synchronization the voltage fluctuation should not exceed 3% at the at the point of common coupling. Synchronization Limits: The limits allowing for synchronization are 1. Phase angle- +/-20 degrees 2. Maximum voltage difference – 7% 3. Maximum slip frequency – 0.44%
  • 3. Relays: For checking the synchronization “synch check relay” must be used. The usage of relays can’t apply for induction generators. The use of synch check relay is to accept as a backup during synchronization and to ensure a generator will not connect to a dead distribution line. Synchronization of Induction Generators: For the synchronization of induction generators it just needs to be run up to synchronization speed and connected. For this purpose standard motor controllers will be used. To mechanically drive the generators up to synchronization speed turbine shaft power will be used. The speed of the motors depends on supplied frequency and number of poles on the generators. Synchronization of Synchronous Machines: For synchronous generators output waveform should be in phase with the grid voltage waveform or with in specified limits. The rate of change of phase angle between the grid and the machine (generator) must be with in the specified limits. Some other rules are variable speed drive arrangement to maintain a constant output frequency, inter connection protection between the generator and distribution system. Failure of Synchronization: Synchronization circuit may fail for responding to a received input pulse when the received input pulse is shorted than the sampling period of the synchronizer. Then no synchronized representation will take place. When the pulse rate of the input signal is higher than the synchronization rate of the synchronizer then also it may fail to respond. Some times the synchronizer it self may fail by ignoring input events. These all are the circumstances which could create problems if not detected. There are various reasons for failure of power grid synchronization.
  • 4. Synchronization Failures and their Detections: There are some situations where the generators and some local loads have become disconnected from main distribution lines. Due to this reduction in quality of supply, and it may prevent automatic reconnection of devices. This is called as islanding. For this reason islanding must be detected immediately and producing power must be stopped immediately. Due to Islanding following hazards may take place 1. Generally distributed lines are earthed only at the sub station. When the distributing lines and generators are disconnected the line is not earthed. Due to this reason line voltages may excessive. 2. The fault level contribution from the grid to sub-station may be lost. This will effect the operation of protection on distributed lines. Due to this sufficient current may not be generated. 3. Due to Islanding synchronization can’t be maintained. When the grip attempts to reconnect with distribution line it may be out of synchronization at the reconnection point. Due to this, suddenly large power may flows which cause damage for generators, distribution units and consumer products. Some other disadvantages due to islanding are the voltage levels may go outside of normal operating limits, and the quality of supply may be reduced. Detection methods of Islanding: Detection of islanding can be done through active and passive methods. Passive methods look for transient events on the grid and active methods will probe the grid by sending signals from the distribution point of grid. Loss of Mains Protection (LoM) will be designed to sense the disconnection of generators and loads when an island has been created. The most utilized LoM detection methods may fail to detect islanding when the production matches closely with the consumption in the island zone. This blind area is called Non Detection Zone (NDZ). The size of NDZ can be reduced by tightening the LoM setting relays.
  • 5. Active Methods: Impedance measurement, Detection of impedance at specific frequency, slip mode frequency shift, Frequency bias, and frequency jump detection methods are some passive methods for islanding detection. The advantage of impedance measurement method is an extremely small NDZ for a single inverter. Slip mode frequency shift method is relatively easy to implement. It is highly effective in islanding prevention when compared to other detection methods. Passive Methods: All grid-connected PV inverters are required to have Over/Under frequency protections methods and Under/Over voltage protection methods that cause the inverter to stop supplying power to the utility grid if the frequency or voltage of grid at the point of coupling. Block Diagram These protection methods protect consumer’s equipment and also servicing as anti-islanding methods. Voltage Phase Jump detection, and Detection of voltage harmonics are some more passive methods for detection islanding. The Under/Over voltage protection methods and the Under/over frequency methods are required other than preventing islanding. Several islanding
  • 6. prevention methods produce abnormal voltage, and frequency. Under/Over voltage protection methods and Under/Over frequency protection methods are low cost methods for the detection islanding. Applications of Power grid failure Detection: Lighting is one of the main causes for power system faults. The entire power system is consisting electrically of power plants, sub-stations and transmission lines, distribution feeders and power consumers. Detecting the synchronization failure between generators and power grid is the major advantage such as saving the energy. Then we can avoid the loss of power consumption by disconnecting from the power consumption devices. When there is an Under/over voltage or under/over frequency, then the comparator will detect the difference the actual power and reactive. If there is no failure of power grid synchronization then the detectors will give the zero values. Based on the Under/over voltage and under/over frequency values the power suppliers will be disconnected if any out of limitation values are observed.