WELCOME
SYMMETRICAL FAULT DETECTION DURING
POWER SWING
ABSTRACT
• If a fault occurs during a power swing, it should be detected
and the unblocking function should be invoked to clear the
fault as soon as possible.
• Distance relays are getting blocked during power swing to
ensure reliability of the power system.
• Due to the symmetric nature of signals during the power
swing, symmetrical faults are difficult to be detected.
• In this paper, a differential power-based fault detection
technique is proposed for the detection of symmetrical faults
during power swings.
Cont…
• The differential power is calculated from the difference in
predicted and actual samples of voltage and current.
• The predicted voltage and current samples are obtained
using the auto regression technique.
• The proposed method is tested for different fault conditions
and the results are compared with the available method.
• The proposed method is found to identify symmetrical faults
accurately during slow and fast power swings for different
power systems.
Literature survey
• Power Swing which is basically caused by the large disturbances in
the power system which if not blocked could cause wrong operation
of the distance relay and can generates wrong or undesired tripping
of the transmission line circuit breaker.
• To prevent unwanted distance or other relay operation during a
Power Swing, we did fundamental studies of traditional and
advanced detection and prevention methods.
• However, many studies have shown that undesirable zone 3
distance relay operations have initiated tripping which lead to
cascading events and finally wide-area voltage collapse (Jonsson
and Daadler, 2003; Kim et al, 2005; Jin and Sindhu, 2008 ; Lim et al,
2008).
Cont…
• To improve reliability of relay operation, adaptive scheme for
distance protection has been introduced by many researches
(Horowitz, Phadke and Thorpe, 1988, Thorpe et al, 1988: Jonsson
and Daadler, 2003; Kim, Heo and Aggarwal, 2005; Lim et al, 2008).
• In adaptive distance protection relaying, an important aspect to be
considered is developing an indicator that can differentiate between
faults and power swings.
• The objective is to permit the trip signals during faults and block the
trip signals during other events.
• My enhancement to the topic is to clear or rectify the condition using
The Fault Mitigation Technique.
LITERATURE REVIEW PAPERS
Detection of Symmetrical Faults by Distance Relays During Power
Swings.
(IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010)
• To maintain security of distance relays, power swing blocking is
necessary to prevent unintended operation under power swings.
• This paper presents a new method for detecting a symmetrical fault during
a power swing, based on extracting components of the current waveform
using the Prony method.
• The merit of the proposed method was demonstrated by simulating
various cases including solid faults and arc fault on a typical power
system.
• The ease of implementation as well as accuracy and high speed of fault
detection are important advantages of the proposed method.
A Novel Approach to Detect Symmetrical
Faults Occurring During Power Swings by
Using Frequency Components of Instantaneous
Three-Phase Active Power
(IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012)
• Based on the damping frequency component of 50 (or 60) Hz created on
instantaneous three-phase active power profile after inception of a
symmetrical fault, the proposed method will be able to detect the fault in
less than one power cycle.
• This detection method can be readily implemented, and is immune to the
power swing slip frequency, fault inception time, and fault location.
• The proposed method has several advantages that are superior to the
existing methods. First, since it requires only three-phase active power,
which can be simply calculated by production of instantaneous voltage
and current, and FFT, which is coded in all digital relays, the new method
can be readily implemented. Second, the new method is very fast.
Fast Distance Relay Scheme for Detecting
Symmetrical Fault During Power Swing
(IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 4, OCTOBER 2010)
• The paper provides a fast detection scheme for symmetrical fault during
power swing for distance relay, which is based on extracting the high-
frequency component energy of forward and backward traveling waves
induced by faults.
• The multi resolution analysis based on wavelet transform has the ability to
decompose the analyzed signals into different frequency bands. The
selection of mother wavelet and the number of levels of wavelet transform
are carefully studied.
• The fault can be identified by feature extracting from the d1 component of
Daubechies-8 (Db8) wavelet transform.
• This proposed method can be used for distance relay operation blocking
or monitoring.
A Classification Approach Using Support Vector
Machines to Prevent Distance Relay Mal-operation
Under Power Swing and Voltage Instability
(IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012)
• Distance relays, in the power transmission systems, are susceptible to the mal-
operation under certain system events, such as power swings and voltage
instability
• The proposed scheme segregates the power system events into faults, power
swings, and voltage instability.
• This paper also proposes a new index, called the relay ranking index, for
identifying the relays most vulnerable to the mal-operation due to power
swings and voltage instability.
• The scheme effectively discriminates the dynamic encroachment events and
differentiates the system events into power swings and voltage instability by
utilizing the transmission- line reactive power loss as a key indicator for the
voltage-unstable situation.
Mitigating the Impacts of CCVT Subsidence
Transients on the Distance Relay
(IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 2, APRIL 2012)
• The paper presents a comprehensive time-domain model of the
coupling capacitor voltage transformer (CCVT) to investigate the effect
of CCVT subsidence transients on the distance relay.
• The studies show that voltage-zero subsidence transients can
adversely impact the performance of the distance relay and result in
the overreach problem.
• The method is based on improving the degree of accuracy of the
voltage Phasor estimation during the CCVT subsidence transients.
• The proposed method is not affected by harmonics and high-
frequency transient distortions of the voltage, and prevents the relay
overreach problem.
Review of existing methods
• In a power system disturbance-like faults, generator
disconnection and change in the large block of
loads are the main reasons for power swing.
• Large variations in voltage and current causes
undesired tripping of distance relay which may lead
to subsequent line outages.
• The power swing blocking (PSB) function is used to
prevent mis-operation of distance relays during
swing.
• If a fault occurs during the power swing, it should
be detected and suppressed.
• Conventional fault detection techniques may fail to
distinguish fault during the power swing.
• Symmetric nature of phase voltages and currents
during the swing makes this task tedious.
PROPOSED METHOD
• Full-cycle sample points of voltage and current
are predicted using auto regression technique
for any phase.
• It models the nth value of a variable as a
function of previous values, where k is the order
of the model.
• The accuracy of the prediction technique
improves with a higher value of k.
PHASE 1 - CASE STUDY
• The method is tested for various fault conditions
during the power swing for a 400-kV double-
circuit transmission system (i)
• A 230-kV WSCC 3-machine, a nine-bus system
(ii)
• Simulation and analysis are going to be done
through PSCAD/EMTDC
• i)
• ii)
ANALYSIS WITH AUTO REGRESSION
PROGRAMME
• Auto regression is a special technique for
regression analysis.
• The technique models nth values of the system
as a function of K previous values.
• Higher values of K improves the system
prediction accuracy.
Cont…
• The expression for the Kth order auto regression model
is
• where a1,a2….aK are the auto regression coefficients
and i’s are the samples of the variable.
• The calculation of coefficients are done by considering
the P available samples of the system.
Cont…
• matrix form of the system can be written as
• It can be further written as
• The future sample points are calculated using
available samples and [A]
Cont…
• The expression for obtaining future samples
(next q samples) is
• The accuracy of prediction decreases with
length of q.
• The accuracy of the technique depends on the
selection of k, p, q.
Cont…
• The coefficients of the auto regression technique are
calculated using previous samples of a variable and
these samples gives a clear picture of the future
disturbances and system oscillations.
• The difference between the predicted and actual values
of the variable is found to be negligible when there is no
external disturbance with the selected system.
Cont…
• The differential components of voltage and
current at any sampling instant of time are
calculated as follows:
Cont…
• The rms values of differential voltage and
current are calculated over a period of one cycle
Where N is the number of samples per cycle
Cont…
• The differential power ΔP is calculated
from the rms voltage and current as
RESULTS FOR THE DOUBLE-CIRCUIT LINE
• The system is simulated using PSCAD/EMTDC
software with a distributed transmission-line model.
• A three-phase fault is created in Line-2 at point F at
0.5 s, which is cleared after 0.1 s by the opening of
breakers B3 and B4. As a result, the distance relay R1
in line-1 experiences a power swing.
• Any fault in line-1 during the swing has to be detected
by relay R1.
FLOW DIAGRAM FOR THE PROPOSED
DOUBLE CIRCUIT LINE
Results
Differential component of voltage
Differential component of current
• Differential power for the 3Phase fault at 3.65s
during power swing.
Inference
• The difference in the actual and predicted samples of the
voltage and current during the power swing followed by a
three-phase fault at 3.65 s are shown.
• The wave forms obtained are clearly showing the
predicted and actual samples of voltage, current and
power during the swing and fault.
• Difference in predicted and actual samples of voltage
and current is less during the power swing and high for
the fault period.
• The differential power can be obtained directly from the
current – voltage waveforms.
• The magnitude of ΔP is negligible for the power swing
and high for the fault period.
• The algorithm identifies the fault if the magnitude
exceeds the threshold value of ΔP.
• The selection of threshold value is much important to get
a more accurate fault detection.
• The threshold value should be greater than the
maximum differential power during the swing condition.
CONCLUSION
• Detection of symmetrical fault during power swing is actually a
threat to power system protection.
• The base paper is hereby proposing an auto-regression based
study of symmetrical fault components during the swing period.
• But mitigating a fault is much beneficial than making a tripping with
the CBs.
• The thesis is thus proposing a fault mitigation scheme to assure an
improved reliability with the power system.

More Related Content

PDF
Transient Stability Assessment and Enhancement in Power System
PDF
Expert system for sweep frequency response analysis of power transformer
PDF
Wavelet based detection and location of faults in 400kv, 50km Underground Po...
PDF
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...
PPTX
final slide..ps.pptx
PDF
B010620715
PPTX
stability analysis tool in smart grid.pptx
PPTX
Current and Voltage Transformers _23_10_2021.pptx
Transient Stability Assessment and Enhancement in Power System
Expert system for sweep frequency response analysis of power transformer
Wavelet based detection and location of faults in 400kv, 50km Underground Po...
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...
final slide..ps.pptx
B010620715
stability analysis tool in smart grid.pptx
Current and Voltage Transformers _23_10_2021.pptx

Similar to presentation.pptx (20)

PDF
IRJET- A Simple Approach to Identify Power System Transmission Line Faults us...
PDF
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
PPTX
performance analysis tool in smart gris .pptx
PPTX
20EEE659T – UNIT 3 - POWER SYSTEM PLANNING AND RELIABILITY.pptx
PDF
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
PPTX
Extra high voltage long ac transmission lines
PDF
POWER SYSTEM ANALYSIS_254ppt.pdf
PDF
Concurrent Detection and Classification of Faults in Matrix Converter using T...
PPTX
Final presentation [Autosaved].pptxFinal presentation [Autosaved].pptxFinal p...
PPT
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
PPTX
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
PPTX
Distribu pQ.pptx
PDF
Power Quality Disturbaces Clasification And Automatic Detection Using Wavelet...
PDF
DigSILENT PF - 05 short circuit theory
PDF
DigSILENT PF - 06 (es) short circuit theory
PDF
A High-Performance SPWM Controller for Three-Phase UPS Systems Operating Unde...
PDF
Kf3517721775
PDF
Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...
PDF
Pe3426652670
PPTX
Summary Presentation on PMU Based Transmission Line Protection Scheme
IRJET- A Simple Approach to Identify Power System Transmission Line Faults us...
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
performance analysis tool in smart gris .pptx
20EEE659T – UNIT 3 - POWER SYSTEM PLANNING AND RELIABILITY.pptx
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Extra high voltage long ac transmission lines
POWER SYSTEM ANALYSIS_254ppt.pdf
Concurrent Detection and Classification of Faults in Matrix Converter using T...
Final presentation [Autosaved].pptxFinal presentation [Autosaved].pptxFinal p...
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Distribu pQ.pptx
Power Quality Disturbaces Clasification And Automatic Detection Using Wavelet...
DigSILENT PF - 05 short circuit theory
DigSILENT PF - 06 (es) short circuit theory
A High-Performance SPWM Controller for Three-Phase UPS Systems Operating Unde...
Kf3517721775
Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...
Pe3426652670
Summary Presentation on PMU Based Transmission Line Protection Scheme
Ad

Recently uploaded (20)

PDF
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PDF
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
PPTX
Construction Project Organization Group 2.pptx
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PDF
III.4.1.2_The_Space_Environment.p pdffdf
DOCX
573137875-Attendance-Management-System-original
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPT
introduction to datamining and warehousing
PDF
Categorization of Factors Affecting Classification Algorithms Selection
PPTX
UNIT 4 Total Quality Management .pptx
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PDF
Level 2 – IBM Data and AI Fundamentals (1)_v1.1.PDF
PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
PPTX
Sustainable Sites - Green Building Construction
PDF
Well-logging-methods_new................
PPTX
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
Embodied AI: Ushering in the Next Era of Intelligent Systems
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
Construction Project Organization Group 2.pptx
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
III.4.1.2_The_Space_Environment.p pdffdf
573137875-Attendance-Management-System-original
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
introduction to datamining and warehousing
Categorization of Factors Affecting Classification Algorithms Selection
UNIT 4 Total Quality Management .pptx
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
Level 2 – IBM Data and AI Fundamentals (1)_v1.1.PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
Sustainable Sites - Green Building Construction
Well-logging-methods_new................
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
Ad

presentation.pptx

  • 2. SYMMETRICAL FAULT DETECTION DURING POWER SWING
  • 3. ABSTRACT • If a fault occurs during a power swing, it should be detected and the unblocking function should be invoked to clear the fault as soon as possible. • Distance relays are getting blocked during power swing to ensure reliability of the power system. • Due to the symmetric nature of signals during the power swing, symmetrical faults are difficult to be detected. • In this paper, a differential power-based fault detection technique is proposed for the detection of symmetrical faults during power swings.
  • 4. Cont… • The differential power is calculated from the difference in predicted and actual samples of voltage and current. • The predicted voltage and current samples are obtained using the auto regression technique. • The proposed method is tested for different fault conditions and the results are compared with the available method. • The proposed method is found to identify symmetrical faults accurately during slow and fast power swings for different power systems.
  • 5. Literature survey • Power Swing which is basically caused by the large disturbances in the power system which if not blocked could cause wrong operation of the distance relay and can generates wrong or undesired tripping of the transmission line circuit breaker. • To prevent unwanted distance or other relay operation during a Power Swing, we did fundamental studies of traditional and advanced detection and prevention methods. • However, many studies have shown that undesirable zone 3 distance relay operations have initiated tripping which lead to cascading events and finally wide-area voltage collapse (Jonsson and Daadler, 2003; Kim et al, 2005; Jin and Sindhu, 2008 ; Lim et al, 2008).
  • 6. Cont… • To improve reliability of relay operation, adaptive scheme for distance protection has been introduced by many researches (Horowitz, Phadke and Thorpe, 1988, Thorpe et al, 1988: Jonsson and Daadler, 2003; Kim, Heo and Aggarwal, 2005; Lim et al, 2008). • In adaptive distance protection relaying, an important aspect to be considered is developing an indicator that can differentiate between faults and power swings. • The objective is to permit the trip signals during faults and block the trip signals during other events. • My enhancement to the topic is to clear or rectify the condition using The Fault Mitigation Technique.
  • 7. LITERATURE REVIEW PAPERS Detection of Symmetrical Faults by Distance Relays During Power Swings. (IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010) • To maintain security of distance relays, power swing blocking is necessary to prevent unintended operation under power swings. • This paper presents a new method for detecting a symmetrical fault during a power swing, based on extracting components of the current waveform using the Prony method. • The merit of the proposed method was demonstrated by simulating various cases including solid faults and arc fault on a typical power system. • The ease of implementation as well as accuracy and high speed of fault detection are important advantages of the proposed method.
  • 8. A Novel Approach to Detect Symmetrical Faults Occurring During Power Swings by Using Frequency Components of Instantaneous Three-Phase Active Power (IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012) • Based on the damping frequency component of 50 (or 60) Hz created on instantaneous three-phase active power profile after inception of a symmetrical fault, the proposed method will be able to detect the fault in less than one power cycle. • This detection method can be readily implemented, and is immune to the power swing slip frequency, fault inception time, and fault location. • The proposed method has several advantages that are superior to the existing methods. First, since it requires only three-phase active power, which can be simply calculated by production of instantaneous voltage and current, and FFT, which is coded in all digital relays, the new method can be readily implemented. Second, the new method is very fast.
  • 9. Fast Distance Relay Scheme for Detecting Symmetrical Fault During Power Swing (IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 4, OCTOBER 2010) • The paper provides a fast detection scheme for symmetrical fault during power swing for distance relay, which is based on extracting the high- frequency component energy of forward and backward traveling waves induced by faults. • The multi resolution analysis based on wavelet transform has the ability to decompose the analyzed signals into different frequency bands. The selection of mother wavelet and the number of levels of wavelet transform are carefully studied. • The fault can be identified by feature extracting from the d1 component of Daubechies-8 (Db8) wavelet transform. • This proposed method can be used for distance relay operation blocking or monitoring.
  • 10. A Classification Approach Using Support Vector Machines to Prevent Distance Relay Mal-operation Under Power Swing and Voltage Instability (IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012) • Distance relays, in the power transmission systems, are susceptible to the mal- operation under certain system events, such as power swings and voltage instability • The proposed scheme segregates the power system events into faults, power swings, and voltage instability. • This paper also proposes a new index, called the relay ranking index, for identifying the relays most vulnerable to the mal-operation due to power swings and voltage instability. • The scheme effectively discriminates the dynamic encroachment events and differentiates the system events into power swings and voltage instability by utilizing the transmission- line reactive power loss as a key indicator for the voltage-unstable situation.
  • 11. Mitigating the Impacts of CCVT Subsidence Transients on the Distance Relay (IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 2, APRIL 2012) • The paper presents a comprehensive time-domain model of the coupling capacitor voltage transformer (CCVT) to investigate the effect of CCVT subsidence transients on the distance relay. • The studies show that voltage-zero subsidence transients can adversely impact the performance of the distance relay and result in the overreach problem. • The method is based on improving the degree of accuracy of the voltage Phasor estimation during the CCVT subsidence transients. • The proposed method is not affected by harmonics and high- frequency transient distortions of the voltage, and prevents the relay overreach problem.
  • 12. Review of existing methods • In a power system disturbance-like faults, generator disconnection and change in the large block of loads are the main reasons for power swing. • Large variations in voltage and current causes undesired tripping of distance relay which may lead to subsequent line outages. • The power swing blocking (PSB) function is used to prevent mis-operation of distance relays during swing.
  • 13. • If a fault occurs during the power swing, it should be detected and suppressed. • Conventional fault detection techniques may fail to distinguish fault during the power swing. • Symmetric nature of phase voltages and currents during the swing makes this task tedious.
  • 14. PROPOSED METHOD • Full-cycle sample points of voltage and current are predicted using auto regression technique for any phase. • It models the nth value of a variable as a function of previous values, where k is the order of the model. • The accuracy of the prediction technique improves with a higher value of k.
  • 15. PHASE 1 - CASE STUDY • The method is tested for various fault conditions during the power swing for a 400-kV double- circuit transmission system (i) • A 230-kV WSCC 3-machine, a nine-bus system (ii) • Simulation and analysis are going to be done through PSCAD/EMTDC
  • 17. ANALYSIS WITH AUTO REGRESSION PROGRAMME • Auto regression is a special technique for regression analysis. • The technique models nth values of the system as a function of K previous values. • Higher values of K improves the system prediction accuracy.
  • 18. Cont… • The expression for the Kth order auto regression model is • where a1,a2….aK are the auto regression coefficients and i’s are the samples of the variable. • The calculation of coefficients are done by considering the P available samples of the system.
  • 19. Cont… • matrix form of the system can be written as • It can be further written as • The future sample points are calculated using available samples and [A]
  • 20. Cont… • The expression for obtaining future samples (next q samples) is • The accuracy of prediction decreases with length of q. • The accuracy of the technique depends on the selection of k, p, q.
  • 21. Cont… • The coefficients of the auto regression technique are calculated using previous samples of a variable and these samples gives a clear picture of the future disturbances and system oscillations. • The difference between the predicted and actual values of the variable is found to be negligible when there is no external disturbance with the selected system.
  • 22. Cont… • The differential components of voltage and current at any sampling instant of time are calculated as follows:
  • 23. Cont… • The rms values of differential voltage and current are calculated over a period of one cycle Where N is the number of samples per cycle
  • 24. Cont… • The differential power ΔP is calculated from the rms voltage and current as
  • 25. RESULTS FOR THE DOUBLE-CIRCUIT LINE • The system is simulated using PSCAD/EMTDC software with a distributed transmission-line model. • A three-phase fault is created in Line-2 at point F at 0.5 s, which is cleared after 0.1 s by the opening of breakers B3 and B4. As a result, the distance relay R1 in line-1 experiences a power swing. • Any fault in line-1 during the swing has to be detected by relay R1.
  • 26. FLOW DIAGRAM FOR THE PROPOSED DOUBLE CIRCUIT LINE
  • 29. • Differential power for the 3Phase fault at 3.65s during power swing.
  • 30. Inference • The difference in the actual and predicted samples of the voltage and current during the power swing followed by a three-phase fault at 3.65 s are shown. • The wave forms obtained are clearly showing the predicted and actual samples of voltage, current and power during the swing and fault. • Difference in predicted and actual samples of voltage and current is less during the power swing and high for the fault period.
  • 31. • The differential power can be obtained directly from the current – voltage waveforms. • The magnitude of ΔP is negligible for the power swing and high for the fault period. • The algorithm identifies the fault if the magnitude exceeds the threshold value of ΔP. • The selection of threshold value is much important to get a more accurate fault detection. • The threshold value should be greater than the maximum differential power during the swing condition.
  • 32. CONCLUSION • Detection of symmetrical fault during power swing is actually a threat to power system protection. • The base paper is hereby proposing an auto-regression based study of symmetrical fault components during the swing period. • But mitigating a fault is much beneficial than making a tripping with the CBs. • The thesis is thus proposing a fault mitigation scheme to assure an improved reliability with the power system.