SSR 303
One Channel 3 Amp Switch
(Rx Only) - Z-Wave
User and Installation Instructions
2
3
The Secure SSR 303 receiver is a single channel
receiver originally designed for the control of central
heating which can also be operated by third party
controllers which support ‘Thermostat Mode SET’
commands or‘BinarySwitchSET’commands.
This SSR 303 will act as a repeater once added into
the Z-Wave network, providing an alternative
communication route for units which otherwise would
not be within communication distance of each other.
The Secure SSR 303 forms part of a Z-Wave PlusTM
homeautomation network.
This document provides information specific to the Z-
Wave technology implemented, to ensure
interoperability between the SSR 303 receiver and
other Z-Wave products.
4
SSR 303 Receiver Unit
The SSR 303 receiver unit receives the Z-Wave
radio signals from the 3rd party Z-Wave controllers.
In the unlikely event of a communication failure it is
possible to override the system and switch ON and
OFF using the ON/OFF buttons on the SSR 303
receiver as a local override.
If the override is used to override the system when it is
functioning correctly then the override will be cancelled
by the next switching operation and normal operation
will be resumed. In any case, with no further
intervention, normal operation will be restored within
one hour of theoverride being operated.
5
Installing the receiver
Installing theSSR 303
The SSR 303 receiver should
be located as near as is
practical to the device to be
controlled, as well as a
convenient mains electricity
supply. To remove the wall plate
from the SSR 303, undo the two
retaining screws located on the
underside, the wall plate should
now be easily removed. Once
the wall plate has been removed
from the packaging please ensure the SSR 303 is
re-sealed to prevent damage from dust, debris etc.
The wall plate should be fitted with the retaining screws
located at the bottom and in a position which allowsa
total clearance of at least 50mm around the SSR
303 receiver.
6
DirectWallMounting
Offer the plate to the wall in the position where the
SSR 303 is to be mounted and mark the fixing
positions through the slots in the wall plate. Drill and
plug the wall, then secure the plate into position. The
slots in the wall plate will compensate for any
misalignment of the fixings.
WallBoxMounting
The wall plate may be fitted directly on to a single gang
flush wiring box complying with BS4662, using two
M3.5 screws. The receiver is suitable for mounting on a
flat surface only; it is not suitable for mounting on an
unearthed metal surface.
7
Electrical Connections
All necessary electrical connections should now be
made. Flush wiring can enter from the rear through the
aperture in the back plate.
The mains supply terminals are intended to be
connected tothesupply bymeans of fixed wiring.
The receiver is mains powered and requires a 3 Amp
fusedspur.
The recommended cablesize is 1.Omm2.
The receiver is double insulated and does not require
an earth connection, an earth connection block is
provided on the back plate for terminating any cable
earth conductors. Earth continuity must be maintained
and all bare earth conductors must be sleeved. Ensure
that no conductors are left protruding outside the
central spaceenclosed bythe back plate.
8
Please ensure that all installations comply with current IEE
regulations.
SSR303 internal wiring diagram
Internal
Electronics
230V ~ 50Hz COMM OFF ON
The receiver has voltage free contacts.
Fit link between L & 2 for mains voltage applications
9
Receiver status LED
This unit has three buttons and three LEDs - ON, OFF and Network
(from top to bottom) that are used as follows:-
LED indication Unit mode Button usage
Solid OFF LED
Flashing Network LED
Unit is currently
removed from the
network
OFF and ON -
Switches channel
relay OFF or ON
respectively.
Network - Network
function
Flashing ON LED
(Green) 3s only Solid
OFF LED
Unit has been
successfully added on
the network
OFF and ON -
No function
Network - Network
function
Solid OFF LED Unit is reflecting the
status OFF the
relay unit. The
output is OFF.
Or, unit has finished
the addition process.
Or, unit has been
added and has just
been powered up on
the mains
OFF and ON -
switches channel
relay OFF or ON
respectively.
Network - Network
function
10
Solid ON LED Unit is reflecting the
status of the relay
output. The output is
ON.
OFF and ON -
switches channel
relay OFF or ON
respectively.
Network - Network
function
Solid OFF LED
Solid Network LED
Unit is in failsafe mode
and the relay output is
OFF.
OFF and ON -
switches channel
relay OFF or ON
respectively.
Network - Network
function
Solid ON LED
Solid Network LED
Unit is in Failsafe mode
and the relay output
has been turned ON
via the ON button
Or, Unit is currently
removed from the
network and ON by
button operation.
OFF and ON -
switches channel
relay OFF or ON
respectively.
Network - Network
function
11
Adding to a third partycontroller
To add the unit to a 3rd party controller follows these
steps, alsoknown as ‘inclusion’inZ-Wave terminology.
- Ensure the network LED is flashing on the SSR
303, if not follow the steps in ‘Disconnecting from a
network’first.
- Put the 3rd partycontrollerintoinclusionmode.
- Press and hold the network button on the SSR 303
until the ‘ON’LED’s start flashing.
- The SSR 303 has been added onto the network
when the ‘OFF’LED goes solid red.
NOTE: If the ON LED does not flash then the add
process has been unsuccessful.
12
Removing from a network
To remove from a Z-Wave network, follow the steps,
below, also known as ‘exclusion’ in, Z-Wave,
terminology
- Put the 3rd party controller intoexclusionmode.
- Press andhold thenetwork buttonon the SSR 303.
- The SSR 303 has been removed from the network
when the Network LED starts flashing.
NOTE: If the Network LED does not flash the remove
process has been unsuccessful.
NOTE: This product can be included and operated in
any Z-Wave network with other Z-Wave certified
devices from other manufacturers and/or other
applications.All non-battery operated nodes within the
network will act as repeaters regardless of vendor to
increase reliability of the network.
13
Node Information Frame - NIF
Pressing and holding the network button for 1 second
will trigger the SSR 303 to issue a Node Information
Frame and enter Classic learn mode for 2s and then in
NWI (Network Wide Inclusion) learn mode. This is
useful to associate/disassociate the SSR 303 with a
control group or just to determine the device and
command classes supported. This can be done at any
timebut will not provide anyindication tothe operator.
Z-Wave Repeater
This SSR 303 will act as a repeater once added into
the Z-Wave network, providing an alternative
communication route for units which otherwise would
not bewithincommunication distance of each other.
Device reset:
“Please use this procedure only when the primary
controller is missing or otherwise inoperable.”
Follow “Removing from a Network” process.
14
Supported Device and command classes
Z-Wave Plus Device
Classes
Implemented Device Class
Generic Device Class:
Specific Device Class: Basic
Device Class:
GENERIC TYPE SWITCH BINARY
SPECIFIC TYPE POWER SWITCH BINARY
ROUTING SLAVE
Command Class Commands Supported
Manufacturer Specific (V2) Get
Report
Device Specific Get
Device Specific Report
Manufacturer ID = 0x0059
Product Type ID = 0x0003
Product ID = 0x0005 (SSR 303)
Device ID Type 0 and 1 for serial number (Data format Binary, length4
Bytes)
Version (V2) Get
Report
Version Command Class Get
Version Command Class Report
Provides the version number of the Z-Wave stack, Command Class,
Firmware and Hardware.
15
Z-Wave Plus Info (V2) Get
Report
RoleType:ROLE_TYPE_SLAVE_ALWAYS_ON
Node Type:
ZWAVEPLUS_INFO_REPORT_NODE_TYPE_ZWAVEPLUS_NODE
Installer Icon: ICON_TYPE_GENERIC_ON_OFF_POWER_SWITCH
User Icon: ICON_TYPE_GENERIC_ON_OFF_POWER_SWITCH
Association (V2) Set
Get
Report
Remove
Supported Groupings Get
Supported Groupings Report
Specific Group Get
Product supports one group (Lifeline) and has a maximum of 4 nodes.
Association Group Info (V1) Group Name Get
Group Name Report
Group Info get
Group Info Report
Group Command List Get
Group Command List Report
16
Only one association group is supported
Group 1:
name - “Lifeline”
Profile MSB -ASSOCIATION_GROUP_INFO_REPORT_PROFILE_GENERAL
Profile LSB -
ASSOCIATION_GROUP_INFO_REPORT_PROFILE_GENERAL_LIFELINE
Supported Command class and command -
COMMAND_CLASS_SWITCH_BINARY, SWITCH_BINARY_REPORT
Thermostat Mode (V1) Set
Get
Report
Supported Get
Supported Report
Only ‘Idle Mode’ and ‘Heat Mode’ are supported within this command class,
which can either set or read.
The SSR 303 has a failsafe mode where by the relay is turned OFF if
another Thermostat Mode SET command has not been received within 60
minutes.
Switch Binary (V1) Set
Get
Report
Supports SET and GET to control the relay.
Opposed to the Thermostat command class there is no failsafe mode. If
Binary Switch SET command is received than previously active failsafe
mode closed.
17
Basic (V1) Set
Get
Report
The Basic command class has been mapped to Switch Binary command
class as follows:
Basic Set : Mapped to Switch Binary Set.
Basic Get : Mapped to Switch Binary Get.
Basic Report : Mapped to Switch Binary Report
Same as Switch Binary command class there is no failsafe mode. If Basic
SET command is received than previously active failsafe mode closed.
Power Level (V1) Power Level Set
Power Level Get
Power Level Report
Power Level Test Node Set
Power Level Test Node Get
Power Level Test Node Report
Power Level Command Class defines RF transmit power
controlling commands useful when installing or testing a network.
Note: For more information about Z-Wave command classes and their
use refer to "SDS12652 and SDS12657 Z-Wave Command Class
Specification" version 8 or above.
Note: After removing from existing Z-Wave network, device comes in
factory default state and will not send device reset locally notification.
18
Receiver specification SSR 303
Power Supply 230v 50Hz
Contact type Micro disconnection
Wiring configuration Voltage free c/o (SPDT)
Contact voltage rating 230v ac 50Hz (30v dc)
Contact current rating 3A (1A inductive)
Impulse rating Category II – 2500v
Transmitter frequency 868.42MHz
Receiver category Category 3Power
Class Class B
Standards EN 60730-2-7
ETSI EN 300 220-2 / ETSI EN 301
489-3
Dimensions 86 x 86 x 36.25mm
Enclosure Flame retardant thermoplastic
Ingress protection IP30
Pollution degree Degree 2
Insulation class Class II
Software class A
Control type Type 1B
Electronic control
Temperature r a n g e 0-40˚C
Ball pressure temperature 75˚C
Purpose of control 1 channel RF receiver switch
19
European Head Office
Secure Controls (UK) Ltd.
South Bristol Business Park
Roman Farm Road
Bristol, BS4 1UP, UK
e: info@securetogether.com
www.securetogether.com
European Sales Office
CEWE Instrument AB
Box 1006, 611 31 Nyköping
t: +46 8 600 80 60
e: info@securetogether.com
www.securetogether.com
www.securetogether.com
Australia Sales Office
Secure Australasia Pty Ltd
258 Darebin Road
Fairfield VIC 3078
Australia
p: +61 3 9485 6000
f: +61 3 9485 6099
e: info@securetogether.com
www.securetogether.com
Secure Meters Ltd
Pratap Nagar Industrial Area
Udaipur 313003
India
p: +91 294 2492 300-05
f: +91 294 2492 310
e: mktg@securetogether.com
www.securetogether.com
Elegant Metering Solutions FZE
4EA 326, P.O. Box 54857
Dubai Airport Free Zone
Dubai, UAE
p: +971 50 6575166
f: +971 04 204 5619
e: emsfze@emsdxb.ae
www.securetogether.com
Part Number P84074 Issue Number 6

More Related Content

PPT
Subnetting Cara Cepat.ppt
PDF
NX5500設定 - Centralized Controller Deployment -
PDF
Manual SEC_SCS318 secure
PDF
Wall plug switch with metering po pp start guide
PDF
Manual zmnhxd1
PDF
Mini price on off z wave plus everspring
PDF
Mini jack on off and counter z wave plus everspring
PDF
Aeotec Multisensor 7 Manual
Subnetting Cara Cepat.ppt
NX5500設定 - Centralized Controller Deployment -
Manual SEC_SCS318 secure
Wall plug switch with metering po pp start guide
Manual zmnhxd1
Mini price on off z wave plus everspring
Mini jack on off and counter z wave plus everspring
Aeotec Multisensor 7 Manual

Similar to Ssr 303 user manual (20)

PDF
Mco_tps312
PDF
Ph psr03-zipato-z-wave-remote-user-manual
PDF
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manual english
PDF
Mco_tps314
PDF
Philio_pan04_User manual
PDF
Manual steinel rs led d2 (indoor light with led)
PDF
Manual Zipato PAB01
PDF
Wall Plug switch with Metering Z-Wave.me ZME_064374 manual english
PDF
Micro switch module qubino manual
PDF
Pop 123610 manual
PDF
Eur stellaz manual
PDF
Fortrezz s 03-manual_us
PDF
Manual co detector-popp_en
PDF
Manual motion sensor with led spotlight xled home 2 - z-wave plus - steinel
PDF
Mini Socket Dimmer Z-Wave Everspring manual
PDF
ZIP Pan03 - Zipato micromodule single switch max.load 11 a user manual v1.0
PDF
Water meter secure start guide
PDF
manual vision security VIS_ZR1202
PDF
Z wave.me double controller set for duro 200 manual
PDF
Z wave.me controller set for duro 200 manual
Mco_tps312
Ph psr03-zipato-z-wave-remote-user-manual
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manual english
Mco_tps314
Philio_pan04_User manual
Manual steinel rs led d2 (indoor light with led)
Manual Zipato PAB01
Wall Plug switch with Metering Z-Wave.me ZME_064374 manual english
Micro switch module qubino manual
Pop 123610 manual
Eur stellaz manual
Fortrezz s 03-manual_us
Manual co detector-popp_en
Manual motion sensor with led spotlight xled home 2 - z-wave plus - steinel
Mini Socket Dimmer Z-Wave Everspring manual
ZIP Pan03 - Zipato micromodule single switch max.load 11 a user manual v1.0
Water meter secure start guide
manual vision security VIS_ZR1202
Z wave.me double controller set for duro 200 manual
Z wave.me controller set for duro 200 manual
Ad

More from Domotica daVinci (20)

PDF
Manual de usuario Dongle Zigbee 3.0 Sonoff
PDF
2Channel Dimmer Module Zigbee NetPlus Manual
PDF
Shelly Qubini Dry Contact Module Z-Wave Manual
PDF
Zi-Stick UBS Dongle ZIgbee from Aeotec manual
PDF
Manual controlador de pared Zigbee quatro battery.pdf
PDF
MOES-User-Manual AL23-211223-MHUB-MS.pdf
PDF
Tete thermostatique Zigbee MOES BRT-100 V2.pdf
PDF
Cherubini Meta Z-Wave Double Switch A510083-84-90
PDF
Cherubini Meta Z-Wave Smart Plug Manual A510068
PDF
Wave_Shutter_user_guide_multilang_print_V3.pdf
PDF
Quinto Z-Wave Heltun_HE-RS01_User_Manual_B9AH.pdf
PDF
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdf
PDF
Manual Eurotronic Thermostatic Valve Comry Z-Wave
PDF
Manual sensor Zigbee 3.0 MOES ZSS-X-PIRL-C
PDF
zigbee motion sensor user manual NAS-PD07B2.pdf
PDF
Range extender 7 - Aeotec - Manual
PDF
Z stick 7 user guide
PDF
ESB 200 H-Tronic Manual
PDF
wiDom Smart Roller Shutter Z-Wave Plus Module Manual
PDF
wiDom Smart dry contact module Z-Wave Plus Manual
Manual de usuario Dongle Zigbee 3.0 Sonoff
2Channel Dimmer Module Zigbee NetPlus Manual
Shelly Qubini Dry Contact Module Z-Wave Manual
Zi-Stick UBS Dongle ZIgbee from Aeotec manual
Manual controlador de pared Zigbee quatro battery.pdf
MOES-User-Manual AL23-211223-MHUB-MS.pdf
Tete thermostatique Zigbee MOES BRT-100 V2.pdf
Cherubini Meta Z-Wave Double Switch A510083-84-90
Cherubini Meta Z-Wave Smart Plug Manual A510068
Wave_Shutter_user_guide_multilang_print_V3.pdf
Quinto Z-Wave Heltun_HE-RS01_User_Manual_B9AH.pdf
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdf
Manual Eurotronic Thermostatic Valve Comry Z-Wave
Manual sensor Zigbee 3.0 MOES ZSS-X-PIRL-C
zigbee motion sensor user manual NAS-PD07B2.pdf
Range extender 7 - Aeotec - Manual
Z stick 7 user guide
ESB 200 H-Tronic Manual
wiDom Smart Roller Shutter Z-Wave Plus Module Manual
wiDom Smart dry contact module Z-Wave Plus Manual
Ad

Recently uploaded (20)

PDF
Empathic Computing: Creating Shared Understanding
PDF
NewMind AI Weekly Chronicles - August'25-Week II
PDF
Review of recent advances in non-invasive hemoglobin estimation
PDF
gpt5_lecture_notes_comprehensive_20250812015547.pdf
PDF
Encapsulation theory and applications.pdf
PDF
Mobile App Security Testing_ A Comprehensive Guide.pdf
PPTX
A Presentation on Artificial Intelligence
PDF
Agricultural_Statistics_at_a_Glance_2022_0.pdf
PPT
Teaching material agriculture food technology
PDF
Encapsulation_ Review paper, used for researhc scholars
PPTX
Spectroscopy.pptx food analysis technology
PDF
Build a system with the filesystem maintained by OSTree @ COSCUP 2025
PDF
Assigned Numbers - 2025 - Bluetooth® Document
PPTX
Digital-Transformation-Roadmap-for-Companies.pptx
PPTX
sap open course for s4hana steps from ECC to s4
PDF
Architecting across the Boundaries of two Complex Domains - Healthcare & Tech...
PDF
Per capita expenditure prediction using model stacking based on satellite ima...
DOCX
The AUB Centre for AI in Media Proposal.docx
PDF
Advanced methodologies resolving dimensionality complications for autism neur...
PPTX
ACSFv1EN-58255 AWS Academy Cloud Security Foundations.pptx
Empathic Computing: Creating Shared Understanding
NewMind AI Weekly Chronicles - August'25-Week II
Review of recent advances in non-invasive hemoglobin estimation
gpt5_lecture_notes_comprehensive_20250812015547.pdf
Encapsulation theory and applications.pdf
Mobile App Security Testing_ A Comprehensive Guide.pdf
A Presentation on Artificial Intelligence
Agricultural_Statistics_at_a_Glance_2022_0.pdf
Teaching material agriculture food technology
Encapsulation_ Review paper, used for researhc scholars
Spectroscopy.pptx food analysis technology
Build a system with the filesystem maintained by OSTree @ COSCUP 2025
Assigned Numbers - 2025 - Bluetooth® Document
Digital-Transformation-Roadmap-for-Companies.pptx
sap open course for s4hana steps from ECC to s4
Architecting across the Boundaries of two Complex Domains - Healthcare & Tech...
Per capita expenditure prediction using model stacking based on satellite ima...
The AUB Centre for AI in Media Proposal.docx
Advanced methodologies resolving dimensionality complications for autism neur...
ACSFv1EN-58255 AWS Academy Cloud Security Foundations.pptx

Ssr 303 user manual

  • 1. 1 SSR 303 One Channel 3 Amp Switch (Rx Only) - Z-Wave User and Installation Instructions
  • 2. 2
  • 3. 3 The Secure SSR 303 receiver is a single channel receiver originally designed for the control of central heating which can also be operated by third party controllers which support ‘Thermostat Mode SET’ commands or‘BinarySwitchSET’commands. This SSR 303 will act as a repeater once added into the Z-Wave network, providing an alternative communication route for units which otherwise would not be within communication distance of each other. The Secure SSR 303 forms part of a Z-Wave PlusTM homeautomation network. This document provides information specific to the Z- Wave technology implemented, to ensure interoperability between the SSR 303 receiver and other Z-Wave products.
  • 4. 4 SSR 303 Receiver Unit The SSR 303 receiver unit receives the Z-Wave radio signals from the 3rd party Z-Wave controllers. In the unlikely event of a communication failure it is possible to override the system and switch ON and OFF using the ON/OFF buttons on the SSR 303 receiver as a local override. If the override is used to override the system when it is functioning correctly then the override will be cancelled by the next switching operation and normal operation will be resumed. In any case, with no further intervention, normal operation will be restored within one hour of theoverride being operated.
  • 5. 5 Installing the receiver Installing theSSR 303 The SSR 303 receiver should be located as near as is practical to the device to be controlled, as well as a convenient mains electricity supply. To remove the wall plate from the SSR 303, undo the two retaining screws located on the underside, the wall plate should now be easily removed. Once the wall plate has been removed from the packaging please ensure the SSR 303 is re-sealed to prevent damage from dust, debris etc. The wall plate should be fitted with the retaining screws located at the bottom and in a position which allowsa total clearance of at least 50mm around the SSR 303 receiver.
  • 6. 6 DirectWallMounting Offer the plate to the wall in the position where the SSR 303 is to be mounted and mark the fixing positions through the slots in the wall plate. Drill and plug the wall, then secure the plate into position. The slots in the wall plate will compensate for any misalignment of the fixings. WallBoxMounting The wall plate may be fitted directly on to a single gang flush wiring box complying with BS4662, using two M3.5 screws. The receiver is suitable for mounting on a flat surface only; it is not suitable for mounting on an unearthed metal surface.
  • 7. 7 Electrical Connections All necessary electrical connections should now be made. Flush wiring can enter from the rear through the aperture in the back plate. The mains supply terminals are intended to be connected tothesupply bymeans of fixed wiring. The receiver is mains powered and requires a 3 Amp fusedspur. The recommended cablesize is 1.Omm2. The receiver is double insulated and does not require an earth connection, an earth connection block is provided on the back plate for terminating any cable earth conductors. Earth continuity must be maintained and all bare earth conductors must be sleeved. Ensure that no conductors are left protruding outside the central spaceenclosed bythe back plate.
  • 8. 8 Please ensure that all installations comply with current IEE regulations. SSR303 internal wiring diagram Internal Electronics 230V ~ 50Hz COMM OFF ON The receiver has voltage free contacts. Fit link between L & 2 for mains voltage applications
  • 9. 9 Receiver status LED This unit has three buttons and three LEDs - ON, OFF and Network (from top to bottom) that are used as follows:- LED indication Unit mode Button usage Solid OFF LED Flashing Network LED Unit is currently removed from the network OFF and ON - Switches channel relay OFF or ON respectively. Network - Network function Flashing ON LED (Green) 3s only Solid OFF LED Unit has been successfully added on the network OFF and ON - No function Network - Network function Solid OFF LED Unit is reflecting the status OFF the relay unit. The output is OFF. Or, unit has finished the addition process. Or, unit has been added and has just been powered up on the mains OFF and ON - switches channel relay OFF or ON respectively. Network - Network function
  • 10. 10 Solid ON LED Unit is reflecting the status of the relay output. The output is ON. OFF and ON - switches channel relay OFF or ON respectively. Network - Network function Solid OFF LED Solid Network LED Unit is in failsafe mode and the relay output is OFF. OFF and ON - switches channel relay OFF or ON respectively. Network - Network function Solid ON LED Solid Network LED Unit is in Failsafe mode and the relay output has been turned ON via the ON button Or, Unit is currently removed from the network and ON by button operation. OFF and ON - switches channel relay OFF or ON respectively. Network - Network function
  • 11. 11 Adding to a third partycontroller To add the unit to a 3rd party controller follows these steps, alsoknown as ‘inclusion’inZ-Wave terminology. - Ensure the network LED is flashing on the SSR 303, if not follow the steps in ‘Disconnecting from a network’first. - Put the 3rd partycontrollerintoinclusionmode. - Press and hold the network button on the SSR 303 until the ‘ON’LED’s start flashing. - The SSR 303 has been added onto the network when the ‘OFF’LED goes solid red. NOTE: If the ON LED does not flash then the add process has been unsuccessful.
  • 12. 12 Removing from a network To remove from a Z-Wave network, follow the steps, below, also known as ‘exclusion’ in, Z-Wave, terminology - Put the 3rd party controller intoexclusionmode. - Press andhold thenetwork buttonon the SSR 303. - The SSR 303 has been removed from the network when the Network LED starts flashing. NOTE: If the Network LED does not flash the remove process has been unsuccessful. NOTE: This product can be included and operated in any Z-Wave network with other Z-Wave certified devices from other manufacturers and/or other applications.All non-battery operated nodes within the network will act as repeaters regardless of vendor to increase reliability of the network.
  • 13. 13 Node Information Frame - NIF Pressing and holding the network button for 1 second will trigger the SSR 303 to issue a Node Information Frame and enter Classic learn mode for 2s and then in NWI (Network Wide Inclusion) learn mode. This is useful to associate/disassociate the SSR 303 with a control group or just to determine the device and command classes supported. This can be done at any timebut will not provide anyindication tothe operator. Z-Wave Repeater This SSR 303 will act as a repeater once added into the Z-Wave network, providing an alternative communication route for units which otherwise would not bewithincommunication distance of each other. Device reset: “Please use this procedure only when the primary controller is missing or otherwise inoperable.” Follow “Removing from a Network” process.
  • 14. 14 Supported Device and command classes Z-Wave Plus Device Classes Implemented Device Class Generic Device Class: Specific Device Class: Basic Device Class: GENERIC TYPE SWITCH BINARY SPECIFIC TYPE POWER SWITCH BINARY ROUTING SLAVE Command Class Commands Supported Manufacturer Specific (V2) Get Report Device Specific Get Device Specific Report Manufacturer ID = 0x0059 Product Type ID = 0x0003 Product ID = 0x0005 (SSR 303) Device ID Type 0 and 1 for serial number (Data format Binary, length4 Bytes) Version (V2) Get Report Version Command Class Get Version Command Class Report Provides the version number of the Z-Wave stack, Command Class, Firmware and Hardware.
  • 15. 15 Z-Wave Plus Info (V2) Get Report RoleType:ROLE_TYPE_SLAVE_ALWAYS_ON Node Type: ZWAVEPLUS_INFO_REPORT_NODE_TYPE_ZWAVEPLUS_NODE Installer Icon: ICON_TYPE_GENERIC_ON_OFF_POWER_SWITCH User Icon: ICON_TYPE_GENERIC_ON_OFF_POWER_SWITCH Association (V2) Set Get Report Remove Supported Groupings Get Supported Groupings Report Specific Group Get Product supports one group (Lifeline) and has a maximum of 4 nodes. Association Group Info (V1) Group Name Get Group Name Report Group Info get Group Info Report Group Command List Get Group Command List Report
  • 16. 16 Only one association group is supported Group 1: name - “Lifeline” Profile MSB -ASSOCIATION_GROUP_INFO_REPORT_PROFILE_GENERAL Profile LSB - ASSOCIATION_GROUP_INFO_REPORT_PROFILE_GENERAL_LIFELINE Supported Command class and command - COMMAND_CLASS_SWITCH_BINARY, SWITCH_BINARY_REPORT Thermostat Mode (V1) Set Get Report Supported Get Supported Report Only ‘Idle Mode’ and ‘Heat Mode’ are supported within this command class, which can either set or read. The SSR 303 has a failsafe mode where by the relay is turned OFF if another Thermostat Mode SET command has not been received within 60 minutes. Switch Binary (V1) Set Get Report Supports SET and GET to control the relay. Opposed to the Thermostat command class there is no failsafe mode. If Binary Switch SET command is received than previously active failsafe mode closed.
  • 17. 17 Basic (V1) Set Get Report The Basic command class has been mapped to Switch Binary command class as follows: Basic Set : Mapped to Switch Binary Set. Basic Get : Mapped to Switch Binary Get. Basic Report : Mapped to Switch Binary Report Same as Switch Binary command class there is no failsafe mode. If Basic SET command is received than previously active failsafe mode closed. Power Level (V1) Power Level Set Power Level Get Power Level Report Power Level Test Node Set Power Level Test Node Get Power Level Test Node Report Power Level Command Class defines RF transmit power controlling commands useful when installing or testing a network. Note: For more information about Z-Wave command classes and their use refer to "SDS12652 and SDS12657 Z-Wave Command Class Specification" version 8 or above. Note: After removing from existing Z-Wave network, device comes in factory default state and will not send device reset locally notification.
  • 18. 18 Receiver specification SSR 303 Power Supply 230v 50Hz Contact type Micro disconnection Wiring configuration Voltage free c/o (SPDT) Contact voltage rating 230v ac 50Hz (30v dc) Contact current rating 3A (1A inductive) Impulse rating Category II – 2500v Transmitter frequency 868.42MHz Receiver category Category 3Power Class Class B Standards EN 60730-2-7 ETSI EN 300 220-2 / ETSI EN 301 489-3 Dimensions 86 x 86 x 36.25mm Enclosure Flame retardant thermoplastic Ingress protection IP30 Pollution degree Degree 2 Insulation class Class II Software class A Control type Type 1B Electronic control Temperature r a n g e 0-40˚C Ball pressure temperature 75˚C Purpose of control 1 channel RF receiver switch
  • 19. 19 European Head Office Secure Controls (UK) Ltd. South Bristol Business Park Roman Farm Road Bristol, BS4 1UP, UK e: info@securetogether.com www.securetogether.com European Sales Office CEWE Instrument AB Box 1006, 611 31 Nyköping t: +46 8 600 80 60 e: info@securetogether.com www.securetogether.com www.securetogether.com Australia Sales Office Secure Australasia Pty Ltd 258 Darebin Road Fairfield VIC 3078 Australia p: +61 3 9485 6000 f: +61 3 9485 6099 e: info@securetogether.com www.securetogether.com
  • 20. Secure Meters Ltd Pratap Nagar Industrial Area Udaipur 313003 India p: +91 294 2492 300-05 f: +91 294 2492 310 e: mktg@securetogether.com www.securetogether.com Elegant Metering Solutions FZE 4EA 326, P.O. Box 54857 Dubai Airport Free Zone Dubai, UAE p: +971 50 6575166 f: +971 04 204 5619 e: emsfze@emsdxb.ae www.securetogether.com Part Number P84074 Issue Number 6