Mª Rocío Rodríguez Barroso
Department of Environmental
Technologies
University of Cadiz
Integral water Cycle
SUPPLY
SANITATION
TREATMENT
REUSE
ÍNDEX
3
Urban Water Cycle: SUPPLY
Regulation
Deposits
SWT
acuífer
surface
STATION WATER TREATMENT:
DRINKING WATER
LEGISLATION SUPPLING WATER:
-Real Decreto 927/1988, State
Regulation of drinking water
production
-Real Decreto 140/2003 of water for
human consumption
SYPPLIES: springs and wetlands fed by rivers and
groundwater
SWT: STATION WATER TREATMENT
5
Urban Water Cycle : SANITATION
Regulation
Deposits
WTP
EDAR
(spanish)
SWT
ETAP
(spanish)
acuifer
surficial
Reuse
WASTEWATER TREATMENT PLANT:
WasteWATER
STATION WATER TREATMENT:
Drinking water
SANITATION: SEWAGE/ DISPOSAL
EDAR-RANILLA EDAR-COPERO
 TREATMENT: What is a WTP- Water treatment plant?
It is an installing that collects wastewater from a population or industry,
and after a series of treatments and processes, are cleaned and returns to a
receiving stream (river, reservoir or sea).
Influent-wastewater EDAR
Effluent-
Treated
water
1.
Sludge-(mud)2.
1.
2.
Reuse??
Agricultural application ??
SUPPLY / TREATMENT
SANITATION / TREATMENT
REUSE
2. INTEGRATED WATER CYCLE IN GUADALETE RIVER
STUDY ZONE
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
SUPPLY
POPULATION
UPPER COURSE: 62 558 inhabitant
Guadalete River: 11 villages
Majaciete River: 5 villages
LOWER COURSE: 261 121 inhabitant
Guadalete River: 15 villages
TOTAL: 333 709 inhabitant
Stadium Santiago Bernabeu (1 Hm3 )
Olympic pool (1500 m3 )
How much water have we got?
TOTAL: 333 709 inhabit
Endowment: 120 l/inh day
40 045 m3/day = 14,6 Hm3/year
Guadalete River
3 reservoirs (437 Hm3)
Majaceite River
2 reservoirs (935 Hm3)
•Zahara-El Gastor: 223 Hm3
•Bornos: 200 Hm3
•Arcos: 14 Hm3
•Guadalcacín: 800 Hm3
•Los Hurones: 135 Hm3
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
SUPPLY How much water need the population?
12
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
SUPPLY
Guadalete basin
13
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
SUPPLY
Station Water
Treatmemt
2 RESERVOIRS: MAJACEITE RIVER
Guadalcacín: 800hm3; presa
materiales sueltos; aliviadero de
lamina libre y 4 tomas de agua
Los Hurones: 135hm3; presa de
gravedad; aliviadero en vertedero y 3
tomas de agua
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
SUPPLY
15
SSS
STATION WATER TREATMENT:
DRINKING WATER - El Montañés
Capacidad: 2500 l/seg, hasta 5000 l/seg
4 decandadores 28 m 
12 filtros de 14.60 m x 9,46 m
TECNOLOGÍAS: Precloración-
decantación-filtración-desinfección con
cloro
5 depósitos de almacenamiento
semienterrados: 200.000 m3
h: 6 m
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
SUPPLY
SUPPLY / TREATMENT
SANITATION / TREATMENT
REUSE
2. INTEGRATED WATER CYCLE IN GUADALETE RIVER
17
STP
SWT
acuíferos
superficial
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
REGULATIONS
WASTEWATER TREATMENT RULES:
DIRECTIVE (European Union)
91/271/CEE
TRANSPOSITION
- Real Decreto-Ley 11/1995
- Real Decreto 509/1996
-REUSE WASTEWATER:
-REAL DECRETO 1620/2007, de 7 de
diciembre, por el que se establece el
régimen jurídico de la reutilización de
las aguas depuradas
DIRECTIVE (European Union) 91/271/CEE: Artícle 2
E.h. (equivalent inhabitant): following the EU criteria by which an equivalent inhabitant
produces 60 grams of BOD5 per day, caused by domestic activities.
Related with presence of ORGANIC MATTER in wastewater
Analysis:
BOD: Biochemical Oxygen Demand (mg/l O2)
QOD: Chemical Oxyen Demand (mg/l O2)
TOC: Total Organic Carbon (mg/l)
Pollution Load (g/day) = Concentration (BOD mg/l O2) x Caudal (m3/day)
E-h = Pollution Load / 60 g
Example: Jerez
DBO5 (mg O2/l ): :400
E-h: 272.162
Current Poblation: 210.000 inhab
Cuadro 1. Requisitos para los vertidos procedentes de instalaciones de tratamiento de aguas residuales
urbanas sujetos a lo dispuesto en los artículos 4 y 5 de la presente Directiva. Se aplicará el valor de
concentración o el porcentaje de reducción.
Parámetros Concentración Porcentaje mínimo de
reducción
Método de medida de referencia
Demanda bioquímica de
oxígeno (DBO5 a 20 ºC) sin
nitrificación
25 mg/L O2 70 – 90
40 de conformidad con el
apartado 2 del Art. 4
Muestra homogeneizada, sin filtrar
ni decantar. Determinación del
oxígeno disuelto antes y después
de 5 días de incubación a 20 ºC
1 ºC, en completa oscuridad.
Aplicación de inhibidor de la
nitrificaciónl
Demanda química de
oxígeno (DQO)
125 mg/L O2 75 Muestra homogeneizada, sin filtrar
ni decantar.
Dicromato potásico
Total de sólidos en
suspensión
35 mg/L
35 de
conformidad con
el apartado 2 del
Art. 4 (más de
10.000 h-e)
50 de
conformidad con
el apartado 2 del
Art. 4 (de 2.000 a
10.000 h-e)
90
50 de conformidad con el
apartado 2 del Art, 4 (más
de 10.000 h-e)
Filtración de una muestra
representativa a través de una
memebrana de filtrante de 0,45
micaras. Secado a 105 ºC y
pesaje.
Centrifugación de una muestra
representativa (durante 5 minutos
como mínimo, con una
aceleración media de 2.800 a
3.200 g), secado a 105 ºC y
pesaje.
DIRECTIVE (European Union) 91/271/CEE: chart 1
Cuadro 2. Requisitos para los vertidos procedentes de instalaciones de tratamiento de aguas
residuales urbanas realizados en zonas sensibles propensas a eutrofización. Según la situación
local, se podrá aplicar uno o los dos parámetros. Se aplicará el valor de concentración o el
porcentaje de reducción.
Parámetros Concentración Porcentaje mínimo de
reducción
Método de medida de
referencia
Fósforo total
2 mg/L P (de 10.000 a
100.000 h-e)
1 mg/L P (más de
100.000 h-e)
80
Espectrofotometría
de absorción
molecular
Nitrógeno total
15 mg/L N (de 10.000 a
100.000 h-e)
10 mg/L N (más de
100.000 h-e)
70 - 80
Espectrofotometría
de absorción
molecular
DIRECTIVE (European Union) 91/271/CEE: chart 2
DQO (mg/l O2)
DBO5 (mg/l O2)
Sólidos Suspensión (mg/l)
Fósforo total (mg/l)
Nitrógeno total (mg/l)
DQO < 125 mg/l O2 (75 %)
DBO5 < 25 mg/l O2 (70 - 90 %)
Sólidos Suspensión < 35 mg/l (90 %)
Fósforo total < 2 mg/l (80 %)
Nitrógeno total < 15 mg/l (70-80 %)
EXAMPLE
DQO (mg/l O2): 800
DBO5 (mg/l O2): 400
Sólidos Suspensión (mg/l): 380
Fósforo total (mg/l): 15
Nitrógeno total (mg/l): 65
DQO < 125 mg/l O2 (75 % → 200 mg/l)
DBO5 < 25 mg/l O2 (85 % → 60 mg/l)
Sólidos Suspensión < 35 mg/l (90% → 38 mg/l)
Fósforo total < 2 mg/l (80% → 3 mg/l)
Nitrógeno total < 15 mg/l (75% → 16.3 mg/l)
Untreated:
INLET
Treated:
OUTLET
Questions…..?
1. How many Water Treatment Plants are in Guadalete basin?
2. Are they according with the rules (Directive European Union)
3. Is the quality of the water in the river in good condition?
Let´s see
Activated Sludge
FANGOS ACTIVADOS
Villages: Ubrique
Bacterial beds
LECHOS BACTERIANOS
Olvera N y S
Algodonales
El Gastor
Zahara de la Sierra
Puerto Serrano
Álcalá del Valle
Peat beds
LECHOS DE TURBA
Setenil de las Budegas
Torrealháquime
Grazalema
El Bosque
Villaluenga
Biodisc
BIODISCOS
Benamahoma
UPPER COURSE:
13 WTP (villages)- 3 villages without WTP
Population: 62 558 inhabitant – and E-h: 83 546 E-h
1. How many Water Treatment Plant are in the Guadalete
basin?
Water Treatment Technologies
Activated Sludge
FANGOS ACTIVADOS
Jerez (little town)
Arcos
Bacterial beds
LECHOS BACTERIANOS
Villamartín
Paterna de la Rivera
Espera
Biodisc
BIODISCOS
La Barca
El Torno
Nueva Jarilla
Torrecera
Reactors underground
REACTORES SUBTERRÁNEOS
La Ina, S. Isidro
Majarromaque, Lomopardo
Water Treatment Technologies
LOWER COURSE:
13 villages- 5 villages without WTP
Population: 261 121 inhabitant – and E-h: 455 000 E-h
PROYECT 1: Wastewater study of WTP from Guadalete Basin (2002-2004)
according to the normative?
Río Guadalete Río Majaceite
Código Población Código Población
UPPER COURSE:
62. 558 inhabitant
U-10 Setenil U-27 Benamahoma
U-08 Alcalá del Valle U-12 El Bosque
U-24 Torrealháquime U-43 Benaocaz (V)
U-04 Olvera U-03 Ubrique
U-11 Grazalema U-21 Villaluenga del R.
U-15 Zahara de la Sierra
U-13 El Gastor
U-06 Algodonales
U-07 Puerto Serrano
U-31 Villamartín
U-40 Prado del Rey
LOWER COURSE:
261. 121 inhabitant
U-33 Bornos (V)
U-02 Arcos de la Frontera
U-38 Espera
U-25 Majarromaque (Jer.
U-09 La Barca (Jerez)
U-18 Torrecera (Jerez)
U-37 Paterna
U-16 El Torno (Jerez)
U-22 S. Isidro (Jerez)
U-20 La In a (Jerez)
U-29 Lomopardo (Jerez)
U-17 Nueva Jarilla (Jerez)
U-01 Jerez de la Frontera
U-42 Algar (V)
U-39 S. José del Valle (V)
(V = Vertido) (Los Códigos son los empleados por Comisaría de Aguas de Sevilla)
Physico-chemical Analysis
Temperature Total Nitrógeno (Nt)
pH Total Phospforo (Pt)
Oxygen (%) Conductivity (CE)
BOD5
QO D
Biodegradabity (CB)
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
WASTEWATER
2. Are they according with the normative (Directive European Union)
Tecnología Población hab-eq
% de Reducción Cumplimiento
RD 509/1996DBO5 DQO SS Ntotal Ptotal
Fangos activados Ubrique (PN) 12.032 67,8 57,1 40,3 20,6 48,8 NO
Lechos bacterianos Olvera N 9.349 88,4 83,2 92,1 29,5 42,6 SI
Olvera S 9.349 44,7 68,0 67,1 21,3 40,2 NO
Algodonales 7.584 83,8 77,3 77,8 0,0 27,6 SI
El Gastor 3.614 86,3 99,7 87,5 39,7 59,1 SI
Zahara (PN) 2.577 87,2 83,3 86,6 28,7 21,9 NO
Lagunaje El Bosque (PN) 1.257 21,3 24,6 0,0 56,6 41,7 NO
Alcalá del V 2.602 2,9 0,0 31,8 46,3 41,9 NO
Filtros de turba Setenil 2.491 57,4 50,7 57,2 7,5 52,8 NO
Torrealháq 930 58,3 37,6 24,3 21,1 23,5 NO
Grazalema (PN) 3.149 76,7 72,4 75,1 3,7 0,0 NO
Villaluenga (PN) 1.487 85,9 73,0 30,0 46,5 61,3 NO
Biodiscos Benamahom (PN) 763 51,4 39,9 46,2 11,8 72 NO
Límites RD 509/1996 70-90 75 70-90 80 70-80
(PN) Poblaciones del Parque Natural de la Sierra de Grazalema que vierten en zonas sensibles
PROYECT 1: upper course
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
WASTEWATER
TECNOLOGÍA Población H-E
% de Reducción Cumplimiento
RD 509/1996DBO5 DQO SS Ntotal Ptotal
Fangos activados Jerez 272.162 94´6 88´1 92´5 69´2 85´8 SI
Arcos 92.183 90´8 92´8 95´3 57´6 46´0 SI
Lechos bacterianos Villamartín 35.920 93´7 88´8 68´8 63’9 72´7 NO
Paterna 8.986 50´0 49´1 55´9 37´9 0 NO
Biodiscos La Barca 11.077 92´8 90´0 96´1 73´4 75´9 SÍ
Nueva Jarilla 1.201 67´3 65´3 74´1 50´7 28´8 NO
Torrecera 4.452 91´7 90´6 97´0 56´4 69´4 SI
La Ina 155 0´0 0´0 0´0 0´0 0´0 NO
S. Isidro 159 18´3 19´6 0´0 21´8 6´1 NO
Majarromaque 451 36´2 6´3 0´0 24´4 33´3 NO
Lomopardo 1.117 0´0 0´0 54´4 30´1 3´8 NO
Límites RD 509/1996 70-90 75 70-90 80 70-80
PROYECT 1: lower course
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
WASTEWATER
Código Punto de
muestreo
Habitantes Porc
%
Hab-
equiv
Código Punto de
muestreo
Habitantes Porc
%
Hab-
equiv
CUENCA ALTA CUENCA BAJA
U-10 Setenil 3 016 0,93 2 491 U-31 Villamartín 12 145 3,75 35 950
U-05 Alcalá del V 5 355 1,65 2 602 U-33 Bornos 8 164 2,52 6 310
U-24 Torrealháquime 877 0,27 930 U-02 Arcos 29 420 9,09 92 183
U-04 Olvera 8 585 2,65 18 698 U-38 Espera 3 909 1,21 6 215
U-11 Grazalema 1 828 0,56 3 149 U-25 Majarromaque 850 0,26 451
U-15 Zahara 1 556 0,48 2 577 U-09 La Barca 3 800 2,52 11 077
U-13 El Gastor 1 948 0,60 3 614 U-18 Torrecera 1 200 0,37 4 452
U-06 Algodonales 5 630 1,74 7 584 U-37 Paterna 5 354 1,65 8 986
U-07 Pto. Serrano 6 852 2,12 13 770 U-16 El Torno 1 200 0,37 3 339
U-40 Prado Rey 5 968 1,84 12 389 U-22 S. Isidro 600 0,19 159
U-27 Benamahoma 397 0,12 763 U-20 La Ina 800 0,25 155
U-12 El Bosque 2 004 0,62 1 257 U-29 Lomopardo 1 100 0,34 1 117
U-43 Benaocaz 729 0,23 203 U-17 Nª Jarilla 1 600 0,39 1 201
U-03 Ubrique 17 362 5,36 12 032 U-01 Jerez 185 125 57,19 272 162
U-21 Villaluenga 481 0,15 1 487 U-42 Algar 1 644 0,51 4 908
U39 S.José del V 4 210 0,30 7 084
TOTAL C. A. 62 588 19,33 83 546 TOTAL C. B. 261.121 80,66 455.749
TOTAL CUENCA 323.709 100,00 539.295
Coloreado de amarillo: Poblaciones sin EDAR en funcionamiento
La CUENCA ALTA con el 19,33 % de la población genera el 15,49 % de loshabitantes-equivalentes
La CUENCA BAJA con el 80,66 % de la población genera el 84,44 % de los habitantes-equivalentes
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
WASTEWATER
Compared study between both basins
HABITANTES
(2005)
VERTIDOS HAB– EQUIV Ratio
(h-e)/hm3/año litros/día % Cuenca h-e % Cuenca
TOTAL
upper
course
62 588 6 356 887 17 406 124 18,55 83 546 15,49 1,33
TOTAL
lower
course
261.121 27.904.669 76.451.148 81,45 455.749 84,51 1,75
TOTAL
CUENCA
323.709 34.261.556 93.857.271 100 539.295 100 1,67
Abreviaturas: h = habitantes (h-e) = habitantes-equivalentes
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
WASTEWATER
Anual load generated by the urban (before the WTP)
Carga DBO5 = 5 960 Tm/año de O2. 50,45 % del total
Carga DQO = 9 191 Tm/año de O2. 44,69 % del total
Carga SS = 4 275 Tm/año de SS. 33,83 % del total
Carga DBO5 = 5 854 Tm/año de O2. 49,55 % del total
Carga DQO = 11 377 Tm/año de O2. 55,31 % del total
Carga SS = 8 096Tm/año de SS. 66,17 % del total
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
DBO5 DQO SS
%CARGAANUAL
PARÁMETROS CONTROLADOS
CARGA ANUAL GENERADA
RESTO POBLACIONES JEREZ
JEREZ
other populations
wastewater
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
WASTEWATER
Wastewater WITHOUT treatment
Pollution Load (g/day) = Concentration (BOD mg/l O2) x Caudal (m3/day)
E-h = Pollution Load / 60 g
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
DBO DQO SS
%CARGAANUAL
PARÁMETROS CONTROLADOS
CARGA ANUAL DE VERTIDOS AL GUADALETE
RESTO POBLACIONES
JEREZ
Carga DBO5 = 321 Tm/año de O2. 13,79 % del total
Carga DQO = 1 104 Tm/año de O2. 23,88 % del total
Carga SS = 321 Tm/año de SS. 13,81 % del total
Carga DBO5 = 2 006 Tm/año de O2. 86,21 % del total
Carga DQO = 3 520 Tm/año de O2. 76,12 % del total
Carga SS = 2 003 Tm/año de SS. 86,18 % del total
JEREZ
other
populations
Wastewater treated
Anual load dicharges by the urban (after SSS)
2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER
WASTEWATER
Wastewater with treatment
POPULATIONS Discharges
m3/ año
Anual load dicharges
(Tm/year)
DBO
Tm/año O2
DQO
Tm/año O2
SS
Tm/año
CURRENTLY: Without treatment
TOTAL 3.237.967 1.198 1.946 887
FUTURE: With treatment
TOTAL 3.237.967 81 405 113
Differences 1.117 1.541 774
Another questions:
1. what is happening with the 8 villages without treatment? (8 populations with
32 676 E-h)
2. when the plant will be built, how much would reduce their annual load?
Without treatment 12.371 Tm SS
This investigation (2002-2004): 2.324 Tm SS
Future: WTP built and operating
properly
1.550 Tm SS
3. Is the quality of the water in the river in good condition?
Second project
Código Punto de muestreo
UPPER COURSE
Majaceite River
Ubrique-1
Upstream from
WTP
Ubrique-2
Downstream from
WTP
Bosque-1
Upstream from
WTP
Bosque-2
Downstream from
WTP
Arcos-1
Upstream from
WTP
LOWER COURSE
Guadalete River
Arcos-2
Downstream from
WTP
Jerez-1
Upstream from
WTP
Jerez-2
Downstream from
WTP
ANALYSES
T Nitrógeno Fluoruros
pH Nitratos Cianuros
CE Nitritos Metales
Oxígeno Amonio
DBO5 Fosfatos
DQO Hierro
SS Manganeso
Point Stations
PROjECT 2: Controls on the receiving stream from Guadalete Basin (2002-2004)
Muestras
DBO5
mg/l O2
DQO
mg/l O2
SS
mg/l
Ubrique-1 7 13 11
Ubrique-2 14 32 21
El Bosque-1 8 25 15
El Bosque-2 7 23 25
Arcos-1 8 32 15
Arcos-2 37 99 107
Jerez-1 7 31 158
Jerez-2 8 26 170
mg/l
PROjECT 2: organic load in the water river
Arcos 2: plant not operating properly
Jerez 2: diffuse pollution (agricultural land drag, by rainfall and runoff)
River pollution indices: WQI- Water Quality Index
(Pesce &
Wunderlin, 2000)
Ci
Parám. Pi 100 90 80 70 60 50 40 30 20 10 0
Rangos de valores analíticos
pH 1 7 7-8 7-8,5 7-9 6,5-7 6-9,5 5-10 4-11 3-12 2-13 1-14
CE 2 <0,75 <1,00 <1,25 <1,50 <2,00 <2,50 <3,00 <5,00 <8,00 <12,00 >12
SS 4 <20 <40 <60 <80 <100 <120 <160 <240 <320 <400 >400
NH4
+ 3 <0,01 <0,05 <0,10 <0,20 <0,30 <0,40 <0,50 <0,75 <1,00 <1,25 >1,25
NO2
- 2 <0,005 <0,01 <0,03 <0,05 <0,10 <0,15 <0,20 <0,25 <0,50 <1,00 >1,00
NO3
- 2 <0,5 <2,0 <4,0 <6,0 <8,0 <10,0 <15,0 <20,0 <50,0 <100,0 >100,0
PT 1 <0,2 <1,6 <3,2 <6,4 <9,6 <16,0 <32,0 <64,0 <96,0 <160,0 >160
DQO 3 <5 <10 <20 <30 <40 <50 <60 <80 <100 <150 >150
DBO5 3 <0,5 <2,0 <3 <4 <5 <6 <8 <10 <12 <15 >15
OD 4 ≥7,5 >7,0 >6,5 >6,0 >5,0 >4,0 >3,5 >3,0 >2,0 >1,0 >1,0
T 1 21/16 22/15 24/14 26/12 28/10 30/5 32/0 36/-2 40/-4 45/-6 >45/<-6
Todos los valores, excepto pH, en mg/l Conductividad CE en mS/cm
River pollution indices: clasification
Punto de
muestreo
WQI CALIFICACIÓN
Ubrique-1 61 MEDIUM
Ubrique-2 52 MEDIUM
El Bosque-1 56 MEDIUM
El Bosque-2 54 MEDIUM
Arcos-1 41 BAD
Arcos-2 20 VERY BAD
Jerez-1 32 BAD
Jerez-2 28 BAD
WQI Clasification
0-25 Very BAD
25-50 BAD
51-70 MEDIUM
71-90 GOOD
91-100 EXCELENT
Parameters analysed (11)
pH, CE, SS, NH4, NO3, NO2, Pt,
DQO, DBO5, OD, T
Questions…..?
1. How many Wastewater Treatment Plants are in the
Guadalete basin?
2. Are according with the law (Directive European Union)
3. Is the quality of the water in the river in good condition?
4. HOW ARE NOW THE TREATMENT PLANTS?
Let´s see
Lecture 4  rocio rodriguez
Lecture 4  rocio rodriguez
46 % of population without treatment
Report on the situation of waste water treatment in the
Province of Cádiz
2.2.3.1. VILLAGES WITHOUT SWT
Benaocaz. Vertido a acequia Bornos. Vertido al embalse de
Bornos
Trebujena. Vertido a acequia
San José del Valle. Vertido a
arrollo Los Toreros.
Tarifa. Pretratamiento
ACTUACIÓN
PREVISTA
OBRAS DECLARADAS
DE INTERÉS DE CAA
HABITANTES
BENAOCAZ
EDAR y colectores. No
existe proyecto. Existe
estudio de alternativas.
EDAR y colectores en
Benaocaz y Grazalema
693
BORNOS
En Proyecto EDAR y
colectores
Por error no los
incluyeron en el
Acuerdo, pero son
necesidades. La EDAR
de Bornos ya está en
proyecto
8.074
SAN JOSÉ
DEL VALLE
EDAR y colectores. A
fecha de oct. 2012 no
hay terrenos. Existe
proyecto de AJEMSA
EDAR y colectores en
Medina Sidonia, San
José del Valle y sus
núcleos
4.117
TREBUJENA
EDAR y colectores.
Actualmente oct. 2012
no existe proyecto
EDAR y colectores en
Trebujena
6.890
TARIFA
Existen terrenos y
proyecto.
A falta de asignación
presupuestaria.
Ampliación, EDAR y
colectores en Tarifa y
sus núcleos
15.217
Report on the situation of waste water treatment in the
Province of Cádiz
46 % de la población de la provincia de Cádiz no depuren sus aguas o no lo hacen
con las condiciones establecidas (549.814 habitantes).
2.2 Informe sobre la situación de la depuración
de las aguas residuales en la Provincia de Cádiz.
2.2.4. WATER BILL. A quick calculation………………:
 CUOTA FIJA: 1 € por vivienda / mes
 CUOTA VARIABLE: bloque 1 (< 10 m3) , 0.10 €/m3 consumido
 Año 1: se paga 30 % = 0.03 €/m3 consumido
 Año 2: 50 % = = 0.05 €/m3 consumido
 Año 3: 60 % = = 0.06 €/m3 consumido
 Año 4: 80 % = = 0.08 €/m3 consumido
 ANDALUCÍA (8.415.490 habitantes) (mayo 2011 – mayo 2012)
Año €/m3
Consumo
CUOTA VARIABLE
Cuota Servicio
CUOTA FIJA Total
2012 0,03 12.900.946,17 € 50.492.940,00 € 63.393.886,17 €
2013 0,05 21.501.576,95 € 50.492.940,00 € 71.994.516,95 €
2014 0,06 25.801.892,34 € 50.492.940,00 € 76.294.832,34 €
2015 0,08 34.402.523,12 € 50.492.940,00 € 84.895.463,12 €
296.578.698,58 €
CONCLUSIONS
1. How many Wastewater Treatment Plants are in the
Guadalete basin?
There are sufficient WTP but their operative were not correctly
performing.
2. Are they according with the legislation(Directive European
Union)
No, and currently most of the Plants are in a worse situation than years
ago
3. Is the quality of the water in the river in good condition?
No, and probably in a worse situation than 2004
Is Guadalete Basin according to Water
Framework Directive for 2015?
What is the solution?
Thanks for your attention

Más contenido relacionado

PPT
Calidad de aguas
PDF
Productos quimicos y espacios confinados en comunidades de vecinos
PDF
4. felipe sandoval, aqua chile
PPT
FUNCIONAMIENTO DEL SISTEMA ANAEROBIO DE TRATAMIENTO BIOLÓGICO SAMM®
PDF
taller_PI_meta35_2 (1).pdf
PDF
4. Felipe Sandoval - Aqua Chile
PPT
Gestion de las aguas residuales en huacho emapa huacho s.a.
DOCX
Memoria de calculo completo planta
Calidad de aguas
Productos quimicos y espacios confinados en comunidades de vecinos
4. felipe sandoval, aqua chile
FUNCIONAMIENTO DEL SISTEMA ANAEROBIO DE TRATAMIENTO BIOLÓGICO SAMM®
taller_PI_meta35_2 (1).pdf
4. Felipe Sandoval - Aqua Chile
Gestion de las aguas residuales en huacho emapa huacho s.a.
Memoria de calculo completo planta

La actualidad más candente (20)

PPT
1. tratamiento agua residual diapositivas
PDF
Tecnologias para-desinfeccion-y-cloracion-2
PDF
Clase11
 
PPTX
Tratamiento de agua residuales [autoguardado]
PDF
Aguas servidas
PDF
Taller pi meta35_2
PPTX
Cloracion y desinfeccion 2014
PDF
4. Felipe Sandoval - Aqua Chile
PPT
Tratamiento Agua Rastro
PDF
Modulo 3 ptaru_ene19
PPTX
uso de filtros ceramicos en tratamiento de agua del rio tumbes
PPT
Aguas residuales Industriales
PDF
Marco general aguas residuales
PPTX
TRATAMIENTO DE AGUAS RESIDUALES
PDF
Filtro para aguas jabonosas
PDF
Monitoreo de la calidad del agua
PPTX
Evaluación comparativa de sistemas de purificación de agua para consumo
PDF
Ponencia58
DOCX
Cuestionario (2)
1. tratamiento agua residual diapositivas
Tecnologias para-desinfeccion-y-cloracion-2
Clase11
 
Tratamiento de agua residuales [autoguardado]
Aguas servidas
Taller pi meta35_2
Cloracion y desinfeccion 2014
4. Felipe Sandoval - Aqua Chile
Tratamiento Agua Rastro
Modulo 3 ptaru_ene19
uso de filtros ceramicos en tratamiento de agua del rio tumbes
Aguas residuales Industriales
Marco general aguas residuales
TRATAMIENTO DE AGUAS RESIDUALES
Filtro para aguas jabonosas
Monitoreo de la calidad del agua
Evaluación comparativa de sistemas de purificación de agua para consumo
Ponencia58
Cuestionario (2)
Publicidad

Similar a Lecture 4 rocio rodriguez (20)

PPTX
MÉTODOS AVANZADOS DE POTABILIZACIÓN Y TRATAMIENTO DE AGUAS.pptx
PPTX
Presentacion materiales (1)
PDF
Depuracion del-agua residual en españa
PDF
2111 diseno de un reactor biologico de fangos activos
PPTX
20 Gestión de aguas residuales en ecuador - SENAGUA
PDF
Informe Prácticas Aguas Residuales EDAR
PDF
Ic02 t2 a_02_apa_para_desinfeccion
PDF
Ic02 t2 a_02_apa_para_desinfeccion
PDF
Tratamiento de Aguas Residuales
PPTX
Work ptar.wiki 3
PPTX
Foro Edar Nerja
PDF
Diseño de una instalación desaladora de agua de mar (IDAM)
PPS
reutilizacion_aguas.pps
PDF
1 Introducción tratamiento de agua industriales .pdf
PDF
aguas_domesticas.pdf
PDF
Propuesta tecnica etap modular 500 m3 h
PDF
Proyecto planta de tratamiento de aguas residuales 2
PPTX
Wiki 3 720 garcia, jimenez, echeverry, suárez.pptx
PDF
Sesion 1-Caracterizacion de aguas residuales.pdf
PDF
Ptar chilpina presentación a nivel avanzado 81 diap
MÉTODOS AVANZADOS DE POTABILIZACIÓN Y TRATAMIENTO DE AGUAS.pptx
Presentacion materiales (1)
Depuracion del-agua residual en españa
2111 diseno de un reactor biologico de fangos activos
20 Gestión de aguas residuales en ecuador - SENAGUA
Informe Prácticas Aguas Residuales EDAR
Ic02 t2 a_02_apa_para_desinfeccion
Ic02 t2 a_02_apa_para_desinfeccion
Tratamiento de Aguas Residuales
Work ptar.wiki 3
Foro Edar Nerja
Diseño de una instalación desaladora de agua de mar (IDAM)
reutilizacion_aguas.pps
1 Introducción tratamiento de agua industriales .pdf
aguas_domesticas.pdf
Propuesta tecnica etap modular 500 m3 h
Proyecto planta de tratamiento de aguas residuales 2
Wiki 3 720 garcia, jimenez, echeverry, suárez.pptx
Sesion 1-Caracterizacion de aguas residuales.pdf
Ptar chilpina presentación a nivel avanzado 81 diap
Publicidad

Más de Henk Massink (20)

PPT
Cu07821 ppt9 recapitulation
PPTX
Gastcollege mli
PPTX
Cu07821 10management and maintenance2015
PPTX
Cu07821 9 zoning plan2015
PPTX
Cu07821 8 weirs
PPTX
Cu07821 7 culverts new
PPTX
Cu07821 6 pumping stations_update
PPTX
Cu07821 5 drainage
PPTX
Cu07821 4 soil
PPTX
Cu07821 3 precipitation and evapotranspiration
PPTX
Cu07821 2 help
PPTX
Cu07821 1 intro_1415
PDF
Research portfolio delta_academy_s2_2014_2015
PDF
Research portfolio da arc 2014-2015 s1
DOC
Cu06997 assignment 6 2014_answer
PPTX
Jacobapolder
PDF
Research portfolios1 2013_2014 jan july 2014
PPTX
Presentatie AET voor scholieren 15-11-2013
PPTX
Vision group1(5)
PPTX
Final presentation spain quattro
Cu07821 ppt9 recapitulation
Gastcollege mli
Cu07821 10management and maintenance2015
Cu07821 9 zoning plan2015
Cu07821 8 weirs
Cu07821 7 culverts new
Cu07821 6 pumping stations_update
Cu07821 5 drainage
Cu07821 4 soil
Cu07821 3 precipitation and evapotranspiration
Cu07821 2 help
Cu07821 1 intro_1415
Research portfolio delta_academy_s2_2014_2015
Research portfolio da arc 2014-2015 s1
Cu06997 assignment 6 2014_answer
Jacobapolder
Research portfolios1 2013_2014 jan july 2014
Presentatie AET voor scholieren 15-11-2013
Vision group1(5)
Final presentation spain quattro

Último (20)

PDF
MODULO I ENFERMERIA BASICA.pdf HIstoria en enfermeria
PDF
Aqui No Hay Reglas Hastings-Meyer Ccesa007.pdf
DOCX
TEXTO DE TRABAJO DE EDUCACION RELIGIOSA - CUARTO GRADO.docx
PDF
LIBRO 2-SALUD Y AMBIENTE-4TO CEBA avanzado.pdf
PDF
Mi Primer Millon - Poissant - Godefroy Ccesa007.pdf
PDF
Los10 Mandamientos de la Actitud Mental Positiva Ccesa007.pdf
PDF
RM2025 - FUNDAMENTOS TEÓRICOS - PEDIATRÍA.pdf
PPTX
Clase 3 del silabo-gestion y control financiero
DOCX
PLANES DE área ciencias naturales y aplicadas
PDF
Nadie puede salvarte excepto Tú - Madame Rouge Ccesa007.pdf
PPTX
4. Qué es un computador PARA GRADO CUARTO.pptx
DOCX
PLAN DE AREA DE CIENCIAS SOCIALES TODOS LOS GRUPOS
PDF
TALLER DE ESTADISTICA BASICA para principiantes y no tan basicos
PDF
Aumente su Autoestima - Lair Ribeiro Ccesa007.pdf
DOC
Manual de Convivencia 2025 actualizado a las normas vigentes
PDF
CURRICULAR DE PRIMARIA santa ursula..pdf
PDF
IPERC...................................
PDF
Jodorowsky, Alejandro - Manual de Psicomagia.pdf
PDF
Telos 127 Generacion Al fa Beta - fundaciontelefonica
PPTX
BIZANCIO. EVOLUCIÓN HISTORICA, RAGOS POLÍTICOS, ECONOMICOS Y SOCIALES
MODULO I ENFERMERIA BASICA.pdf HIstoria en enfermeria
Aqui No Hay Reglas Hastings-Meyer Ccesa007.pdf
TEXTO DE TRABAJO DE EDUCACION RELIGIOSA - CUARTO GRADO.docx
LIBRO 2-SALUD Y AMBIENTE-4TO CEBA avanzado.pdf
Mi Primer Millon - Poissant - Godefroy Ccesa007.pdf
Los10 Mandamientos de la Actitud Mental Positiva Ccesa007.pdf
RM2025 - FUNDAMENTOS TEÓRICOS - PEDIATRÍA.pdf
Clase 3 del silabo-gestion y control financiero
PLANES DE área ciencias naturales y aplicadas
Nadie puede salvarte excepto Tú - Madame Rouge Ccesa007.pdf
4. Qué es un computador PARA GRADO CUARTO.pptx
PLAN DE AREA DE CIENCIAS SOCIALES TODOS LOS GRUPOS
TALLER DE ESTADISTICA BASICA para principiantes y no tan basicos
Aumente su Autoestima - Lair Ribeiro Ccesa007.pdf
Manual de Convivencia 2025 actualizado a las normas vigentes
CURRICULAR DE PRIMARIA santa ursula..pdf
IPERC...................................
Jodorowsky, Alejandro - Manual de Psicomagia.pdf
Telos 127 Generacion Al fa Beta - fundaciontelefonica
BIZANCIO. EVOLUCIÓN HISTORICA, RAGOS POLÍTICOS, ECONOMICOS Y SOCIALES

Lecture 4 rocio rodriguez

  • 1. Mª Rocío Rodríguez Barroso Department of Environmental Technologies University of Cadiz
  • 3. 3 Urban Water Cycle: SUPPLY Regulation Deposits SWT acuífer surface STATION WATER TREATMENT: DRINKING WATER LEGISLATION SUPPLING WATER: -Real Decreto 927/1988, State Regulation of drinking water production -Real Decreto 140/2003 of water for human consumption
  • 4. SYPPLIES: springs and wetlands fed by rivers and groundwater SWT: STATION WATER TREATMENT
  • 5. 5 Urban Water Cycle : SANITATION Regulation Deposits WTP EDAR (spanish) SWT ETAP (spanish) acuifer surficial Reuse WASTEWATER TREATMENT PLANT: WasteWATER STATION WATER TREATMENT: Drinking water
  • 7.  TREATMENT: What is a WTP- Water treatment plant? It is an installing that collects wastewater from a population or industry, and after a series of treatments and processes, are cleaned and returns to a receiving stream (river, reservoir or sea).
  • 9. SUPPLY / TREATMENT SANITATION / TREATMENT REUSE 2. INTEGRATED WATER CYCLE IN GUADALETE RIVER
  • 10. STUDY ZONE 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER SUPPLY POPULATION UPPER COURSE: 62 558 inhabitant Guadalete River: 11 villages Majaciete River: 5 villages LOWER COURSE: 261 121 inhabitant Guadalete River: 15 villages TOTAL: 333 709 inhabitant
  • 11. Stadium Santiago Bernabeu (1 Hm3 ) Olympic pool (1500 m3 ) How much water have we got? TOTAL: 333 709 inhabit Endowment: 120 l/inh day 40 045 m3/day = 14,6 Hm3/year Guadalete River 3 reservoirs (437 Hm3) Majaceite River 2 reservoirs (935 Hm3) •Zahara-El Gastor: 223 Hm3 •Bornos: 200 Hm3 •Arcos: 14 Hm3 •Guadalcacín: 800 Hm3 •Los Hurones: 135 Hm3 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER SUPPLY How much water need the population?
  • 12. 12 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER SUPPLY Guadalete basin
  • 13. 13 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER SUPPLY Station Water Treatmemt
  • 14. 2 RESERVOIRS: MAJACEITE RIVER Guadalcacín: 800hm3; presa materiales sueltos; aliviadero de lamina libre y 4 tomas de agua Los Hurones: 135hm3; presa de gravedad; aliviadero en vertedero y 3 tomas de agua 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER SUPPLY
  • 15. 15 SSS STATION WATER TREATMENT: DRINKING WATER - El Montañés Capacidad: 2500 l/seg, hasta 5000 l/seg 4 decandadores 28 m  12 filtros de 14.60 m x 9,46 m TECNOLOGÍAS: Precloración- decantación-filtración-desinfección con cloro 5 depósitos de almacenamiento semienterrados: 200.000 m3 h: 6 m 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER SUPPLY
  • 16. SUPPLY / TREATMENT SANITATION / TREATMENT REUSE 2. INTEGRATED WATER CYCLE IN GUADALETE RIVER
  • 17. 17 STP SWT acuíferos superficial 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER REGULATIONS WASTEWATER TREATMENT RULES: DIRECTIVE (European Union) 91/271/CEE TRANSPOSITION - Real Decreto-Ley 11/1995 - Real Decreto 509/1996 -REUSE WASTEWATER: -REAL DECRETO 1620/2007, de 7 de diciembre, por el que se establece el régimen jurídico de la reutilización de las aguas depuradas
  • 18. DIRECTIVE (European Union) 91/271/CEE: Artícle 2 E.h. (equivalent inhabitant): following the EU criteria by which an equivalent inhabitant produces 60 grams of BOD5 per day, caused by domestic activities. Related with presence of ORGANIC MATTER in wastewater Analysis: BOD: Biochemical Oxygen Demand (mg/l O2) QOD: Chemical Oxyen Demand (mg/l O2) TOC: Total Organic Carbon (mg/l) Pollution Load (g/day) = Concentration (BOD mg/l O2) x Caudal (m3/day) E-h = Pollution Load / 60 g Example: Jerez DBO5 (mg O2/l ): :400 E-h: 272.162 Current Poblation: 210.000 inhab
  • 19. Cuadro 1. Requisitos para los vertidos procedentes de instalaciones de tratamiento de aguas residuales urbanas sujetos a lo dispuesto en los artículos 4 y 5 de la presente Directiva. Se aplicará el valor de concentración o el porcentaje de reducción. Parámetros Concentración Porcentaje mínimo de reducción Método de medida de referencia Demanda bioquímica de oxígeno (DBO5 a 20 ºC) sin nitrificación 25 mg/L O2 70 – 90 40 de conformidad con el apartado 2 del Art. 4 Muestra homogeneizada, sin filtrar ni decantar. Determinación del oxígeno disuelto antes y después de 5 días de incubación a 20 ºC 1 ºC, en completa oscuridad. Aplicación de inhibidor de la nitrificaciónl Demanda química de oxígeno (DQO) 125 mg/L O2 75 Muestra homogeneizada, sin filtrar ni decantar. Dicromato potásico Total de sólidos en suspensión 35 mg/L 35 de conformidad con el apartado 2 del Art. 4 (más de 10.000 h-e) 50 de conformidad con el apartado 2 del Art. 4 (de 2.000 a 10.000 h-e) 90 50 de conformidad con el apartado 2 del Art, 4 (más de 10.000 h-e) Filtración de una muestra representativa a través de una memebrana de filtrante de 0,45 micaras. Secado a 105 ºC y pesaje. Centrifugación de una muestra representativa (durante 5 minutos como mínimo, con una aceleración media de 2.800 a 3.200 g), secado a 105 ºC y pesaje. DIRECTIVE (European Union) 91/271/CEE: chart 1
  • 20. Cuadro 2. Requisitos para los vertidos procedentes de instalaciones de tratamiento de aguas residuales urbanas realizados en zonas sensibles propensas a eutrofización. Según la situación local, se podrá aplicar uno o los dos parámetros. Se aplicará el valor de concentración o el porcentaje de reducción. Parámetros Concentración Porcentaje mínimo de reducción Método de medida de referencia Fósforo total 2 mg/L P (de 10.000 a 100.000 h-e) 1 mg/L P (más de 100.000 h-e) 80 Espectrofotometría de absorción molecular Nitrógeno total 15 mg/L N (de 10.000 a 100.000 h-e) 10 mg/L N (más de 100.000 h-e) 70 - 80 Espectrofotometría de absorción molecular DIRECTIVE (European Union) 91/271/CEE: chart 2
  • 21. DQO (mg/l O2) DBO5 (mg/l O2) Sólidos Suspensión (mg/l) Fósforo total (mg/l) Nitrógeno total (mg/l) DQO < 125 mg/l O2 (75 %) DBO5 < 25 mg/l O2 (70 - 90 %) Sólidos Suspensión < 35 mg/l (90 %) Fósforo total < 2 mg/l (80 %) Nitrógeno total < 15 mg/l (70-80 %) EXAMPLE DQO (mg/l O2): 800 DBO5 (mg/l O2): 400 Sólidos Suspensión (mg/l): 380 Fósforo total (mg/l): 15 Nitrógeno total (mg/l): 65 DQO < 125 mg/l O2 (75 % → 200 mg/l) DBO5 < 25 mg/l O2 (85 % → 60 mg/l) Sólidos Suspensión < 35 mg/l (90% → 38 mg/l) Fósforo total < 2 mg/l (80% → 3 mg/l) Nitrógeno total < 15 mg/l (75% → 16.3 mg/l) Untreated: INLET Treated: OUTLET
  • 22. Questions…..? 1. How many Water Treatment Plants are in Guadalete basin? 2. Are they according with the rules (Directive European Union) 3. Is the quality of the water in the river in good condition? Let´s see
  • 23. Activated Sludge FANGOS ACTIVADOS Villages: Ubrique Bacterial beds LECHOS BACTERIANOS Olvera N y S Algodonales El Gastor Zahara de la Sierra Puerto Serrano Álcalá del Valle Peat beds LECHOS DE TURBA Setenil de las Budegas Torrealháquime Grazalema El Bosque Villaluenga Biodisc BIODISCOS Benamahoma UPPER COURSE: 13 WTP (villages)- 3 villages without WTP Population: 62 558 inhabitant – and E-h: 83 546 E-h 1. How many Water Treatment Plant are in the Guadalete basin? Water Treatment Technologies
  • 24. Activated Sludge FANGOS ACTIVADOS Jerez (little town) Arcos Bacterial beds LECHOS BACTERIANOS Villamartín Paterna de la Rivera Espera Biodisc BIODISCOS La Barca El Torno Nueva Jarilla Torrecera Reactors underground REACTORES SUBTERRÁNEOS La Ina, S. Isidro Majarromaque, Lomopardo Water Treatment Technologies LOWER COURSE: 13 villages- 5 villages without WTP Population: 261 121 inhabitant – and E-h: 455 000 E-h
  • 25. PROYECT 1: Wastewater study of WTP from Guadalete Basin (2002-2004) according to the normative? Río Guadalete Río Majaceite Código Población Código Población UPPER COURSE: 62. 558 inhabitant U-10 Setenil U-27 Benamahoma U-08 Alcalá del Valle U-12 El Bosque U-24 Torrealháquime U-43 Benaocaz (V) U-04 Olvera U-03 Ubrique U-11 Grazalema U-21 Villaluenga del R. U-15 Zahara de la Sierra U-13 El Gastor U-06 Algodonales U-07 Puerto Serrano U-31 Villamartín U-40 Prado del Rey LOWER COURSE: 261. 121 inhabitant U-33 Bornos (V) U-02 Arcos de la Frontera U-38 Espera U-25 Majarromaque (Jer. U-09 La Barca (Jerez) U-18 Torrecera (Jerez) U-37 Paterna U-16 El Torno (Jerez) U-22 S. Isidro (Jerez) U-20 La In a (Jerez) U-29 Lomopardo (Jerez) U-17 Nueva Jarilla (Jerez) U-01 Jerez de la Frontera U-42 Algar (V) U-39 S. José del Valle (V) (V = Vertido) (Los Códigos son los empleados por Comisaría de Aguas de Sevilla) Physico-chemical Analysis Temperature Total Nitrógeno (Nt) pH Total Phospforo (Pt) Oxygen (%) Conductivity (CE) BOD5 QO D Biodegradabity (CB) 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER WASTEWATER 2. Are they according with the normative (Directive European Union)
  • 26. Tecnología Población hab-eq % de Reducción Cumplimiento RD 509/1996DBO5 DQO SS Ntotal Ptotal Fangos activados Ubrique (PN) 12.032 67,8 57,1 40,3 20,6 48,8 NO Lechos bacterianos Olvera N 9.349 88,4 83,2 92,1 29,5 42,6 SI Olvera S 9.349 44,7 68,0 67,1 21,3 40,2 NO Algodonales 7.584 83,8 77,3 77,8 0,0 27,6 SI El Gastor 3.614 86,3 99,7 87,5 39,7 59,1 SI Zahara (PN) 2.577 87,2 83,3 86,6 28,7 21,9 NO Lagunaje El Bosque (PN) 1.257 21,3 24,6 0,0 56,6 41,7 NO Alcalá del V 2.602 2,9 0,0 31,8 46,3 41,9 NO Filtros de turba Setenil 2.491 57,4 50,7 57,2 7,5 52,8 NO Torrealháq 930 58,3 37,6 24,3 21,1 23,5 NO Grazalema (PN) 3.149 76,7 72,4 75,1 3,7 0,0 NO Villaluenga (PN) 1.487 85,9 73,0 30,0 46,5 61,3 NO Biodiscos Benamahom (PN) 763 51,4 39,9 46,2 11,8 72 NO Límites RD 509/1996 70-90 75 70-90 80 70-80 (PN) Poblaciones del Parque Natural de la Sierra de Grazalema que vierten en zonas sensibles PROYECT 1: upper course 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER WASTEWATER
  • 27. TECNOLOGÍA Población H-E % de Reducción Cumplimiento RD 509/1996DBO5 DQO SS Ntotal Ptotal Fangos activados Jerez 272.162 94´6 88´1 92´5 69´2 85´8 SI Arcos 92.183 90´8 92´8 95´3 57´6 46´0 SI Lechos bacterianos Villamartín 35.920 93´7 88´8 68´8 63’9 72´7 NO Paterna 8.986 50´0 49´1 55´9 37´9 0 NO Biodiscos La Barca 11.077 92´8 90´0 96´1 73´4 75´9 SÍ Nueva Jarilla 1.201 67´3 65´3 74´1 50´7 28´8 NO Torrecera 4.452 91´7 90´6 97´0 56´4 69´4 SI La Ina 155 0´0 0´0 0´0 0´0 0´0 NO S. Isidro 159 18´3 19´6 0´0 21´8 6´1 NO Majarromaque 451 36´2 6´3 0´0 24´4 33´3 NO Lomopardo 1.117 0´0 0´0 54´4 30´1 3´8 NO Límites RD 509/1996 70-90 75 70-90 80 70-80 PROYECT 1: lower course 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER WASTEWATER
  • 28. Código Punto de muestreo Habitantes Porc % Hab- equiv Código Punto de muestreo Habitantes Porc % Hab- equiv CUENCA ALTA CUENCA BAJA U-10 Setenil 3 016 0,93 2 491 U-31 Villamartín 12 145 3,75 35 950 U-05 Alcalá del V 5 355 1,65 2 602 U-33 Bornos 8 164 2,52 6 310 U-24 Torrealháquime 877 0,27 930 U-02 Arcos 29 420 9,09 92 183 U-04 Olvera 8 585 2,65 18 698 U-38 Espera 3 909 1,21 6 215 U-11 Grazalema 1 828 0,56 3 149 U-25 Majarromaque 850 0,26 451 U-15 Zahara 1 556 0,48 2 577 U-09 La Barca 3 800 2,52 11 077 U-13 El Gastor 1 948 0,60 3 614 U-18 Torrecera 1 200 0,37 4 452 U-06 Algodonales 5 630 1,74 7 584 U-37 Paterna 5 354 1,65 8 986 U-07 Pto. Serrano 6 852 2,12 13 770 U-16 El Torno 1 200 0,37 3 339 U-40 Prado Rey 5 968 1,84 12 389 U-22 S. Isidro 600 0,19 159 U-27 Benamahoma 397 0,12 763 U-20 La Ina 800 0,25 155 U-12 El Bosque 2 004 0,62 1 257 U-29 Lomopardo 1 100 0,34 1 117 U-43 Benaocaz 729 0,23 203 U-17 Nª Jarilla 1 600 0,39 1 201 U-03 Ubrique 17 362 5,36 12 032 U-01 Jerez 185 125 57,19 272 162 U-21 Villaluenga 481 0,15 1 487 U-42 Algar 1 644 0,51 4 908 U39 S.José del V 4 210 0,30 7 084 TOTAL C. A. 62 588 19,33 83 546 TOTAL C. B. 261.121 80,66 455.749 TOTAL CUENCA 323.709 100,00 539.295 Coloreado de amarillo: Poblaciones sin EDAR en funcionamiento La CUENCA ALTA con el 19,33 % de la población genera el 15,49 % de loshabitantes-equivalentes La CUENCA BAJA con el 80,66 % de la población genera el 84,44 % de los habitantes-equivalentes 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER WASTEWATER
  • 29. Compared study between both basins HABITANTES (2005) VERTIDOS HAB– EQUIV Ratio (h-e)/hm3/año litros/día % Cuenca h-e % Cuenca TOTAL upper course 62 588 6 356 887 17 406 124 18,55 83 546 15,49 1,33 TOTAL lower course 261.121 27.904.669 76.451.148 81,45 455.749 84,51 1,75 TOTAL CUENCA 323.709 34.261.556 93.857.271 100 539.295 100 1,67 Abreviaturas: h = habitantes (h-e) = habitantes-equivalentes 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER WASTEWATER
  • 30. Anual load generated by the urban (before the WTP) Carga DBO5 = 5 960 Tm/año de O2. 50,45 % del total Carga DQO = 9 191 Tm/año de O2. 44,69 % del total Carga SS = 4 275 Tm/año de SS. 33,83 % del total Carga DBO5 = 5 854 Tm/año de O2. 49,55 % del total Carga DQO = 11 377 Tm/año de O2. 55,31 % del total Carga SS = 8 096Tm/año de SS. 66,17 % del total 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% DBO5 DQO SS %CARGAANUAL PARÁMETROS CONTROLADOS CARGA ANUAL GENERADA RESTO POBLACIONES JEREZ JEREZ other populations wastewater 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER WASTEWATER Wastewater WITHOUT treatment Pollution Load (g/day) = Concentration (BOD mg/l O2) x Caudal (m3/day) E-h = Pollution Load / 60 g
  • 31. 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% DBO DQO SS %CARGAANUAL PARÁMETROS CONTROLADOS CARGA ANUAL DE VERTIDOS AL GUADALETE RESTO POBLACIONES JEREZ Carga DBO5 = 321 Tm/año de O2. 13,79 % del total Carga DQO = 1 104 Tm/año de O2. 23,88 % del total Carga SS = 321 Tm/año de SS. 13,81 % del total Carga DBO5 = 2 006 Tm/año de O2. 86,21 % del total Carga DQO = 3 520 Tm/año de O2. 76,12 % del total Carga SS = 2 003 Tm/año de SS. 86,18 % del total JEREZ other populations Wastewater treated Anual load dicharges by the urban (after SSS) 2.- INTEGRATED WATER CYCLE IN GUADALETE RIVER WASTEWATER Wastewater with treatment
  • 32. POPULATIONS Discharges m3/ año Anual load dicharges (Tm/year) DBO Tm/año O2 DQO Tm/año O2 SS Tm/año CURRENTLY: Without treatment TOTAL 3.237.967 1.198 1.946 887 FUTURE: With treatment TOTAL 3.237.967 81 405 113 Differences 1.117 1.541 774 Another questions: 1. what is happening with the 8 villages without treatment? (8 populations with 32 676 E-h) 2. when the plant will be built, how much would reduce their annual load? Without treatment 12.371 Tm SS This investigation (2002-2004): 2.324 Tm SS Future: WTP built and operating properly 1.550 Tm SS
  • 33. 3. Is the quality of the water in the river in good condition? Second project
  • 34. Código Punto de muestreo UPPER COURSE Majaceite River Ubrique-1 Upstream from WTP Ubrique-2 Downstream from WTP Bosque-1 Upstream from WTP Bosque-2 Downstream from WTP Arcos-1 Upstream from WTP LOWER COURSE Guadalete River Arcos-2 Downstream from WTP Jerez-1 Upstream from WTP Jerez-2 Downstream from WTP ANALYSES T Nitrógeno Fluoruros pH Nitratos Cianuros CE Nitritos Metales Oxígeno Amonio DBO5 Fosfatos DQO Hierro SS Manganeso Point Stations PROjECT 2: Controls on the receiving stream from Guadalete Basin (2002-2004)
  • 35. Muestras DBO5 mg/l O2 DQO mg/l O2 SS mg/l Ubrique-1 7 13 11 Ubrique-2 14 32 21 El Bosque-1 8 25 15 El Bosque-2 7 23 25 Arcos-1 8 32 15 Arcos-2 37 99 107 Jerez-1 7 31 158 Jerez-2 8 26 170 mg/l PROjECT 2: organic load in the water river Arcos 2: plant not operating properly Jerez 2: diffuse pollution (agricultural land drag, by rainfall and runoff)
  • 36. River pollution indices: WQI- Water Quality Index (Pesce & Wunderlin, 2000) Ci Parám. Pi 100 90 80 70 60 50 40 30 20 10 0 Rangos de valores analíticos pH 1 7 7-8 7-8,5 7-9 6,5-7 6-9,5 5-10 4-11 3-12 2-13 1-14 CE 2 <0,75 <1,00 <1,25 <1,50 <2,00 <2,50 <3,00 <5,00 <8,00 <12,00 >12 SS 4 <20 <40 <60 <80 <100 <120 <160 <240 <320 <400 >400 NH4 + 3 <0,01 <0,05 <0,10 <0,20 <0,30 <0,40 <0,50 <0,75 <1,00 <1,25 >1,25 NO2 - 2 <0,005 <0,01 <0,03 <0,05 <0,10 <0,15 <0,20 <0,25 <0,50 <1,00 >1,00 NO3 - 2 <0,5 <2,0 <4,0 <6,0 <8,0 <10,0 <15,0 <20,0 <50,0 <100,0 >100,0 PT 1 <0,2 <1,6 <3,2 <6,4 <9,6 <16,0 <32,0 <64,0 <96,0 <160,0 >160 DQO 3 <5 <10 <20 <30 <40 <50 <60 <80 <100 <150 >150 DBO5 3 <0,5 <2,0 <3 <4 <5 <6 <8 <10 <12 <15 >15 OD 4 ≥7,5 >7,0 >6,5 >6,0 >5,0 >4,0 >3,5 >3,0 >2,0 >1,0 >1,0 T 1 21/16 22/15 24/14 26/12 28/10 30/5 32/0 36/-2 40/-4 45/-6 >45/<-6 Todos los valores, excepto pH, en mg/l Conductividad CE en mS/cm
  • 37. River pollution indices: clasification Punto de muestreo WQI CALIFICACIÓN Ubrique-1 61 MEDIUM Ubrique-2 52 MEDIUM El Bosque-1 56 MEDIUM El Bosque-2 54 MEDIUM Arcos-1 41 BAD Arcos-2 20 VERY BAD Jerez-1 32 BAD Jerez-2 28 BAD WQI Clasification 0-25 Very BAD 25-50 BAD 51-70 MEDIUM 71-90 GOOD 91-100 EXCELENT Parameters analysed (11) pH, CE, SS, NH4, NO3, NO2, Pt, DQO, DBO5, OD, T
  • 38. Questions…..? 1. How many Wastewater Treatment Plants are in the Guadalete basin? 2. Are according with the law (Directive European Union) 3. Is the quality of the water in the river in good condition? 4. HOW ARE NOW THE TREATMENT PLANTS? Let´s see
  • 41. 46 % of population without treatment
  • 42. Report on the situation of waste water treatment in the Province of Cádiz 2.2.3.1. VILLAGES WITHOUT SWT Benaocaz. Vertido a acequia Bornos. Vertido al embalse de Bornos Trebujena. Vertido a acequia San José del Valle. Vertido a arrollo Los Toreros. Tarifa. Pretratamiento ACTUACIÓN PREVISTA OBRAS DECLARADAS DE INTERÉS DE CAA HABITANTES BENAOCAZ EDAR y colectores. No existe proyecto. Existe estudio de alternativas. EDAR y colectores en Benaocaz y Grazalema 693 BORNOS En Proyecto EDAR y colectores Por error no los incluyeron en el Acuerdo, pero son necesidades. La EDAR de Bornos ya está en proyecto 8.074 SAN JOSÉ DEL VALLE EDAR y colectores. A fecha de oct. 2012 no hay terrenos. Existe proyecto de AJEMSA EDAR y colectores en Medina Sidonia, San José del Valle y sus núcleos 4.117 TREBUJENA EDAR y colectores. Actualmente oct. 2012 no existe proyecto EDAR y colectores en Trebujena 6.890 TARIFA Existen terrenos y proyecto. A falta de asignación presupuestaria. Ampliación, EDAR y colectores en Tarifa y sus núcleos 15.217
  • 43. Report on the situation of waste water treatment in the Province of Cádiz 46 % de la población de la provincia de Cádiz no depuren sus aguas o no lo hacen con las condiciones establecidas (549.814 habitantes).
  • 44. 2.2 Informe sobre la situación de la depuración de las aguas residuales en la Provincia de Cádiz. 2.2.4. WATER BILL. A quick calculation………………:  CUOTA FIJA: 1 € por vivienda / mes  CUOTA VARIABLE: bloque 1 (< 10 m3) , 0.10 €/m3 consumido  Año 1: se paga 30 % = 0.03 €/m3 consumido  Año 2: 50 % = = 0.05 €/m3 consumido  Año 3: 60 % = = 0.06 €/m3 consumido  Año 4: 80 % = = 0.08 €/m3 consumido  ANDALUCÍA (8.415.490 habitantes) (mayo 2011 – mayo 2012) Año €/m3 Consumo CUOTA VARIABLE Cuota Servicio CUOTA FIJA Total 2012 0,03 12.900.946,17 € 50.492.940,00 € 63.393.886,17 € 2013 0,05 21.501.576,95 € 50.492.940,00 € 71.994.516,95 € 2014 0,06 25.801.892,34 € 50.492.940,00 € 76.294.832,34 € 2015 0,08 34.402.523,12 € 50.492.940,00 € 84.895.463,12 € 296.578.698,58 €
  • 45. CONCLUSIONS 1. How many Wastewater Treatment Plants are in the Guadalete basin? There are sufficient WTP but their operative were not correctly performing. 2. Are they according with the legislation(Directive European Union) No, and currently most of the Plants are in a worse situation than years ago 3. Is the quality of the water in the river in good condition? No, and probably in a worse situation than 2004 Is Guadalete Basin according to Water Framework Directive for 2015? What is the solution?
  • 46. Thanks for your attention