Non-intrusive Methods for Mode
Estimation in Power Systems using
Synchrophasors
Vedran S. Perić
March 15, 2016PhD Defense Presentation
Outline
1
• Oscillations – modes, ambient excitation
2
• Principles of mode estimation
3
• Optimal probing design and signal selection
4
• Mode estimation with non-white loads
5
• Prototype implementation
6
• Conclusions
2/28
Oscillations
 General phenomenon
 Excitation types
 Omnipresent random
excitation (ambient)
 Intrinsic property of
the system (modes)
3/28
Electromechanical oscillations in
power systems
”The largest and most complex machine
ever built by humankind”
4/28
49.85
49.9
49.95
50
50.05
50.1
50.15
08:00:00 08:05:00 08:10:00 08:15:00
f[Hz]
20110219_0755-0825
Freq. Mettlen Freq. Brindisi Freq. Kassoe
Why do we care ?
PMU Data
Oscillations if lightly damped can lead to a system black-out
Occupy transmission capacities, increase losses, wear and tear
February 19th 2011 – North-South Inter-Area Oscillation
Continuously monitor frequency and damping
5/28
Application objectives
Avoid black-outs
Real-time monitoring
Decision support
tools
Control actions
6/28
Outline
1
• Oscillations – ambient excitation, modes
2
• Principles of mode estimation
3
• Optimal probing design and signal selection
4
• Mode estimation with non-white loads
5
• Prototype implementation
6
• Conclusions
7/28
Basic principles of mode estimation
Power system
dx/dt=Ax+Bu
y=Cx+Du
Inputs
(load noise)
Outputs
(PMUs)
Deterministic
signal
Exactly known excitation brings new information
that can be used for improved mode identification
Probing signals
FACTS devices
AVR
Turbine governors
H(θ,z)
G(θ,z)
e(t) y(t)
u(t) - designed
input signal
Aggregated
load noise
Single output model
8/28
 Model structure of the power system
o ARMAX
o Box Jenkins
Mathematical formulation
 Optimization problem:
min
𝜃
1
𝑁
𝑡=1
𝑁
𝜀 𝑡, 𝜃 2 𝜀(𝑡, 𝜃) = 𝑦(𝑡) − 𝑦
⌢
(𝑡|𝑡 − 1
Solution - identified model
( , ) ( , )
( ) ( ) ( )
( , ) ( , )
B z C z
y t u t e t
A z D z
 
 
  Contain information about
the critical modes/poles
9/28
Model order selection
 Too low model order => bias of the estimate
 Too high model order => large variance/inaccuracy
Data length Time resolutionvs
Methods:
 Residual analysis
 Singular value analysis
 Akaike Information Criterion
 Variance-Accounted-For
10/28
Outline
1
• Oscillations – ambient excitation, modes
2
• Principles of mode estimation
3
• Optimal probing design and signal selection
4
• Mode estimation with non-white loads
5
• Prototype implementation
6
• Conclusions
11/28
Optimal probing – problem formulation
 Objective: Identify the
critical damping ratio of G(z)
 

 
         




 
   
       
   
 
1 * *
0 0 0 02
1
( , ) ( , ) ( , ) ( , )
2 2
( )u euu e
N N
P F F d F F d
H(θ,z)
G(θ,z)
e(t) y(t)
u(t) - input signal
load measurement
How should the probing signal look like ?
12/28
Spectrum influences accuracy

1
P Good estimate

1
P Bad estimate
 ( )u
 ( )u
There is a limit how strong probing can be
Stronger probing provides better accuracy
Spectrum calculation of the probing signal
1) Control effort 2) System disturbance 3) Accuracy
Objective function
 
 
   
  
   
         
   
 
2
1 2
(t)
min ( ) (s) ( )
2 2u uu
k k
J d G d
Constraint: var( ) T
i i i
e P e r
   r - tolerance
Input power Output power
(frequency deviation)
 Requirements :
Optimization problem in a form of LMI
The solution is the power spectrum of the probing signal
14/28
Time domain probing signal realization
 Spectrum calculation (solved)
 Time domain signal realization
LMI
Signal realization
max var(ζ)
Multisine
ACF (rd)
min(upeak
2
/urms
2
)
FIR filter
min(║ r-rd║2
)
white noise - e(t)
u(t)
u(t)
u(t)
Probing Φu(ω) calculation
13/28
A method for probing signal realization
 Power spectrum



  ( ) ( )
m
j r
u des
r m
ACF r e
1
1
( ) ( ) ( )
k
k
i
ACF u i u i
k 
 
 
 
 
2
( )
0
( ) ( )
M K
k des
u k
min ACF ACF

 



 Sample autocorrelation
 Optimization
 Efficient recursive algorithm
15/28
Aimed probing
autocorrelation
General expression
for autocorrelation
Time domain signal as
the decision variable
Optimal probing signal design results
0 0.5 1 1.5 2 2.5
0
5000
10000
15000
Frequency [Hz]
Powerspectrum
0 0.5 1 1.5 2 2.5
0
1
2
3
4
x 10
5
Frequency [Hz]
Powerspectrum
Input spectrum parameterization
White noise Multi-sine FIR filter
var{u(t)} 10410.0 1441.58 1933.55
var{y(t)} 1.6761 1.598 1.5515
var{uy(t)} 6881.10 2318.81 2518.24
The same accuracy obtained with the 5-7 times weaker
excitation
The same input power provides 4-5 times better accuracy
(0.25*10-5)
Damping variance < 10-5
Benefits of
the proposed
method
16/28
KTH Nordic 32
Minimized
input power
Minimized
disturbance2 critical modes
0.5Hz & 0.76Hz
Reactive power
probing
Optimal signal selection for mode
estimation
 Only a few signals are sufficient for accurate estimation
 Large number of signals introduce bias and extensive
computational effort
 Variance of the estimate describes estimation quality
Compute asymptotic variance for each measured signal
Rank the signals
Select the top ones
 

 
          
 

 
   
        
   
 
1 * *
0 0 0 02
1
( , ) ( , ) ( , ) ( , ) ( )
2 2e e u u u
N N
P F F d F F d



    



 
   
 

1 *
0 0
( , ) ( , )
2 e e
N
P F F d
17/28
49 48 50 17 40 31 18 42 44 47
0.09
0.1
0.11
0.12
0.13
0.14
0.15
1 2 3 4 5 6 7 8 9 10
Voltage angles
37 26 36 32 34 39 38 43 22 21
0.15
0.16
0.17
0.18
0.19
0.2
0.21
0.22
0.23
1 2 3 4 5 6 7 8 9 10
Voltage magnitudes
Optimal signal selection results
18/28
Outline
1
• Oscillations – ambient excitation, modes
2
• Principles of mode estimation
3
• Optimal probing design and signal selection
4
• Mode estimation with non-white loads
5
• Prototype implementation
6
• Conclusions
19/28
Ambient mode estimation with
non-white loads - Approach
20
 Transmission/distribution
border points have PMUs
 Non-white loads are inputs
 Input-output identification
Source: EirGrid plc
Transmission
Distribution
20/28
Non-white noise excitation
corrupts results of the classical
mode estimators
Mode estimation considering spectral
characteristics of load
 Direct closed loop identification
 Only modes of the transmission
parts are identified
0 0.5 1 1.5 2
0.495
0.497
0.499
0.501
0.503
0.505

ModeFrequency[Hz]
0 0.5 1 1.5 2 2.5 3
0.495
0.497
0.499
0.501
0.503
0.505
0 0.5 1 1.5 2
1
1.8
2.6
3.4
4.2
5
0 0.5 1 1.5 2 2.5 3
1
1.8
2.6
3.4
4.2
5
Kpf
ModeDamping[%]
Mode frequency vs 
Mode frequency vs Kpf
Mode damping vs 
Mode damping vs Kpf
𝑃𝐿 = 𝑃0
𝑉
𝑉0
𝛼
(1 + 𝐾 𝑝𝑓 𝛥𝑓)
Transmission
Load Power State (V,θ)
Loads
Independent disturbance
(white noise)
21/28
 Load effects are compensated
afterwards
Results – Presence of forced oscillations
0 20 40 60 80 100
0
0.2
0.4
0.6
0.8
1
1.2
Damping ratio [%]
Frequency[Hz]
Estimated modes
Real system modes
0 20 40 60 80 100
0
0.2
0.4
0.6
0.8
1
1.2
Damping ratio [%]
Frequency[Hz]
Estimated modes
Real system modes
Yule-Walker method
Forced oscillation (0.45 Hz)
0 20 40 60 80 100
0
0.2
0.4
0.6
0.8
1
1.2
Damping ratio [%]
Frequency[Hz]
Estimated modes
Real system modes
N4SID method
 KTH Nordic32 system with forced oscillation at 0.45 Hz
 Monte Carlo simulations (large number of mode estimations)
 Classical methods:
– Forced oscillation estimated as a critical mode
– Real system mode masked by the forced oscillation
Classical methods Proposed method
22/28
Proposed method discerns the forced oscillation
Results – white noise input
 When all assumptions used in
classical mode estimators are
fully satisfied
 All methods provide similar
results
0 20 40 60 80 100
0
0.2
0.4
0.6
0.8
1
1.2
Damping ratio [%]
Frequency[Hz]
Estimated modes
Real system modes
0 20 40 60 80 100
0
0.2
0.4
0.6
0.8
1
1.2
Damping ratio [%]
Frequency[Hz]
Estimated modes
Real system modes
0 20 40 60 80 100
0
0.2
0.4
0.6
0.8
1
1.2
Damping ratio [%]
Frequency[Hz]
Estimated modes
Real system modes
Classical methods
Yule-Walker method N4SID method
Parameters
Yule-
Walker
N4SID
Proposed
Method
Mode1
Mean {f} [Hz] 0.4972 0.4978 0.4966
Mean {} [%] 3.3081 4.1213 3.8104
Var {f} 8.8670e-6 1.6260e-5 1.6592e-5
Var {} 0.2728 0.7942 0.8561
Mode2
Mean {f} [Hz] 0.7334 0.7309 0.7386
Mean {} [%] 3.8184 4.7095 3.5497
Var {f} 1.4072e-5 6.2711e-5 2.3151e-5
Var{} 0.3563 1.7925 0.5965
Proposed method
23/28
Outline
1
• Oscillations – ambient excitation, modes
2
• Principles of mode estimation
3
• Optimal probing design and signal selection
4
• Mode estimation with non-white loads
5
• Prototype implementation
6
• Conclusions
24/28
 Power system or real-time simulator
 Phasor measurement units (PMUs).
 Phasor data concentrator (PDC)
SDK
PMU 1
PMU 2
PMU n
PDC
Comm.
Network
IEEE C37.118 Protocol
KTH SmarTS Lab
Wide Area Measurements System
Real
system
Real time
simulator
User
application
Source Measurements Comm. Infrastructure Decoder
 Communication Network
 Software Development Kit (SDK)
 User applications
25/28
Prototype mode estimation application
 LabVIEW platform
 Real-life data
 The critical mode 0.39 Hz
damping ratio 9 %
(average)
 Other modes are
observable at 0.2 Hz, 1 Hz
and 1.4 Hz
 0.5 Hz mode sporadically
appears as a poorly
damped mode
26/28
Conclusions
 A comprehensive way of dealing with mode estimation
uncertainty.
 Probing when carefully designed provides a good mode
estimation accuracy at low cost.
 Some signals provide better mode estimates than others.
Quality signal criterion is proposed.
 A method that eliminates negative effects of non-white ambient
excitation is proposed.
 Testing of the mode estimation tools needs to include other
components of the system.
27/28
Thank you!
Questions?
Vedran Perić
email:vperic@kth.se
28/28

More Related Content

PDF
Multiple Sensors Soft-Failure Diagnosis Based on Kalman Filter
PPTX
A Novel Extended Adaptive Thresholding for Industrial Alarm Systems
PPT
MS_thesis_presentation
PDF
Hendrik_VANDEMAELE_Report
DOCX
Design and Implementation of an RPM Sensor and Power System for the Study and...
PDF
Performance Comparison of Identification Methods Applied to Power Systems for...
PDF
Filter-Type Fault Detection and Exclusion (FDE) on Multi-Frequency GNSS Receiver
PDF
Discrete Nonlinear Optimal Control of S/C Formations Near The L1 and L2 poi...
Multiple Sensors Soft-Failure Diagnosis Based on Kalman Filter
A Novel Extended Adaptive Thresholding for Industrial Alarm Systems
MS_thesis_presentation
Hendrik_VANDEMAELE_Report
Design and Implementation of an RPM Sensor and Power System for the Study and...
Performance Comparison of Identification Methods Applied to Power Systems for...
Filter-Type Fault Detection and Exclusion (FDE) on Multi-Frequency GNSS Receiver
Discrete Nonlinear Optimal Control of S/C Formations Near The L1 and L2 poi...

What's hot (6)

PDF
Control of new 3 d chaotic system
PPT
reliability workshop
PDF
Influence of Sensorless Control on the Noise of Switched Reluctance Motor Drive
PDF
Jp2416601666
PDF
KMEM4212_Applied Vibration_Group Assignment_Report_CL 3
PPTX
FYP_Thesis Presentation
Control of new 3 d chaotic system
reliability workshop
Influence of Sensorless Control on the Noise of Switched Reluctance Motor Drive
Jp2416601666
KMEM4212_Applied Vibration_Group Assignment_Report_CL 3
FYP_Thesis Presentation
Ad

Similar to Vedran Peric's PhD Defense Presentation: Non-intrusive Methods for Mode Estimation in Power Systems using Synchrophasors (20)

PDF
Optimal Multisine Probing Signal Design for Power System Electromechanical Mo...
DOCX
Measurement_interarea_oscillation with.docx
PPTX
Detection of Power Line Disturbances using DSP Techniques
PDF
Performance Comparison of Power Quality Evaluation Using Advanced High Resolu...
PDF
Lecture 29
PDF
Adaptive and inteligence
PDF
STAN Tool overview
PPTX
Real-Time Testing of a Decentralized PMU Data-Based Power Systems Mode Estim...
PPTX
Low frequency mode estimation
PPTX
Stability of IBR Dominated Grids - IEEE PEDG 2025 - short.pptx
PDF
call for papers, research paper publishing, where to publish research paper, ...
PPTX
IEEE International Conference Presentation
PPTX
Presentation on the power quality and accuracy
PDF
Stability of Target Resonance Modes: Ina Quadrature Polarization Context
PPTX
presentation_btp
PDF
Power System State Estimation - A Review
PPTX
Distributed_Array_Algos.pptx
PDF
Icaee paper id 116.pdf
PDF
Oscillatory Stability Prediction Using PSO Based Synchronizing and Damping To...
PDF
USRP Implementation of Max-Min SNR Signal Energy based Spectrum Sensing Algor...
Optimal Multisine Probing Signal Design for Power System Electromechanical Mo...
Measurement_interarea_oscillation with.docx
Detection of Power Line Disturbances using DSP Techniques
Performance Comparison of Power Quality Evaluation Using Advanced High Resolu...
Lecture 29
Adaptive and inteligence
STAN Tool overview
Real-Time Testing of a Decentralized PMU Data-Based Power Systems Mode Estim...
Low frequency mode estimation
Stability of IBR Dominated Grids - IEEE PEDG 2025 - short.pptx
call for papers, research paper publishing, where to publish research paper, ...
IEEE International Conference Presentation
Presentation on the power quality and accuracy
Stability of Target Resonance Modes: Ina Quadrature Polarization Context
presentation_btp
Power System State Estimation - A Review
Distributed_Array_Algos.pptx
Icaee paper id 116.pdf
Oscillatory Stability Prediction Using PSO Based Synchronizing and Damping To...
USRP Implementation of Max-Min SNR Signal Energy based Spectrum Sensing Algor...
Ad

More from Luigi Vanfretti (20)

PPTX
Hopf Bifurcation Control of Power Systems Nonlinear Dynamics Via a Dynamic St...
PPTX
Hopf Bifurcation Control of Power System Nonlinear Dynamics via a Dynamic Sta...
PPTX
Vulnerability of Synchrophasor-based WAMPAC Applications’ to Time-Synchroniza...
PPTX
Model-Simulation-and-Measurement-Based Systems Engineering of Power System Sy...
PDF
Monitoring of Transmission and Distribution Grids using PMUs
PPTX
Hands-on-OpenIPSL.org using OpenModelica!
PPTX
Modeling and Simulation of Electrical Power Systems using OpenIPSL.org and Gr...
PPTX
Phasor State Estimation Weighting Coefficients for AC and Hybrid Networks wit...
PPTX
A SGAM-Based Architecture for Synchrophasor Applications Facilitating TSO/DSO...
PPTX
A Three-Phase VSC-HVDC Average Value Model Implementation using Modelica and ...
PDF
Impact of GPS Signal Loss and Spoofing on Power System Synchrophasor Applicat...
PPTX
Open Source Software Tools for Synchrophasor Applications
PDF
Synchrophasor Applications Facilitating Interactions between Transmission and...
PDF
Real-Time Simulation for MBSE of Synchrophasor Systems
PDF
Workshop on Synchrophasors and Control Applications for Power Systems
PDF
Wanted!: Open M&S Standards and Technologies for the Smart Grid - Introducing...
PDF
Binding CIM and Modelica for Consistent Power System Dynamic Model Exchange a...
PDF
Real-Time Hardware-in-the-Loop Testing of an Excitation Control System for Os...
PDF
PMU-Based Real-Time Damping Control System Software and Hardware Architecture...
PDF
06 2015 pesgm_wllv_vsc
Hopf Bifurcation Control of Power Systems Nonlinear Dynamics Via a Dynamic St...
Hopf Bifurcation Control of Power System Nonlinear Dynamics via a Dynamic Sta...
Vulnerability of Synchrophasor-based WAMPAC Applications’ to Time-Synchroniza...
Model-Simulation-and-Measurement-Based Systems Engineering of Power System Sy...
Monitoring of Transmission and Distribution Grids using PMUs
Hands-on-OpenIPSL.org using OpenModelica!
Modeling and Simulation of Electrical Power Systems using OpenIPSL.org and Gr...
Phasor State Estimation Weighting Coefficients for AC and Hybrid Networks wit...
A SGAM-Based Architecture for Synchrophasor Applications Facilitating TSO/DSO...
A Three-Phase VSC-HVDC Average Value Model Implementation using Modelica and ...
Impact of GPS Signal Loss and Spoofing on Power System Synchrophasor Applicat...
Open Source Software Tools for Synchrophasor Applications
Synchrophasor Applications Facilitating Interactions between Transmission and...
Real-Time Simulation for MBSE of Synchrophasor Systems
Workshop on Synchrophasors and Control Applications for Power Systems
Wanted!: Open M&S Standards and Technologies for the Smart Grid - Introducing...
Binding CIM and Modelica for Consistent Power System Dynamic Model Exchange a...
Real-Time Hardware-in-the-Loop Testing of an Excitation Control System for Os...
PMU-Based Real-Time Damping Control System Software and Hardware Architecture...
06 2015 pesgm_wllv_vsc

Recently uploaded (20)

PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
Well-logging-methods_new................
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
web development for engineering and engineering
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PPTX
Sustainable Sites - Green Building Construction
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PPT
Project quality management in manufacturing
PPTX
Welding lecture in detail for understanding
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Embodied AI: Ushering in the Next Era of Intelligent Systems
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Well-logging-methods_new................
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
web development for engineering and engineering
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
Automation-in-Manufacturing-Chapter-Introduction.pdf
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
Model Code of Practice - Construction Work - 21102022 .pdf
Sustainable Sites - Green Building Construction
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
Project quality management in manufacturing
Welding lecture in detail for understanding
R24 SURVEYING LAB MANUAL for civil enggi
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...

Vedran Peric's PhD Defense Presentation: Non-intrusive Methods for Mode Estimation in Power Systems using Synchrophasors

  • 1. Non-intrusive Methods for Mode Estimation in Power Systems using Synchrophasors Vedran S. Perić March 15, 2016PhD Defense Presentation
  • 2. Outline 1 • Oscillations – modes, ambient excitation 2 • Principles of mode estimation 3 • Optimal probing design and signal selection 4 • Mode estimation with non-white loads 5 • Prototype implementation 6 • Conclusions 2/28
  • 3. Oscillations  General phenomenon  Excitation types  Omnipresent random excitation (ambient)  Intrinsic property of the system (modes) 3/28
  • 4. Electromechanical oscillations in power systems ”The largest and most complex machine ever built by humankind” 4/28
  • 5. 49.85 49.9 49.95 50 50.05 50.1 50.15 08:00:00 08:05:00 08:10:00 08:15:00 f[Hz] 20110219_0755-0825 Freq. Mettlen Freq. Brindisi Freq. Kassoe Why do we care ? PMU Data Oscillations if lightly damped can lead to a system black-out Occupy transmission capacities, increase losses, wear and tear February 19th 2011 – North-South Inter-Area Oscillation Continuously monitor frequency and damping 5/28
  • 6. Application objectives Avoid black-outs Real-time monitoring Decision support tools Control actions 6/28
  • 7. Outline 1 • Oscillations – ambient excitation, modes 2 • Principles of mode estimation 3 • Optimal probing design and signal selection 4 • Mode estimation with non-white loads 5 • Prototype implementation 6 • Conclusions 7/28
  • 8. Basic principles of mode estimation Power system dx/dt=Ax+Bu y=Cx+Du Inputs (load noise) Outputs (PMUs) Deterministic signal Exactly known excitation brings new information that can be used for improved mode identification Probing signals FACTS devices AVR Turbine governors H(θ,z) G(θ,z) e(t) y(t) u(t) - designed input signal Aggregated load noise Single output model 8/28
  • 9.  Model structure of the power system o ARMAX o Box Jenkins Mathematical formulation  Optimization problem: min 𝜃 1 𝑁 𝑡=1 𝑁 𝜀 𝑡, 𝜃 2 𝜀(𝑡, 𝜃) = 𝑦(𝑡) − 𝑦 ⌢ (𝑡|𝑡 − 1 Solution - identified model ( , ) ( , ) ( ) ( ) ( ) ( , ) ( , ) B z C z y t u t e t A z D z       Contain information about the critical modes/poles 9/28
  • 10. Model order selection  Too low model order => bias of the estimate  Too high model order => large variance/inaccuracy Data length Time resolutionvs Methods:  Residual analysis  Singular value analysis  Akaike Information Criterion  Variance-Accounted-For 10/28
  • 11. Outline 1 • Oscillations – ambient excitation, modes 2 • Principles of mode estimation 3 • Optimal probing design and signal selection 4 • Mode estimation with non-white loads 5 • Prototype implementation 6 • Conclusions 11/28
  • 12. Optimal probing – problem formulation  Objective: Identify the critical damping ratio of G(z)                                        1 * * 0 0 0 02 1 ( , ) ( , ) ( , ) ( , ) 2 2 ( )u euu e N N P F F d F F d H(θ,z) G(θ,z) e(t) y(t) u(t) - input signal load measurement How should the probing signal look like ? 12/28 Spectrum influences accuracy  1 P Good estimate  1 P Bad estimate  ( )u  ( )u There is a limit how strong probing can be Stronger probing provides better accuracy
  • 13. Spectrum calculation of the probing signal 1) Control effort 2) System disturbance 3) Accuracy Objective function                                2 1 2 (t) min ( ) (s) ( ) 2 2u uu k k J d G d Constraint: var( ) T i i i e P e r    r - tolerance Input power Output power (frequency deviation)  Requirements : Optimization problem in a form of LMI The solution is the power spectrum of the probing signal 14/28
  • 14. Time domain probing signal realization  Spectrum calculation (solved)  Time domain signal realization LMI Signal realization max var(ζ) Multisine ACF (rd) min(upeak 2 /urms 2 ) FIR filter min(║ r-rd║2 ) white noise - e(t) u(t) u(t) u(t) Probing Φu(ω) calculation 13/28
  • 15. A method for probing signal realization  Power spectrum      ( ) ( ) m j r u des r m ACF r e 1 1 ( ) ( ) ( ) k k i ACF u i u i k          2 ( ) 0 ( ) ( ) M K k des u k min ACF ACF        Sample autocorrelation  Optimization  Efficient recursive algorithm 15/28 Aimed probing autocorrelation General expression for autocorrelation Time domain signal as the decision variable
  • 16. Optimal probing signal design results 0 0.5 1 1.5 2 2.5 0 5000 10000 15000 Frequency [Hz] Powerspectrum 0 0.5 1 1.5 2 2.5 0 1 2 3 4 x 10 5 Frequency [Hz] Powerspectrum Input spectrum parameterization White noise Multi-sine FIR filter var{u(t)} 10410.0 1441.58 1933.55 var{y(t)} 1.6761 1.598 1.5515 var{uy(t)} 6881.10 2318.81 2518.24 The same accuracy obtained with the 5-7 times weaker excitation The same input power provides 4-5 times better accuracy (0.25*10-5) Damping variance < 10-5 Benefits of the proposed method 16/28 KTH Nordic 32 Minimized input power Minimized disturbance2 critical modes 0.5Hz & 0.76Hz Reactive power probing
  • 17. Optimal signal selection for mode estimation  Only a few signals are sufficient for accurate estimation  Large number of signals introduce bias and extensive computational effort  Variance of the estimate describes estimation quality Compute asymptotic variance for each measured signal Rank the signals Select the top ones                                         1 * * 0 0 0 02 1 ( , ) ( , ) ( , ) ( , ) ( ) 2 2e e u u u N N P F F d F F d                     1 * 0 0 ( , ) ( , ) 2 e e N P F F d 17/28
  • 18. 49 48 50 17 40 31 18 42 44 47 0.09 0.1 0.11 0.12 0.13 0.14 0.15 1 2 3 4 5 6 7 8 9 10 Voltage angles 37 26 36 32 34 39 38 43 22 21 0.15 0.16 0.17 0.18 0.19 0.2 0.21 0.22 0.23 1 2 3 4 5 6 7 8 9 10 Voltage magnitudes Optimal signal selection results 18/28
  • 19. Outline 1 • Oscillations – ambient excitation, modes 2 • Principles of mode estimation 3 • Optimal probing design and signal selection 4 • Mode estimation with non-white loads 5 • Prototype implementation 6 • Conclusions 19/28
  • 20. Ambient mode estimation with non-white loads - Approach 20  Transmission/distribution border points have PMUs  Non-white loads are inputs  Input-output identification Source: EirGrid plc Transmission Distribution 20/28 Non-white noise excitation corrupts results of the classical mode estimators
  • 21. Mode estimation considering spectral characteristics of load  Direct closed loop identification  Only modes of the transmission parts are identified 0 0.5 1 1.5 2 0.495 0.497 0.499 0.501 0.503 0.505  ModeFrequency[Hz] 0 0.5 1 1.5 2 2.5 3 0.495 0.497 0.499 0.501 0.503 0.505 0 0.5 1 1.5 2 1 1.8 2.6 3.4 4.2 5 0 0.5 1 1.5 2 2.5 3 1 1.8 2.6 3.4 4.2 5 Kpf ModeDamping[%] Mode frequency vs  Mode frequency vs Kpf Mode damping vs  Mode damping vs Kpf 𝑃𝐿 = 𝑃0 𝑉 𝑉0 𝛼 (1 + 𝐾 𝑝𝑓 𝛥𝑓) Transmission Load Power State (V,θ) Loads Independent disturbance (white noise) 21/28  Load effects are compensated afterwards
  • 22. Results – Presence of forced oscillations 0 20 40 60 80 100 0 0.2 0.4 0.6 0.8 1 1.2 Damping ratio [%] Frequency[Hz] Estimated modes Real system modes 0 20 40 60 80 100 0 0.2 0.4 0.6 0.8 1 1.2 Damping ratio [%] Frequency[Hz] Estimated modes Real system modes Yule-Walker method Forced oscillation (0.45 Hz) 0 20 40 60 80 100 0 0.2 0.4 0.6 0.8 1 1.2 Damping ratio [%] Frequency[Hz] Estimated modes Real system modes N4SID method  KTH Nordic32 system with forced oscillation at 0.45 Hz  Monte Carlo simulations (large number of mode estimations)  Classical methods: – Forced oscillation estimated as a critical mode – Real system mode masked by the forced oscillation Classical methods Proposed method 22/28 Proposed method discerns the forced oscillation
  • 23. Results – white noise input  When all assumptions used in classical mode estimators are fully satisfied  All methods provide similar results 0 20 40 60 80 100 0 0.2 0.4 0.6 0.8 1 1.2 Damping ratio [%] Frequency[Hz] Estimated modes Real system modes 0 20 40 60 80 100 0 0.2 0.4 0.6 0.8 1 1.2 Damping ratio [%] Frequency[Hz] Estimated modes Real system modes 0 20 40 60 80 100 0 0.2 0.4 0.6 0.8 1 1.2 Damping ratio [%] Frequency[Hz] Estimated modes Real system modes Classical methods Yule-Walker method N4SID method Parameters Yule- Walker N4SID Proposed Method Mode1 Mean {f} [Hz] 0.4972 0.4978 0.4966 Mean {} [%] 3.3081 4.1213 3.8104 Var {f} 8.8670e-6 1.6260e-5 1.6592e-5 Var {} 0.2728 0.7942 0.8561 Mode2 Mean {f} [Hz] 0.7334 0.7309 0.7386 Mean {} [%] 3.8184 4.7095 3.5497 Var {f} 1.4072e-5 6.2711e-5 2.3151e-5 Var{} 0.3563 1.7925 0.5965 Proposed method 23/28
  • 24. Outline 1 • Oscillations – ambient excitation, modes 2 • Principles of mode estimation 3 • Optimal probing design and signal selection 4 • Mode estimation with non-white loads 5 • Prototype implementation 6 • Conclusions 24/28
  • 25.  Power system or real-time simulator  Phasor measurement units (PMUs).  Phasor data concentrator (PDC) SDK PMU 1 PMU 2 PMU n PDC Comm. Network IEEE C37.118 Protocol KTH SmarTS Lab Wide Area Measurements System Real system Real time simulator User application Source Measurements Comm. Infrastructure Decoder  Communication Network  Software Development Kit (SDK)  User applications 25/28
  • 26. Prototype mode estimation application  LabVIEW platform  Real-life data  The critical mode 0.39 Hz damping ratio 9 % (average)  Other modes are observable at 0.2 Hz, 1 Hz and 1.4 Hz  0.5 Hz mode sporadically appears as a poorly damped mode 26/28
  • 27. Conclusions  A comprehensive way of dealing with mode estimation uncertainty.  Probing when carefully designed provides a good mode estimation accuracy at low cost.  Some signals provide better mode estimates than others. Quality signal criterion is proposed.  A method that eliminates negative effects of non-white ambient excitation is proposed.  Testing of the mode estimation tools needs to include other components of the system. 27/28