TRANSFORMER
ACCESSORIES
FOR TESTING
AND
PROTECTION
By
Durgada Sagar
Electrical Engineering Student
Reva University
Bangalore
Standard Accessories on a Oil Filled
Transformer
Liquid level gauge
Liquid temperature gauge
Pressure-vacuum gauge
Pressure relief device
Winding temperature gauge
Transformer cooling fans
High voltage bushings
Low voltage bushings
De-energized tap-changer
Buchholz relay
galvanized radiators
Breather
Lifting lugs
Jacking facilities
Multi-ratio, current
transformers (CTs) for relaying
service
Surge arresters
Grounding devices, such as
reactors and resistors
De-energized tap
changer (DETC)
Load tap changers
Conservator oil preservation
systems
Various monitoring devices for
gas, oil and winding
temperatures; power factor;
moisture; etc.
Most customer-specified
accessories
Liquid Level Gauge
• Provides continuous indication of
the liquid level inside of a
transformer’s main tank, conservator
tank or load tap changer
compartment.
• Basically, it consists of a float-arm
inside the tank, an indicating pointer.
• Float travel ranges from min to max
markings for various tank
configurations
Liquid Temperature Gauge
• known as electromechanical
thermometers or OTIs are
essential devices on oil-filled
transformers, providing accurate
temperature measurement of the
oil within.
• The temperature gauge is furnished
to indicate the top liquid
temperature in the tank in degrees
Centigrade.
• The thermometer can be furnished
with two SPDT contacts for a high
temperature alarm, for energizing a
fan circuit or for a low temperature
alarm.
Pressure-Vacuum Gauge
• Designed to balance pressure and vacuum conditions
within a sealed vessel by releasing or admitting air and gas.
• High pressures indicate an overload or trouble inside the
tank and should be investigated immediately. A sustained
zero pressure reading indicates a leak or a defective gauge.
• If internal pressure reaches the pre-determined setting,
valve will exhaust gas from the tank. If vacuum inside
vessel becomes too great, the valve will admit air into the
tank
• Note: Typically the transformer is filled with oil and
pressurized with nitrogen to a pressure of 0.2 atm (3 Psi)
[Std Atm = 1atm = 14.69595 psi]
psi = Pound-Force per square inch
1 pound = 0.45 kg
Pressure Relief Device
• The PRD is used for the relief of excessive
pressure buildup in large volumes of gas or
fluid in transformers. Its patented dual
gasket system provides quick response time
and automatically reseals after pressure has
subsided.
• Should the tank pressure increase above
that for which the device is set, the gas
pressure will lift the diaphragm and let the
gas escape quickly. Immediately after the
pressure returns to normal, the diaphragm
will reset and reseal the transformer.
Winding Temperature Gauge
• All large transformers have an oil or a winding
temperature indicating device of some type, and
most have temperature recorders as well. Indication
may be for top-oil temperature or hotspot
temperature. Additional temperature-sensing
equipment may be installed to provide alarm and
control signals needed to activate automatic cooling
systems.
• Indicator operation may be:
• Purely mechanical (tank-mounted temperature gauge
or thermometer),
• Purely electrical (SCADA transducer and some chart
recorders), or
• A combination of the two (chart recorder and
multipoint temp recorder).
Transformer Cooling Fans
• In order to increase the transformer
load without overheating the windings, a set
of fans can be furnished as an optional item
.Fan control consists of a contact on either
the liquid temperature gauge or the
winding temperature gauge (when furnished),
and “Manual-Auto” control switch .
• Recommended Maximum Temperature
settings are;
A. Oil Temperature Indicator: 85°C
B. Winding Temperature Indicator:
105°C
High-Voltage Bushings
• Solid porcelain bushings consist of high-grade porcelain
cylinders that conductors pass through. Outside surfaces
have a series of skirts to increase the leakage path distance to
the grounded metal case.
• High-voltage bushings are generally oil-filled condenser type.
• Condenser types have a central conductor wound with
alternating layers of paper insulation and tin foil and filled
with insulating oil.
• A good indication of insulation deterioration is a slowly
rising power factor. The most common cause of failure is
moisture entrance through the top bushing seal.
• Care must be taken in handling the bushing to avoid cracking
the porcelain or damaging its surface.
Tap-Changer
Do not operate the tap-changer while the transformer is
energized! Doing so can result in severe personal injury and
equipment damage.
• The tap-changer provides a
means of changing the voltage
ratio of a de-energized
transformer without breaking
the transformer seal.
• It is operated by means of
a rotatable handle located on
the side of the transformer.
• The tap-changer is normally
provided with five or
seven positions.
Buchholz’s Relay
• Buchholz relay is used for the protection of transformers from the faults occurring inside the transformer.
• Internal faults such as an insulation faults between turns, breakdown of core of transformer, core heating energize
the alarm circuit and one can predict the type of fault in the transformer
• More severe types of faults, such as short circuit between phases or to earth and faults in the tap changing
equipment energize the trip circuit and immediately isolate the transformer from the rest of power system
Silica gel Breather
• The function of breather in
transformer is to filter out the
moisture from air. Breather
consist of silica gel which absorbs
the moisture from air.
• The main reason to remove
moisture from air is because the
moisture degrades the dielectric
strength of the transformer oil.
Surge Arrestors
• Lightning arresters are
protective devices for limiting
surge voltages due to lightning
strikes or equipment faults or
other events, to prevent
damage to equipment and
disruption of service. Also
called surge arresters.
• Many surge divertors are essentially non-linear resistors which when subjected to high transient overvoltage have
their resistance go to zero, thereby creating a short circuit and blowing a fuse.
• In this way it protects against damage due to serious overvoltage and also disconnects the equipment from the
circuit.
Current Transformer
• A current
transformer (CT) is a type
of transformer that is used
to reduce or multiply
an alternating current (AC).
It produces a current in its
secondary which is
proportional to the current
in its primary.
The current transformer is used to reduce the currents in power systems, producing proportional
currents in the unit’s secondary windings that remain isolated from the main circuit.
The replica current is then used as an input to a protective relay, which can then automatically
isolate part of the power circuit should it experience a fault.A CT for operation
on a 110 kV grid
References
◦ electrical-engineering-portal.com
◦ Researchgate.net
◦ Library.e.abb.com (ABB Group)
◦ Wikipedia.com
◦ insulect.com
◦ Testguy.net
◦ www.qualitrolcorp.com
◦ Spxtransformersolutions.com
◦ Azom.com
◦ Sadtem.com

More Related Content

PDF
Testing of transformer
PDF
Transformer testing
PDF
Power factor improvement
PPTX
Power factor
PPTX
Protection & switchgear
DOCX
PPTX
Electrical HT/LT Motor protection
PDF
Blackout Avoidance & Undervoltage Load Shedding
Testing of transformer
Transformer testing
Power factor improvement
Power factor
Protection & switchgear
Electrical HT/LT Motor protection
Blackout Avoidance & Undervoltage Load Shedding

What's hot (20)

PPTX
Transformer ppt.
PPTX
transformer protection
PPTX
Switchgear presentation
PPT
Operation and maintenance of transformer
PDF
Advanced Electrical Drive Controls, Types and Implementation”
PPTX
On load tap changer
PDF
Generator Protection By - Er Rahul Sharma
PDF
Transformer overcurrent
PPT
Power transformer
PDF
Transformer differential protection
PPTX
Synchronous motor drive
PPTX
Different types of Transformers used in Generating Station
PPT
Circuit Breaker : Types
PPSX
Excitation system for alternator
PDF
Dol starter by kantiakapil
PPTX
Transformer
PPTX
speed control of three phase induction motor
PPTX
Electrical transmission line
PPTX
Induction motor
PPT
three phase induction machine starter
Transformer ppt.
transformer protection
Switchgear presentation
Operation and maintenance of transformer
Advanced Electrical Drive Controls, Types and Implementation”
On load tap changer
Generator Protection By - Er Rahul Sharma
Transformer overcurrent
Power transformer
Transformer differential protection
Synchronous motor drive
Different types of Transformers used in Generating Station
Circuit Breaker : Types
Excitation system for alternator
Dol starter by kantiakapil
Transformer
speed control of three phase induction motor
Electrical transmission line
Induction motor
three phase induction machine starter
Ad

Similar to Transformer Accessories for Testing and Protection (20)

PPTX
Transformer Protection
PPTX
Inspection and Testing of various electrical equipment
PPTX
electricalsystemprotection-transformerprotection-190111055726.pptx
DOCX
Transformer
PPTX
POWER GRID
PPTX
10 different equipment used in Distribution Substation
PPTX
Transformer Overview.pptx
PPT
500MW presentation - 11102006.PPT
PDF
Boiler ppt
PPTX
Presentation training
PPTX
1.Transformer.pptx
PDF
Presentation_On_Summer_Training_from_UPP.pdf
PPTX
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
PPTX
Maintenance schedule of Substation.
PPTX
Transformer protection
PDF
transformerprotection-180102061059.pdf
PPT
Replacement Parts Industries (RPI) Everything You Ever Wanted to Know About S...
PPTX
Ppt on 132 kv gss by ashok khoja
PPT
UNIT III PROTECTION OF TRANSFORMER OCTOBER 2 (2).ppt
PPTX
Chapter 2 three-phase-transformers.pptx
Transformer Protection
Inspection and Testing of various electrical equipment
electricalsystemprotection-transformerprotection-190111055726.pptx
Transformer
POWER GRID
10 different equipment used in Distribution Substation
Transformer Overview.pptx
500MW presentation - 11102006.PPT
Boiler ppt
Presentation training
1.Transformer.pptx
Presentation_On_Summer_Training_from_UPP.pdf
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Maintenance schedule of Substation.
Transformer protection
transformerprotection-180102061059.pdf
Replacement Parts Industries (RPI) Everything You Ever Wanted to Know About S...
Ppt on 132 kv gss by ashok khoja
UNIT III PROTECTION OF TRANSFORMER OCTOBER 2 (2).ppt
Chapter 2 three-phase-transformers.pptx
Ad

Recently uploaded (20)

PDF
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
PDF
Categorization of Factors Affecting Classification Algorithms Selection
PDF
III.4.1.2_The_Space_Environment.p pdffdf
PDF
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
PDF
Improvement effect of pyrolyzed agro-food biochar on the properties of.pdf
PDF
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
PDF
Visual Aids for Exploratory Data Analysis.pdf
PPTX
Management Information system : MIS-e-Business Systems.pptx
PPTX
Fundamentals of Mechanical Engineering.pptx
PPTX
tack Data Structure with Array and Linked List Implementation, Push and Pop O...
PPTX
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
PPTX
Module 8- Technological and Communication Skills.pptx
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PPTX
CyberSecurity Mobile and Wireless Devices
PDF
August -2025_Top10 Read_Articles_ijait.pdf
PDF
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
PDF
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
PDF
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
PPTX
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
PDF
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
Categorization of Factors Affecting Classification Algorithms Selection
III.4.1.2_The_Space_Environment.p pdffdf
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
Improvement effect of pyrolyzed agro-food biochar on the properties of.pdf
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
Visual Aids for Exploratory Data Analysis.pdf
Management Information system : MIS-e-Business Systems.pptx
Fundamentals of Mechanical Engineering.pptx
tack Data Structure with Array and Linked List Implementation, Push and Pop O...
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
Module 8- Technological and Communication Skills.pptx
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
CyberSecurity Mobile and Wireless Devices
August -2025_Top10 Read_Articles_ijait.pdf
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...

Transformer Accessories for Testing and Protection

  • 2. Standard Accessories on a Oil Filled Transformer Liquid level gauge Liquid temperature gauge Pressure-vacuum gauge Pressure relief device Winding temperature gauge Transformer cooling fans High voltage bushings Low voltage bushings De-energized tap-changer Buchholz relay galvanized radiators Breather Lifting lugs Jacking facilities
  • 3. Multi-ratio, current transformers (CTs) for relaying service Surge arresters Grounding devices, such as reactors and resistors De-energized tap changer (DETC) Load tap changers Conservator oil preservation systems Various monitoring devices for gas, oil and winding temperatures; power factor; moisture; etc. Most customer-specified accessories
  • 4. Liquid Level Gauge • Provides continuous indication of the liquid level inside of a transformer’s main tank, conservator tank or load tap changer compartment. • Basically, it consists of a float-arm inside the tank, an indicating pointer. • Float travel ranges from min to max markings for various tank configurations
  • 5. Liquid Temperature Gauge • known as electromechanical thermometers or OTIs are essential devices on oil-filled transformers, providing accurate temperature measurement of the oil within. • The temperature gauge is furnished to indicate the top liquid temperature in the tank in degrees Centigrade. • The thermometer can be furnished with two SPDT contacts for a high temperature alarm, for energizing a fan circuit or for a low temperature alarm.
  • 6. Pressure-Vacuum Gauge • Designed to balance pressure and vacuum conditions within a sealed vessel by releasing or admitting air and gas. • High pressures indicate an overload or trouble inside the tank and should be investigated immediately. A sustained zero pressure reading indicates a leak or a defective gauge. • If internal pressure reaches the pre-determined setting, valve will exhaust gas from the tank. If vacuum inside vessel becomes too great, the valve will admit air into the tank • Note: Typically the transformer is filled with oil and pressurized with nitrogen to a pressure of 0.2 atm (3 Psi) [Std Atm = 1atm = 14.69595 psi] psi = Pound-Force per square inch 1 pound = 0.45 kg
  • 7. Pressure Relief Device • The PRD is used for the relief of excessive pressure buildup in large volumes of gas or fluid in transformers. Its patented dual gasket system provides quick response time and automatically reseals after pressure has subsided. • Should the tank pressure increase above that for which the device is set, the gas pressure will lift the diaphragm and let the gas escape quickly. Immediately after the pressure returns to normal, the diaphragm will reset and reseal the transformer.
  • 8. Winding Temperature Gauge • All large transformers have an oil or a winding temperature indicating device of some type, and most have temperature recorders as well. Indication may be for top-oil temperature or hotspot temperature. Additional temperature-sensing equipment may be installed to provide alarm and control signals needed to activate automatic cooling systems. • Indicator operation may be: • Purely mechanical (tank-mounted temperature gauge or thermometer), • Purely electrical (SCADA transducer and some chart recorders), or • A combination of the two (chart recorder and multipoint temp recorder).
  • 9. Transformer Cooling Fans • In order to increase the transformer load without overheating the windings, a set of fans can be furnished as an optional item .Fan control consists of a contact on either the liquid temperature gauge or the winding temperature gauge (when furnished), and “Manual-Auto” control switch . • Recommended Maximum Temperature settings are; A. Oil Temperature Indicator: 85°C B. Winding Temperature Indicator: 105°C
  • 10. High-Voltage Bushings • Solid porcelain bushings consist of high-grade porcelain cylinders that conductors pass through. Outside surfaces have a series of skirts to increase the leakage path distance to the grounded metal case. • High-voltage bushings are generally oil-filled condenser type. • Condenser types have a central conductor wound with alternating layers of paper insulation and tin foil and filled with insulating oil. • A good indication of insulation deterioration is a slowly rising power factor. The most common cause of failure is moisture entrance through the top bushing seal. • Care must be taken in handling the bushing to avoid cracking the porcelain or damaging its surface.
  • 11. Tap-Changer Do not operate the tap-changer while the transformer is energized! Doing so can result in severe personal injury and equipment damage. • The tap-changer provides a means of changing the voltage ratio of a de-energized transformer without breaking the transformer seal. • It is operated by means of a rotatable handle located on the side of the transformer. • The tap-changer is normally provided with five or seven positions.
  • 12. Buchholz’s Relay • Buchholz relay is used for the protection of transformers from the faults occurring inside the transformer. • Internal faults such as an insulation faults between turns, breakdown of core of transformer, core heating energize the alarm circuit and one can predict the type of fault in the transformer • More severe types of faults, such as short circuit between phases or to earth and faults in the tap changing equipment energize the trip circuit and immediately isolate the transformer from the rest of power system
  • 13. Silica gel Breather • The function of breather in transformer is to filter out the moisture from air. Breather consist of silica gel which absorbs the moisture from air. • The main reason to remove moisture from air is because the moisture degrades the dielectric strength of the transformer oil.
  • 14. Surge Arrestors • Lightning arresters are protective devices for limiting surge voltages due to lightning strikes or equipment faults or other events, to prevent damage to equipment and disruption of service. Also called surge arresters. • Many surge divertors are essentially non-linear resistors which when subjected to high transient overvoltage have their resistance go to zero, thereby creating a short circuit and blowing a fuse. • In this way it protects against damage due to serious overvoltage and also disconnects the equipment from the circuit.
  • 15. Current Transformer • A current transformer (CT) is a type of transformer that is used to reduce or multiply an alternating current (AC). It produces a current in its secondary which is proportional to the current in its primary. The current transformer is used to reduce the currents in power systems, producing proportional currents in the unit’s secondary windings that remain isolated from the main circuit. The replica current is then used as an input to a protective relay, which can then automatically isolate part of the power circuit should it experience a fault.A CT for operation on a 110 kV grid
  • 16. References ◦ electrical-engineering-portal.com ◦ Researchgate.net ◦ Library.e.abb.com (ABB Group) ◦ Wikipedia.com ◦ insulect.com ◦ Testguy.net ◦ www.qualitrolcorp.com ◦ Spxtransformersolutions.com ◦ Azom.com ◦ Sadtem.com

Editor's Notes

  • #3: https://electrical-engineering-portal.com/the-most-common-accessories-you-can-find-on-oil-filled-transformer
  • #13: Buchholz relay in transformer is an oil container housed the connecting pipe from main tank to conservator tank. Buchholz relay function is based on very simple mechanical phenomenon. It is mechanically actuated. Whenever there will be a minor internal fault in the transformer such as an insulation faults between turns, breakdown of core of transformer, core heating, the transformer insulating oil will be decomposed in different hydrocarbon gases, CO2 and CO. The gases produced due to decomposition of transformer insulating oil will accumulate in the upper part the Buchholz container which causes fall of oil level in it. Fall of oil level means lowering the position of float and thereby tilting the mercury switch. The contacts of this mercury switch are closed and an alarm circuit energized. By collecting the accumulated gases from the gas release pockets on the top of the relay and by analyzing them one can predict the type of fault in the transformer. More severe types of faults, such as short circuit between phases or to earth and faults in the tap changing equipment, are accompanied by a surge of oil which strikes the baffle plate and causes the mercury switch of the lower element to close. This switch energized the trip circuit of the circuit breakers associated with the transformer and immediately isolate the faulty transformer from the rest of the electrical power system by inter tripping the circuit breakers associated with both LV and HV sides of the transformer. This is how Buchholz relay functions.
  • #14: The function of breather in transformer is to filter out the moisture from air. Breather consist of silica gel which absorbs the moisture from air. When there is overloading on transformer, the winding of transformer gets heated so the oil in main tank of transformer also get heated. The hot oil started expanding. There is conservator tank at the top of transformer which allows adequate space for expansion of oil. Therefore during overloading condition the oil move to the conservator tank. In normal operating condition, the oil come back to main tank from conservator tank. Now, there is vacant space in the conservator tank which is filled with the air. Conservator tank is never completely filled as it has to allow space for expanding oil from main tank. The air which is there in conservator tank is coming from atmosphere through the breather and breather contains silica gel in it. This silica gel absorbs the moisture from air. The main reason to remove moisture from air is because the moisture degrades the dielectric strength of the transformer oil.