Requirements for Electrical Installations IEE Wiring Regulations  17 th  Edition Part 4 Chapter 44
IEE Wiring Regulations  17 th  Edition - Part 4 As previously stated: It consists of only 4 chapters,  41 – Protection against Electric Shock . 42 – Protection against Thermal Effects . 43 – Protection against Overcurrent. Last one Tonight: -  44 – Protection against voltage disturbances    and Electromagnetic Disturbances .
Requirements for Electrical Installations IEE Wiring Regulations  17 th  Edition Part 4 Chapter 44
Chapter 44 Protection against Overcurrent  There are 6 sections in this chapter 440 – Introduction 441 – Not used 442 – Protection of low voltage installations      against temporary overvoltages due to        various faults 443 – Protection of overvoltages of atmospheric    origin or due to switching 444 –  Reserved for   Measures against electromagnetic   Influences 445 – Protection against undervoltages
Chapter 442 Protection of low voltage installations against  temporary   overvoltages  due to earth faults in the high voltage system due to faults in the low voltage system   The following four situations can have an effect on the safety of an LV installation by creating temporary overvoltages: A fault between the HV system and Earth in the transformer. (Regulation Group 442.2) Loss of the supply neutral in the LV installation (Regulation 442.3)
Chapter 442 Protection of low voltage installations against  temporary   overvoltages  due to earth faults in the high voltage system due to faults in the low voltage system Accidental earthing of a line conductor of an LV IT system. (Regulation 442.4) Short-circuit between a line conductor and neutral in the LV installation. (Regulation 442).
443 – Protection against overvoltages of atmospheric origin or due to switching As the UK has ≤ 25 thunderstorm days per year (AQ1),  NO  additional protection is required against overvoltages of atmospheric origin where installations are supplied by LV overhead lines,  provided   …
Required minimum impulse withstand voltage Refer to Table 44.4 for examples of various impulse categories of equipment Nominal voltage of the installation V Required minimum impulse withstand voltage   kV Category  IV   (equipment with very high impulse voltage) Category  III   (equipment with high impulse voltage) Category  II   (equipment with normal impulse voltage) Category  I  (equipment with reduced impulse voltage) 230/240 or 277/480 6 4 2.5 1.5 400/690 8 6 4 2.5 1000 Values to be determined by the system engineer or, in the absence of information, the values for 400/690 V can be chosen.
443 – Protection against overvoltages of atmospheric origin or due to switching Switching overvoltages  may be generated within an installation as the result of switching of: high current loads, inductive loads, such as motors, transformers or arc welding equipment, or  capacitive loads, such as power factor correction equipment.
444 – Measures against electromagnetic influences Reserved for  future use
445 – Protection against undervoltage
445 – Protection against undervoltage As in 131.1 (v) we are going to protect persons and livestock against Mechanical movement from electrically actuated equipment . . . . .
445 – Protection against undervoltage This also includes:- Suitable time delay being incorporated in the operation of an undervoltage protection device. Any time delay not reactivate a contactor and not impede the disconnection of a control or protective device. That such a device shall be compatible with the requirements for starting as stated in the appropriate British Standard. Where the automatic reclosure of a device may cause danger
445 – Protection against undervoltage The most used equipment falling into this category is:- Incorporated into motor starters . . . . i.e. The “No Volt Coil” in the contactor.
Chapter 44 Protection against Overcurrent Does this make sense? GOOD  – We will carry on -  -   -   -   -   -   -   - To Part 5 - - - - - -  Next Session

More Related Content

PPT
17th Edition Part 4 3
PPT
17th Edition Parts 53 To 56
PPT
17th Edition Part 4
PPT
17th Edition Part 2 3
PPT
17th Edition Part 4 2
PDF
2005 16 autumn_wiring_matters__complete_no_adverts
PPT
17th Edition Part 5 1
PPT
17th Edition Parts 703 On
17th Edition Part 4 3
17th Edition Parts 53 To 56
17th Edition Part 4
17th Edition Part 2 3
17th Edition Part 4 2
2005 16 autumn_wiring_matters__complete_no_adverts
17th Edition Part 5 1
17th Edition Parts 703 On

What's hot (20)

PPT
17th Edition Part 6
PPT
17th Edition Part 701
PPT
17th Edition Part 5 2 1
PPT
17th Eedition Part 702
PPT
17th Edition Part 524 To 529
PDF
Understanding Arc Flash
PDF
Presentation o surge protection devices
PDF
Richard Blakeley - Options for managing safety with elderly switchgear
PPTX
Circuit protection devices perfect ppt
PPT
Surge supressor
PDF
Vcb ppt.
PPTX
2015 Arc Flash Conference MV Switchgear Standards
PPTX
ABB switchgear safety hazards passive & active arc fault protection by David ...
PDF
BEAMA Guide To Surge Protection Devices (SPD's) - Selection, Application & Th...
PDF
Code questions
PPTX
Improving the reliability of feeder protection using digital relays
PDF
Ocpd 07-23-13
PDF
Selective Coordination
PPTX
Power system protection
PDF
ABB HRC High Voltage Fuse Links
17th Edition Part 6
17th Edition Part 701
17th Edition Part 5 2 1
17th Eedition Part 702
17th Edition Part 524 To 529
Understanding Arc Flash
Presentation o surge protection devices
Richard Blakeley - Options for managing safety with elderly switchgear
Circuit protection devices perfect ppt
Surge supressor
Vcb ppt.
2015 Arc Flash Conference MV Switchgear Standards
ABB switchgear safety hazards passive & active arc fault protection by David ...
BEAMA Guide To Surge Protection Devices (SPD's) - Selection, Application & Th...
Code questions
Improving the reliability of feeder protection using digital relays
Ocpd 07-23-13
Selective Coordination
Power system protection
ABB HRC High Voltage Fuse Links
Ad

Similar to 17th Edition Part 4 4 (20)

PDF
Guide to Surge Protection Devices
PDF
Design Development and Testing of an Overvoltage and Undervoltage Protection ...
PPTX
Surge and Lightning Protection Oct 2020
PDF
Hager Guide to Surge Protection.pdf
PPT
17thEdition.ppt
PPT
basic electrical engineering pdf........
PPTX
Insulation coordination.
PDF
MCC Motor Control Center 2
PDF
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
PDF
20240730115742_STC-ESS-ZT51X00B-001 wall mounted 51V100Ah&51V200Ahoperating m...
PDF
Power System Stability Issues
PDF
Transient overvoltages and currents: TOVs and swells
PPTX
Transformers & Transformer Vaults Specification
PPT
6654882 presentation-on-insulation-co ordination
PDF
244109578 estandar-iec-60947-2-pdf
PPTX
file-9.pptx
PPT
Reactors
PPTX
file-9.pptx
PDF
Power system stability issues and Defence Mechanism in Indian Grid
PPTX
High Voltage Design and Installations Master Class
Guide to Surge Protection Devices
Design Development and Testing of an Overvoltage and Undervoltage Protection ...
Surge and Lightning Protection Oct 2020
Hager Guide to Surge Protection.pdf
17thEdition.ppt
basic electrical engineering pdf........
Insulation coordination.
MCC Motor Control Center 2
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
20240730115742_STC-ESS-ZT51X00B-001 wall mounted 51V100Ah&51V200Ahoperating m...
Power System Stability Issues
Transient overvoltages and currents: TOVs and swells
Transformers & Transformer Vaults Specification
6654882 presentation-on-insulation-co ordination
244109578 estandar-iec-60947-2-pdf
file-9.pptx
Reactors
file-9.pptx
Power system stability issues and Defence Mechanism in Indian Grid
High Voltage Design and Installations Master Class
Ad

More from Paul Holden (8)

DOC
Plan Of The 17th Edition
PPT
Earthing Arrangements
PPT
Earthing Arrangements 17th
PPT
17th Edition Regs F I R S T
PPT
17th Edition Regs S E C O N D
PPT
17th Edition Info
PPT
17th Regs Intro
PPT
17th Edition Part 5 2 2
Plan Of The 17th Edition
Earthing Arrangements
Earthing Arrangements 17th
17th Edition Regs F I R S T
17th Edition Regs S E C O N D
17th Edition Info
17th Regs Intro
17th Edition Part 5 2 2

Recently uploaded (20)

PPTX
IMMUNITY IMMUNITY refers to protection against infection, and the immune syst...
PDF
grade 11-chemistry_fetena_net_5883.pdf teacher guide for all student
PPTX
Institutional Correction lecture only . . .
PDF
Black Hat USA 2025 - Micro ICS Summit - ICS/OT Threat Landscape
PDF
Chinmaya Tiranga quiz Grand Finale.pdf
PDF
Complications of Minimal Access Surgery at WLH
PPTX
PPT- ENG7_QUARTER1_LESSON1_WEEK1. IMAGERY -DESCRIPTIONS pptx.pptx
PPTX
Introduction-to-Literarature-and-Literary-Studies-week-Prelim-coverage.pptx
PDF
A GUIDE TO GENETICS FOR UNDERGRADUATE MEDICAL STUDENTS
PPTX
Lesson notes of climatology university.
PDF
The Lost Whites of Pakistan by Jahanzaib Mughal.pdf
PDF
A systematic review of self-coping strategies used by university students to ...
PDF
GENETICS IN BIOLOGY IN SECONDARY LEVEL FORM 3
PPTX
Cell Structure & Organelles in detailed.
PPTX
202450812 BayCHI UCSC-SV 20250812 v17.pptx
PDF
ANTIBIOTICS.pptx.pdf………………… xxxxxxxxxxxxx
PDF
OBE - B.A.(HON'S) IN INTERIOR ARCHITECTURE -Ar.MOHIUDDIN.pdf
PDF
Supply Chain Operations Speaking Notes -ICLT Program
PPTX
human mycosis Human fungal infections are called human mycosis..pptx
PPTX
Pharma ospi slides which help in ospi learning
IMMUNITY IMMUNITY refers to protection against infection, and the immune syst...
grade 11-chemistry_fetena_net_5883.pdf teacher guide for all student
Institutional Correction lecture only . . .
Black Hat USA 2025 - Micro ICS Summit - ICS/OT Threat Landscape
Chinmaya Tiranga quiz Grand Finale.pdf
Complications of Minimal Access Surgery at WLH
PPT- ENG7_QUARTER1_LESSON1_WEEK1. IMAGERY -DESCRIPTIONS pptx.pptx
Introduction-to-Literarature-and-Literary-Studies-week-Prelim-coverage.pptx
A GUIDE TO GENETICS FOR UNDERGRADUATE MEDICAL STUDENTS
Lesson notes of climatology university.
The Lost Whites of Pakistan by Jahanzaib Mughal.pdf
A systematic review of self-coping strategies used by university students to ...
GENETICS IN BIOLOGY IN SECONDARY LEVEL FORM 3
Cell Structure & Organelles in detailed.
202450812 BayCHI UCSC-SV 20250812 v17.pptx
ANTIBIOTICS.pptx.pdf………………… xxxxxxxxxxxxx
OBE - B.A.(HON'S) IN INTERIOR ARCHITECTURE -Ar.MOHIUDDIN.pdf
Supply Chain Operations Speaking Notes -ICLT Program
human mycosis Human fungal infections are called human mycosis..pptx
Pharma ospi slides which help in ospi learning

17th Edition Part 4 4

  • 1. Requirements for Electrical Installations IEE Wiring Regulations 17 th Edition Part 4 Chapter 44
  • 2. IEE Wiring Regulations 17 th Edition - Part 4 As previously stated: It consists of only 4 chapters, 41 – Protection against Electric Shock . 42 – Protection against Thermal Effects . 43 – Protection against Overcurrent. Last one Tonight: - 44 – Protection against voltage disturbances and Electromagnetic Disturbances .
  • 3. Requirements for Electrical Installations IEE Wiring Regulations 17 th Edition Part 4 Chapter 44
  • 4. Chapter 44 Protection against Overcurrent There are 6 sections in this chapter 440 – Introduction 441 – Not used 442 – Protection of low voltage installations against temporary overvoltages due to various faults 443 – Protection of overvoltages of atmospheric origin or due to switching 444 – Reserved for Measures against electromagnetic Influences 445 – Protection against undervoltages
  • 5. Chapter 442 Protection of low voltage installations against temporary overvoltages due to earth faults in the high voltage system due to faults in the low voltage system The following four situations can have an effect on the safety of an LV installation by creating temporary overvoltages: A fault between the HV system and Earth in the transformer. (Regulation Group 442.2) Loss of the supply neutral in the LV installation (Regulation 442.3)
  • 6. Chapter 442 Protection of low voltage installations against temporary overvoltages due to earth faults in the high voltage system due to faults in the low voltage system Accidental earthing of a line conductor of an LV IT system. (Regulation 442.4) Short-circuit between a line conductor and neutral in the LV installation. (Regulation 442).
  • 7. 443 – Protection against overvoltages of atmospheric origin or due to switching As the UK has ≤ 25 thunderstorm days per year (AQ1), NO additional protection is required against overvoltages of atmospheric origin where installations are supplied by LV overhead lines, provided …
  • 8. Required minimum impulse withstand voltage Refer to Table 44.4 for examples of various impulse categories of equipment Nominal voltage of the installation V Required minimum impulse withstand voltage   kV Category IV (equipment with very high impulse voltage) Category III (equipment with high impulse voltage) Category II (equipment with normal impulse voltage) Category I (equipment with reduced impulse voltage) 230/240 or 277/480 6 4 2.5 1.5 400/690 8 6 4 2.5 1000 Values to be determined by the system engineer or, in the absence of information, the values for 400/690 V can be chosen.
  • 9. 443 – Protection against overvoltages of atmospheric origin or due to switching Switching overvoltages may be generated within an installation as the result of switching of: high current loads, inductive loads, such as motors, transformers or arc welding equipment, or capacitive loads, such as power factor correction equipment.
  • 10. 444 – Measures against electromagnetic influences Reserved for future use
  • 11. 445 – Protection against undervoltage
  • 12. 445 – Protection against undervoltage As in 131.1 (v) we are going to protect persons and livestock against Mechanical movement from electrically actuated equipment . . . . .
  • 13. 445 – Protection against undervoltage This also includes:- Suitable time delay being incorporated in the operation of an undervoltage protection device. Any time delay not reactivate a contactor and not impede the disconnection of a control or protective device. That such a device shall be compatible with the requirements for starting as stated in the appropriate British Standard. Where the automatic reclosure of a device may cause danger
  • 14. 445 – Protection against undervoltage The most used equipment falling into this category is:- Incorporated into motor starters . . . . i.e. The “No Volt Coil” in the contactor.
  • 15. Chapter 44 Protection against Overcurrent Does this make sense? GOOD – We will carry on - - - - - - - - To Part 5 - - - - - - Next Session

Editor's Notes

  • #6: Section 442 includes some difficult concepts for many students and covers requirements/situations many students are unlikely to get involved with. Section 442 gives rules for the designer and installer of the substation. It is suggested, therefore, that the best approach to this subject matter is to provide an overview of the general requirements It would be wise to mention that the requirements of Regulations 442.2.1 and 442.2.2 are deemed to be fulfilled for installations receiving a supply at low voltage from a system for distribution of electricity to the public In addition, refer to Regulation 442.2.3 for the need NOT to perform the calculation U 1 , U 2 and U f (see Fig 44.1) as it mainly falls into the responsibility of the substation installer/owner/operator to fulfil requirement provided by IEC 61936-1.
  • #8: This section deals with protection of electrical installations against transient overvoltages of atmospheric origin transmitted by the supply distribution system and against switching overvoltages generated by the equipment within the installation. The term ‘overvoltages of atmospheric origin’ relates to lightning, although direct lightning strikes on the LV lines of supply network or on electrical installations are not taken into account . Often, overvoltages of atmospheric origin are induced into overhead lines by nearby lighting strikes or the close proximity and movement of charged clouds . Two levels of protection against overvoltage are identified in Section 443: Equipment should have an adequate impulse withstand voltage for its intended use, or surge protection devices are used, which is not required in the majority of installations in the United Kingdom.
  • #9: The rated impulse withstand voltage of an item of equipment is the peak value of an impulse voltage of prescribed form and polarity that the equipment can withstand under specified test conditions without failure. Surge protection devices is an alternative to the AQ criteria. (443.2.4 refers.)
  • #11: This is an empty Section at the moment. Information may be added when Amendment No. 1 is issued.
  • #12: Suitable precautions need to be taken where a reduction or loss in voltage may occur to such a level so as to cause failure of equipment, or in some cases damage depending on the nature of the equipment connected. For example, a three-phase motor may be damaged by the motor drawing current from only two phases. Where unexpected restarting of a motor might cause danger it should be fitted with means to prevent automatic restarting after a stoppage due to a drop in voltage or failure of supply