Occupancy Classifications
and Loads
 You must always determine the occupancy
classification and the occupancy load to
establish the parameters that are to be used
for your project.
 An occupancy classification is assigned to the
building or space. It is a broad classification.
(educational)
 Building type is more specific. It is a specific
class or category within an occupancy. (high
school)
 The number of people or occupants for which
the code will require you to provide means of
egress or exiting in your design.
 The occupant load sets the minimum level of
exiting that must be provided
 Number of exits
 Widths of corridors
 Distance to nearest exit
 The maximum number that can occupy the
space.
 An older term used by the older codes.
 Must be assigned to the building or to a space
within the building
 One of the most important steps in the code
process
 Should be the first thing you determine when
designing an interior
 Will affect code requirement pertaining to:
 Occupant load
 Means of egress
 Egress capacities
 Finish selection
 Number of plumbing fixtures
 As well as other areas (shown in fig. 2.1, page 58)
 Existing buildings are already determined
 Buildings with different types of tenants
require that occupancy classifications be
determined for each tenant.
 Careful attention to renovation work (ie: a
warehouse converting to apartments)
 Have a code official approve your decision if
you are unsure
 The ten most common occupancies are:
 Assembly
 Business
 Educational
 Factory or Industrial
 Hazardous
 Institutional
 Mercantile
 Residential
 Storage
 Utility and Misc.
 You will need to know three things before you can
accurately determine the occupancy classification
 The type of activity occurring
 The expected number of occupants and
 If any unusual hazards are present
 These factors can affect the classification of a
building type. (ie: if a particular building is planned
to serve a large number of people, it may be
classified as an Assembly)
 Unusual hazards can either change an occupancy to
a stricter classification or simply require all or part of
a building to be classified as a Hazardous
occupancy…subject to tougher codes. (page 61)
 Large groups of people
 Night occupancies
 Mobility of occupants
 Familiarity of occupants
 Potential spread of fire
 Refer to pages 63-83
 Whether an occupancy is new or existing
becomes important when using the LSC.
 An occupancy is considered new if it falls in
the following categories:
 New construction
 Relocation into an existing building
 New addition to an existing building
 Occupancy is staying in existing space, but
changing size or use
 Incidental Use (page 88) (hazardous areas that are
relatively small, storage, furnace rooms, boiler
rooms, laundry rooms etc.) Additional fire and
smoke protection may be required.
 Accessory Occupancy (page 89) A smaller
occupancy that is typically less than 10% of the total
area of the floor on which it is located. Mercantile
(M) with design center (B) can be considered as an
accessory and not have to design using two
occupancy requirements
 Mixed Occupancies: When two or more
occupancies occur in the same building - under one
roof. (Hotels with restaurants, ballrooms, exercise
rooms will be both Assembly and Business)
 Trend for the future
 Different codes will apply to each
 Requires fire-walls between spaces
 Treat as its own entity
 Office building with a childcare center
(Business/Educational)
 Hospitals with cafeterias (Institutional/Assembly)
 Malls with food courts (mercantile/assembly)
 Certain occupancy classifications are also affected
by the ADA. (page 95)
 Federal building and 1 and 2 family dwelling are not
regulated by the ADA.
 Restaurants and Cafeterias (Assembly)
 Libraries (business or educational)
 Mercantile and many businesses
 Medical (healthcare)
 Transient lodging (residential and correctional/detention)
 Childcare
 An occupant load is the second thing you
need to determine at the beginning of a
project.
 It sets the minimum number of occupants for
which you must design the means of egress
from a building or specific area.
 Each code set a predetermined amount of
space or sq. ft for each occupant. This figure
is called the load factor.
 The load factor is used to help you determine
the occupant load for a space or a building.
 The load factor will help to determine the
number of people that will be using the
corridors, stairs and exits in the event of a fire
 See table on page 101.
 This factor indicates the amount of space or area it
is assumed each person present will require
 Although the sq foot figures may seem high for one
person, they allow for furniture and equipment and
in some cases corridors, closets and other
miscellaneous areas.
 It is always represented in sq. feet; however, it can
be a gross or a net figure.
 The gross area refers to the building as a whole and includes
all misc. spaces within the exterior walls.
 The net area refers to actual occupied spaces and does not
include accessory spaces such as corridors, restrooms, utility
closets etc.
 When net figures are required, it is assumed that the
occupants who are using an ancillary area would have left
the occupied space to do so. (ex: a student walking in a
hallway would already have been counted as a student in the
classroom)
 Note: a Load factor has nothing to do with individual space
allocation with planning a facility.
 Occupancy Load = Floor Area (sq. ft) / Occupant Factor
 Even if you know that your client will have
fewer occupants, you must plan the space
based on the determined load figures as
required by the codes.
 You must figure each occupant load
separately
 Example: Multistory buildings may have
mercantile, business on one floor. Figure
each occupancy type for each floor and add
them together
 Example wasTemple Baptist Church prior to
construction of new sanctuary:
 Worship hall is also a basketball court
 Fellowship hall is also cafeteria
 Figure the occupancy load based on the
largest concentration of people.
 Common in Assembly occupancies
 The seats are considered fixed if they do not easily
move.
 Theaters
 Churches
 Stadiums, bleachers
 Do not use standard formula
 Count actual seats
 For seats without arms, figure 18” for each occupant
 12’ pew is 144” divided by 18 = 8 people
 The occupant load that you determine in the
beginning of a project will be used again later
in your code research to determine the
means of egress, such as
 The number of exits
 Width of exits
 Placement of exits
 Every assembly room or Assembly occupancy
usually requires the approved occupant load
to be permanently posted near the main exit
from the space.
 A typical sign might read
 “Occupancy by more than 100 persons is
dangerous and unlawful.”

More Related Content

PPTX
Fire regulations for buildings
PDF
Mix use building case Study
PDF
Fire safety as per National Building Code-2016
PPTX
Provision for fire protection in high rise buildings
PPTX
Literature ; shopping mall
PPTX
SELECT CITYWALK MALL JAMIA MILLIA ISLAMIA DELHI
PDF
Case study on group housing - Architectural design
PPTX
Group housing case study
Fire regulations for buildings
Mix use building case Study
Fire safety as per National Building Code-2016
Provision for fire protection in high rise buildings
Literature ; shopping mall
SELECT CITYWALK MALL JAMIA MILLIA ISLAMIA DELHI
Case study on group housing - Architectural design
Group housing case study

What's hot (20)

PPTX
Auditorium design ppt
PDF
Critical Analysis: Dept. of Architecture, CET
PPTX
Case study kohinoor square Mumbai
PDF
Standards of School
PPTX
Design of seminar hall
PPTX
HOUSING CASE STUDY
PPTX
Shopping mall case study
PPTX
Select city walk mall case study
PPTX
NISHA'S PLAY SCHOOL , GOA
PPTX
Presentation case study convention center
PDF
Primary School Architectural Design - India
PPTX
PDF
Amanora Future Towers, Hadapsar, Pune - Case Study
PDF
National building code for residential apartments in india
PDF
High rise building case study
PPTX
COMMERCIAL LITERATURE.pptx
PPTX
Architectural design - Case Study on Restaurants
PDF
college campus Case study
PPTX
PREFABRICATED CONSTRUCTION CASE STUDY: THE HEMISPHERE
PDF
Case Study of Triveni Kala Sangam
Auditorium design ppt
Critical Analysis: Dept. of Architecture, CET
Case study kohinoor square Mumbai
Standards of School
Design of seminar hall
HOUSING CASE STUDY
Shopping mall case study
Select city walk mall case study
NISHA'S PLAY SCHOOL , GOA
Presentation case study convention center
Primary School Architectural Design - India
Amanora Future Towers, Hadapsar, Pune - Case Study
National building code for residential apartments in india
High rise building case study
COMMERCIAL LITERATURE.pptx
Architectural design - Case Study on Restaurants
college campus Case study
PREFABRICATED CONSTRUCTION CASE STUDY: THE HEMISPHERE
Case Study of Triveni Kala Sangam
Ad

Similar to Occupancy Load (20)

DOCX
Project On Facility Layout
DOCX
Chapter 16. Facility Layout DecisionAfter selecting a facility.docx
PDF
eSim2016_paper_jon_hand
PPT
Building Codes And The Design Process
PDF
Fire protection engineering design and sustainability
PDF
Zondits ecorithminterview v4 jnp
PPT
Ch09
PPTX
Economics poster 2 jdm rev3_lgl clfinal
PDF
Warehousing Case Study
DOCX
Appendix b
POT
Facility layout-material-handling
PDF
TWO WAREHOUSE INVENTORY MODEL FOR DETERIORATING THINGS WITH SHORTAGES BELOW T...
DOCX
SRI AARUTHRAA CONSTRUCTION
PPTX
Blueprint Reading for Construction Trades
PDF
Life Safety Code: NFPA 101, IFC 2015 & OSHA Subpart E
DOCX
SRI AARUTHRAA CONSTRUCTION
DOCX
SRI AARUTHRAA CONSTRUCTION
PDF
IPU 40487 Smart Buildings White Paper
PDF
lecture-4-location-models-2.pdf
PDF
Project On Facility Layout
Chapter 16. Facility Layout DecisionAfter selecting a facility.docx
eSim2016_paper_jon_hand
Building Codes And The Design Process
Fire protection engineering design and sustainability
Zondits ecorithminterview v4 jnp
Ch09
Economics poster 2 jdm rev3_lgl clfinal
Warehousing Case Study
Appendix b
Facility layout-material-handling
TWO WAREHOUSE INVENTORY MODEL FOR DETERIORATING THINGS WITH SHORTAGES BELOW T...
SRI AARUTHRAA CONSTRUCTION
Blueprint Reading for Construction Trades
Life Safety Code: NFPA 101, IFC 2015 & OSHA Subpart E
SRI AARUTHRAA CONSTRUCTION
SRI AARUTHRAA CONSTRUCTION
IPU 40487 Smart Buildings White Paper
lecture-4-location-models-2.pdf
Ad

More from Tala Jazzy (20)

PDF
Work samples TALA JAZZY
PDF
Tala Jazzy Portfolio
PPTX
165 CHARLES ST,NY,NY
PPTX
Hagia sophia
PPTX
Falling water by frank lloyd
PPTX
Architectural history
PPTX
The rotunda
PPTX
Le castel béranger
PDF
Architectural History
PDF
fire resistant assemblies
PDF
fire resistant assemblies
PDF
Construction types
PDF
Means of egress
PPT
Sustainable design
PPT
PPTX
Victorian House
PPT
roof systems
PPT
foundations
PPT
Doors and windows
PPT
Building site and zoning
Work samples TALA JAZZY
Tala Jazzy Portfolio
165 CHARLES ST,NY,NY
Hagia sophia
Falling water by frank lloyd
Architectural history
The rotunda
Le castel béranger
Architectural History
fire resistant assemblies
fire resistant assemblies
Construction types
Means of egress
Sustainable design
Victorian House
roof systems
foundations
Doors and windows
Building site and zoning

Recently uploaded (20)

PPTX
An introduction to AI in research and reference management
PDF
GREEN BUILDING MATERIALS FOR SUISTAINABLE ARCHITECTURE AND BUILDING STUDY
PPTX
Media And Information Literacy for Grade 12
PDF
Phone away, tabs closed: No multitasking
PPTX
Complete Guide to Microsoft PowerPoint 2019 – Features, Tools, and Tips"
PDF
Design Thinking - Module 1 - Introduction To Design Thinking - Dr. Rohan Dasg...
PPTX
joggers park landscape assignment bandra
PPT
UNIT I- Yarn, types, explanation, process
PPTX
Entrepreneur intro, origin, process, method
PDF
SEVA- Fashion designing-Presentation.pdf
PPT
Machine printing techniques and plangi dyeing
PPTX
Special finishes, classification and types, explanation
PDF
Facade & Landscape Lighting Techniques and Trends.pptx.pdf
PPTX
BSCS lesson 3.pptxnbbjbb mnbkjbkbbkbbkjb
PPTX
6- Architecture design complete (1).pptx
PPTX
mahatma gandhi bus terminal in india Case Study.pptx
PDF
Interior Structure and Construction A1 NGYANQI
DOCX
The story of the first moon landing.docx
PDF
Trusted Executive Protection Services in Ontario — Discreet & Professional.pdf
PDF
YOW2022-BNE-MinimalViableArchitecture.pdf
An introduction to AI in research and reference management
GREEN BUILDING MATERIALS FOR SUISTAINABLE ARCHITECTURE AND BUILDING STUDY
Media And Information Literacy for Grade 12
Phone away, tabs closed: No multitasking
Complete Guide to Microsoft PowerPoint 2019 – Features, Tools, and Tips"
Design Thinking - Module 1 - Introduction To Design Thinking - Dr. Rohan Dasg...
joggers park landscape assignment bandra
UNIT I- Yarn, types, explanation, process
Entrepreneur intro, origin, process, method
SEVA- Fashion designing-Presentation.pdf
Machine printing techniques and plangi dyeing
Special finishes, classification and types, explanation
Facade & Landscape Lighting Techniques and Trends.pptx.pdf
BSCS lesson 3.pptxnbbjbb mnbkjbkbbkbbkjb
6- Architecture design complete (1).pptx
mahatma gandhi bus terminal in india Case Study.pptx
Interior Structure and Construction A1 NGYANQI
The story of the first moon landing.docx
Trusted Executive Protection Services in Ontario — Discreet & Professional.pdf
YOW2022-BNE-MinimalViableArchitecture.pdf

Occupancy Load

  • 2.  You must always determine the occupancy classification and the occupancy load to establish the parameters that are to be used for your project.
  • 3.  An occupancy classification is assigned to the building or space. It is a broad classification. (educational)  Building type is more specific. It is a specific class or category within an occupancy. (high school)
  • 4.  The number of people or occupants for which the code will require you to provide means of egress or exiting in your design.  The occupant load sets the minimum level of exiting that must be provided  Number of exits  Widths of corridors  Distance to nearest exit
  • 5.  The maximum number that can occupy the space.  An older term used by the older codes.
  • 6.  Must be assigned to the building or to a space within the building  One of the most important steps in the code process  Should be the first thing you determine when designing an interior
  • 7.  Will affect code requirement pertaining to:  Occupant load  Means of egress  Egress capacities  Finish selection  Number of plumbing fixtures  As well as other areas (shown in fig. 2.1, page 58)
  • 8.  Existing buildings are already determined  Buildings with different types of tenants require that occupancy classifications be determined for each tenant.  Careful attention to renovation work (ie: a warehouse converting to apartments)  Have a code official approve your decision if you are unsure
  • 9.  The ten most common occupancies are:  Assembly  Business  Educational  Factory or Industrial  Hazardous  Institutional  Mercantile  Residential  Storage  Utility and Misc.
  • 10.  You will need to know three things before you can accurately determine the occupancy classification  The type of activity occurring  The expected number of occupants and  If any unusual hazards are present  These factors can affect the classification of a building type. (ie: if a particular building is planned to serve a large number of people, it may be classified as an Assembly)
  • 11.  Unusual hazards can either change an occupancy to a stricter classification or simply require all or part of a building to be classified as a Hazardous occupancy…subject to tougher codes. (page 61)  Large groups of people  Night occupancies  Mobility of occupants  Familiarity of occupants  Potential spread of fire
  • 12.  Refer to pages 63-83
  • 13.  Whether an occupancy is new or existing becomes important when using the LSC.  An occupancy is considered new if it falls in the following categories:  New construction  Relocation into an existing building  New addition to an existing building  Occupancy is staying in existing space, but changing size or use
  • 14.  Incidental Use (page 88) (hazardous areas that are relatively small, storage, furnace rooms, boiler rooms, laundry rooms etc.) Additional fire and smoke protection may be required.  Accessory Occupancy (page 89) A smaller occupancy that is typically less than 10% of the total area of the floor on which it is located. Mercantile (M) with design center (B) can be considered as an accessory and not have to design using two occupancy requirements
  • 15.  Mixed Occupancies: When two or more occupancies occur in the same building - under one roof. (Hotels with restaurants, ballrooms, exercise rooms will be both Assembly and Business)  Trend for the future  Different codes will apply to each  Requires fire-walls between spaces  Treat as its own entity  Office building with a childcare center (Business/Educational)  Hospitals with cafeterias (Institutional/Assembly)  Malls with food courts (mercantile/assembly)
  • 16.  Certain occupancy classifications are also affected by the ADA. (page 95)  Federal building and 1 and 2 family dwelling are not regulated by the ADA.  Restaurants and Cafeterias (Assembly)  Libraries (business or educational)  Mercantile and many businesses  Medical (healthcare)  Transient lodging (residential and correctional/detention)  Childcare
  • 17.  An occupant load is the second thing you need to determine at the beginning of a project.  It sets the minimum number of occupants for which you must design the means of egress from a building or specific area.  Each code set a predetermined amount of space or sq. ft for each occupant. This figure is called the load factor.
  • 18.  The load factor is used to help you determine the occupant load for a space or a building.  The load factor will help to determine the number of people that will be using the corridors, stairs and exits in the event of a fire  See table on page 101.
  • 19.  This factor indicates the amount of space or area it is assumed each person present will require  Although the sq foot figures may seem high for one person, they allow for furniture and equipment and in some cases corridors, closets and other miscellaneous areas.  It is always represented in sq. feet; however, it can be a gross or a net figure.
  • 20.  The gross area refers to the building as a whole and includes all misc. spaces within the exterior walls.  The net area refers to actual occupied spaces and does not include accessory spaces such as corridors, restrooms, utility closets etc.  When net figures are required, it is assumed that the occupants who are using an ancillary area would have left the occupied space to do so. (ex: a student walking in a hallway would already have been counted as a student in the classroom)  Note: a Load factor has nothing to do with individual space allocation with planning a facility.
  • 21.  Occupancy Load = Floor Area (sq. ft) / Occupant Factor
  • 22.  Even if you know that your client will have fewer occupants, you must plan the space based on the determined load figures as required by the codes.
  • 23.  You must figure each occupant load separately  Example: Multistory buildings may have mercantile, business on one floor. Figure each occupancy type for each floor and add them together
  • 24.  Example wasTemple Baptist Church prior to construction of new sanctuary:  Worship hall is also a basketball court  Fellowship hall is also cafeteria  Figure the occupancy load based on the largest concentration of people.
  • 25.  Common in Assembly occupancies  The seats are considered fixed if they do not easily move.  Theaters  Churches  Stadiums, bleachers  Do not use standard formula  Count actual seats  For seats without arms, figure 18” for each occupant  12’ pew is 144” divided by 18 = 8 people
  • 26.  The occupant load that you determine in the beginning of a project will be used again later in your code research to determine the means of egress, such as  The number of exits  Width of exits  Placement of exits
  • 27.  Every assembly room or Assembly occupancy usually requires the approved occupant load to be permanently posted near the main exit from the space.  A typical sign might read  “Occupancy by more than 100 persons is dangerous and unlawful.”