SlideShare a Scribd company logo
2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications
Jurata
FUSE PROTECTION OF TRANSFORMER POLE SUBSTATION IN
POLAND
Józef Ossowicki(1)
, Remigiusz Joeck(2)
Instytut Elektrotechniki Oddział w Gdańsku(1)
, 80-557 Gdańsk, ul. Narwicka 1
ENERGA SA(2)
, 80-557 Gdańsk, ul. Marynarki Pol. 130, remigiusz.joeck@energa.pl
Abstract: The transformers protection in pole substations MV/LV 15/0,4 kV or 20/0,4 kV, is closely connected
with the protection of complete substation. In Poland, on the MV side mainly expulsion fuses are used but on
the LV side are used current limiting fuses with t-I characteristic gG or gF. It was proved that transformers rated
up to 400 kVA could be effectively and inexpensively protected by fuses against results of overloads and short-
circuits.
Keywords: protection, transformer pole substation, expulsion fuses, overload, short-circuits, t-I characteristic
1. Introduction
Correct protection of transformer pole substation
MV/LV against overloads and short-circuits, has an
essential influence on consumers supply continuity
and safety of people or animals situated close to the
substations. In Poland MV pole substations with
typical rated voltage of 15/0,4 kV or 20/0,4 kV are
mainly situated on the terrains of: agriculture, small
industrial plants or other consumers. They are built as
free–standing constructions with solutions depending
on local conditions. Many years of domestic
maintenance experiences proved [4] that the cheapest
as well as effective transformer protection in these
substations on the MV and LV side against results of
overloads and short-circuits, are properly selected
fuses [1, 3, 8, 10, 11]. In Poland for 40 years for
protection of three-phase transformers rated up to
400 kVA on the 15 kV or 20 kV side, where
prospective short-circuit current does not exceed 3,15
kA [4, 8, 19], were used domestic expulsion fuses
(fig. 1A). For protection of larger transformers or in
case of larger short-circuit currents there are used
limiting fuses (fig. 1B).
Voltage, rated current and breaking capacity of a
fuse are selected according to the basic rules, taking
into consideration permissible transformer overloads.
The permissible operation overload is essential in the
case of distribution transformers. It was accepted that
distribution oil transformer overloads with current
1,5 InT and 1,3 InT should not lasted longer than
adequately 2 and 10 h [5]. Due to the fact that the
transformer has thermal time-constant larger than
series connected conductors and apparatus, all circuit
elements [5] should have the rated current larger than
transformer e.g. In ≥1,25InT. This rule applies also
secondary transformer circuit.
At the beginning of the 70-ties there was a
tendency in Western Europe, especially in France to
simplify transformer pole substation by
eliminating protections on the MV side. Many
fuses were removed what was explained that they
operate due to not justified reasons. It was soon
apparent that the fuses lack of was the reason of
many transformers faults which were dangerous for
surrounding. There were stated cases of oil leaks and
even oil ignition which is an unacceptable ecological
danger for the environment.
Considering different ways of transformer pole
substation protection, the transformers faults
statistics should be observed. Statistics from different
countries could differ a lot, because they concern
transformers produced, installed, protected and
2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications
Jurata
supervised according to the rules of specific technical
education. Polish observations of 6 000 distribution
transformers from period 1990 – 1992, proved that
every year 1% of them are damaged, c.a. 2/3 faults
are internal short-circuit of HV windings, from these
windings to core or oil tank, and also between HV
winding and LV winding [5]. (Undoubtedly, the
newest domestic transformers have several times
lower fault rates). Similar German observation [1] of
600 000 oil distribution transformers, proved that
average fault rate was ten times lower because every
year 0,1% transformers were damaged. Despite a
small fault amount in the latest years, due to the
ecological requirements, there is an observed
noticeable comeback to protection of transformer
pole substations by fuses. It was proved by
experimental testing [2] carried out on single-phase
transformer substations models, rated 50 and 100
kVA. The testing aim was an explanation of MV
fuses operation without reasons especially during
atmospheric discharges. The good example could be
the co-operation between French power engineers
and SIBA company where the new fuse construction
was developed [20]. It enables easy fuse links
replacement by hot stick from the ground level
(without pole climbing).
On the contrary to West Europe experiences, in
Poland almost for 10 years there is a tendency to
eliminate MV fuses in pole substations which are
rated lower than 400 kVA [6, 12]. It is a result of too
many unjustified reasons of expulsion fuse
operations, caused probably by information lack in
catalogues how to select properly these fuses
considering operation co-ordination with fuses on the
LV side. For example in the catalogue [19] there are
presented recommended expulsion fuse nominal
currents for transformer protection on the rated
voltage of 15 kV. The maximum nominal currents of
fuses with gG characteristic which can be used on the
0,4 kV side there were not mentioned.
2. Fuse selection in transformer pole
substations
In Poland are used three variants of transformer
substation protection by fuses (fig. 1).
A B C
Fig. 1. Protection methods of transformer pole substations MV/LV
gG or gF
T
MV
gG or gF
T
MV
LV/gG
gG or gF
T
MV
LV/gTr
2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications
Jurata
The protection method should be selected according
to nominal transformer power and prospective short-
circuit current on the MV side.
• A – On the MV side are used expulsion fuses
when nominal transformer power is not larger
than 400 kVA and prospective short-circuit
current does not exceed 3,15 kA (unless the
expulsion fuses producer proves that his fuses
can be used for protection of transformers with
larger nominal power or in network with larger
prospective short-circuit current).
• B – On the MV side are used classic current
limiting fuses when prospective short-circuit
current is larger than 3,15 kA or when nominal
transformer power exceeds 400 kVA.
• C – Is used when nominal transformer power
is larger than 630 kVA and does not exceed
1000 kVA.
Typical transformer pole substation (fig. 2)
consists of a transformer (T) with nominal power not
exceeding 250 kVA supplied from MV network
usually through expulsion fuses (1), and surge
arresters (not shown on the fig. 2).
Fig. 2. Typical diagram of transformer pole substation ( overvoltage protection is not shown )
In the new products offered among other
producers by ZRE Gdańsk [18] one of MV fuse base
insulator is also a surge arrester. On the
transformers secondary side, in the LV part,
particular outgoing feeders are protected by fuses (2)
with t-I characteristic gG or fast gF in case of rural
network when shock prevention is required.
3. Protection on the MV side
The tasks of MV fuses in transformer pole substation
are:
• protection of the substation part between fuses
connections and transformer clamps against
results of short-circuits,
• transformer protection against: oil tank fault, oil
leak and possible its ignition due to the short-
circuit inside transformer caused by e.g.
insulation breakdown,
• cut-off of two and three-phase short-circuits when
they appears on the secondary transformer side,
on the substation part between bushings and fuse
entrance clamps or fuse load switches on the
particular outgoing feeders (fig. 2).
Fuses for transformers protection should have big
enough operation current If0,1 with prearcing time of
MV
15 kV
1
20 A
T
250 kVA
LV
gG or gF
0,4 kV 2
2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications
Jurata
0,1 s regarding making current holding and
selectivity with protections on the secondary side.
Relative value (with reference to nominal current of
fuse-link In should fulfil the condition (1) [16]
25,0
1,0
100
7 





⋅≥ n
n
f I
I
I
(1)
Fuses should have relatively small prearcing
current If10 in time 10 s due to detection of turn to
turn short-circuit on the secondary transformer side
and selectivity with preceding protections, so the
condition (2) [16] should be fulfilled
6
10
≤
n
f
I
I
(2)
MV fuses should be selected according to the
following:
• Their nominal short-circuit breaking
capacity declared by producer should be not
lower than prospective short-circuit current in
the installation place.
• They should not operate during transformer
switching on in any phase time. It is a
convention [5, 8] that prearcing time at current
12 InT ≥ 0,1 s ; and at current 25 InT ≥ 0,01s. In
their catalogues fuse producers usually describe
type and values of fuse nominal currents which
should be used for transformers protection.
• Their t-I characteristic in prearcing time
(starting from overload to short-circuit in whole
range) should run above t-I characteristic of LV
fuse cut-off for the biggest nominal current of
fuse situated in LV switchgear (fig. 3). Usually
it is accepted that it is the close current to
nominal transformer current InT.
• They should operate in a period shorter than
1 s, if two or three-phase short-circuit on the
secondary transformer side in the substation
part between bushings and LV fuses clamps
appear (fig. 2);
• The maximum value of Joule integral I2
t of
MV fuse cut-off should not exceed 105
A2
s. This
condition is caused by durability of transformer
tank to bursting when internal short-circuit
occurs in the transformer [10].
Requirements mentioned above are easily met in
domestic expulsion fuses [4, 17, 19].
On the Fig. 3, continuous lines present prearcing
t-I characteristics of expulsion fuses for rated voltage
of 15 kV (have been produced in Poland for many
years). Dashed lines show the characteristics
(calculated to the 15 kV side) of maximum fuse
disconnection time (characteristic gG) permitted by
Polish Standard [14]. Fuses from many producers are
in use in Poland. Their t-I characteristics sometimes
differ a lot but all of them should be placed in
required band shown in Polish Standard [14]. Due to
their variety maximum characteristics of permissible
disconnection times should be chosen in the
selectivity analysis. The greatest approach between
these characteristics, occurs when short circuit
current on the 0,4 kV side calculated to the 15 kV
side is ca. 2,5In of expulsion fuse.
2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications
Jurata
Fig. 3. Example of t-I characteristics of: prearcing domestic expulsion15 kV fuses (continuous lines); gG fuse
disconnection calculated to the 15 kV side (dashed lines). Explanations in the text …
In Table 1 it is shown an example of properly selected domestic expulsion fuses which protect the transformers
rated 63 ÷ 400 kVA. On the 0,4 kV side there are used fuses with gG characteristic.
Table 1. Example of fuse selection in transformer pole substations 15/0,4 kV
Transformer
rated power
[kVA]
Nominal voltage 15 kV Nominal voltage 0,4 kV
Transformer
rated current [A]
Fuse rated
current [A]
Transformer
rated current [A]
Fuse rated*)
current [A]
63
100
160
250
400
2,43
3,85
6,20
9,60
15,40
6
10
16
20
25
91,0
144,5
231,0
361,0
578,0
63
125
200
315
400
*) It is the largest rated current of gG fuse-link which assures selective fuse operations.
2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications
Jurata
4. Protection on the LV side
• Fuse selection and protection method of
transformer pole substation on the LV side
depends mainly on nominal transformer power,
less on fuse type or prospective short-circuit
current on the MV side.
• To protect transformers rated up to 400 kVA
against results of overloads and short-circuits,
properly selected fuses on outgoing feeders in
LV switchgear (fig. 1A) should be satisfied,
because in opinion of experienced people there
is a low probability of exceeding permissible
transformer overloads by current 1,3 InT during
10 h and current 1,5 InT during 2 h.
• To protect transformers larger than 400
kVA should be used a protection on the
entrance to the LV switchgear. For this purpose
fuses with transformer characteristic gTr are the
most suitable [17] (fig. 1C). Their advantages
are that they enable full using of permissible
transformer overload [9] and better limit short-
circuit current than fuses with gG characteristic.
5. Conclusions
• Many years of maintenance experiences in West
Europe concerning use of classic limiting fuses
and Polish experiences in use MV expulsion
fuses, point at that the cheapest and also most
effective way of transformer protection and other
parts of substation, against results of overload and
short-circuit are properly selected fuses.
• For transformer protection on the MV side with
nominal power not exceeding 400 kVA, when
prospective short-circuit currents do not exceed
3,15 kA, domestic expulsion fuses are
recommended [18].
• Transformers larger than 400 kVA should be
protected by classic short-circuit current limiting
fuses when prospective short-circuit current
exceeds 3,15 kA on the MV side.
• The mistakes in maintenance can be avoided if
expulsion fuse links are marked by transformer
nominal power and not by nominal current,
according to the standard DIN/VDE [17] for LV
fuse links with gTr characteristic.
• The MV fuses task is to protect transformers
against results of internal short-circuit (oil tank
damage, oil leak and possible its ignition due to
short-circuit occurred inside the transformer) and
cut-off of two and three-phase short-circuit when
it appears on the primary or secondary side in the
substation part between transformer clamps and
fuses.
• Due to the introduction of a new standard PN-IEC
60282-2 [14], some technical parameters of
domestic expulsion fuses (especially for rated
current of 6A) should be corrected and catalogues
completed with necessary technical data,
especially Joule integral I2
t in prearcing time and
during cut-off is what is needed for designers and
users for proper fuses application.
6. References
[1] Hampel W. ; Hartmann E.; Karlscheur
W.;Tenberge W.: „Schutz von
Verteilungstransformatoren“,
Elektrizitätswirschaft, Jg. 91 (1992), Heft 25 z.
1660-1663
[2] Hamel A.; Paquette M.; St-Jean G.: “Nuisance
Fuse Operation on MV Transformers During
Storms”, IEEE Transactions on Power Delivery,
Vol. 5, No. 4, November 1990
[3] Hartmann E.: „Verhalten und Schutz von
Verteilungstransformatoren“, CIRED 89
[4] Kacprzak B.; Hyrczak A.: “Service experience
of new high-voltage expulsion fuses at rural
outdoor networks”, CIRED 1989, s. 76-79
[5] Lipski T.; Musiał E.: „Bezpieczniki topikowe i
ich zastosowania”, Rozdz.8.4.
2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications
Jurata
Podręcznik przygotowany do druku
[6] Michniewski R.: „Eksploatacja stacji
transformatorowych 15/0,4 kV słupowych
uproszczonych w ZE Toruń S.A.”, Biul. Infor.
PTPiREE, nr 2/96
[7] Ossowicki J.; Sibilski H.: „Zabezpieczenia
rozdzielnic pierścieniowych średniego
napięcia”, WE 2000, nr 9
[8] Ossowicki J.: „Nowoczesne zabezpieczenia
transformatorów rozdzielczych”,
Przedsiębiorstwo ENERGO- EKO- TECH
Poznań - Kiekrz paźdz. 2000
[9] Ossowicki J.: „Bezpieczniki topikowe o
charakterystyce gTr w stacjach
transformatorowych”, Biul. Infor. PTPiREE nr
3/2002
[10] Planzlaff K.P., Schemmann B.: „Prűfung des
Verhaltens bei inneren Fehlern im
Transformatorenraum bei nicht begehbaren
Ortsnetzstationen“, Elektrizitätswirtschafft, Jg.
89(1990) Heft 16/17
[11] Popeck C.A., Lewis W.A. and Allen G. D.: “The
Application of Current Limiting to
Distribution Circuit Protection”, USA 1977
[12] „STANDARDY TECHNICZNE
OBOWIĄZUJĄCE DLA URZĄDZEŃ SN i
nN EKSPLOATOWANYCH W ENERDZE
GDAŃSKIEJ KOMPANII
ENERGETYCZNEJ”, S.A. Gdańsk styczeń
2002
[13] PN-92/E-06110: „Bezpieczniki topikowe
wysokiego napięcia. Bezpieczniki ograniczające
prąd”
[14] PN-HD 630.2.1. S5: 2003 (U) „Bezpieczniki
topikowe niskonapięciowe. Część 2-1:
Wymagania dodatkowe dotyczące
bezpieczników przeznaczonych do wymiany
przez osoby wykwalifikowane (przeznaczone
głównie do stosowania w przemyśle). Sekcja od
I do V: Przykłady typowych znormalizowanych
bezpieczników”
[15] PN-IEC 60282-2: „Bezpieczniki topikowe
wysokonapięciowe. Bezpieczniki gazo-
wydmuchowe”, listopad 1999
[16] IEC Publ. 787: “Application guide for the
selection of fuse-links of high voltage fuses for
transformer circuit applications”, 1983
[17] DIN/VDE 0636-201/A10 z października 1997.:
„Niederspannungssicherungen (NH-System)
Teil 2: Zusätzliche Anforderungen an
Sicherungen zum Gebrauch durch
Elektrofachkräfte bzw. elektrotechnisch
unterwiesene Personen (Sicherungen
überwiegend für den industriellen Gebrauch).
Hauptabschnitte I bis V“
[18] Katalog firmy ZRE Gdańsk:
„Wysokonapięciowy zespół zabezpieczający
typu WZZ”
[19] Katalog firmy ZRE Gdańsk: „Wkładka
bezpiecznikowa gazowydmuchowa
napowietrzna typu WBGN”
[20] Katalog firmy SIBA: „HH –Sicherungseinsätze
HH 1- 03/00“

More Related Content

PPT
500MW presentation - 11102006.PPT
PDF
Lineprotection basics june2008
PPT
Basic protection and relaying
PPT
Pilot protection
PPTX
ppt on industrial training of final year studen from ptcul 132kv substation ...
PPT
Busbar Blocking System
PDF
Transformer overcurrent
PDF
15 years of experience stator ground fault protection
500MW presentation - 11102006.PPT
Lineprotection basics june2008
Basic protection and relaying
Pilot protection
ppt on industrial training of final year studen from ptcul 132kv substation ...
Busbar Blocking System
Transformer overcurrent
15 years of experience stator ground fault protection

What's hot (20)

PDF
Power transformer testing and commissioning guidelines r
DOCX
DOCUMENT FOR SOTF PROTECTION FINAL
PDF
RVR-1(3) automatic step voltage regulator
PDF
Substation Maintenance
PDF
ABB Medium Voltage MV Indoor Voltage Transformers VT'S - 3.3kV to 40.5kV - A...
PPT
Testing,maintenance&protection
PPT
Numerical protection 2
PPT
Introduction to TVS Overvoltage Protection Devices
PDF
Performance of quadrilateral relay on EHV transmission line protection during...
PDF
7UT612 Transformer Differential Protection relay
PPTX
Shubham chamoli 132 kv substation presenttation
PPTX
Autoreclose
PDF
7SR23 High Impedance Bus Bar Protection Relay
PDF
Transformer testing
PPT
Introduction to Thyristor Power Controllers
PPT
Testing and Condition Monitoring of Substation Equipments
PDF
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
PDF
M type Pole mounted Vacuum type Auto recloser catalog
PDF
RLW type pole mounted vacuum load break switch
PPSX
ECNG 3015 - Overcurrent Protection
Power transformer testing and commissioning guidelines r
DOCUMENT FOR SOTF PROTECTION FINAL
RVR-1(3) automatic step voltage regulator
Substation Maintenance
ABB Medium Voltage MV Indoor Voltage Transformers VT'S - 3.3kV to 40.5kV - A...
Testing,maintenance&protection
Numerical protection 2
Introduction to TVS Overvoltage Protection Devices
Performance of quadrilateral relay on EHV transmission line protection during...
7UT612 Transformer Differential Protection relay
Shubham chamoli 132 kv substation presenttation
Autoreclose
7SR23 High Impedance Bus Bar Protection Relay
Transformer testing
Introduction to Thyristor Power Controllers
Testing and Condition Monitoring of Substation Equipments
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
M type Pole mounted Vacuum type Auto recloser catalog
RLW type pole mounted vacuum load break switch
ECNG 3015 - Overcurrent Protection
Ad

Viewers also liked (20)

PDF
2011 10-10 joeck psm ukladanie kabli dla farm wiatrowych offshore
PDF
2012 10-10 joeck koncepcja budowy sieci morskich na morzu bałtyckim
PDF
2011 09-07 joeck polish offshoregrid
PDF
2004 06-22 joeck gdynia awaryjność głowic kablowych w stacjach wnętrzowych sn-nn
PDF
2012 10-10 joeck concept of the offshore grid development on the baltic sea
PDF
2003 03-04 joeck energo-eko-tech-kable sn-n n
PDF
2007 06-13 joeck jurata dosycanie głowic sn
PDF
2007 06-13 joeck jurata trójniki nn
PDF
2015 09-05 joeck magazynowanie energii
PDF
Analsis of very fast transient over voltages in gas insulated substations
PPT
Estimation of a_pole_mounted_substation
PDF
substation 101
DOC
PPTX
Alok ppt new 13 aprl
PPTX
Gas insulated sub station 2
DOC
System and method for generating electric power
PPT
electrical engineering
PPTX
1.substation layouts
PPTX
Power generation from railway track
PPTX
Power generation through railway track
2011 10-10 joeck psm ukladanie kabli dla farm wiatrowych offshore
2012 10-10 joeck koncepcja budowy sieci morskich na morzu bałtyckim
2011 09-07 joeck polish offshoregrid
2004 06-22 joeck gdynia awaryjność głowic kablowych w stacjach wnętrzowych sn-nn
2012 10-10 joeck concept of the offshore grid development on the baltic sea
2003 03-04 joeck energo-eko-tech-kable sn-n n
2007 06-13 joeck jurata dosycanie głowic sn
2007 06-13 joeck jurata trójniki nn
2015 09-05 joeck magazynowanie energii
Analsis of very fast transient over voltages in gas insulated substations
Estimation of a_pole_mounted_substation
substation 101
Alok ppt new 13 aprl
Gas insulated sub station 2
System and method for generating electric power
electrical engineering
1.substation layouts
Power generation from railway track
Power generation through railway track
Ad

Similar to 2003 09-08 joeck icefa fuse protection in transformer pole substation (20)

PDF
600v Medium Voltage Transformer Fuses for Circuit Protection
PPT
Transformer design and protection
PDF
BPMI TRANSFORMER PROTECTION.pptx.pdf
DOCX
Power Quality Variations in Distribution Circuits
PDF
Surge protection with shah jaydeep
DOC
Notes1 intro
PDF
Transfguide transformer protection application guide
PDF
Transformer guide
PDF
EE 582 lect 2- 3 surges 1446 2 522.pdf
ODP
Transformers protection, an introduction
PPTX
Power quality & demand side management
PPTX
transformer protection
PDF
11.[21 28]voltage stability improvement using the 21st century power transformer
PPT
Pd Maintenance
PPTX
620693379-Distribution-Line-Protection-1.pptx
PDF
Lightning and Surge Protection Strategy for Instrumentation
PDF
TR Protection relay testing with details Abb
PDF
ABB Medium Voltage Indoor Fuses - ABB CEF-S High Voltage Current Limiting Fus...
PDF
Spd electrical protection handbook
600v Medium Voltage Transformer Fuses for Circuit Protection
Transformer design and protection
BPMI TRANSFORMER PROTECTION.pptx.pdf
Power Quality Variations in Distribution Circuits
Surge protection with shah jaydeep
Notes1 intro
Transfguide transformer protection application guide
Transformer guide
EE 582 lect 2- 3 surges 1446 2 522.pdf
Transformers protection, an introduction
Power quality & demand side management
transformer protection
11.[21 28]voltage stability improvement using the 21st century power transformer
Pd Maintenance
620693379-Distribution-Line-Protection-1.pptx
Lightning and Surge Protection Strategy for Instrumentation
TR Protection relay testing with details Abb
ABB Medium Voltage Indoor Fuses - ABB CEF-S High Voltage Current Limiting Fus...
Spd electrical protection handbook

Recently uploaded (20)

PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
86236642-Electric-Loco-Shed.pdf jfkduklg
PDF
Abrasive, erosive and cavitation wear.pdf
PPTX
Current and future trends in Computer Vision.pptx
PDF
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PDF
Integrating Fractal Dimension and Time Series Analysis for Optimized Hyperspe...
PPTX
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
PDF
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
PPT
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PDF
Analyzing Impact of Pakistan Economic Corridor on Import and Export in Pakist...
PPTX
Nature of X-rays, X- Ray Equipment, Fluoroscopy
PPTX
Safety Seminar civil to be ensured for safe working.
PPTX
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
PDF
Visual Aids for Exploratory Data Analysis.pdf
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
introduction to high performance computing
PPTX
Fundamentals of Mechanical Engineering.pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Automation-in-Manufacturing-Chapter-Introduction.pdf
86236642-Electric-Loco-Shed.pdf jfkduklg
Abrasive, erosive and cavitation wear.pdf
Current and future trends in Computer Vision.pptx
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
Integrating Fractal Dimension and Time Series Analysis for Optimized Hyperspe...
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Analyzing Impact of Pakistan Economic Corridor on Import and Export in Pakist...
Nature of X-rays, X- Ray Equipment, Fluoroscopy
Safety Seminar civil to be ensured for safe working.
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
Visual Aids for Exploratory Data Analysis.pdf
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
introduction to high performance computing
Fundamentals of Mechanical Engineering.pptx

2003 09-08 joeck icefa fuse protection in transformer pole substation

  • 1. 2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications Jurata FUSE PROTECTION OF TRANSFORMER POLE SUBSTATION IN POLAND Józef Ossowicki(1) , Remigiusz Joeck(2) Instytut Elektrotechniki Oddział w Gdańsku(1) , 80-557 Gdańsk, ul. Narwicka 1 ENERGA SA(2) , 80-557 Gdańsk, ul. Marynarki Pol. 130, remigiusz.joeck@energa.pl Abstract: The transformers protection in pole substations MV/LV 15/0,4 kV or 20/0,4 kV, is closely connected with the protection of complete substation. In Poland, on the MV side mainly expulsion fuses are used but on the LV side are used current limiting fuses with t-I characteristic gG or gF. It was proved that transformers rated up to 400 kVA could be effectively and inexpensively protected by fuses against results of overloads and short- circuits. Keywords: protection, transformer pole substation, expulsion fuses, overload, short-circuits, t-I characteristic 1. Introduction Correct protection of transformer pole substation MV/LV against overloads and short-circuits, has an essential influence on consumers supply continuity and safety of people or animals situated close to the substations. In Poland MV pole substations with typical rated voltage of 15/0,4 kV or 20/0,4 kV are mainly situated on the terrains of: agriculture, small industrial plants or other consumers. They are built as free–standing constructions with solutions depending on local conditions. Many years of domestic maintenance experiences proved [4] that the cheapest as well as effective transformer protection in these substations on the MV and LV side against results of overloads and short-circuits, are properly selected fuses [1, 3, 8, 10, 11]. In Poland for 40 years for protection of three-phase transformers rated up to 400 kVA on the 15 kV or 20 kV side, where prospective short-circuit current does not exceed 3,15 kA [4, 8, 19], were used domestic expulsion fuses (fig. 1A). For protection of larger transformers or in case of larger short-circuit currents there are used limiting fuses (fig. 1B). Voltage, rated current and breaking capacity of a fuse are selected according to the basic rules, taking into consideration permissible transformer overloads. The permissible operation overload is essential in the case of distribution transformers. It was accepted that distribution oil transformer overloads with current 1,5 InT and 1,3 InT should not lasted longer than adequately 2 and 10 h [5]. Due to the fact that the transformer has thermal time-constant larger than series connected conductors and apparatus, all circuit elements [5] should have the rated current larger than transformer e.g. In ≥1,25InT. This rule applies also secondary transformer circuit. At the beginning of the 70-ties there was a tendency in Western Europe, especially in France to simplify transformer pole substation by eliminating protections on the MV side. Many fuses were removed what was explained that they operate due to not justified reasons. It was soon apparent that the fuses lack of was the reason of many transformers faults which were dangerous for surrounding. There were stated cases of oil leaks and even oil ignition which is an unacceptable ecological danger for the environment. Considering different ways of transformer pole substation protection, the transformers faults statistics should be observed. Statistics from different countries could differ a lot, because they concern transformers produced, installed, protected and
  • 2. 2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications Jurata supervised according to the rules of specific technical education. Polish observations of 6 000 distribution transformers from period 1990 – 1992, proved that every year 1% of them are damaged, c.a. 2/3 faults are internal short-circuit of HV windings, from these windings to core or oil tank, and also between HV winding and LV winding [5]. (Undoubtedly, the newest domestic transformers have several times lower fault rates). Similar German observation [1] of 600 000 oil distribution transformers, proved that average fault rate was ten times lower because every year 0,1% transformers were damaged. Despite a small fault amount in the latest years, due to the ecological requirements, there is an observed noticeable comeback to protection of transformer pole substations by fuses. It was proved by experimental testing [2] carried out on single-phase transformer substations models, rated 50 and 100 kVA. The testing aim was an explanation of MV fuses operation without reasons especially during atmospheric discharges. The good example could be the co-operation between French power engineers and SIBA company where the new fuse construction was developed [20]. It enables easy fuse links replacement by hot stick from the ground level (without pole climbing). On the contrary to West Europe experiences, in Poland almost for 10 years there is a tendency to eliminate MV fuses in pole substations which are rated lower than 400 kVA [6, 12]. It is a result of too many unjustified reasons of expulsion fuse operations, caused probably by information lack in catalogues how to select properly these fuses considering operation co-ordination with fuses on the LV side. For example in the catalogue [19] there are presented recommended expulsion fuse nominal currents for transformer protection on the rated voltage of 15 kV. The maximum nominal currents of fuses with gG characteristic which can be used on the 0,4 kV side there were not mentioned. 2. Fuse selection in transformer pole substations In Poland are used three variants of transformer substation protection by fuses (fig. 1). A B C Fig. 1. Protection methods of transformer pole substations MV/LV gG or gF T MV gG or gF T MV LV/gG gG or gF T MV LV/gTr
  • 3. 2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications Jurata The protection method should be selected according to nominal transformer power and prospective short- circuit current on the MV side. • A – On the MV side are used expulsion fuses when nominal transformer power is not larger than 400 kVA and prospective short-circuit current does not exceed 3,15 kA (unless the expulsion fuses producer proves that his fuses can be used for protection of transformers with larger nominal power or in network with larger prospective short-circuit current). • B – On the MV side are used classic current limiting fuses when prospective short-circuit current is larger than 3,15 kA or when nominal transformer power exceeds 400 kVA. • C – Is used when nominal transformer power is larger than 630 kVA and does not exceed 1000 kVA. Typical transformer pole substation (fig. 2) consists of a transformer (T) with nominal power not exceeding 250 kVA supplied from MV network usually through expulsion fuses (1), and surge arresters (not shown on the fig. 2). Fig. 2. Typical diagram of transformer pole substation ( overvoltage protection is not shown ) In the new products offered among other producers by ZRE Gdańsk [18] one of MV fuse base insulator is also a surge arrester. On the transformers secondary side, in the LV part, particular outgoing feeders are protected by fuses (2) with t-I characteristic gG or fast gF in case of rural network when shock prevention is required. 3. Protection on the MV side The tasks of MV fuses in transformer pole substation are: • protection of the substation part between fuses connections and transformer clamps against results of short-circuits, • transformer protection against: oil tank fault, oil leak and possible its ignition due to the short- circuit inside transformer caused by e.g. insulation breakdown, • cut-off of two and three-phase short-circuits when they appears on the secondary transformer side, on the substation part between bushings and fuse entrance clamps or fuse load switches on the particular outgoing feeders (fig. 2). Fuses for transformers protection should have big enough operation current If0,1 with prearcing time of MV 15 kV 1 20 A T 250 kVA LV gG or gF 0,4 kV 2
  • 4. 2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications Jurata 0,1 s regarding making current holding and selectivity with protections on the secondary side. Relative value (with reference to nominal current of fuse-link In should fulfil the condition (1) [16] 25,0 1,0 100 7       ⋅≥ n n f I I I (1) Fuses should have relatively small prearcing current If10 in time 10 s due to detection of turn to turn short-circuit on the secondary transformer side and selectivity with preceding protections, so the condition (2) [16] should be fulfilled 6 10 ≤ n f I I (2) MV fuses should be selected according to the following: • Their nominal short-circuit breaking capacity declared by producer should be not lower than prospective short-circuit current in the installation place. • They should not operate during transformer switching on in any phase time. It is a convention [5, 8] that prearcing time at current 12 InT ≥ 0,1 s ; and at current 25 InT ≥ 0,01s. In their catalogues fuse producers usually describe type and values of fuse nominal currents which should be used for transformers protection. • Their t-I characteristic in prearcing time (starting from overload to short-circuit in whole range) should run above t-I characteristic of LV fuse cut-off for the biggest nominal current of fuse situated in LV switchgear (fig. 3). Usually it is accepted that it is the close current to nominal transformer current InT. • They should operate in a period shorter than 1 s, if two or three-phase short-circuit on the secondary transformer side in the substation part between bushings and LV fuses clamps appear (fig. 2); • The maximum value of Joule integral I2 t of MV fuse cut-off should not exceed 105 A2 s. This condition is caused by durability of transformer tank to bursting when internal short-circuit occurs in the transformer [10]. Requirements mentioned above are easily met in domestic expulsion fuses [4, 17, 19]. On the Fig. 3, continuous lines present prearcing t-I characteristics of expulsion fuses for rated voltage of 15 kV (have been produced in Poland for many years). Dashed lines show the characteristics (calculated to the 15 kV side) of maximum fuse disconnection time (characteristic gG) permitted by Polish Standard [14]. Fuses from many producers are in use in Poland. Their t-I characteristics sometimes differ a lot but all of them should be placed in required band shown in Polish Standard [14]. Due to their variety maximum characteristics of permissible disconnection times should be chosen in the selectivity analysis. The greatest approach between these characteristics, occurs when short circuit current on the 0,4 kV side calculated to the 15 kV side is ca. 2,5In of expulsion fuse.
  • 5. 2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications Jurata Fig. 3. Example of t-I characteristics of: prearcing domestic expulsion15 kV fuses (continuous lines); gG fuse disconnection calculated to the 15 kV side (dashed lines). Explanations in the text … In Table 1 it is shown an example of properly selected domestic expulsion fuses which protect the transformers rated 63 ÷ 400 kVA. On the 0,4 kV side there are used fuses with gG characteristic. Table 1. Example of fuse selection in transformer pole substations 15/0,4 kV Transformer rated power [kVA] Nominal voltage 15 kV Nominal voltage 0,4 kV Transformer rated current [A] Fuse rated current [A] Transformer rated current [A] Fuse rated*) current [A] 63 100 160 250 400 2,43 3,85 6,20 9,60 15,40 6 10 16 20 25 91,0 144,5 231,0 361,0 578,0 63 125 200 315 400 *) It is the largest rated current of gG fuse-link which assures selective fuse operations.
  • 6. 2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications Jurata 4. Protection on the LV side • Fuse selection and protection method of transformer pole substation on the LV side depends mainly on nominal transformer power, less on fuse type or prospective short-circuit current on the MV side. • To protect transformers rated up to 400 kVA against results of overloads and short-circuits, properly selected fuses on outgoing feeders in LV switchgear (fig. 1A) should be satisfied, because in opinion of experienced people there is a low probability of exceeding permissible transformer overloads by current 1,3 InT during 10 h and current 1,5 InT during 2 h. • To protect transformers larger than 400 kVA should be used a protection on the entrance to the LV switchgear. For this purpose fuses with transformer characteristic gTr are the most suitable [17] (fig. 1C). Their advantages are that they enable full using of permissible transformer overload [9] and better limit short- circuit current than fuses with gG characteristic. 5. Conclusions • Many years of maintenance experiences in West Europe concerning use of classic limiting fuses and Polish experiences in use MV expulsion fuses, point at that the cheapest and also most effective way of transformer protection and other parts of substation, against results of overload and short-circuit are properly selected fuses. • For transformer protection on the MV side with nominal power not exceeding 400 kVA, when prospective short-circuit currents do not exceed 3,15 kA, domestic expulsion fuses are recommended [18]. • Transformers larger than 400 kVA should be protected by classic short-circuit current limiting fuses when prospective short-circuit current exceeds 3,15 kA on the MV side. • The mistakes in maintenance can be avoided if expulsion fuse links are marked by transformer nominal power and not by nominal current, according to the standard DIN/VDE [17] for LV fuse links with gTr characteristic. • The MV fuses task is to protect transformers against results of internal short-circuit (oil tank damage, oil leak and possible its ignition due to short-circuit occurred inside the transformer) and cut-off of two and three-phase short-circuit when it appears on the primary or secondary side in the substation part between transformer clamps and fuses. • Due to the introduction of a new standard PN-IEC 60282-2 [14], some technical parameters of domestic expulsion fuses (especially for rated current of 6A) should be corrected and catalogues completed with necessary technical data, especially Joule integral I2 t in prearcing time and during cut-off is what is needed for designers and users for proper fuses application. 6. References [1] Hampel W. ; Hartmann E.; Karlscheur W.;Tenberge W.: „Schutz von Verteilungstransformatoren“, Elektrizitätswirschaft, Jg. 91 (1992), Heft 25 z. 1660-1663 [2] Hamel A.; Paquette M.; St-Jean G.: “Nuisance Fuse Operation on MV Transformers During Storms”, IEEE Transactions on Power Delivery, Vol. 5, No. 4, November 1990 [3] Hartmann E.: „Verhalten und Schutz von Verteilungstransformatoren“, CIRED 89 [4] Kacprzak B.; Hyrczak A.: “Service experience of new high-voltage expulsion fuses at rural outdoor networks”, CIRED 1989, s. 76-79 [5] Lipski T.; Musiał E.: „Bezpieczniki topikowe i ich zastosowania”, Rozdz.8.4.
  • 7. 2003-09-08 ICEFA, Seventh International Conference on Electrical Fuses and their Applications Jurata Podręcznik przygotowany do druku [6] Michniewski R.: „Eksploatacja stacji transformatorowych 15/0,4 kV słupowych uproszczonych w ZE Toruń S.A.”, Biul. Infor. PTPiREE, nr 2/96 [7] Ossowicki J.; Sibilski H.: „Zabezpieczenia rozdzielnic pierścieniowych średniego napięcia”, WE 2000, nr 9 [8] Ossowicki J.: „Nowoczesne zabezpieczenia transformatorów rozdzielczych”, Przedsiębiorstwo ENERGO- EKO- TECH Poznań - Kiekrz paźdz. 2000 [9] Ossowicki J.: „Bezpieczniki topikowe o charakterystyce gTr w stacjach transformatorowych”, Biul. Infor. PTPiREE nr 3/2002 [10] Planzlaff K.P., Schemmann B.: „Prűfung des Verhaltens bei inneren Fehlern im Transformatorenraum bei nicht begehbaren Ortsnetzstationen“, Elektrizitätswirtschafft, Jg. 89(1990) Heft 16/17 [11] Popeck C.A., Lewis W.A. and Allen G. D.: “The Application of Current Limiting to Distribution Circuit Protection”, USA 1977 [12] „STANDARDY TECHNICZNE OBOWIĄZUJĄCE DLA URZĄDZEŃ SN i nN EKSPLOATOWANYCH W ENERDZE GDAŃSKIEJ KOMPANII ENERGETYCZNEJ”, S.A. Gdańsk styczeń 2002 [13] PN-92/E-06110: „Bezpieczniki topikowe wysokiego napięcia. Bezpieczniki ograniczające prąd” [14] PN-HD 630.2.1. S5: 2003 (U) „Bezpieczniki topikowe niskonapięciowe. Część 2-1: Wymagania dodatkowe dotyczące bezpieczników przeznaczonych do wymiany przez osoby wykwalifikowane (przeznaczone głównie do stosowania w przemyśle). Sekcja od I do V: Przykłady typowych znormalizowanych bezpieczników” [15] PN-IEC 60282-2: „Bezpieczniki topikowe wysokonapięciowe. Bezpieczniki gazo- wydmuchowe”, listopad 1999 [16] IEC Publ. 787: “Application guide for the selection of fuse-links of high voltage fuses for transformer circuit applications”, 1983 [17] DIN/VDE 0636-201/A10 z października 1997.: „Niederspannungssicherungen (NH-System) Teil 2: Zusätzliche Anforderungen an Sicherungen zum Gebrauch durch Elektrofachkräfte bzw. elektrotechnisch unterwiesene Personen (Sicherungen überwiegend für den industriellen Gebrauch). Hauptabschnitte I bis V“ [18] Katalog firmy ZRE Gdańsk: „Wysokonapięciowy zespół zabezpieczający typu WZZ” [19] Katalog firmy ZRE Gdańsk: „Wkładka bezpiecznikowa gazowydmuchowa napowietrzna typu WBGN” [20] Katalog firmy SIBA: „HH –Sicherungseinsätze HH 1- 03/00“