Hybrid islanding detection method based on the rate of change
of frequency and load impedance
Hasmaini Mohamad, Zuhaila Mat Yasin, Nur Ashida Salim, Bibi Norasiqin Sheikh Rahimullah,
Kanendra Naidu
School of Electrical Engineering, College of Engineering, Universiti Teknologi MARA, 40450 Shah Alam, Selangor,
Malaysia
Article Info ABSTRACT
Article history:
Received Jun 7, 2021
Revised Aug 24, 2021
Accepted Oct 8, 2021
Interconnection of distributed generation (DG) in distribution system will
result in formation of islands in the event of loss of main supply. This scenario
is harmful to the power system, hence quick detection is critical to halt the
formation of islands. Among the common passive and active detection
methods available, the hybrid detection method is identified as the most
reliable method. This paper proposes a new hybrid method using the
combination of passive and active technique which is the rate of change of
frequency (ROCOF) and load impedance, respectively. The passive method
works when the value of ROCOF exceeds the threshold value which is set at
0.3Hz/s. The active method works when it detects low value of ROCOF and
immediately inject a pre-specified load into the system to increase the
ROCOF value up to its threshold value. Simulation study on different case
studies is carried out on distribution test system to evaluate the performance
of the proposed method. Results show that this method is effective in
detecting any events that could result in islanding.
Keywords:
Distributed generation
Islanding detection
Load impedance
Rate of change of frequency
This is an open access article under the CC BY-SA license.
Corresponding Author:
Hasmaini Mohamad
School of Electrical Engineering, College of Engineering
Universiti Teknologi MARA, Shah Alam, Selangor, Malaysia
Email: hasmaini@uitm.edu.my
1. INTRODUCTION
Distributed generation (DG) is a small-scale power generation technology installed in the vicinity of
the end users in order to produce electricity. DGs cover any net metered or commercial-scale generation that
is connected to the grid at the distribution level. DGs are important as they offer many benefits to the power
system such as enhancing the efficiency of electricity supply, reducing distribution and transmission losses
and delivering clean and sustainable power to the customers. However, there is a technical issue called
islanding which occurs when DG continues supplying power to a part of the distribution system eventhough
the connection to the grid is interrupted during catastrophic event.
Islanding can be either intentional or unintentional islanding. Intentional islanding is a properly
planned process to improve the system reliability where DG continuously supply power to critical loads in
the event of power supply failure from the grid. Readiness of an advanced control scheme in ensuring a
smooth changes from grid connected to islanding mode of operation is required. With the controller in place,
the grid can sectionalize itself by allowing the DG to supply the islands’ load until the main power supply is
re-established. On the other hand, unintentional islanding may result in damaging the DG since it operates
without proper control mechanism for islanding [1]. Similarly, this is hazardous for utility workers working
in the distribution system who are unaware that the network is still operational. This situation usually occurs
 ISSN: 2302-9285
Bulletin of Electr Eng & Inf, Vol. 10, No. 6, December 2021 : 2997 – 3006
2998
when the power is being fed via the DG to the system during loss of main supply form the grid . The
exposure to live system can be fatal to the utility workers [2]. Therefore, DG’s protection scheme has to
detect the islanding situation and immediately disconnect DG from the network. This is referred to as
islanding detection method.
Islanding detection methods for both intentional and unintentional islanding are generally classified
into local and remote methods. Local method can be further categorized into active and passive methods
while remote method is based on communication between the utility and the DGs [3]. Passive method
identifies islanding by monitoring the parameters such as frequency, voltage, current, active power, reactive
power and harmonic distortion. Many techniques were subsequently introduced with various combination of
parameters and settings such as rate of change of positive and negative sequence component [4], rate of
change of frequency (ROCOF) [5], rate of change of output power [6], rate of change of voltage and changes
in power factors [7], voltage unbalance and total harmonic distortion of current [8] and combinations of four
passive parameters [9]. The very recent research considered load angle and mechanical power parameters
[10], undervoltage block function [11] and sensitivity of different passive parameters [12]. When the
distribution system is islanded, these parameters are significantly affected. Detection relies on the threshold
setting for each parameter which will discriminate islanding and non-islanding type of disturbance. However,
islanding is difficult to detect when there is minimal power mismatch between generation and load in the
islanded system. If the threshold values is too high, islanding might not be detected while if the threshold
values is too low, it could result in false tripping of DG.
The weakness of the passive method can be complemented by active method, which can detect the
occurrences of islanding even under zero power imbalance between generation and load. Active method
identifies a grid failure or islanding by injecting a small signal into the system. This method is applicable for
inverter based DGs. Methods such as active positive feedback islanding detection schemes [13], DC/AC
inverter acting as virtual capacitor [14], frequency dependent ZIP–Exponential static load model [15],
impedance-based analysis of the active frequency drift (AFD) [16], d-axis current injection [17], islanding
detection index based on resistance seen from the SSSG terminal with respect to the angular frequency [18]
and high-frequency signal injection for multiple parallel-connected inverters based DG [19]. These methods
outperforms the passive method but are rather expensive and pose power quality deterioration.
The recent trend of islanding detection using intelligent based and hybrid methods where both
associated with passive and/or active method. Intelligent method is based on the application of artificial
neural network (ANN), fuzzy logic control (FLC), evolutionary programming (EP), decision tree (DT) [20],
adaptive neuro fuzzy inference system (ANFIS) [21], and support vector machine (SVM) [22]. These
methods help to classify islanding/non islanding events based on training and testing data obtained from the
simulation/experiment conducted on the test system. Testing on different types of faults based on passive
parameter is rigorously carried out to generate huge amount of data. As a result, the classification is accurate
with a nearly zero non-detection zone (NDZ) and detection is reached in a very short time. However, any
changes made on the test system such as network expansion, will cause the need of a new set training data for
classification process.
Introduction of hybrid islanding detection method [23] can overcome the shortcomings in passive or
active method approach. It combines the advantages of both method to offer more effective result compared
to passive/active method alone. Hybrid method proposed in the literatures considered combination of voltage
unbalance and frequency set point [24], average rate of voltage change and real power shift [25], voltage
unbalance (VU) and high-frequency (HF) impedance [26], dynamic characteristics of synchronous generator
and signal processing technique [27], voltage unbalance and total harmonic distortion (VU/THD) and
bilateral reactive power variation (BRPV) [28], rate of change of exciter voltage (RCEV) and open-close
circuit breaker (OCCB) at a DG connection point [29]. In addition, there is also a new approach of hybrid
method using combination of active, passive and communication technique [30]. Each method has different
detection performance depending on the chosen combination. The active technique is normally adopted when
passive technique alone is unable to detect islanding scenario particularly during minimal power mismatch.
So far, the hybrid method employs the combination of a new type of passive method with an advanced active
method. However, the research work on hybrid method using the ROCOF which is commonly adopted by
utility companies has not been explored in detail. This is important as a comprehensive investigation is
required on the practicality of applying proposed hybrid method to existing islanding detection technique.
This paper proposes a new hybrid method which combines ROCOF as the passive method and
injection of load impedance as the active method. ROCOF is chosen since it is commonly used as the main
protection system in distribution system. ROCOF operates when it detects islanding based on the rate of
changes of frequency that exceeds the threshold limit. The load impedance is injected to the system when it
detects a small value of ROCOF. The injection will increase the value of ROCOF up to the specified limit.
This will ensure that the islanding detection is successful even there is a small power mismatch. The main
Bulletin of Electr Eng & Inf ISSN: 2302-9285 
Hybrid islanding detection method based on the rate of change of frequency … (Hasmaini Mohamad)
2999
contributions of this studies are: 1) quick islanding detection which is less than 20ms, 2) effective detection
of islanding and non-islanding event, and 3) employs a simple method using standard parameter
measurement. This method is modelled and simulated using PSCAD/EMTDC simulation tools. In order to
evaluate this method, there are seven case studies introduced which are loss of main, fault at adjacent line
(single line to ground fault, line to line to ground fault, and three phase fault) and fault near to DG (single
line to ground fault, line to line to ground fault, and three phase fault). This paper is organized as follows in
which the proposed hybrid detection method and test system are elaborated in section 2, result and discussion
are explained in section 3 and finally conclusion is drawn in section 4.
2. RESEARCH METHOD
The hybrid islanding detection method applied in this study uses ROCOF as a passive method and
the injection of load impedance as the active method. The modelling of the proposed method and test system
are described in the following section.
2.1. Modeling proposed method
Two modules comprising of active and passive method are developed for the proposed hybrid
method as depicted in Figure 1. Passive and active module are located in the DG protection unit and at the
generator bus, respectively.
Figure 1. Principal operation of the proposed method
The development concept of the hybrid method is shown in Figure 2. The passive method module is
used to continuously monitor the ROCOF value which is taken from the speed measurement of DG. The
proposed method detects any islanding event whenever the ROCOF value exceeds the specified threshold. A
tripping signal is subsequently sent to circuit breaker of the DG’s protection system thus prohibiting the DG
from supplying the load. Active method module will only be activated to inject an additional load to the
system whenever it detects ROCOF value less than the threshold value. Details of the islanding detection
process is described in Figure 3.
Figure 2. Block diagram of the proposed method
 ISSN: 2302-9285
Bulletin of Electr Eng & Inf, Vol. 10, No. 6, December 2021 : 2997 – 3006
3000
The process starts with the determination of frequency from the speed measurement of DG. Then,
derivative component is used to calculate the rate of change of frequency (ROCOF). The active and passive
method are designed specifically for detection purposes considering the ROCOF as the input. The script for
designing the module is written using FORTRAN programming language. The passive module is designed
based on the comparison between the calculated ROCOF value and ROCOF threshold setting. Detection
module will be triggered once the ROCOF value surpass the threshold value. The common setting for
ROCOF threshold is between 0.1Hz/s to 1Hz/s [12]. In this study, the threshold value of 0.3Hz/s is used.
Meanwhile, the output of the active method module will send a signal to inject a load with a value of 330kW
to the system when the magnitude of the calculated ROCOF is less than 0.3Hz/s. The value of the injected
load cannot be too high because it will cause system interference. The value of 330kW is deemed suitable for
the system is determined from several tests conducted for LOM as recorded in Table 1. The value of active
load highly depends on the power imbalance the moment system experiences disturbance. Lower power
imbalance of less than 270MW, would require an injection of a large load value of 540kW. High value of
load is infeasible for islanding detection purposes as it would incur high cost. The load injection for power
imbalance greater than 280MW would result in a steep increase of ROCOF value to more than 0.3Hz/s,
hence triggering islanding detection mechanism and subsequently the DG breaker is tripped.
Figure 3. Flow chart of the proposed islanding detection method
Table 1. Analysis of the islanding detection on different range of ∆P for various load values
Range of ∆P(kW) Load(kW) Detect Islanding Preferable
90–270 150kW ×
330kW ×
540kW ✓ Prefer
280–430 150kW ×
330kW ✓ Prefer
540kW ✓
440–540 150kW ✓ Prefer
330kW ✓
540kW ✓
2.2. Test network
The test system shown in Figure 4 was modelled using PSCAD software. The 7-bus system operates
at 50Hz, 33kV, and includes a 100MVA generator as main supply. As shown in the Figure 4, there are two
step-down transformers of 33/11 kV and 11/3.3 kV rated at 20MVA and 2MVA respectively. The 2MVA
Bulletin of Electr Eng & Inf ISSN: 2302-9285 
Hybrid islanding detection method based on the rate of change of frequency … (Hasmaini Mohamad)
3001
transformer is placed at the end of the distribution line where DG is located. The DG is modelled as a hydro
turbine generator rated at 2 MVA. The loads connected to the system are static loads.
Figure 4. 7-bus test system
3. RESULT AND ANALYSIS
In order to evaluate the effectiveness of the proposed method, three case studies are simulated based
on the 7-bus test system. The three case studies are:
− Case 1: Loss of main
− Case 2: Various fault at line connected to DG (DG Line)
− Case 3: Various fault at line adjacent to DG at line 4-5
The faults considered in this study are single line to ground fault, line to line to ground fault, and three phase
fault. Case 1 which is loss of main, a signal is sent to open breaker A to disconnect the main supply at t = 10
seconds. Case 2, three different types of faults are applied at line connected to DG as indicated in Figure 4.
As for case 3, three different types of faults are applied at adjacent line (line 4-5) as indicated in Figure 4.
Results for the three case studies are tabulated in Table 2.
Table 2. Breaker trip status for all three cases
Cases Type of Events Breaker B Condition
1 Loss of main TRIP
2 Single line to ground fault TRIP
Line to line to ground fault TRIP
Three phase faults TRIP
3 Single line to ground fault NOT TRIP
Line to line to ground fault NOT TRIP
Three phase faults NOT TRIP
3.1. Loss of main
The system frequency immediately increases in response to the disconnection of main grid from the
distribution network. Based on Figure 5, the frequency of DG increases until it hits 71Hz then gradually
drops to 30Hz. The frequency increment contributes to the increment of the ROCOF value. As can be seen in
Figure 6, the ROCOF reading at t=10 seconds exceeds the ROCOF threshold which has been set at 0.3Hz/s.
As a result, a signal is sent to trip the breaker B. The islanding detection mechanism verifies that loss of main
is islanding scenario and proceeds to trip breaker B causing the DG to shut down. The change of active
power due to the islanding caused the frequency drops and unstable. Only passive method works for this case
since the ROCOF value is greater than the threshold value. The high value of frequency and df/dt is due to a
large power imbalance between generation and load the moment system is disconnected from the main.
 ISSN: 2302-9285
Bulletin of Electr Eng & Inf, Vol. 10, No. 6, December 2021 : 2997 – 3006
3002
Figure 5. Frequency of DG for loss of main Figure 6. ROCOF measurement for loss of main
3.2. Fault at DG line
As mentioned earlier, three types of faults are simulated which are three phase fault, single line to
ground fault, and line to line to ground fault. The fault is simulated at t=10 seconds with 0.05 seconds of fault
duration. For all type of faults, the reading of ROCOF exceeds the ROCOF’s threshold value which causes
breaker B to trip. Figures 7 and 8 shows the frequency response and ROCOF value respectively when a
three-phase fault is applied to the system. Eventhough the fault duration is very short, huge impact to the
system frequency can be seen following the fault. The response is almost similar to the response due to loss
of main. The hybrid module manages to successfully detect the islanding scenario due to the fault location
location is near to DG which contributes to the high ROCOF value.
Figure 7. Frequency of DG for three phase fault Figure 8. ROCOF measurement for three phase fault
3.3. Fault at adjacent line (line 4-5)
The adjacent line is located at the same bus with the DG line. The fault setting is set similar to case
2. Results show that breaker B does not trip for all three types of faults. The system frequency stays at 50Hz
following the fault as shown in Figure 9 (a). This causes the ROCOF to remain at zero value even after fault
as shown in Figure 9 (b). The fault does not impact the system since it is applied at the load side as it does
not interfere the power flow from power supply to DG.
(a) (b)
Figure 9. These figures are; (a) frequency, (b) ROCOF measurement for three phase faults at adjacent line1
3.4. Comparative analysis
Comparative analysis is carried out to analyse the advantage of having an active method in the
proposed hybrid method. Simulation is performed for case 1 by using two different detection method: 1)
passive method and 2) hybrid method module. The simulation is carried out for a small value of power
mismatch, ∆P. Based on results shown in Figure 10, the reading of ROCOF for passive method does not even
Bulletin of Electr Eng & Inf ISSN: 2302-9285 
Hybrid islanding detection method based on the rate of change of frequency … (Hasmaini Mohamad)
3003
reach the threshold value since ∆P is small. However, with the proposed hybrid method which combines
passive and active method, the injection of load impedance from active method pushes the reading of
ROCOF to reach the threshold value. As a result, the proposed method able to detect islanding for a small
value of power imbalance as recorded in Table 3. This proves that the hybrid detection method gives better
performance than passive method in detecting islanding event. Moreover, non-detection zone (NDZ), which
is one of the most important criteria for islanding detection method is also assessed in identifying the area
that both methods fail to detect islanding scenario. Rigorous testing is carried out to identify an accurate NDZ
for both methods. The NDZ shown in Figure 11 obviously differentiate the accuracy of detection for both
methods where the hybrid method has a smaller NDZ compared to the passive method. The result indicates
that more islanding events can be detected by hybrid method compared to passive method, thus increasing
the islanding detection reliability. In terms of detection time, the proposed hybrid method would detect
islanding event in 35 ms and 70 ms for passive and hybrid method respectively. This indicates that the
proposed method is better compared to other methods listed in Table 4. However, in real world application,
the time taken may vary accordingly depending on the signal and communication delay.
Figure 10. Comparison of ROCOF between hybrid method and passive method
Table 3. Result of loss of main with hybrid and passive method
Cases Breaker B Condition
Loss of main Hybrid Method TRIP
Passive Method NOT TRIP
Figure 11. NDZ for ROCOF and hybrid methods
Table 4. Comparative analysis on islanding detection time
Detection Method Detection time (ms)
Undervoltage block function [11] 136.2
Voltage Unbalance and Total Harmonic Distortion of Current [8] 129
Rate of Change of Exciter Voltage with Circuit Breaker Switching Strategy [29] 100 (passive)
300 (hybrid)
Proposed method 35 (passive)
70 (hybrid)
 ISSN: 2302-9285
Bulletin of Electr Eng & Inf, Vol. 10, No. 6, December 2021 : 2997 – 3006
3004
4. CONCLUSION
This paper presents a hybrid islanding detection method by using the rate of change of frequency
(ROCOF) and the injection of load impedance. Several case studies have been simulated on the test
distribution system to assess the effectiveness of the proposed method. Results proved that the method
effectively detected all event that could result in islanding. Comparison studies including the NDZ
assessment with the passive method further validated the islanding detection performance of the hybrid
method.
ACKNOWLEDGEMENTS
This work is supported by the Ministry of Higher Education and Universiti Teknologi MARA,
Malaysia under FRGS research grant (Grant Code: 600-IRMI/FRGS 5/3(090/2019)).
REFERENCES
[1] J. R. Reddy, A. Pandian, R. Dhanasekharan, Ch. R. Reddy, B. P. Lakshmi, “Islanding detection of integrated
distributed generation with advanced controller,” Indonesian Journal of Electrical Engineering and Computer
Science, vol. 17, no. 3, pp. 1626-1631, 2020, doi: 10.11591/ijeecs.v17.i3.pp1626-1631.
[2] S. Raza, H. Amjad, M. Umer and A. Khalid, “Analysis of power system parameters for islanding detection using
wavelet transform,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 17, no. 3, pp. 1184-
1193, 2020, doi: 10.11591/ijeecs.v17.i3.pp1184-1193.
[3] J. A. Laghari, H. Mokhlis, M. Karimi, A. H. A. Bakar, and H. Mohamad, “Computational Intelligence based
techniques for islanding detection of distributed generation in distribution network: A review,” Energy Conversion
and Management, vol. 88, pp. 139-152, 2014, doi: 10.1016/j.enconman.2014.08.024.
[4] A. Sharma and R. Sunitha, “Unintentional islanding detection in microgrid,” International Conference on Energy,
Communication, Data Analytics and Soft Computing ICECDS, 2017, pp. 2519-2523, doi:
10.1109/ICECDS.2017.8389907.
[5] J. R. Reddy and A. Pandian, “Improved ROCOF relay for islanding detection of solar distributed generation,”
Indonesian Journal of Electrical Engineering and Computer Science, vol. 14, no. 3, pp. 1105-1113, 2019, doi:
10.11591/ijeecs.v14.i3.pp1105-1113.
[6] S. Nikolovski, H. R. Baghaee and D. Mlakić, “Islanding Detection of Synchronous Generator-Based DGs using
Rate of Change of Reactive Power,” EEE Systems Journal, vol. 13, no. 4, pp. 4344-4354, 2019, doi:
10.1109/JSYST.2018.2889981.
[7] S. K. Salman, D. J. King and G. Weller, “New loss of mains detection algorithm for embedded generation using
rate of change of voltage and changes in power factors,” Seventh International Conference on Developments in
Power System Protection (IEE), 2001, pp. 82-85, doi: 10.1049/cp:20010105.
[8] Sung-Il Jang and Kwang-Ho Kim, “An islanding detection method for distributed generations using voltage
unbalance and total harmonic distortion of current,” IEEE Transactions on Power Delivery, vol. 19, no. 2, pp. 745-
752, April 2004, doi: 10.1109/TPWRD.2003.822964.
[9] Sung-Il Jang and Kwang-Ho Kim, “Development of a logical rule-based islanding detection method for distributed
resources,” IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.02CH37309),
2002, pp. 800-806 vol.2, doi: 10.1109/PESW.2002.985117.
[10] H. Abdi, A. Rostami, and N. Rezaei, “A Novel Passive Islanding Detection Scheme for Synchronous-type DG
using Load Angle and Mechanical Power Parameters,” Electric Power Systems Research, vol. 192, p. 106968,
2021, doi: https://doi.org/10.1016/j.epsr.2020.106968.
[11] D. Motter and J. C. M. Vieira, “Improving the islanding detection performance of passive protection by using the
undervoltage block function,” Electric Power Systems Research, vol. 184, p. 106293, 2020, doi:
10.1016/j.epsr.2020.106293.
[12] S. Raza, T. ur Rahman, M. Saeed, and S. Jameel, “Performance analysis of power system parameters for islanding
detection using mathematical morphology,” Ain Shams Engineering Journal, vol. 12, no. 1, pp. 517-527, 2021, doi:
/10.1016/j.asej.2020.07.023.
[13] A. M. I. Mohamad and Y. A. I. Mohamed, “Impedance-Based Analysis and Stabilization of Active DC Distribution
Systems With Positive Feedback Islanding Detection Schemes,” IEEE Transactions on Power Electronics, vol. 33,
no. 11, pp. 9902-9922, 2018, doi: 10.1109/TPEL.2018.2790945.
[14] W. J. Chiang, H. L. Jou, and J. C. Wu, “Active islanding detection method for inverter-based distribution
generation power system,” International Journal of Electrical Power & Energy Systems, vol. 42, no. 1, pp. 158-
166, 2012, doi: 10.1016/j.ijepes.2012.03.038.
[15] A. Samui and S. R. Samantaray, “An active islanding detection scheme for inverter-based DG with frequency
dependent ZIP–Exponential static load model,” International Journal of Electrical Power & Energy Systems, vol.
78, pp. 41-50, 2016, doi: 10.1016/j.ijepes.2015.11.054.
[16] B. Wen, D. Boroyevich, R. Burgos, Z. Shen and P. Mattavelli, “Impedance-Based Analysis of Active Frequency
Drift Islanding Detection for Grid-Tied Inverter System,” IEEE Transactions on Industry Applications, vol. 52, no.
1, pp. 332-341, 2016, doi: 10.1109/TIA.2015.2480847.
Bulletin of Electr Eng & Inf ISSN: 2302-9285 
Hybrid islanding detection method based on the rate of change of frequency … (Hasmaini Mohamad)
3005
[17] S. Murugesan, V. Murali and S. A. Daniel, “Hybrid Analyzing Technique for Active Islanding Detection Based on
d-Axis Current Injection,” IEEE Systems Journal, vol. 12, no. 4, pp. 3608-3617, 2018, doi:
10.1109/JSYST.2017.2730364.
[18] R. Bekhradian, M. Davarpanah and M. Sanaye-Pasand, “Novel Approach for Secure Islanding Detection in
Synchronous Generator Based Microgrids,” IEEE Transactions on Power Delivery, vol. 34, no. 2, pp. 457-466,
2019, doi: 10.1109/TPWRD.2018.2869300.
[19] D. Reigosa, F. Briz, C. Blanco, P. García and J. Manuel Guerrero, “Active Islanding Detection for Multiple
Parallel-Connected Inverter-Based Distributed Generators Using High-Frequency Signal Injection,” IEEE
Transactions on Power Electronics, vol. 29, no. 3, pp. 1192-1199, March 2014, doi: 10.1109/TPEL.2013.2263845.
[20] H. Mohamad, A. N. Ab Salam, N. M. Razali, N. A. Salim, and Z. M. Yasin, “A New Islanding Detection
Technique Based on Passive Parameter using a Combination of Artificial Neural Network and Evolutionary
Programming Algorithm,” Journal of Electrical and Electronic Systems Research, vol. 18, pp. 1-8, 2021.
[21] D. Mlakić, H. R. Baghaee and S. Nikolovski, “A Novel ANFIS-Based Islanding Detection for Inverter-Interfaced
Microgrids,” IEEE Transactions on Smart Grid, vol. 10, no. 4, pp. 4411-4424, 2019, doi:
10.1109/TSG.2018.2859360.
[22] H. R. Baghaee, D. Mlakić, S. Nikolovski and T. Dragicević, “Support Vector Machine-Based Islanding and Grid
Fault Detection in Active Distribution Networks,” IEEE Journal of Emerging and Selected Topics in Power
Electronics, vol. 8, no. 3, pp. 2385-2403, 2020, doi: 10.1109/JESTPE.2019.2916621.
[23] B. P. L. K. Suresh, P. Anusha, Sk. Najma, B. I. Rajkumar, Ch. Rami Reddy, “A passive islanding detection method
for hybrid distributed generation system under balanced islanding,” Indonesian Journal of Electrical Engineering
and Computer Science, vol. 14, no. 1, pp. 9-19, 2019, doi: 10.11591/ijeecs.v14.i1.pp9-19.
[24] V. Menon and M. H. Nehrir, “A Hybrid Islanding Detection Technique Using Voltage Unbalance and Frequency
Set Point,” IEEE Transactions on Power Systems, vol. 22, no. 1, pp. 442-448, 2007, doi:
10.1109/TPWRS.2006.887892.
[25] P. Mahat, Z. Chen and B. Bak-Jensen, “A Hybrid Islanding Detection Technique Using Average Rate of Voltage
Change and Real Power Shift,” IEEE Transactions on Power Delivery, vol. 24, no. 2, pp. 764-771, April 2009, doi:
10.1109/TPWRD.2009.2013376.
[26] M. Mohiti, Z. Mahmoodzadeh and M. Vakilian, “A hybrid micro grid islanding detection method,” 13th
International Conference on Environment and Electrical Engineering (EEEIC), 2013, pp. 342-347, doi:
10.1109/EEEIC-2.2013.6737933.
[27] R. Zamani, M. E. Hamedani Golshan, H. Haes Alhelou, and N. Hatziargyriou, “A novel hybrid islanding detection
method using dynamic characteristics of synchronous generator and signal processing technique,” Electric Power
Systems Research, vol. 175, p. 105911, 2019, doi: 10.1016/j.epsr.2019.105911.
[28] G. Wang, F. Gao, J. Liu, Q. Li and Y. Zhao, “Design consideration and performance analysis of a hybrid islanding
detection method combining voltage unbalance/total harmonic distortion and bilateral reactive power variation,”
CPSS Transactions on Power Electronics and Applications, vol. 5, no. 1, pp. 86-100, 2020, doi:
10.24295/CPSSTPEA.2020.00008.
[29] A. Rostami, A. Jalilian, M. T. Hagh, K. M. Muttaqi and J. Olamaei, “Islanding Detection of Distributed Generation
Based on Rate of Change of Exciter Voltage With Circuit Breaker Switching Strategy,” IEEE Transactions on
Industry Applications, vol. 55, no. 1, pp. 954-963, 2019, doi: 10.1109/TIA.2018.2868547.
[30] S. D. Kermany, M. Joorabian, S. Deilami and M. A. S. Masoum, “Hybrid Islanding Detection in Microgrid With
Multiple Connection Points to Smart Grids Using Fuzzy-Neural Network,” IEEE Transactions on Power Systems,
vol. 32, no. 4, pp. 2640-2651, 2017, doi: 10.1109/TPWRS.2016.2617344.
BIOGRAPHIES OF AUTHORS
Hasmaini Mohamad received the B.Eng., M.Eng., and Ph.D. degrees from the University of
Malaya, in 1999, 2004, and 2013, respectively. She started her career as a lecturer in Universiti
Teknologi MARA in 2003 where currently she is an Associate Professor at the School of
Electrical Engineering, College of Engineering. Apart from that, she has published more than
50 journal papers including high impact ISI journals and 20 conference papers. Her major
research interest includes islanding operation of distributed generation, hydro generation, load
sharing technique, and load shedding scheme.
Zuhaila Mat Yasin graduated from Universiti Sains Malaysia with honours degree in
Electrical and Electronics Engineering in 1998. She obtained her MSc degree in 2008 and PhD
degree in 2015 from Universiti Teknologi MARA. She is currently a senior lecturer at
Universiti Teknologi MARA. Her research interest includes power system operation,
optimization, distributed generation, Artificial Intelligence and smart grid system.
 ISSN: 2302-9285
Bulletin of Electr Eng & Inf, Vol. 10, No. 6, December 2021 : 2997 – 3006
3006
Nur Ashida Salim received her PhD in Electrical Engineering from Universiti Teknologi
MARA in 2015, Master in Engineering (Power System & Electrical Energy) from Universiti
Malaya in 2006 and Bachelor in Electrical Engineering (Hons.) from Universiti Teknologi
MARA in 2003. She is currently an Associate Professor at the School of Electrical
Engineering, College of Engineering Universiti Teknologi MARA. Her research includes
power system reliability, power system planning, power system stability, power system asset
management and other related areas. To date, she has published more than 40 journal articles
and many proceeding papers.
Bibi Norasiqin Sheikh Rahimullah obtained her MSC in Electrical Power Engineering from
University of Strathclyde, UK in 1992. She is currently attached with College of Engineering,
Universiti Teknologi MARA, Shah Alam, Selangor, Malaysia as an Associate Professor. She
has authored and co-authored various proceeding and journal papers in electrical engineering
and education field.
Kanendra Naidu received the master’s and Ph.D. degrees in electrical engineering from the
University of Malaya, in 2011 and 2015, respectively. He is currently a Senior Lecturer with
the Universiti Teknologi MARA (UiTM), Shah Alam. His research interest includes electrical
engineering specializing in the implementation of artificial intelligence in power systems. He
also has strong working experience in a variety of evolutionary and swarm-based optimization
techniques, graph theory, wavelet transform, and artificial neural networks.

More Related Content

PDF
A New Hybrid Wavelet Neural Network and Interactive Honey Bee Matting Optimiz...
PDF
J010146169
PDF
ENERGY EFFICIENT ROUTING IN WIRELESS SENSOR NETWORKS BASED ON QOS
PPT
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
PPT
Mg protection 04022018
DOCX
Final Year Project IEEE 2015
PDF
28 16107 paper 088 ijeecs(edit)
PDF
Energy Efficient Clustering Protocol for Wireless Sensor Networks using Parti...
A New Hybrid Wavelet Neural Network and Interactive Honey Bee Matting Optimiz...
J010146169
ENERGY EFFICIENT ROUTING IN WIRELESS SENSOR NETWORKS BASED ON QOS
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
Mg protection 04022018
Final Year Project IEEE 2015
28 16107 paper 088 ijeecs(edit)
Energy Efficient Clustering Protocol for Wireless Sensor Networks using Parti...

What's hot (19)

PDF
Performance of symmetric and asymmetric links in wireless networks
PDF
A transient current based micro grid connected power system protection scheme...
PDF
Energy efficient chaotic whale optimization technique for data gathering in w...
PDF
Resume- EE
PDF
Fault location techniques in smart distribution system
PDF
Microgrid Protection
PDF
05546953
PDF
IRJET- Power Quality Monitoring & Analysis using Smart Multi-Function Meter
PDF
PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAY
PPSX
Presentation, IEEE ENERGY CONVERSION CONGRESS & EXPO 2018
PDF
A Review Paper on Power Consumption Improvements in WSN
PDF
A LOW-ENERGY DATA AGGREGATION PROTOCOL USING AN EMERGENCY EFFICIENT HYBRID ME...
PDF
A Survey- Energy Efficient Techniques in WBAN
PPT
Transient stability analysis of inverter interfaced distributed generators in...
PDF
Genetic Algorithm based Optimal Placement of Distributed Generation Reducing ...
PDF
Ieee pq
PDF
40220140507004
PDF
Frequency Scanning Techniques for Subsynchronous Resonance Screening Analysis
PPSX
Presentation22
Performance of symmetric and asymmetric links in wireless networks
A transient current based micro grid connected power system protection scheme...
Energy efficient chaotic whale optimization technique for data gathering in w...
Resume- EE
Fault location techniques in smart distribution system
Microgrid Protection
05546953
IRJET- Power Quality Monitoring & Analysis using Smart Multi-Function Meter
PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAY
Presentation, IEEE ENERGY CONVERSION CONGRESS & EXPO 2018
A Review Paper on Power Consumption Improvements in WSN
A LOW-ENERGY DATA AGGREGATION PROTOCOL USING AN EMERGENCY EFFICIENT HYBRID ME...
A Survey- Energy Efficient Techniques in WBAN
Transient stability analysis of inverter interfaced distributed generators in...
Genetic Algorithm based Optimal Placement of Distributed Generation Reducing ...
Ieee pq
40220140507004
Frequency Scanning Techniques for Subsynchronous Resonance Screening Analysis
Presentation22
Ad

Similar to Hybrid islanding detection method based on the rate of change of frequency and load impedance (20)

PDF
A Passive Islanding Detection Method for Neutral point clamped Multilevel Inv...
PDF
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
PDF
A novel fault location approach for radial power distribution systems
PDF
An accurate technique for supervising distance relays during power swing
PDF
Active Anti-Islanding Protection For Grid Connected Solar Photovoltaic Power ...
PDF
PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS EQUIPPED WITH DISTRIBUTED GEN...
PPTX
Electrical _engineering_ minor_PPTx.pptx
PDF
Enhanced two-terminal impedance-based fault location using sequence values
PDF
An approach for a multi-stage under-frequency based load shedding scheme for...
PDF
Fault Diagnosis of a High Voltage Transmission Line Using Waveform Matching A...
PDF
Fault Location Of Transmission Line
PDF
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
PDF
A Survey of Fault Tolerance Methods in Wireless Sensor Networks
PDF
Fault diagnosis of a high voltage transmission line using waveform matching a...
PDF
126 a fuzzy rule based approach for islanding
PDF
A comprehensive fuzzy-based scheme for online detection of operational and t...
PDF
A New Under-Frequency Load Shedding Method Using the Voltage Electrical Dista...
PDF
TRANSMISSION LINE HEALTH PREDICTION SYSTEM IN HVDC AND HVAC LINES
PDF
Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...
PDF
FAULT DETECTION SCHEME OF 5 BUS BY ANN AND ANFIS
A Passive Islanding Detection Method for Neutral point clamped Multilevel Inv...
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
A novel fault location approach for radial power distribution systems
An accurate technique for supervising distance relays during power swing
Active Anti-Islanding Protection For Grid Connected Solar Photovoltaic Power ...
PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS EQUIPPED WITH DISTRIBUTED GEN...
Electrical _engineering_ minor_PPTx.pptx
Enhanced two-terminal impedance-based fault location using sequence values
An approach for a multi-stage under-frequency based load shedding scheme for...
Fault Diagnosis of a High Voltage Transmission Line Using Waveform Matching A...
Fault Location Of Transmission Line
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
A Survey of Fault Tolerance Methods in Wireless Sensor Networks
Fault diagnosis of a high voltage transmission line using waveform matching a...
126 a fuzzy rule based approach for islanding
A comprehensive fuzzy-based scheme for online detection of operational and t...
A New Under-Frequency Load Shedding Method Using the Voltage Electrical Dista...
TRANSMISSION LINE HEALTH PREDICTION SYSTEM IN HVDC AND HVAC LINES
Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...
FAULT DETECTION SCHEME OF 5 BUS BY ANN AND ANFIS
Ad

More from journalBEEI (20)

PDF
Square transposition: an approach to the transposition process in block cipher
PDF
Hyper-parameter optimization of convolutional neural network based on particl...
PDF
Supervised machine learning based liver disease prediction approach with LASS...
PDF
A secure and energy saving protocol for wireless sensor networks
PDF
Plant leaf identification system using convolutional neural network
PDF
Customized moodle-based learning management system for socially disadvantaged...
PDF
Understanding the role of individual learner in adaptive and personalized e-l...
PDF
Prototype mobile contactless transaction system in traditional markets to sup...
PDF
Wireless HART stack using multiprocessor technique with laxity algorithm
PDF
Implementation of double-layer loaded on octagon microstrip yagi antenna
PDF
The calculation of the field of an antenna located near the human head
PDF
Exact secure outage probability performance of uplinkdownlink multiple access...
PDF
Design of a dual-band antenna for energy harvesting application
PDF
Transforming data-centric eXtensible markup language into relational database...
PDF
Key performance requirement of future next wireless networks (6G)
PDF
Noise resistance territorial intensity-based optical flow using inverse confi...
PDF
Modeling climate phenomenon with software grids analysis and display system i...
PDF
An approach of re-organizing input dataset to enhance the quality of emotion ...
PDF
Parking detection system using background subtraction and HSV color segmentation
PDF
Quality of service performances of video and voice transmission in universal ...
Square transposition: an approach to the transposition process in block cipher
Hyper-parameter optimization of convolutional neural network based on particl...
Supervised machine learning based liver disease prediction approach with LASS...
A secure and energy saving protocol for wireless sensor networks
Plant leaf identification system using convolutional neural network
Customized moodle-based learning management system for socially disadvantaged...
Understanding the role of individual learner in adaptive and personalized e-l...
Prototype mobile contactless transaction system in traditional markets to sup...
Wireless HART stack using multiprocessor technique with laxity algorithm
Implementation of double-layer loaded on octagon microstrip yagi antenna
The calculation of the field of an antenna located near the human head
Exact secure outage probability performance of uplinkdownlink multiple access...
Design of a dual-band antenna for energy harvesting application
Transforming data-centric eXtensible markup language into relational database...
Key performance requirement of future next wireless networks (6G)
Noise resistance territorial intensity-based optical flow using inverse confi...
Modeling climate phenomenon with software grids analysis and display system i...
An approach of re-organizing input dataset to enhance the quality of emotion ...
Parking detection system using background subtraction and HSV color segmentation
Quality of service performances of video and voice transmission in universal ...

Recently uploaded (20)

PDF
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PDF
Design Guidelines and solutions for Plastics parts
PPTX
communication and presentation skills 01
PDF
Categorization of Factors Affecting Classification Algorithms Selection
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PPTX
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
PPT
Total quality management ppt for engineering students
PPTX
Current and future trends in Computer Vision.pptx
PDF
737-MAX_SRG.pdf student reference guides
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
PPTX
Nature of X-rays, X- Ray Equipment, Fluoroscopy
PDF
SMART SIGNAL TIMING FOR URBAN INTERSECTIONS USING REAL-TIME VEHICLE DETECTI...
PPTX
Artificial Intelligence
PDF
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
PDF
August 2025 - Top 10 Read Articles in Network Security & Its Applications
PDF
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
PDF
BIO-INSPIRED ARCHITECTURE FOR PARSIMONIOUS CONVERSATIONAL INTELLIGENCE : THE ...
PDF
Soil Improvement Techniques Note - Rabbi
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
Design Guidelines and solutions for Plastics parts
communication and presentation skills 01
Categorization of Factors Affecting Classification Algorithms Selection
R24 SURVEYING LAB MANUAL for civil enggi
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
Total quality management ppt for engineering students
Current and future trends in Computer Vision.pptx
737-MAX_SRG.pdf student reference guides
Automation-in-Manufacturing-Chapter-Introduction.pdf
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
Nature of X-rays, X- Ray Equipment, Fluoroscopy
SMART SIGNAL TIMING FOR URBAN INTERSECTIONS USING REAL-TIME VEHICLE DETECTI...
Artificial Intelligence
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
August 2025 - Top 10 Read Articles in Network Security & Its Applications
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
BIO-INSPIRED ARCHITECTURE FOR PARSIMONIOUS CONVERSATIONAL INTELLIGENCE : THE ...
Soil Improvement Techniques Note - Rabbi

Hybrid islanding detection method based on the rate of change of frequency and load impedance

  • 1. Bulletin of Electrical Engineering and Informatics Vol. 10, No. 6, December 2021, pp. 2997~3006 ISSN: 2302-9285, DOI: 10.11591/eei.v10i6.3246 2997 Journal homepage: http://beei.org Hybrid islanding detection method based on the rate of change of frequency and load impedance Hasmaini Mohamad, Zuhaila Mat Yasin, Nur Ashida Salim, Bibi Norasiqin Sheikh Rahimullah, Kanendra Naidu School of Electrical Engineering, College of Engineering, Universiti Teknologi MARA, 40450 Shah Alam, Selangor, Malaysia Article Info ABSTRACT Article history: Received Jun 7, 2021 Revised Aug 24, 2021 Accepted Oct 8, 2021 Interconnection of distributed generation (DG) in distribution system will result in formation of islands in the event of loss of main supply. This scenario is harmful to the power system, hence quick detection is critical to halt the formation of islands. Among the common passive and active detection methods available, the hybrid detection method is identified as the most reliable method. This paper proposes a new hybrid method using the combination of passive and active technique which is the rate of change of frequency (ROCOF) and load impedance, respectively. The passive method works when the value of ROCOF exceeds the threshold value which is set at 0.3Hz/s. The active method works when it detects low value of ROCOF and immediately inject a pre-specified load into the system to increase the ROCOF value up to its threshold value. Simulation study on different case studies is carried out on distribution test system to evaluate the performance of the proposed method. Results show that this method is effective in detecting any events that could result in islanding. Keywords: Distributed generation Islanding detection Load impedance Rate of change of frequency This is an open access article under the CC BY-SA license. Corresponding Author: Hasmaini Mohamad School of Electrical Engineering, College of Engineering Universiti Teknologi MARA, Shah Alam, Selangor, Malaysia Email: hasmaini@uitm.edu.my 1. INTRODUCTION Distributed generation (DG) is a small-scale power generation technology installed in the vicinity of the end users in order to produce electricity. DGs cover any net metered or commercial-scale generation that is connected to the grid at the distribution level. DGs are important as they offer many benefits to the power system such as enhancing the efficiency of electricity supply, reducing distribution and transmission losses and delivering clean and sustainable power to the customers. However, there is a technical issue called islanding which occurs when DG continues supplying power to a part of the distribution system eventhough the connection to the grid is interrupted during catastrophic event. Islanding can be either intentional or unintentional islanding. Intentional islanding is a properly planned process to improve the system reliability where DG continuously supply power to critical loads in the event of power supply failure from the grid. Readiness of an advanced control scheme in ensuring a smooth changes from grid connected to islanding mode of operation is required. With the controller in place, the grid can sectionalize itself by allowing the DG to supply the islands’ load until the main power supply is re-established. On the other hand, unintentional islanding may result in damaging the DG since it operates without proper control mechanism for islanding [1]. Similarly, this is hazardous for utility workers working in the distribution system who are unaware that the network is still operational. This situation usually occurs
  • 2.  ISSN: 2302-9285 Bulletin of Electr Eng & Inf, Vol. 10, No. 6, December 2021 : 2997 – 3006 2998 when the power is being fed via the DG to the system during loss of main supply form the grid . The exposure to live system can be fatal to the utility workers [2]. Therefore, DG’s protection scheme has to detect the islanding situation and immediately disconnect DG from the network. This is referred to as islanding detection method. Islanding detection methods for both intentional and unintentional islanding are generally classified into local and remote methods. Local method can be further categorized into active and passive methods while remote method is based on communication between the utility and the DGs [3]. Passive method identifies islanding by monitoring the parameters such as frequency, voltage, current, active power, reactive power and harmonic distortion. Many techniques were subsequently introduced with various combination of parameters and settings such as rate of change of positive and negative sequence component [4], rate of change of frequency (ROCOF) [5], rate of change of output power [6], rate of change of voltage and changes in power factors [7], voltage unbalance and total harmonic distortion of current [8] and combinations of four passive parameters [9]. The very recent research considered load angle and mechanical power parameters [10], undervoltage block function [11] and sensitivity of different passive parameters [12]. When the distribution system is islanded, these parameters are significantly affected. Detection relies on the threshold setting for each parameter which will discriminate islanding and non-islanding type of disturbance. However, islanding is difficult to detect when there is minimal power mismatch between generation and load in the islanded system. If the threshold values is too high, islanding might not be detected while if the threshold values is too low, it could result in false tripping of DG. The weakness of the passive method can be complemented by active method, which can detect the occurrences of islanding even under zero power imbalance between generation and load. Active method identifies a grid failure or islanding by injecting a small signal into the system. This method is applicable for inverter based DGs. Methods such as active positive feedback islanding detection schemes [13], DC/AC inverter acting as virtual capacitor [14], frequency dependent ZIP–Exponential static load model [15], impedance-based analysis of the active frequency drift (AFD) [16], d-axis current injection [17], islanding detection index based on resistance seen from the SSSG terminal with respect to the angular frequency [18] and high-frequency signal injection for multiple parallel-connected inverters based DG [19]. These methods outperforms the passive method but are rather expensive and pose power quality deterioration. The recent trend of islanding detection using intelligent based and hybrid methods where both associated with passive and/or active method. Intelligent method is based on the application of artificial neural network (ANN), fuzzy logic control (FLC), evolutionary programming (EP), decision tree (DT) [20], adaptive neuro fuzzy inference system (ANFIS) [21], and support vector machine (SVM) [22]. These methods help to classify islanding/non islanding events based on training and testing data obtained from the simulation/experiment conducted on the test system. Testing on different types of faults based on passive parameter is rigorously carried out to generate huge amount of data. As a result, the classification is accurate with a nearly zero non-detection zone (NDZ) and detection is reached in a very short time. However, any changes made on the test system such as network expansion, will cause the need of a new set training data for classification process. Introduction of hybrid islanding detection method [23] can overcome the shortcomings in passive or active method approach. It combines the advantages of both method to offer more effective result compared to passive/active method alone. Hybrid method proposed in the literatures considered combination of voltage unbalance and frequency set point [24], average rate of voltage change and real power shift [25], voltage unbalance (VU) and high-frequency (HF) impedance [26], dynamic characteristics of synchronous generator and signal processing technique [27], voltage unbalance and total harmonic distortion (VU/THD) and bilateral reactive power variation (BRPV) [28], rate of change of exciter voltage (RCEV) and open-close circuit breaker (OCCB) at a DG connection point [29]. In addition, there is also a new approach of hybrid method using combination of active, passive and communication technique [30]. Each method has different detection performance depending on the chosen combination. The active technique is normally adopted when passive technique alone is unable to detect islanding scenario particularly during minimal power mismatch. So far, the hybrid method employs the combination of a new type of passive method with an advanced active method. However, the research work on hybrid method using the ROCOF which is commonly adopted by utility companies has not been explored in detail. This is important as a comprehensive investigation is required on the practicality of applying proposed hybrid method to existing islanding detection technique. This paper proposes a new hybrid method which combines ROCOF as the passive method and injection of load impedance as the active method. ROCOF is chosen since it is commonly used as the main protection system in distribution system. ROCOF operates when it detects islanding based on the rate of changes of frequency that exceeds the threshold limit. The load impedance is injected to the system when it detects a small value of ROCOF. The injection will increase the value of ROCOF up to the specified limit. This will ensure that the islanding detection is successful even there is a small power mismatch. The main
  • 3. Bulletin of Electr Eng & Inf ISSN: 2302-9285  Hybrid islanding detection method based on the rate of change of frequency … (Hasmaini Mohamad) 2999 contributions of this studies are: 1) quick islanding detection which is less than 20ms, 2) effective detection of islanding and non-islanding event, and 3) employs a simple method using standard parameter measurement. This method is modelled and simulated using PSCAD/EMTDC simulation tools. In order to evaluate this method, there are seven case studies introduced which are loss of main, fault at adjacent line (single line to ground fault, line to line to ground fault, and three phase fault) and fault near to DG (single line to ground fault, line to line to ground fault, and three phase fault). This paper is organized as follows in which the proposed hybrid detection method and test system are elaborated in section 2, result and discussion are explained in section 3 and finally conclusion is drawn in section 4. 2. RESEARCH METHOD The hybrid islanding detection method applied in this study uses ROCOF as a passive method and the injection of load impedance as the active method. The modelling of the proposed method and test system are described in the following section. 2.1. Modeling proposed method Two modules comprising of active and passive method are developed for the proposed hybrid method as depicted in Figure 1. Passive and active module are located in the DG protection unit and at the generator bus, respectively. Figure 1. Principal operation of the proposed method The development concept of the hybrid method is shown in Figure 2. The passive method module is used to continuously monitor the ROCOF value which is taken from the speed measurement of DG. The proposed method detects any islanding event whenever the ROCOF value exceeds the specified threshold. A tripping signal is subsequently sent to circuit breaker of the DG’s protection system thus prohibiting the DG from supplying the load. Active method module will only be activated to inject an additional load to the system whenever it detects ROCOF value less than the threshold value. Details of the islanding detection process is described in Figure 3. Figure 2. Block diagram of the proposed method
  • 4.  ISSN: 2302-9285 Bulletin of Electr Eng & Inf, Vol. 10, No. 6, December 2021 : 2997 – 3006 3000 The process starts with the determination of frequency from the speed measurement of DG. Then, derivative component is used to calculate the rate of change of frequency (ROCOF). The active and passive method are designed specifically for detection purposes considering the ROCOF as the input. The script for designing the module is written using FORTRAN programming language. The passive module is designed based on the comparison between the calculated ROCOF value and ROCOF threshold setting. Detection module will be triggered once the ROCOF value surpass the threshold value. The common setting for ROCOF threshold is between 0.1Hz/s to 1Hz/s [12]. In this study, the threshold value of 0.3Hz/s is used. Meanwhile, the output of the active method module will send a signal to inject a load with a value of 330kW to the system when the magnitude of the calculated ROCOF is less than 0.3Hz/s. The value of the injected load cannot be too high because it will cause system interference. The value of 330kW is deemed suitable for the system is determined from several tests conducted for LOM as recorded in Table 1. The value of active load highly depends on the power imbalance the moment system experiences disturbance. Lower power imbalance of less than 270MW, would require an injection of a large load value of 540kW. High value of load is infeasible for islanding detection purposes as it would incur high cost. The load injection for power imbalance greater than 280MW would result in a steep increase of ROCOF value to more than 0.3Hz/s, hence triggering islanding detection mechanism and subsequently the DG breaker is tripped. Figure 3. Flow chart of the proposed islanding detection method Table 1. Analysis of the islanding detection on different range of ∆P for various load values Range of ∆P(kW) Load(kW) Detect Islanding Preferable 90–270 150kW × 330kW × 540kW ✓ Prefer 280–430 150kW × 330kW ✓ Prefer 540kW ✓ 440–540 150kW ✓ Prefer 330kW ✓ 540kW ✓ 2.2. Test network The test system shown in Figure 4 was modelled using PSCAD software. The 7-bus system operates at 50Hz, 33kV, and includes a 100MVA generator as main supply. As shown in the Figure 4, there are two step-down transformers of 33/11 kV and 11/3.3 kV rated at 20MVA and 2MVA respectively. The 2MVA
  • 5. Bulletin of Electr Eng & Inf ISSN: 2302-9285  Hybrid islanding detection method based on the rate of change of frequency … (Hasmaini Mohamad) 3001 transformer is placed at the end of the distribution line where DG is located. The DG is modelled as a hydro turbine generator rated at 2 MVA. The loads connected to the system are static loads. Figure 4. 7-bus test system 3. RESULT AND ANALYSIS In order to evaluate the effectiveness of the proposed method, three case studies are simulated based on the 7-bus test system. The three case studies are: − Case 1: Loss of main − Case 2: Various fault at line connected to DG (DG Line) − Case 3: Various fault at line adjacent to DG at line 4-5 The faults considered in this study are single line to ground fault, line to line to ground fault, and three phase fault. Case 1 which is loss of main, a signal is sent to open breaker A to disconnect the main supply at t = 10 seconds. Case 2, three different types of faults are applied at line connected to DG as indicated in Figure 4. As for case 3, three different types of faults are applied at adjacent line (line 4-5) as indicated in Figure 4. Results for the three case studies are tabulated in Table 2. Table 2. Breaker trip status for all three cases Cases Type of Events Breaker B Condition 1 Loss of main TRIP 2 Single line to ground fault TRIP Line to line to ground fault TRIP Three phase faults TRIP 3 Single line to ground fault NOT TRIP Line to line to ground fault NOT TRIP Three phase faults NOT TRIP 3.1. Loss of main The system frequency immediately increases in response to the disconnection of main grid from the distribution network. Based on Figure 5, the frequency of DG increases until it hits 71Hz then gradually drops to 30Hz. The frequency increment contributes to the increment of the ROCOF value. As can be seen in Figure 6, the ROCOF reading at t=10 seconds exceeds the ROCOF threshold which has been set at 0.3Hz/s. As a result, a signal is sent to trip the breaker B. The islanding detection mechanism verifies that loss of main is islanding scenario and proceeds to trip breaker B causing the DG to shut down. The change of active power due to the islanding caused the frequency drops and unstable. Only passive method works for this case since the ROCOF value is greater than the threshold value. The high value of frequency and df/dt is due to a large power imbalance between generation and load the moment system is disconnected from the main.
  • 6.  ISSN: 2302-9285 Bulletin of Electr Eng & Inf, Vol. 10, No. 6, December 2021 : 2997 – 3006 3002 Figure 5. Frequency of DG for loss of main Figure 6. ROCOF measurement for loss of main 3.2. Fault at DG line As mentioned earlier, three types of faults are simulated which are three phase fault, single line to ground fault, and line to line to ground fault. The fault is simulated at t=10 seconds with 0.05 seconds of fault duration. For all type of faults, the reading of ROCOF exceeds the ROCOF’s threshold value which causes breaker B to trip. Figures 7 and 8 shows the frequency response and ROCOF value respectively when a three-phase fault is applied to the system. Eventhough the fault duration is very short, huge impact to the system frequency can be seen following the fault. The response is almost similar to the response due to loss of main. The hybrid module manages to successfully detect the islanding scenario due to the fault location location is near to DG which contributes to the high ROCOF value. Figure 7. Frequency of DG for three phase fault Figure 8. ROCOF measurement for three phase fault 3.3. Fault at adjacent line (line 4-5) The adjacent line is located at the same bus with the DG line. The fault setting is set similar to case 2. Results show that breaker B does not trip for all three types of faults. The system frequency stays at 50Hz following the fault as shown in Figure 9 (a). This causes the ROCOF to remain at zero value even after fault as shown in Figure 9 (b). The fault does not impact the system since it is applied at the load side as it does not interfere the power flow from power supply to DG. (a) (b) Figure 9. These figures are; (a) frequency, (b) ROCOF measurement for three phase faults at adjacent line1 3.4. Comparative analysis Comparative analysis is carried out to analyse the advantage of having an active method in the proposed hybrid method. Simulation is performed for case 1 by using two different detection method: 1) passive method and 2) hybrid method module. The simulation is carried out for a small value of power mismatch, ∆P. Based on results shown in Figure 10, the reading of ROCOF for passive method does not even
  • 7. Bulletin of Electr Eng & Inf ISSN: 2302-9285  Hybrid islanding detection method based on the rate of change of frequency … (Hasmaini Mohamad) 3003 reach the threshold value since ∆P is small. However, with the proposed hybrid method which combines passive and active method, the injection of load impedance from active method pushes the reading of ROCOF to reach the threshold value. As a result, the proposed method able to detect islanding for a small value of power imbalance as recorded in Table 3. This proves that the hybrid detection method gives better performance than passive method in detecting islanding event. Moreover, non-detection zone (NDZ), which is one of the most important criteria for islanding detection method is also assessed in identifying the area that both methods fail to detect islanding scenario. Rigorous testing is carried out to identify an accurate NDZ for both methods. The NDZ shown in Figure 11 obviously differentiate the accuracy of detection for both methods where the hybrid method has a smaller NDZ compared to the passive method. The result indicates that more islanding events can be detected by hybrid method compared to passive method, thus increasing the islanding detection reliability. In terms of detection time, the proposed hybrid method would detect islanding event in 35 ms and 70 ms for passive and hybrid method respectively. This indicates that the proposed method is better compared to other methods listed in Table 4. However, in real world application, the time taken may vary accordingly depending on the signal and communication delay. Figure 10. Comparison of ROCOF between hybrid method and passive method Table 3. Result of loss of main with hybrid and passive method Cases Breaker B Condition Loss of main Hybrid Method TRIP Passive Method NOT TRIP Figure 11. NDZ for ROCOF and hybrid methods Table 4. Comparative analysis on islanding detection time Detection Method Detection time (ms) Undervoltage block function [11] 136.2 Voltage Unbalance and Total Harmonic Distortion of Current [8] 129 Rate of Change of Exciter Voltage with Circuit Breaker Switching Strategy [29] 100 (passive) 300 (hybrid) Proposed method 35 (passive) 70 (hybrid)
  • 8.  ISSN: 2302-9285 Bulletin of Electr Eng & Inf, Vol. 10, No. 6, December 2021 : 2997 – 3006 3004 4. CONCLUSION This paper presents a hybrid islanding detection method by using the rate of change of frequency (ROCOF) and the injection of load impedance. Several case studies have been simulated on the test distribution system to assess the effectiveness of the proposed method. Results proved that the method effectively detected all event that could result in islanding. Comparison studies including the NDZ assessment with the passive method further validated the islanding detection performance of the hybrid method. ACKNOWLEDGEMENTS This work is supported by the Ministry of Higher Education and Universiti Teknologi MARA, Malaysia under FRGS research grant (Grant Code: 600-IRMI/FRGS 5/3(090/2019)). REFERENCES [1] J. R. Reddy, A. Pandian, R. Dhanasekharan, Ch. R. Reddy, B. P. Lakshmi, “Islanding detection of integrated distributed generation with advanced controller,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 17, no. 3, pp. 1626-1631, 2020, doi: 10.11591/ijeecs.v17.i3.pp1626-1631. [2] S. Raza, H. Amjad, M. Umer and A. Khalid, “Analysis of power system parameters for islanding detection using wavelet transform,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 17, no. 3, pp. 1184- 1193, 2020, doi: 10.11591/ijeecs.v17.i3.pp1184-1193. [3] J. A. Laghari, H. Mokhlis, M. Karimi, A. H. A. Bakar, and H. Mohamad, “Computational Intelligence based techniques for islanding detection of distributed generation in distribution network: A review,” Energy Conversion and Management, vol. 88, pp. 139-152, 2014, doi: 10.1016/j.enconman.2014.08.024. [4] A. Sharma and R. Sunitha, “Unintentional islanding detection in microgrid,” International Conference on Energy, Communication, Data Analytics and Soft Computing ICECDS, 2017, pp. 2519-2523, doi: 10.1109/ICECDS.2017.8389907. [5] J. R. Reddy and A. Pandian, “Improved ROCOF relay for islanding detection of solar distributed generation,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 14, no. 3, pp. 1105-1113, 2019, doi: 10.11591/ijeecs.v14.i3.pp1105-1113. [6] S. Nikolovski, H. R. Baghaee and D. Mlakić, “Islanding Detection of Synchronous Generator-Based DGs using Rate of Change of Reactive Power,” EEE Systems Journal, vol. 13, no. 4, pp. 4344-4354, 2019, doi: 10.1109/JSYST.2018.2889981. [7] S. K. Salman, D. J. King and G. Weller, “New loss of mains detection algorithm for embedded generation using rate of change of voltage and changes in power factors,” Seventh International Conference on Developments in Power System Protection (IEE), 2001, pp. 82-85, doi: 10.1049/cp:20010105. [8] Sung-Il Jang and Kwang-Ho Kim, “An islanding detection method for distributed generations using voltage unbalance and total harmonic distortion of current,” IEEE Transactions on Power Delivery, vol. 19, no. 2, pp. 745- 752, April 2004, doi: 10.1109/TPWRD.2003.822964. [9] Sung-Il Jang and Kwang-Ho Kim, “Development of a logical rule-based islanding detection method for distributed resources,” IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.02CH37309), 2002, pp. 800-806 vol.2, doi: 10.1109/PESW.2002.985117. [10] H. Abdi, A. Rostami, and N. Rezaei, “A Novel Passive Islanding Detection Scheme for Synchronous-type DG using Load Angle and Mechanical Power Parameters,” Electric Power Systems Research, vol. 192, p. 106968, 2021, doi: https://doi.org/10.1016/j.epsr.2020.106968. [11] D. Motter and J. C. M. Vieira, “Improving the islanding detection performance of passive protection by using the undervoltage block function,” Electric Power Systems Research, vol. 184, p. 106293, 2020, doi: 10.1016/j.epsr.2020.106293. [12] S. Raza, T. ur Rahman, M. Saeed, and S. Jameel, “Performance analysis of power system parameters for islanding detection using mathematical morphology,” Ain Shams Engineering Journal, vol. 12, no. 1, pp. 517-527, 2021, doi: /10.1016/j.asej.2020.07.023. [13] A. M. I. Mohamad and Y. A. I. Mohamed, “Impedance-Based Analysis and Stabilization of Active DC Distribution Systems With Positive Feedback Islanding Detection Schemes,” IEEE Transactions on Power Electronics, vol. 33, no. 11, pp. 9902-9922, 2018, doi: 10.1109/TPEL.2018.2790945. [14] W. J. Chiang, H. L. Jou, and J. C. Wu, “Active islanding detection method for inverter-based distribution generation power system,” International Journal of Electrical Power & Energy Systems, vol. 42, no. 1, pp. 158- 166, 2012, doi: 10.1016/j.ijepes.2012.03.038. [15] A. Samui and S. R. Samantaray, “An active islanding detection scheme for inverter-based DG with frequency dependent ZIP–Exponential static load model,” International Journal of Electrical Power & Energy Systems, vol. 78, pp. 41-50, 2016, doi: 10.1016/j.ijepes.2015.11.054. [16] B. Wen, D. Boroyevich, R. Burgos, Z. Shen and P. Mattavelli, “Impedance-Based Analysis of Active Frequency Drift Islanding Detection for Grid-Tied Inverter System,” IEEE Transactions on Industry Applications, vol. 52, no. 1, pp. 332-341, 2016, doi: 10.1109/TIA.2015.2480847.
  • 9. Bulletin of Electr Eng & Inf ISSN: 2302-9285  Hybrid islanding detection method based on the rate of change of frequency … (Hasmaini Mohamad) 3005 [17] S. Murugesan, V. Murali and S. A. Daniel, “Hybrid Analyzing Technique for Active Islanding Detection Based on d-Axis Current Injection,” IEEE Systems Journal, vol. 12, no. 4, pp. 3608-3617, 2018, doi: 10.1109/JSYST.2017.2730364. [18] R. Bekhradian, M. Davarpanah and M. Sanaye-Pasand, “Novel Approach for Secure Islanding Detection in Synchronous Generator Based Microgrids,” IEEE Transactions on Power Delivery, vol. 34, no. 2, pp. 457-466, 2019, doi: 10.1109/TPWRD.2018.2869300. [19] D. Reigosa, F. Briz, C. Blanco, P. García and J. Manuel Guerrero, “Active Islanding Detection for Multiple Parallel-Connected Inverter-Based Distributed Generators Using High-Frequency Signal Injection,” IEEE Transactions on Power Electronics, vol. 29, no. 3, pp. 1192-1199, March 2014, doi: 10.1109/TPEL.2013.2263845. [20] H. Mohamad, A. N. Ab Salam, N. M. Razali, N. A. Salim, and Z. M. Yasin, “A New Islanding Detection Technique Based on Passive Parameter using a Combination of Artificial Neural Network and Evolutionary Programming Algorithm,” Journal of Electrical and Electronic Systems Research, vol. 18, pp. 1-8, 2021. [21] D. Mlakić, H. R. Baghaee and S. Nikolovski, “A Novel ANFIS-Based Islanding Detection for Inverter-Interfaced Microgrids,” IEEE Transactions on Smart Grid, vol. 10, no. 4, pp. 4411-4424, 2019, doi: 10.1109/TSG.2018.2859360. [22] H. R. Baghaee, D. Mlakić, S. Nikolovski and T. Dragicević, “Support Vector Machine-Based Islanding and Grid Fault Detection in Active Distribution Networks,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, no. 3, pp. 2385-2403, 2020, doi: 10.1109/JESTPE.2019.2916621. [23] B. P. L. K. Suresh, P. Anusha, Sk. Najma, B. I. Rajkumar, Ch. Rami Reddy, “A passive islanding detection method for hybrid distributed generation system under balanced islanding,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 14, no. 1, pp. 9-19, 2019, doi: 10.11591/ijeecs.v14.i1.pp9-19. [24] V. Menon and M. H. Nehrir, “A Hybrid Islanding Detection Technique Using Voltage Unbalance and Frequency Set Point,” IEEE Transactions on Power Systems, vol. 22, no. 1, pp. 442-448, 2007, doi: 10.1109/TPWRS.2006.887892. [25] P. Mahat, Z. Chen and B. Bak-Jensen, “A Hybrid Islanding Detection Technique Using Average Rate of Voltage Change and Real Power Shift,” IEEE Transactions on Power Delivery, vol. 24, no. 2, pp. 764-771, April 2009, doi: 10.1109/TPWRD.2009.2013376. [26] M. Mohiti, Z. Mahmoodzadeh and M. Vakilian, “A hybrid micro grid islanding detection method,” 13th International Conference on Environment and Electrical Engineering (EEEIC), 2013, pp. 342-347, doi: 10.1109/EEEIC-2.2013.6737933. [27] R. Zamani, M. E. Hamedani Golshan, H. Haes Alhelou, and N. Hatziargyriou, “A novel hybrid islanding detection method using dynamic characteristics of synchronous generator and signal processing technique,” Electric Power Systems Research, vol. 175, p. 105911, 2019, doi: 10.1016/j.epsr.2019.105911. [28] G. Wang, F. Gao, J. Liu, Q. Li and Y. Zhao, “Design consideration and performance analysis of a hybrid islanding detection method combining voltage unbalance/total harmonic distortion and bilateral reactive power variation,” CPSS Transactions on Power Electronics and Applications, vol. 5, no. 1, pp. 86-100, 2020, doi: 10.24295/CPSSTPEA.2020.00008. [29] A. Rostami, A. Jalilian, M. T. Hagh, K. M. Muttaqi and J. Olamaei, “Islanding Detection of Distributed Generation Based on Rate of Change of Exciter Voltage With Circuit Breaker Switching Strategy,” IEEE Transactions on Industry Applications, vol. 55, no. 1, pp. 954-963, 2019, doi: 10.1109/TIA.2018.2868547. [30] S. D. Kermany, M. Joorabian, S. Deilami and M. A. S. Masoum, “Hybrid Islanding Detection in Microgrid With Multiple Connection Points to Smart Grids Using Fuzzy-Neural Network,” IEEE Transactions on Power Systems, vol. 32, no. 4, pp. 2640-2651, 2017, doi: 10.1109/TPWRS.2016.2617344. BIOGRAPHIES OF AUTHORS Hasmaini Mohamad received the B.Eng., M.Eng., and Ph.D. degrees from the University of Malaya, in 1999, 2004, and 2013, respectively. She started her career as a lecturer in Universiti Teknologi MARA in 2003 where currently she is an Associate Professor at the School of Electrical Engineering, College of Engineering. Apart from that, she has published more than 50 journal papers including high impact ISI journals and 20 conference papers. Her major research interest includes islanding operation of distributed generation, hydro generation, load sharing technique, and load shedding scheme. Zuhaila Mat Yasin graduated from Universiti Sains Malaysia with honours degree in Electrical and Electronics Engineering in 1998. She obtained her MSc degree in 2008 and PhD degree in 2015 from Universiti Teknologi MARA. She is currently a senior lecturer at Universiti Teknologi MARA. Her research interest includes power system operation, optimization, distributed generation, Artificial Intelligence and smart grid system.
  • 10.  ISSN: 2302-9285 Bulletin of Electr Eng & Inf, Vol. 10, No. 6, December 2021 : 2997 – 3006 3006 Nur Ashida Salim received her PhD in Electrical Engineering from Universiti Teknologi MARA in 2015, Master in Engineering (Power System & Electrical Energy) from Universiti Malaya in 2006 and Bachelor in Electrical Engineering (Hons.) from Universiti Teknologi MARA in 2003. She is currently an Associate Professor at the School of Electrical Engineering, College of Engineering Universiti Teknologi MARA. Her research includes power system reliability, power system planning, power system stability, power system asset management and other related areas. To date, she has published more than 40 journal articles and many proceeding papers. Bibi Norasiqin Sheikh Rahimullah obtained her MSC in Electrical Power Engineering from University of Strathclyde, UK in 1992. She is currently attached with College of Engineering, Universiti Teknologi MARA, Shah Alam, Selangor, Malaysia as an Associate Professor. She has authored and co-authored various proceeding and journal papers in electrical engineering and education field. Kanendra Naidu received the master’s and Ph.D. degrees in electrical engineering from the University of Malaya, in 2011 and 2015, respectively. He is currently a Senior Lecturer with the Universiti Teknologi MARA (UiTM), Shah Alam. His research interest includes electrical engineering specializing in the implementation of artificial intelligence in power systems. He also has strong working experience in a variety of evolutionary and swarm-based optimization techniques, graph theory, wavelet transform, and artificial neural networks.