Transformer Efficiency
Transformer Rating
Transformer Regulation
Condition for maximum Efficiency
Why Transformers are Rated in kVA, Not in kW?
Rating of a transformer or any electrical machine reflects its load carrying
capability without overheating. Core Losses of the transformer depends on
Voltage (V) and Copper losses ( I²R) depends on Current (A) which passes
through the transformer. That's why the rating of Transformer in kVA, not in
kW.
When a manufacturer makes a transformer, they have no idea of the type of
load that will be used & consequently they can only rate the device according
to its maximum current output that the conductors can safely carry (at unity
Power Factor) & the insulation rating of the conductors (voltage &
temperature). So the transformer is designed for rated voltage and rated
current. We can't predict the power factor while designing the machine,
because power factor depends upon the load which varies time to time.
That’s why the Transformer Rating is expressed in kVA, not in kW.
Regulation of a Transformer
The measure of how well a power transformer maintains constant
secondary voltage over a range of load currents is called the transformer’s
voltage regulation. It can be calculated from the following formula:
As the transformer is loaded, the secondary terminal voltage falls (for a
lagging p.f.). Hence, to keep the output voltage constant, the primary
voltage must be increased. Suppose primary voltage has to be raised from
its rated value 𝑉1 to 𝑉1 ’, then
Problem: A 250/500-V transformer gave the following test results :
OC test : 250 V, 1 A, 80 W on low-voltage side.
SC test : with low-voltage winding short-circuited :20 V; 12 A, 100 W .
Determine the equivalent circuit parameters and insert them on the equivalent circuit
diagram and calculate the full load efficiency when the output is 10 A at 500 volt and
0.8 power factor lagging.
Solution. Open-circuit Test :
As 𝑅0 and 𝑋0 refer to primary, hence we will transfer these values to
primary with the help of transformation ratio
Transformer Efficiency
Efficiency of a Transformer
Efficiency =
Output
Input
A better method is to determine the losses and then to calculate the
efficiency from ;
or
It may be noted here that efficiency is based on power output in watts and
not in volt-amperes, al- though losses are proportional to VA. Hence, at any
volt-ampere load, the efficiency depends on power factor, being maximum at
a power factor of unity.
Condition for Maximum Efficiency
Considering primary side,
or, η
….. (1)
Differentiating both sides of equation (1) with respect to 𝐼1, we get
Condition for Maximum Efficiency
….. (2)
For η to be maximum, Hence, the equation (2) becomes
or Iron loss = Cu loss
All- day Efficiency
The ordinary or commercial efficiency of a transformer is given by the ratio
But there are certain types of transformers whose performance cannot be
judged by this efficiency; distribution transformers have their primaries
energized all the twenty-four hours, although their secondaries supply little or
no-load much of the time during the day except during the house lighting
period. The performance of such is compared on the basis of energy consumed
during a certain time period, usually a day of 24 hours
Problem: A 10 kVA, 500/250 V, single-phase transformer gave the following test results:
S.C. Test (H.V. side) : 60 V, 20 A, 150 W
The maximum efficiency occurs at unity power factor and at 1.20 times full-load current.
Determine full-load efficiency at 0.80 p.f. Also calculate the maximum efficiency.
Solution. Full-load current on H.V. side = 10,000/500 = 20 Amp
S.C. test has been conducted from H.V. side only. Hence, at unity p.f. , full-load
copper-loss is = 150 watts
(a) Maximum efficiency occurs at 1.2 times of full-load current,
So, at unity p.f. corresponding copper loss is = (1.2)2
x 150 = 216 watts
At maximum efficiency, copper-loss = core-loss = 216 watts
Corresponding Power-output = 1.2 x 10,000 x 1.0 = 12 kW
Hence, maximum efficiency at unity P.f. = (12)/(12 + 0.216 + 0.2160) = 0.9653 = 96.53 %
Problem: A 10 kVA, 500/250 V, single-phase transformer gave the following test results:
S.C. Test (H.V. side) : 60 V, 20 A, 150 W
The maximum efficiency occurs at unity power factor and at 1.20 times full-load current.
Determine full-load efficiency at 0.80 p.f. Also calculate the maximum efficiency.
Solution
(b) Full-load efficiency at 0.80 P.f.
Output Power at full-load, 0.80 P.f. = 10,000 x 0.8 = 8000 W, constant core-loss = 216 W
Corresponding copper-loss = 150 W
Total losses = 366 W
Hence, efficiency = (8000/8366) x 100 % = 95.63 %.
Conclusion
Say our substation is loaded to the maximum transformer capacity and we know it is
delivering power at a poor power factor. Our options are:
1. unload the transformer by disconnecting loads from it,
2. buy a larger transformer,
3. provide additional cooling to it (this raises the transformer capacity) or
4. correct the power factor.
Power Factor (P.F.) is the ratio of Working Power to Apparent Power.
P.F. =
𝐾𝑊
𝐾𝑉𝐴
Lagging and Leading Power Factors:
In addition, there is also a difference between a lagging and leading power factor. A lagging
power factor signifies that the load is inductive, as the load will “consume” reactive power,
and therefore the reactive component Q is positive as reactive power travels through the
circuit and is “consumed” by the inductive load. A leading power factor signifies that the
load is capacitive, as the load “supplies” reactive power, and therefore the reactive
component Q is negative as reactive power is being supplied to the circuit.
If θ is the phase angle between the current and voltage, then the power factor is
equal to the cosine of the angle, :

More Related Content

PPTX
Testing of transformer
PPTX
Insulators & It's Types
PDF
132 33kv substation documentation
PPTX
System Modeling & Simulation Introduction
PDF
System dynamics- simulation and modeling social systems
PPT
Efficiency of a transformer
PPTX
Applications of dielectric material
PPTX
TRANSFORMERS and LOSSES
Testing of transformer
Insulators & It's Types
132 33kv substation documentation
System Modeling & Simulation Introduction
System dynamics- simulation and modeling social systems
Efficiency of a transformer
Applications of dielectric material
TRANSFORMERS and LOSSES

What's hot (20)

PDF
Ideal Transformer
PDF
Ac fundamentals
PPTX
IDEAL AND PRACTICAL TRANSFORMER, EQUIVALENT CIRCUIT OF TRANSFORMER|DAY5|BASIC...
PPTX
Classification of distribution systems
PPT
Cycloconverters
PDF
Transformer basics
PPTX
Superposition theorem
PPT
Types of dc generator
PPT
ppt on the Transformer
PPT
Power transformer
PPTX
Sumpner Test on Transformers
PPTX
Invering and non inverting amplifiers
PPTX
Maximum Power Transfer Theorem
PPTX
Transformer
PDF
types of tariffs, advantage of tariff, how tariff work,.pdf
PPTX
Thyristor commutation techniques
PPTX
Load flow study
PPT
Ac fundamentals
PPTX
Voltage sag and it’s mitigation
PPTX
Ideal Transformer
Ac fundamentals
IDEAL AND PRACTICAL TRANSFORMER, EQUIVALENT CIRCUIT OF TRANSFORMER|DAY5|BASIC...
Classification of distribution systems
Cycloconverters
Transformer basics
Superposition theorem
Types of dc generator
ppt on the Transformer
Power transformer
Sumpner Test on Transformers
Invering and non inverting amplifiers
Maximum Power Transfer Theorem
Transformer
types of tariffs, advantage of tariff, how tariff work,.pdf
Thyristor commutation techniques
Load flow study
Ac fundamentals
Voltage sag and it’s mitigation
Ad

Similar to Transformer Efficiency (20)

PDF
Improvement of Load Power Factor by Using Capacitor
PPTX
Power Factor its Importance and Improvement.pptx
PPT
BEF 23803 - Lecture 8 - Conservation of Complex Power.ppt
PPTX
PowerFactorImprovement.pptx
PPT
Power factor presentation
PPT
L08 power amplifier (class a)
PPT
Active and reactive power and its equations
PPTX
Power factor
PPTX
THE POWER FACTOR
PPT
presentation_transformers_1489551826_236516.ppt
PDF
Micro-controller based Automatic Power Factor Correction System Report
PPTX
Open circuit and Short circuit Test Presentaion
PDF
Power Factor
PDF
BERG2133 -Chapter 5. Study Hard and get your Results
PDF
Assignment & solution (selected)
PPT
3.4 analysing transformer
PDF
PDF
Power factor
PDF
Power Factor : Basics and Benefits of Improvement
Improvement of Load Power Factor by Using Capacitor
Power Factor its Importance and Improvement.pptx
BEF 23803 - Lecture 8 - Conservation of Complex Power.ppt
PowerFactorImprovement.pptx
Power factor presentation
L08 power amplifier (class a)
Active and reactive power and its equations
Power factor
THE POWER FACTOR
presentation_transformers_1489551826_236516.ppt
Micro-controller based Automatic Power Factor Correction System Report
Open circuit and Short circuit Test Presentaion
Power Factor
BERG2133 -Chapter 5. Study Hard and get your Results
Assignment & solution (selected)
3.4 analysing transformer
Power factor
Power Factor : Basics and Benefits of Improvement
Ad

More from Muhammad Ridwanul Hoque (20)

PPTX
Reteplase Vs Alteplase in Ischaemic stroke.pptx
PPTX
Clinical Management of Covid-19 (Bangladesh)
PPTX
Enhanced Recovery After Colorectal Surgery
PDF
AC Distribution in Bangladesh (in a nutshell)
PPTX
Impedance Matching
PPTX
Transmission Line Constraints
PPTX
Equipment and Stability Constraints : System Operation
PPTX
Power System Control
PPTX
Issues in Interconnections
PPTX
Hydro Power Plant
PPTX
Steam Power Plant and Rankine Cycles
PPT
Steam Power Plant
PPTX
AC Distribution System in Bangladesh
PPT
Power System Stability
PPT
Economic Operation of Power System
PPT
Unsymmetrical Fault
PPT
Symmetrical Components and Sequence Networks
PPT
Symmetrical Fault
PPT
Power Flow Solution
PPT
Current and Voltage Relation on a Transmission LIne
Reteplase Vs Alteplase in Ischaemic stroke.pptx
Clinical Management of Covid-19 (Bangladesh)
Enhanced Recovery After Colorectal Surgery
AC Distribution in Bangladesh (in a nutshell)
Impedance Matching
Transmission Line Constraints
Equipment and Stability Constraints : System Operation
Power System Control
Issues in Interconnections
Hydro Power Plant
Steam Power Plant and Rankine Cycles
Steam Power Plant
AC Distribution System in Bangladesh
Power System Stability
Economic Operation of Power System
Unsymmetrical Fault
Symmetrical Components and Sequence Networks
Symmetrical Fault
Power Flow Solution
Current and Voltage Relation on a Transmission LIne

Recently uploaded (20)

PPTX
Artificial Intelligence
PDF
Design Guidelines and solutions for Plastics parts
PPTX
Current and future trends in Computer Vision.pptx
PDF
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
PPTX
Fundamentals of Mechanical Engineering.pptx
PPTX
Sorting and Hashing in Data Structures with Algorithms, Techniques, Implement...
PPTX
"Array and Linked List in Data Structures with Types, Operations, Implementat...
PPTX
Fundamentals of safety and accident prevention -final (1).pptx
PPTX
Management Information system : MIS-e-Business Systems.pptx
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
Categorization of Factors Affecting Classification Algorithms Selection
PDF
Visual Aids for Exploratory Data Analysis.pdf
PPTX
Nature of X-rays, X- Ray Equipment, Fluoroscopy
PDF
22EC502-MICROCONTROLLER AND INTERFACING-8051 MICROCONTROLLER.pdf
PDF
August 2025 - Top 10 Read Articles in Network Security & Its Applications
PDF
Soil Improvement Techniques Note - Rabbi
PPTX
Safety Seminar civil to be ensured for safe working.
PDF
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
PDF
III.4.1.2_The_Space_Environment.p pdffdf
PDF
Abrasive, erosive and cavitation wear.pdf
Artificial Intelligence
Design Guidelines and solutions for Plastics parts
Current and future trends in Computer Vision.pptx
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
Fundamentals of Mechanical Engineering.pptx
Sorting and Hashing in Data Structures with Algorithms, Techniques, Implement...
"Array and Linked List in Data Structures with Types, Operations, Implementat...
Fundamentals of safety and accident prevention -final (1).pptx
Management Information system : MIS-e-Business Systems.pptx
R24 SURVEYING LAB MANUAL for civil enggi
Categorization of Factors Affecting Classification Algorithms Selection
Visual Aids for Exploratory Data Analysis.pdf
Nature of X-rays, X- Ray Equipment, Fluoroscopy
22EC502-MICROCONTROLLER AND INTERFACING-8051 MICROCONTROLLER.pdf
August 2025 - Top 10 Read Articles in Network Security & Its Applications
Soil Improvement Techniques Note - Rabbi
Safety Seminar civil to be ensured for safe working.
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
III.4.1.2_The_Space_Environment.p pdffdf
Abrasive, erosive and cavitation wear.pdf

Transformer Efficiency

  • 1. Transformer Efficiency Transformer Rating Transformer Regulation Condition for maximum Efficiency
  • 2. Why Transformers are Rated in kVA, Not in kW? Rating of a transformer or any electrical machine reflects its load carrying capability without overheating. Core Losses of the transformer depends on Voltage (V) and Copper losses ( I²R) depends on Current (A) which passes through the transformer. That's why the rating of Transformer in kVA, not in kW. When a manufacturer makes a transformer, they have no idea of the type of load that will be used & consequently they can only rate the device according to its maximum current output that the conductors can safely carry (at unity Power Factor) & the insulation rating of the conductors (voltage & temperature). So the transformer is designed for rated voltage and rated current. We can't predict the power factor while designing the machine, because power factor depends upon the load which varies time to time. That’s why the Transformer Rating is expressed in kVA, not in kW.
  • 3. Regulation of a Transformer The measure of how well a power transformer maintains constant secondary voltage over a range of load currents is called the transformer’s voltage regulation. It can be calculated from the following formula:
  • 4. As the transformer is loaded, the secondary terminal voltage falls (for a lagging p.f.). Hence, to keep the output voltage constant, the primary voltage must be increased. Suppose primary voltage has to be raised from its rated value 𝑉1 to 𝑉1 ’, then
  • 5. Problem: A 250/500-V transformer gave the following test results : OC test : 250 V, 1 A, 80 W on low-voltage side. SC test : with low-voltage winding short-circuited :20 V; 12 A, 100 W . Determine the equivalent circuit parameters and insert them on the equivalent circuit diagram and calculate the full load efficiency when the output is 10 A at 500 volt and 0.8 power factor lagging. Solution. Open-circuit Test :
  • 6. As 𝑅0 and 𝑋0 refer to primary, hence we will transfer these values to primary with the help of transformation ratio
  • 8. Efficiency of a Transformer Efficiency = Output Input A better method is to determine the losses and then to calculate the efficiency from ; or It may be noted here that efficiency is based on power output in watts and not in volt-amperes, al- though losses are proportional to VA. Hence, at any volt-ampere load, the efficiency depends on power factor, being maximum at a power factor of unity.
  • 9. Condition for Maximum Efficiency Considering primary side, or, η ….. (1) Differentiating both sides of equation (1) with respect to 𝐼1, we get
  • 10. Condition for Maximum Efficiency ….. (2) For η to be maximum, Hence, the equation (2) becomes or Iron loss = Cu loss
  • 11. All- day Efficiency The ordinary or commercial efficiency of a transformer is given by the ratio But there are certain types of transformers whose performance cannot be judged by this efficiency; distribution transformers have their primaries energized all the twenty-four hours, although their secondaries supply little or no-load much of the time during the day except during the house lighting period. The performance of such is compared on the basis of energy consumed during a certain time period, usually a day of 24 hours
  • 12. Problem: A 10 kVA, 500/250 V, single-phase transformer gave the following test results: S.C. Test (H.V. side) : 60 V, 20 A, 150 W The maximum efficiency occurs at unity power factor and at 1.20 times full-load current. Determine full-load efficiency at 0.80 p.f. Also calculate the maximum efficiency. Solution. Full-load current on H.V. side = 10,000/500 = 20 Amp S.C. test has been conducted from H.V. side only. Hence, at unity p.f. , full-load copper-loss is = 150 watts (a) Maximum efficiency occurs at 1.2 times of full-load current, So, at unity p.f. corresponding copper loss is = (1.2)2 x 150 = 216 watts At maximum efficiency, copper-loss = core-loss = 216 watts Corresponding Power-output = 1.2 x 10,000 x 1.0 = 12 kW Hence, maximum efficiency at unity P.f. = (12)/(12 + 0.216 + 0.2160) = 0.9653 = 96.53 %
  • 13. Problem: A 10 kVA, 500/250 V, single-phase transformer gave the following test results: S.C. Test (H.V. side) : 60 V, 20 A, 150 W The maximum efficiency occurs at unity power factor and at 1.20 times full-load current. Determine full-load efficiency at 0.80 p.f. Also calculate the maximum efficiency. Solution (b) Full-load efficiency at 0.80 P.f. Output Power at full-load, 0.80 P.f. = 10,000 x 0.8 = 8000 W, constant core-loss = 216 W Corresponding copper-loss = 150 W Total losses = 366 W Hence, efficiency = (8000/8366) x 100 % = 95.63 %.
  • 15. Say our substation is loaded to the maximum transformer capacity and we know it is delivering power at a poor power factor. Our options are: 1. unload the transformer by disconnecting loads from it, 2. buy a larger transformer, 3. provide additional cooling to it (this raises the transformer capacity) or 4. correct the power factor. Power Factor (P.F.) is the ratio of Working Power to Apparent Power. P.F. = 𝐾𝑊 𝐾𝑉𝐴
  • 16. Lagging and Leading Power Factors: In addition, there is also a difference between a lagging and leading power factor. A lagging power factor signifies that the load is inductive, as the load will “consume” reactive power, and therefore the reactive component Q is positive as reactive power travels through the circuit and is “consumed” by the inductive load. A leading power factor signifies that the load is capacitive, as the load “supplies” reactive power, and therefore the reactive component Q is negative as reactive power is being supplied to the circuit. If θ is the phase angle between the current and voltage, then the power factor is equal to the cosine of the angle, :