SiemensNumericalRelay
Features:
• Cold Load Settings
• Four Settings Groups
• Password Protection – 2 levels
• User Programmable Logic
Description
• The 7SR11 & 7SR12 are overcurrent protection relays developed to enhance the
Argus family of products by providing a familiar product using the latest generation
of hardware technology.
• The 7SR11provides overcurrent and earth fault protection, the 7SR12 comes with
additional voltage inputs providing directional protection. Both relays are available
in single and four pole variants.
• Housed in a 4U high, size E4 or E6 (Optional IEC61850 model) cases, these relays
provide protection, monitoring, instrumentation and metering with integrated input
and output logic, data logging & fault reports. Communication access to the relay
functionality is via a front USB port for local PC connection, a rear electrical RS485
port for remote connection & optional IEC61850 communication through two rear
Ethernet ports (Electrical or Optical).
Functional Diagrams
Monitoring Functions
• Primary/Secondary Current Phases and Earth Direction
• Primary/Secondary Line and Phase Voltages
• Apparent Power and Power Factor
• Real and Reactive Power W Hr & VAr Hr Forward and Reverse
• Historical Demand Record
• Positive Phase Sequence (PPS) Voltage & Current
• Negative Phase Sequence (NPS) Voltage & Current
User Interface
• 20 Character x 4 Line Backlit LCD
• Menu Navigation Keys
• 9 User Programmable Tri-colour LEDs
• User Language Configuration
Serial Communications
• The relay offers a USB serial port as standard on the front of all units. All of the
relays functions can be set on a PC using Reydisp Evolution via the USB port. The
connection is made with a USB cable and operates with a ‘plug and play’
connection, so no pre-setting of the relay is required.
• The front port can be switched off or set to use either the DNP3.0, MODBUS-RTU,
IEC60870-5-103 and ASCII protocols for testing purposes.
• A rear RS485 electrical connection is available on all units for system interface
connections. An internal terminating resistor is provided, which can be connected
into the circuit by adding a wire loop between the relevant terminals
Case Dimensions
Function Overview
• 37 Undercurrent
• 46BC Broken Conductor / Load Unbalance
• 46NPS Negative Phase Sequence Overcurrent
• 49 Thermal Overload
• 50 Instantaneous Overcurrent
• 50G/N/SEF Instantaneous Earth Fault
• 50AFD Arc Flash Detection (6 zones)
• 50BF Circuit Breaker Fail
• 51 Time Delayed Overcurrent
• 51G/N/SEF Time Delayed Measured/Derived/Sensitive EF
• 64H High Impedance REF
• 27/59 Under/Over Voltage
• 47 Negative Phase Sequence Voltage
• 51V Voltage Controlled Overcurrent
• 59N Neutral Voltage Displacement
• 67/50 Directional Instantaneous Overcurrent
• 67/50G/N Directional Instantaneous Earth Fault
Description of Functionality
27/59 Under/Over Voltage
Each element has settings for pickup level, drop-off level and Definite Time Lag (DTL)
delays. Operates if voltage exceeds setting for duration of delay
32S Sensitive Power
This is provided in 4 pole SEF relays and provides elements operated by single phase
measured current in the ISEF input.
37 Undercurrent
Each element has settings for pickup level and Definite Time Lag (DTL) delays.
46BC Phase Unbalance/Broken Conductor
Element has settings for pickup level and DTL delay. With the circuit breaker closed, if the
NPS:PPS current ratio is above setting this could be due to a broken conductor.
46NPS Negative Phase Sequence Overcurrent
Each element has user settings for pickup level and IDMTL or DTL delay, operates if NPS
current exceeds setting and delay.
47 Negative Phase Sequence Voltage
Each element has settings for pickup level and Definite Time Lag (DTL) delays. Operates if
NPS voltage exceeds setting for duration of delay.
Description of Functionality
49 Thermal Overload
The thermal algorithm calculates the thermal states from the measured currents and can be
applied to lines, cables and transformers. Alarm outputs are given for thermal overload and
thermal capacity.
50BF Circuit Breaker Fail
The circuit breaker fail function may be triggered from an internal trip signal or from a
binary input.
51c Cold Load Pickup If a circuit breaker is closed onto a ‘cold’ load, i.e. one that has not
been powered for a prolonged period, this can impose a higher than normal load-current
demand on the system which could exceed normal settings.
50/51 Phase Fault
50 INST/DTL and 51 IDMTL/DTL elements provide overcurrent protection, each with
independent settings for pickup current, time-multiplier (51) and time-delays.
50G/51G/50N/51N Earth Fault/Sensitive Earth Fault
Two earth fault measurement modes are available. One mode directly measures the earth
current from an independent CT, or the residual connection of the 3 line CTs.
Description of Functionality
51V Voltage Controlled Overcurrent
Each phase shaped overcurrent element can be independently controlled by the level of
measured input voltage
50AFD Arc Flash Detector
The 7SR1 relays can be used with the 7XG31 ReyArc range of Arc Flash Detection devices.
55 Power Factor
Each element has settings for Under or Over Power Factor pickup level, Definite Time Lag
(DTL) delay and Lead/Lag Direction.
59N Neutral Overvoltage
Neutral overvoltage can be used to detect earth faults in high impedance earthed or
isolated systems.
60CTS CT Supervision
The relay has two methods of CT supervision.
67/67N Directional Control
Phase, earth and sensitive earth fault elements can be directionalised.
Reydisp Evolution
• Reydisp Evolution is a Windows
based software tool, providing
the means for the user to apply
settings, interrogate settings
and retrieve events and
disturbance waveforms from
the device and is common to
the entire range of Reyrolle
protection relays.
Control Mode
The relay has a control menu with access to commonly used command operations
(except 7SR1102-1*A12-*AA0 models). Access to the control commands is restricted
by a 4 character control function password. Each command requires a select then
execute operation, if the execute operation is not performed within a time window the
command is aborted.
The following control functions are available:
• CB Operation
• Auto Reclose In/Out
• Auto Reclose Trip & Reclose
• Auto Reclose Trip & Lockout
• SEF In/Out
• Inst Prot In/Out
• Hot Line Working In/Out
Construction
• The relay is housed in a 4U high, size E4 or E6 (Optional IEC61850 model) case with
a removable clear fascia cover. The fascia cover can be ordered with or without two
push buttons to allow the user to view the settings and instruments without
removing the cover.
• Two handles are provided to allow the relay to be withdrawn from its case, contacts
in the case ensure that the CT circuits and normally closed contacts remain short
circuited when the relay is withdrawn.
• The rear terminal blocks comprise M4 female terminals for ring crimp wire
connections, to provide a secure and reliable termination.
7SR11 Connection Diagram
Data Communication Interface and Tests
Communication Port Front USB Type B Rear RS485 2 wire electrical IEC61850
optional ports: 2x Electrical RJ45 Ethernet 2x LC Fibre Optic
Ethernet
Protocols IEC60870-5-103 MODBUS RTU (Serial) DNP3.0 O (Serial)
IEC61850 - optional
Fibre Optic Ethernet Data Communication Interface
(IEC 61850 Option)
Type Level Variation
Vibration response 0.5 gn ≤ 5 %
Vibration response 1.0 gn ≤ 5 %
Vibration (Sinusoidal)
Shock and Bump
Type Level Variation
Shock response 5 gn, 11 ms ≤ 5 %
Bump test 10 gn, 16 ms ≤ 5 %
Shock withstand 15 gn, 11 ms ≤ 5 %
Mob No:
Mr. Piyush Rathi- +91-9819614841
Website:
www.reliservsolution.com
Email-ID:
piyush@reliserv.in
sales1@reliserv.in
Address:
Office No: 9, Space Heights,
Plot No. 53/54 , Sector 34,
Kamothe,Navi Mumbai- 410209
Contact us

More Related Content

PDF
Relay Setting Calculation For REF615/ REJ601
PPTX
ppt on industrial training of final year studen from ptcul 132kv substation ...
PPTX
On load tap changer
PPTX
Fault Level Calculation
PPTX
Motor Control Centre
PDF
Generator protection calculations settings
DOCX
5. Switchyard & Substation
PDF
ETAP - Coordination and protecion 2
Relay Setting Calculation For REF615/ REJ601
ppt on industrial training of final year studen from ptcul 132kv substation ...
On load tap changer
Fault Level Calculation
Motor Control Centre
Generator protection calculations settings
5. Switchyard & Substation
ETAP - Coordination and protecion 2

What's hot (20)

PDF
ETAP - Short circuit ansi standard
PPSX
Switch yard & Protection
PPTX
powergrid presentation
PDF
Ipsa mv relay co-ordiantion shaik adam
DOCX
Directional over current relay
PPTX
Lecture 7 Relay Coordination.pptx
PDF
Cable sizing to withstand short-circuit current - Example
PPT
substation protection basics.ppt
PPTX
1.substation layouts
PDF
Transformer overcurrent
PPTX
132KV SUBSTATION UPPTCL
PDF
LBB & BUSBAR PPT Rev 4.5.pdf
PPTX
Relay coordination
PDF
Transformer vector group_test_conditions
PDF
Dcs course
PDF
Bus Bar protection
PDF
7SA522 Distance Protection Relay For Transmission Lines
PDF
RELAY CO-ORDINATION WITH FAULT CALCULATION
PPT
Fault level calculations
PPT
Plcc ppt1
ETAP - Short circuit ansi standard
Switch yard & Protection
powergrid presentation
Ipsa mv relay co-ordiantion shaik adam
Directional over current relay
Lecture 7 Relay Coordination.pptx
Cable sizing to withstand short-circuit current - Example
substation protection basics.ppt
1.substation layouts
Transformer overcurrent
132KV SUBSTATION UPPTCL
LBB & BUSBAR PPT Rev 4.5.pdf
Relay coordination
Transformer vector group_test_conditions
Dcs course
Bus Bar protection
7SA522 Distance Protection Relay For Transmission Lines
RELAY CO-ORDINATION WITH FAULT CALCULATION
Fault level calculations
Plcc ppt1
Ad

Similar to 7SR11 Overcurrent Relay (20)

PDF
7SR110 Argus Relay
PDF
7SR12 Directional Over Current Relay
PDF
7SR120 Argus Relay
PDF
7SR191 Capa Protection Relays
PPTX
7SR10 Overcurrent Relay
PDF
7SR220 Overcurrent Relay
PDF
7SR210 Overcurrent Relay
PDF
7SR157 Synchronising Protective Relay
PDF
7SR158 Argus Relay
PDF
7SR18 Solkor Protection Relay
PDF
7SR242 Transformer Protection Relay
PDF
7SR45 Self Powered Overcurrent Protection Relay
PDF
7SR23 High Impedance Bus Bar Protection Relay
PDF
Iskra Medium Voltage Automation and Protection (Protection relays)
DOC
sirishamadishetty
PDF
Far series outdoor auto circuit recloser
PDF
Far series outdoor auto circuit recloser
PDF
Cockpit White Box
PPT
An overview Study on High Power PD Interface Controller
PPTX
under grund fault ppt (1).pptx
7SR110 Argus Relay
7SR12 Directional Over Current Relay
7SR120 Argus Relay
7SR191 Capa Protection Relays
7SR10 Overcurrent Relay
7SR220 Overcurrent Relay
7SR210 Overcurrent Relay
7SR157 Synchronising Protective Relay
7SR158 Argus Relay
7SR18 Solkor Protection Relay
7SR242 Transformer Protection Relay
7SR45 Self Powered Overcurrent Protection Relay
7SR23 High Impedance Bus Bar Protection Relay
Iskra Medium Voltage Automation and Protection (Protection relays)
sirishamadishetty
Far series outdoor auto circuit recloser
Far series outdoor auto circuit recloser
Cockpit White Box
An overview Study on High Power PD Interface Controller
under grund fault ppt (1).pptx
Ad

More from ashwini reliserv (20)

PDF
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
PDF
SICAM FSI – Fault Sensor Indicator
PDF
SICAM FCG-Fault Collector Gateway
PDF
SICAM FPI - Fault Passage Indicator
PDF
SICAM FCM – Feeder Condition Monitor
PDF
Small Control Center System SICAM 230
PDF
SICAM Diamond (6MD552)
PDF
SICAM Disto substation automation
PDF
SICAM PQ Analyzer
PDF
SICAM SCC (6MD55) automation
PDF
SICAM AK 3 automation
PDF
SICAM PAS Software (6MD90)
PDF
RUGGEDCOM RSL910 vdsl modems
PDF
RUGGEDCOM SFPs accessories
PDF
RUGGEDCOM RPS1300 accessories
PDF
RUGGEDCOM REFLEX software
PDF
RUGGEDCOM ELAN software
PDF
RUGGEDCOM RP110 Ethernet injectors
PDF
RUGGEDCOM RP100 Ethernet injectors
PDF
RUGGEDCOM RS910W wireless lan
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
SICAM FSI – Fault Sensor Indicator
SICAM FCG-Fault Collector Gateway
SICAM FPI - Fault Passage Indicator
SICAM FCM – Feeder Condition Monitor
Small Control Center System SICAM 230
SICAM Diamond (6MD552)
SICAM Disto substation automation
SICAM PQ Analyzer
SICAM SCC (6MD55) automation
SICAM AK 3 automation
SICAM PAS Software (6MD90)
RUGGEDCOM RSL910 vdsl modems
RUGGEDCOM SFPs accessories
RUGGEDCOM RPS1300 accessories
RUGGEDCOM REFLEX software
RUGGEDCOM ELAN software
RUGGEDCOM RP110 Ethernet injectors
RUGGEDCOM RP100 Ethernet injectors
RUGGEDCOM RS910W wireless lan

Recently uploaded (20)

PPTX
Your Trusted SEO Company in San Antonio – Studio0413
PDF
Leveraging Earth Observation Data to Improve Wildfire Prevention and Manageme...
PDF
Musician Corporate Headshots Los Angeles
PPTX
Telecom Expense Management & Optimization – The ITE Group.pptx
PPTX
Moving House Why Removals in Melbourne Make It Easy.pptx
PPTX
Next-Generation Airline Network & Schedule Planning
PDF
Investhill_Report OCD (2007-2024)_2025-1.pdf
PDF
Top In-Demand Occupations for Skilled Migration to Australia in 2025
PDF
Environmental Impact Assessment of Quarrying Plants An IRF Kriging Solution t...
PPTX
Al Tamayoz Company Profile asd asd asdasd
PDF
Elliott Allan Hilsinger_ Creating Meaningful Volunteer Opportunities for Yout...
PDF
Expert Medical Coding Services for Faster Reimbursements.pdf
PPTX
Task 2_ portfolio PP-Food collection drive purpose
PDF
Blush & Brown Modern Minimalist eBook Workbook.pdf
PPTX
Why Outsourcing Debt Collection Saves Time and Money.pptx
PDF
5 Best Sites to Buy Snapchat Accounts (Aged & Pva).pdf
PPTX
Zulu Airline Systems – Innovative Airline Planning Solutions
PDF
Bisleri vs Coca Cola.pdf intellectual property rights
PDF
catalogo de peças da Dominar-400 PEÇAS.pdf
PPTX
Day Care Centre Proposal.pptxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
Your Trusted SEO Company in San Antonio – Studio0413
Leveraging Earth Observation Data to Improve Wildfire Prevention and Manageme...
Musician Corporate Headshots Los Angeles
Telecom Expense Management & Optimization – The ITE Group.pptx
Moving House Why Removals in Melbourne Make It Easy.pptx
Next-Generation Airline Network & Schedule Planning
Investhill_Report OCD (2007-2024)_2025-1.pdf
Top In-Demand Occupations for Skilled Migration to Australia in 2025
Environmental Impact Assessment of Quarrying Plants An IRF Kriging Solution t...
Al Tamayoz Company Profile asd asd asdasd
Elliott Allan Hilsinger_ Creating Meaningful Volunteer Opportunities for Yout...
Expert Medical Coding Services for Faster Reimbursements.pdf
Task 2_ portfolio PP-Food collection drive purpose
Blush & Brown Modern Minimalist eBook Workbook.pdf
Why Outsourcing Debt Collection Saves Time and Money.pptx
5 Best Sites to Buy Snapchat Accounts (Aged & Pva).pdf
Zulu Airline Systems – Innovative Airline Planning Solutions
Bisleri vs Coca Cola.pdf intellectual property rights
catalogo de peças da Dominar-400 PEÇAS.pdf
Day Care Centre Proposal.pptxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx

7SR11 Overcurrent Relay

  • 1. SiemensNumericalRelay Features: • Cold Load Settings • Four Settings Groups • Password Protection – 2 levels • User Programmable Logic
  • 2. Description • The 7SR11 & 7SR12 are overcurrent protection relays developed to enhance the Argus family of products by providing a familiar product using the latest generation of hardware technology. • The 7SR11provides overcurrent and earth fault protection, the 7SR12 comes with additional voltage inputs providing directional protection. Both relays are available in single and four pole variants. • Housed in a 4U high, size E4 or E6 (Optional IEC61850 model) cases, these relays provide protection, monitoring, instrumentation and metering with integrated input and output logic, data logging & fault reports. Communication access to the relay functionality is via a front USB port for local PC connection, a rear electrical RS485 port for remote connection & optional IEC61850 communication through two rear Ethernet ports (Electrical or Optical).
  • 4. Monitoring Functions • Primary/Secondary Current Phases and Earth Direction • Primary/Secondary Line and Phase Voltages • Apparent Power and Power Factor • Real and Reactive Power W Hr & VAr Hr Forward and Reverse • Historical Demand Record • Positive Phase Sequence (PPS) Voltage & Current • Negative Phase Sequence (NPS) Voltage & Current User Interface • 20 Character x 4 Line Backlit LCD • Menu Navigation Keys • 9 User Programmable Tri-colour LEDs • User Language Configuration
  • 5. Serial Communications • The relay offers a USB serial port as standard on the front of all units. All of the relays functions can be set on a PC using Reydisp Evolution via the USB port. The connection is made with a USB cable and operates with a ‘plug and play’ connection, so no pre-setting of the relay is required. • The front port can be switched off or set to use either the DNP3.0, MODBUS-RTU, IEC60870-5-103 and ASCII protocols for testing purposes. • A rear RS485 electrical connection is available on all units for system interface connections. An internal terminating resistor is provided, which can be connected into the circuit by adding a wire loop between the relevant terminals
  • 7. Function Overview • 37 Undercurrent • 46BC Broken Conductor / Load Unbalance • 46NPS Negative Phase Sequence Overcurrent • 49 Thermal Overload • 50 Instantaneous Overcurrent • 50G/N/SEF Instantaneous Earth Fault • 50AFD Arc Flash Detection (6 zones) • 50BF Circuit Breaker Fail • 51 Time Delayed Overcurrent • 51G/N/SEF Time Delayed Measured/Derived/Sensitive EF • 64H High Impedance REF • 27/59 Under/Over Voltage • 47 Negative Phase Sequence Voltage • 51V Voltage Controlled Overcurrent • 59N Neutral Voltage Displacement • 67/50 Directional Instantaneous Overcurrent • 67/50G/N Directional Instantaneous Earth Fault
  • 8. Description of Functionality 27/59 Under/Over Voltage Each element has settings for pickup level, drop-off level and Definite Time Lag (DTL) delays. Operates if voltage exceeds setting for duration of delay 32S Sensitive Power This is provided in 4 pole SEF relays and provides elements operated by single phase measured current in the ISEF input. 37 Undercurrent Each element has settings for pickup level and Definite Time Lag (DTL) delays. 46BC Phase Unbalance/Broken Conductor Element has settings for pickup level and DTL delay. With the circuit breaker closed, if the NPS:PPS current ratio is above setting this could be due to a broken conductor. 46NPS Negative Phase Sequence Overcurrent Each element has user settings for pickup level and IDMTL or DTL delay, operates if NPS current exceeds setting and delay. 47 Negative Phase Sequence Voltage Each element has settings for pickup level and Definite Time Lag (DTL) delays. Operates if NPS voltage exceeds setting for duration of delay.
  • 9. Description of Functionality 49 Thermal Overload The thermal algorithm calculates the thermal states from the measured currents and can be applied to lines, cables and transformers. Alarm outputs are given for thermal overload and thermal capacity. 50BF Circuit Breaker Fail The circuit breaker fail function may be triggered from an internal trip signal or from a binary input. 51c Cold Load Pickup If a circuit breaker is closed onto a ‘cold’ load, i.e. one that has not been powered for a prolonged period, this can impose a higher than normal load-current demand on the system which could exceed normal settings. 50/51 Phase Fault 50 INST/DTL and 51 IDMTL/DTL elements provide overcurrent protection, each with independent settings for pickup current, time-multiplier (51) and time-delays. 50G/51G/50N/51N Earth Fault/Sensitive Earth Fault Two earth fault measurement modes are available. One mode directly measures the earth current from an independent CT, or the residual connection of the 3 line CTs.
  • 10. Description of Functionality 51V Voltage Controlled Overcurrent Each phase shaped overcurrent element can be independently controlled by the level of measured input voltage 50AFD Arc Flash Detector The 7SR1 relays can be used with the 7XG31 ReyArc range of Arc Flash Detection devices. 55 Power Factor Each element has settings for Under or Over Power Factor pickup level, Definite Time Lag (DTL) delay and Lead/Lag Direction. 59N Neutral Overvoltage Neutral overvoltage can be used to detect earth faults in high impedance earthed or isolated systems. 60CTS CT Supervision The relay has two methods of CT supervision. 67/67N Directional Control Phase, earth and sensitive earth fault elements can be directionalised.
  • 11. Reydisp Evolution • Reydisp Evolution is a Windows based software tool, providing the means for the user to apply settings, interrogate settings and retrieve events and disturbance waveforms from the device and is common to the entire range of Reyrolle protection relays.
  • 12. Control Mode The relay has a control menu with access to commonly used command operations (except 7SR1102-1*A12-*AA0 models). Access to the control commands is restricted by a 4 character control function password. Each command requires a select then execute operation, if the execute operation is not performed within a time window the command is aborted. The following control functions are available: • CB Operation • Auto Reclose In/Out • Auto Reclose Trip & Reclose • Auto Reclose Trip & Lockout • SEF In/Out • Inst Prot In/Out • Hot Line Working In/Out
  • 13. Construction • The relay is housed in a 4U high, size E4 or E6 (Optional IEC61850 model) case with a removable clear fascia cover. The fascia cover can be ordered with or without two push buttons to allow the user to view the settings and instruments without removing the cover. • Two handles are provided to allow the relay to be withdrawn from its case, contacts in the case ensure that the CT circuits and normally closed contacts remain short circuited when the relay is withdrawn. • The rear terminal blocks comprise M4 female terminals for ring crimp wire connections, to provide a secure and reliable termination.
  • 15. Data Communication Interface and Tests Communication Port Front USB Type B Rear RS485 2 wire electrical IEC61850 optional ports: 2x Electrical RJ45 Ethernet 2x LC Fibre Optic Ethernet Protocols IEC60870-5-103 MODBUS RTU (Serial) DNP3.0 O (Serial) IEC61850 - optional Fibre Optic Ethernet Data Communication Interface (IEC 61850 Option) Type Level Variation Vibration response 0.5 gn ≤ 5 % Vibration response 1.0 gn ≤ 5 % Vibration (Sinusoidal) Shock and Bump Type Level Variation Shock response 5 gn, 11 ms ≤ 5 % Bump test 10 gn, 16 ms ≤ 5 % Shock withstand 15 gn, 11 ms ≤ 5 %
  • 16. Mob No: Mr. Piyush Rathi- +91-9819614841 Website: www.reliservsolution.com Email-ID: piyush@reliserv.in sales1@reliserv.in Address: Office No: 9, Space Heights, Plot No. 53/54 , Sector 34, Kamothe,Navi Mumbai- 410209 Contact us