Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
4.1.12 Light Demand 2 Table Part2
Using the highest loaded
phase (L2 at 153.25 A)

10% for future additions
= 1.1 x 153.25 = 168.575 A.

More Related Content

PDF
4.1.11 Light Demand 2 Table
PDF
Electrical machines solved objective
PPTX
Electrical Engineering - 2004 Unsolved Paper
PDF
electrical objective
PDF
Ies electrical engineering - electrical machines
PDF
Objective question eee
PDF
PDF
Gate ee 2011 with solutions
4.1.11 Light Demand 2 Table
Electrical machines solved objective
Electrical Engineering - 2004 Unsolved Paper
electrical objective
Ies electrical engineering - electrical machines
Objective question eee
Gate ee 2011 with solutions

What's hot (19)

PDF
Gate ee 2009 with solutions
PDF
Development of Switch Mode Dc Converter Using MATLAB/ dSPACE
PDF
Gate ee 2005 with solutions
PDF
Gate ee 2003 with solutions
PDF
Ee ies'2014-objective paper i (set-a)-final
PPT
Electricity Economics
PDF
Gate ee 2008 with solutions
PDF
Simple Model of DC Motor using LTspice
PDF
Gate ee 2007 with solutions
ODP
LOW POWER DIGITAL DESIGN
PDF
Gate ee 2006 with solutions
PDF
Electrical engineering objective type questions(www.allexamreview.com) أساأ...
PDF
SPICE MODEL of MSE-3000 in SPICE PARK
PDF
A.gate by-rk-kanodia
PPT
ニッケル水素電池のシンプルモデル(LTspice)
PDF
Temple, San Jose Interconnection App Stamped (1)
PPT
Lecture 17
PDF
Solucionario circuitos eléctricos - dorf, svoboda - 6ed
PDF
Electrical circuits & fields
Gate ee 2009 with solutions
Development of Switch Mode Dc Converter Using MATLAB/ dSPACE
Gate ee 2005 with solutions
Gate ee 2003 with solutions
Ee ies'2014-objective paper i (set-a)-final
Electricity Economics
Gate ee 2008 with solutions
Simple Model of DC Motor using LTspice
Gate ee 2007 with solutions
LOW POWER DIGITAL DESIGN
Gate ee 2006 with solutions
Electrical engineering objective type questions(www.allexamreview.com) أساأ...
SPICE MODEL of MSE-3000 in SPICE PARK
A.gate by-rk-kanodia
ニッケル水素電池のシンプルモデル(LTspice)
Temple, San Jose Interconnection App Stamped (1)
Lecture 17
Solucionario circuitos eléctricos - dorf, svoboda - 6ed
Electrical circuits & fields
Ad

Similar to 4.1.12 Light Demand 2 Table Part2 (20)

PDF
4.2.1 Better Load
PDF
4.1.1 Example Single
PDF
4.1.1 Example Single
PDF
4.1.4 Step 2
PDF
General Purpose Relays - Werner Electric
PDF
23 series Power Relays
PDF
Power Relays - Werner Electric
PDF
Brochure product overview_english
PDF
Accendo GloGreen Digital HID (DHID) Ballast B600W-240M Electrical Test Report
PDF
Victron Power Backup Systems
PDF
4.1.9 Light Demand 1
PDF
In Win-Commander Series Power Supply
PDF
Mean well rs-25
PDF
4.1.3 Example Solution Three
PDF
Accendo GloGreen Digital HID (DHID) Ballast B600W-277M Electrical Test Report
PDF
Hybrid solar and wind street light
PDF
Abb rele fronius ig 400 500 masber solar
4.2.1 Better Load
4.1.1 Example Single
4.1.1 Example Single
4.1.4 Step 2
General Purpose Relays - Werner Electric
23 series Power Relays
Power Relays - Werner Electric
Brochure product overview_english
Accendo GloGreen Digital HID (DHID) Ballast B600W-240M Electrical Test Report
Victron Power Backup Systems
4.1.9 Light Demand 1
In Win-Commander Series Power Supply
Mean well rs-25
4.1.3 Example Solution Three
Accendo GloGreen Digital HID (DHID) Ballast B600W-277M Electrical Test Report
Hybrid solar and wind street light
Abb rele fronius ig 400 500 masber solar
Ad

More from Talia Carbis (20)

PDF
7.4.6 slip
PDF
4.1.13 Light Demand 3
PDF
4.1.10 Light Demand 2
PDF
4.1.8 Light Demand
PDF
4.1.7 Example Domestic 3
PDF
4.1.6 Example Domestic 2
PDF
4.1.5 Example Domestic 1
PDF
4.1.2 Example Three
PDF
5.4.4 LR Circuits
PDF
14.5.4 Example 1 Part 1
PDF
14.5.3 Improve
PDF
14.1.2 TRA Power
PDF
14.5.8 Example 1 Part 5
PDF
14.5.7 Example 1 Part 4
PDF
14.5.6 Example 1 Part 3
PDF
14.5.5 Example 1 Part 2
PDF
14.5.2 Correction
PDF
14.5.1 Improvement
PDF
14.4.5 Voltampere
PDF
14.4.4 Three Watt
7.4.6 slip
4.1.13 Light Demand 3
4.1.10 Light Demand 2
4.1.8 Light Demand
4.1.7 Example Domestic 3
4.1.6 Example Domestic 2
4.1.5 Example Domestic 1
4.1.2 Example Three
5.4.4 LR Circuits
14.5.4 Example 1 Part 1
14.5.3 Improve
14.1.2 TRA Power
14.5.8 Example 1 Part 5
14.5.7 Example 1 Part 4
14.5.6 Example 1 Part 3
14.5.5 Example 1 Part 2
14.5.2 Correction
14.5.1 Improvement
14.4.5 Voltampere
14.4.4 Three Watt

Recently uploaded (20)

PDF
Unlocking AI with Model Context Protocol (MCP)
PDF
Blue Purple Modern Animated Computer Science Presentation.pdf.pdf
PDF
Approach and Philosophy of On baking technology
PPTX
1. Introduction to Computer Programming.pptx
PPTX
A Presentation on Artificial Intelligence
PDF
gpt5_lecture_notes_comprehensive_20250812015547.pdf
PDF
Spectral efficient network and resource selection model in 5G networks
PDF
Profit Center Accounting in SAP S/4HANA, S4F28 Col11
PDF
Optimiser vos workloads AI/ML sur Amazon EC2 et AWS Graviton
PPTX
MYSQL Presentation for SQL database connectivity
PPTX
20250228 LYD VKU AI Blended-Learning.pptx
PDF
Electronic commerce courselecture one. Pdf
PPTX
Tartificialntelligence_presentation.pptx
PDF
Empathic Computing: Creating Shared Understanding
PPTX
Big Data Technologies - Introduction.pptx
PDF
Video forgery: An extensive analysis of inter-and intra-frame manipulation al...
PDF
Getting Started with Data Integration: FME Form 101
PDF
Build a system with the filesystem maintained by OSTree @ COSCUP 2025
PDF
Mobile App Security Testing_ A Comprehensive Guide.pdf
PDF
cuic standard and advanced reporting.pdf
Unlocking AI with Model Context Protocol (MCP)
Blue Purple Modern Animated Computer Science Presentation.pdf.pdf
Approach and Philosophy of On baking technology
1. Introduction to Computer Programming.pptx
A Presentation on Artificial Intelligence
gpt5_lecture_notes_comprehensive_20250812015547.pdf
Spectral efficient network and resource selection model in 5G networks
Profit Center Accounting in SAP S/4HANA, S4F28 Col11
Optimiser vos workloads AI/ML sur Amazon EC2 et AWS Graviton
MYSQL Presentation for SQL database connectivity
20250228 LYD VKU AI Blended-Learning.pptx
Electronic commerce courselecture one. Pdf
Tartificialntelligence_presentation.pptx
Empathic Computing: Creating Shared Understanding
Big Data Technologies - Introduction.pptx
Video forgery: An extensive analysis of inter-and intra-frame manipulation al...
Getting Started with Data Integration: FME Form 101
Build a system with the filesystem maintained by OSTree @ COSCUP 2025
Mobile App Security Testing_ A Comprehensive Guide.pdf
cuic standard and advanced reporting.pdf

4.1.12 Light Demand 2 Table Part2

  • 1. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 2. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 3. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 4. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 5. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 6. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 7. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 8. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 9. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 10. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 12. Using the highest loaded phase (L2 at 153.25 A) 10% for future additions = 1.1 x 153.25 = 168.575 A.