SlideShare a Scribd company logo
INSTALLATIONINSTALLATION
SYSTEM INSTALLATION.
Installation personnel will be supervised by
persons who are qualified and
experienced in the installation, inspection,
and testing of electronic premises security
systems. Qualified personnel will include,
but not be limited to, the following:
(1) Equipment manufacturer trained and
certified personnel
INSTALLATIONINSTALLATION
SYSTEM INSTALLATION.
(2) Personnel licensed or certified by
federal, state, or local authority
(3) Personnel certified by an
accreditation program acceptable to
the AHJ
(4) Trained and qualified personnel
employed by an organization listed by
a national testing laboratory for the
servicing of electronic premises
security systems
INSTALLATIONINSTALLATION
POWER SUPPLIES
Code Conformance. All power supplies
will be installed in conformity with the
requirements of NFPA 70, National
Electrical Code, for such equipment and
with the requirements indicated in this
subsection.
INSTALLATION
Unless otherwise permitted by the
manufacturer, control units, power
supplies, and batteries will be mounted
in the vertical, upright position.
INSTALLATIONINSTALLATION
INSTALLATION
Manual Resetting. All equipment requiring
manual resetting to maintain normal
operation will have an indication to the
user that the device has not been
restored to normal.
Equipment Location.
Equipment will be installed in locations
where conditions do not exceed the
voltage, temperature, and humidity limits
specified below or unless listed for the
application.
INSTALLATIONINSTALLATION
INSTALLATION
Voltage, Temperature, and Humidity Variation.
Equipment shall be designed so that it is
capable of performing its intended functions
under the following conditions:
(1) At 85 percent and at 110 percent of the
nameplate primary (main) and secondary
(standby) input voltage(s)
(2) At ambient temperatures of 0°C (32°F) and
49°C (120°F)
(3) At a relative humidity of 85 percent and an
ambient temperature of 30°C (86°F)
INSTALLATIONINSTALLATION
INSTALLATION
Damp, Wet, or Exterior Environments.
Equipment intended for use in damp,
wet, or exterior environments shall be
listed for its use.
Interconnecting Control Units. Control
units, sub-controls, and devices that are
used to interconnect the control unit to
protection devices will be located within
the area being protected by the system.
INSTALLATIONINSTALLATION
INSTALLATION
Damp, Wet, or Exterior Environments cont.
If the enclosures for such equipment are
not located in such an area, the
enclosures will be protected by one of
the following methods:
(1) Continuously under the notice of
assigned security personnel
(2) Located in an area that is accessible
only to authorized personnel
(3) Supervised to annunciate tampering
Control units and sub-controls will be
readily accessible to service personnel.
INSTALLATIONINSTALLATION
INSTALLATION
Protection. To reduce the possibility of
damage by induced transients, circuits
and equipment will be protected in
accordance with the requirements of
NFPA 70, National Electrical Code,
Article 800.
INSTALLATIONINSTALLATION
WIRING.
General. The installation of all wiring,
cable, and equipment will be performed
in a workman-like manner in accordance
with NFPA 70, National Electrical Code,
and specifically with Article 725 or 800,
where applicable.
Optical fiber cables will be protected
against mechanical injury in accordance
with NFPA 70, National Electrical Code,
Article 770.
INSTALLATIONINSTALLATION
WIRING.
General cont. A conductor will be spliced
or joined with a mechanical splicing
device listed for this purpose.
Unless specifically allowed by the
manufacturer’s wiring specifications,
low voltage electronic premises security
system wiring will be spaced at least
5.08 cm (2 in.) from conductors of any
light and power circuits, unless one of
the circuits is in metal raceway.
INSTALLATIONINSTALLATION
WIRING.
General cont. Electronic premises security
system wiring and cables will be of the
appropriate gauge, strands, insulation,
and electrical properties as specified by
the equipment manufacturer.
Termination. Connections of conductors
to terminal parts will ensure a good
connection without damaging the
conductors and be made by means of
pressure connectors, wire binding
screws, or splices to flexible leads.
INSTALLATIONINSTALLATION
WIRING.
Termination cont. Conductors will be
connected to devices and to fittings so
that tension is not transmitted to joints
or terminals.
Wires and cables will not be placed in
such a manner as to prevent access to
equipment.
Terminals for more than one conductor
will be identified and intended for the
purpose.
INSTALLATIONINSTALLATION
WIRING.
Termination cont. Conductors will be of
the same size and composition.
Terminals will be marked or colored coded
where necessary to indicate the proper
connections.
All raceway connections to junction boxes
and at all open ends of raceway or
flexible raceway will be protected from
abrasion and fixed in position in
accordance with NFPA 70, National
Electrical Code, Articles 725 and 800.
INSTALLATIONINSTALLATION
WIRING.
Circuit Identification. Circuit identification
will be within the control panel and
enclosures used for wiring connections.
Circuit identification will be at all field
terminations. The circuit identification
will not be visible to the public.
Strain Relief. Strain relief will be provided
for wiring leaving control panels and
junction boxes not utilizing raceway.
INSTALLATIONINSTALLATION
WIRING.
Service Loop Metallic Conductors. A
minimum 15.24 cm (6 in.) service loop
will be at control panels and enclosures
used for wiring terminations.
A minimum 15.24 cm (6 in.) service loop
will be at field terminations. All service
loops will be mechanically protected.
INSTALLATIONINSTALLATION
WIRING.
Service Loop Optical Fiber Cable. A
service loop will be at control panels and
enclosures used for terminations.
The radius of the service loop will meet the
manufacturer’s specifications. If no
manufacturer’s specifications exist, the
radius will not be less than 10 times the
cable diameter. Service loops will be
mechanically protected.
INSTALLATIONINSTALLATION
WIRING.
Routing of Cables. When determining a logical
pattern for laying out the low-voltage cables
always begin with the manufacturer’s
recommendation for the maximum number of
stations on a single cable run. The pattern
should also take into account the physical
layout of the rooms along with the ease of
trouble-shooting the system cabling. For
example, a 'T' shaped floor might tend itself
to three runs; (one for each log of the "T') or,
if there are a large number of stations in
these corridors, six runs (one for each side
of each leg).
INSTALLATIONINSTALLATION
WIRING.
Splicing of interconnections. NEC
recommends using butt splices or
equivalent crimp-style connectors
for splicing the low-voltage wires.
Electric tape and wire nuts are not
recommended. Each manufacturer
will specify a preferred splicing
method.
INSTALLATIONINSTALLATION
WIRING.
Building-to-Building Wiring. Special care
must be taken in running low-voltage
wiring between buildings because its
location is subject to potentially large
transients and its length may result in
large voltage drops. In addition, proper
consid-eration of ground water leakage
should be taken. Wiring shall conform to
NFPA 70 725.57 Installation of Circuit
Conductors Extending Beyond One
Building.
INSTALLATIONINSTALLATION
WIRING.
Building-to-Building Wiring. Where Class 2
or Class 3 circuit conductors extend
beyond one building and are run so as
to be subject to accidental contact with
electric light or power conductors
operating over 300 volts to ground, or
are exposed to lightning on inter-
building circuits on the same premises,
the requirements of the following shall
also apply:
INSTALLATIONINSTALLATION
WIRING.
Building-to-Building Wiring.
(1) Sections 800.10, 800.12, 800.13, 800.31,
800.32, 800.33, and 800.40 for other than
coaxial conductors
(2) Sections 820.10, 820.33, and 820.40 for
coaxial conductors
Transient Protection. All building-to-
building wiring should be run in an
underground conduit system. Any wiring
in an above-ground conduit system
must have transient protectors (as
specified by the manufacturer).
INSTALLATIONINSTALLATION
WIRING.
Signal Loss. The length of wiring
between buildings may contribute
to signal losses (voltage drops) or
signal deg-radation (accumulated
wire capacitance). Always follow
the manufacturers' guidelines
regarding the length of such runs.
INSTALLATIONINSTALLATION
GROUNDING.
All grounding will be in accordance with
NFPA 70, National Electrical Code,
Articles 250 and 800.
Additional grounding will be in accordance
with manufacturer’s requirements.
All other circuits will test free of grounds.
INSTALLATIONINSTALLATION
ZONING & ANNUNCIATION.
General. All required annunciation means
will be readily accessible to responding
personnel and shall be located as
required by the AHJ to facilitate an
efficient response to the event.
Visible Zone Indication. When required,
the location of an operated initiating
device will be visibly indicated by
building, floor, or other approved
subdivision by annunciation, printout, or
other approved means.
INSTALLATIONINSTALLATION
ZONING & ANNUNCIATION.
Visible Zone Indication cont. When
required, the visible indication will not
be canceled by the operation of an
audible alarm silencing means.
If all locations in alarm are not displayed
simultaneously, visual indication will
show that other locations are in alarm.
INSTALLATIONINSTALLATION
ZONING & ANNUNCIATION.
Testing. All electronic premises security
systems will be maintained and tested in
accordance with NFPA 731 Standard for
the Installation of Electronic Premises
Security Systems Chapter 9.
INSTALLATIONINSTALLATION
ZONING & ANNUNCIATION.
Voltage Drop. Normally, 1-16 rooms will
be on a power riser. The voltage drop
should be tested on each power cable as
follows:
a. Take the measurement at the splice
point of the last splice box on the riser.
b. Attach the voltmeter leads across the
positive and negative power wires (as
specified by the manufacturer).
INSTALLATIONINSTALLATION
ZONING & ANNUNCIATION.
Voltage Drop.
c. Load the system by placing enough
calls to represent 20% of the riser's
calling capacity.
d. The voltage measured should be within
the specified input range for the station
in the room. A reading that is too low
indicates the need for additional or
higher-gauge power wires.
INSTALLATIONINSTALLATION
ZONING & ANNUNCIATION.
Software Control. Where required, all
software provided with an electronic
premises security system shall be listed
for use with the equipment on which it is
installed.
A record of installed software version
numbers will be maintained at the
location of the electronic premises
security system.
INSTALLATIONINSTALLATION
ZONING & ANNUNCIATION.
Software Control.
All software will be protected from
unauthorized changes.
All changes will be tested in accordance
with NFPA 731 Standard for the
Installation of Electronic Premises
Security Systems Chapter 9.

More Related Content

PPT
Access control basics-4
PPT
Access control basics-9
PPT
Access control basics-6
PPTX
Nec and oesc-1
PPT
Access control basics-8
PPTX
Nec and oesc-3
PPTX
Nec and oesc-2
PPT
Access control basics-1
Access control basics-4
Access control basics-9
Access control basics-6
Nec and oesc-1
Access control basics-8
Nec and oesc-3
Nec and oesc-2
Access control basics-1

What's hot (16)

PPT
Burglar alarm basics-6
PPT
Access control basics-5
PPT
Burglar alarm basics-8
DOCX
Abraham CV 03.06.2015
PDF
LayerZero Series 70: eRPP Remote Power Panel
PDF
6000 series
PDF
Catalog cs switch disconnectors_dienhathe.vn
PDF
NGR Monitor
PDF
Technical guide-for-electromagnetic-disturbance-protection
PDF
Presentation o surge protection devices
PPT
Burglar alarm basics-2
PPT
17th Edition Part 4 4
PDF
Ex rc1 spec-en_1215
PDF
Catalog Mitsubishi Inverter FR D700 Global-Beeteco.com
PDF
Cpx eng manual
PDF
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Burglar alarm basics-6
Access control basics-5
Burglar alarm basics-8
Abraham CV 03.06.2015
LayerZero Series 70: eRPP Remote Power Panel
6000 series
Catalog cs switch disconnectors_dienhathe.vn
NGR Monitor
Technical guide-for-electromagnetic-disturbance-protection
Presentation o surge protection devices
Burglar alarm basics-2
17th Edition Part 4 4
Ex rc1 spec-en_1215
Catalog Mitsubishi Inverter FR D700 Global-Beeteco.com
Cpx eng manual
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Ad

Viewers also liked (14)

PPT
LE Calculations 1
PPT
LE Calculations 2
PPT
Fiber optics 1-3
PPT
Fiber optics 1-2
PPT
Fiber optics 1-1
PPTX
Richard Samuel: 'Big Data - Setting the Scene'
PPTX
Taller 3 11 6
PDF
Daniel Townley RN
PPTX
Ejercicio de tablas y graficas
PDF
Microsoft Certifies
PPTX
Guesstimation
DOCX
Pm0011 project planning and scheduling
PPT
39471e30029c77b03e831d217b110bbc
PDF
Raipur Sahitya Mahotsav Case Study and Report
LE Calculations 1
LE Calculations 2
Fiber optics 1-3
Fiber optics 1-2
Fiber optics 1-1
Richard Samuel: 'Big Data - Setting the Scene'
Taller 3 11 6
Daniel Townley RN
Ejercicio de tablas y graficas
Microsoft Certifies
Guesstimation
Pm0011 project planning and scheduling
39471e30029c77b03e831d217b110bbc
Raipur Sahitya Mahotsav Case Study and Report
Ad

Similar to Access control basics-7 (20)

PDF
Wiring design for commercial and industrial buildings
PDF
Fire-Alarm-Installation as per NFPA.pdf
PPTX
Electrical systems
PDF
ELECTRICITYWIRING REGULATION for safety of
PPT
1910electric rev0
PDF
How to Spot Fire Alarm Contractor Shortcuts & Mistakes
PPTX
1910 electrical safety .gi_06259087.pptx
PDF
A Practical Guide To The 17th Edition Of The Wiring Regulations 1st Edition C...
PPTX
MU Electrical safety
PPTX
Nec and oesc-7
PPTX
EET402 electrical system design new M1.pptx
PDF
Electrical power supply and distribution
PDF
NX Air also Any other MV Training Index
PPT
General Or Gc Electrical Safety
DOC
17.cabling system
PDF
Ansi c37-61-1973-ieee-std-321-1973-pdf
PPTX
electric and sanitary.pptx
PDF
Essential Guide Cabeling System 2010
PPT
Safety and environment, Electrical General.ppt
PPT
Wiring design for commercial and industrial buildings
Fire-Alarm-Installation as per NFPA.pdf
Electrical systems
ELECTRICITYWIRING REGULATION for safety of
1910electric rev0
How to Spot Fire Alarm Contractor Shortcuts & Mistakes
1910 electrical safety .gi_06259087.pptx
A Practical Guide To The 17th Edition Of The Wiring Regulations 1st Edition C...
MU Electrical safety
Nec and oesc-7
EET402 electrical system design new M1.pptx
Electrical power supply and distribution
NX Air also Any other MV Training Index
General Or Gc Electrical Safety
17.cabling system
Ansi c37-61-1973-ieee-std-321-1973-pdf
electric and sanitary.pptx
Essential Guide Cabeling System 2010
Safety and environment, Electrical General.ppt

More from grantlerc (20)

PPTX
Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...
PPTX
Fire alarm 3-e-public_emergency_alarm_reporting_systems
PPTX
Fire alarm 3-d-supervising_station_alarm_system
PPTX
Fire alarm 3-b-protected_premises_fire_alarm_system
PPTX
Fire alarm 3-a-emergency_control_functions
PPTX
Fire alarm basics 1-6
PPTX
Fire alarm basics 1-5
PPTX
Fire alarm 2_f_manual supervisory
PPTX
Fire alarm 2_e_combination
PPTX
Fire alarm 2_d_radiant energy detectors
PPTX
Fire alarm 2_c_smoke detectors
PPTX
Fire alarm 2_b_heat detectors
PPTX
Fire alarm 2_a_initiation basics
PPT
Fire basics 1-4-risers_thru_power_supplies_08
PPT
Fire basics 1-3-functions_to_docs_08
PPT
Fire basics 1-2-the_nec_11
PPT
Fire basics 1-1-fundamentals
PPT
Fiber optics 2-7
PPT
Fiber optics 2-6
PPT
Fiber optics 2-5
Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...
Fire alarm 3-e-public_emergency_alarm_reporting_systems
Fire alarm 3-d-supervising_station_alarm_system
Fire alarm 3-b-protected_premises_fire_alarm_system
Fire alarm 3-a-emergency_control_functions
Fire alarm basics 1-6
Fire alarm basics 1-5
Fire alarm 2_f_manual supervisory
Fire alarm 2_e_combination
Fire alarm 2_d_radiant energy detectors
Fire alarm 2_c_smoke detectors
Fire alarm 2_b_heat detectors
Fire alarm 2_a_initiation basics
Fire basics 1-4-risers_thru_power_supplies_08
Fire basics 1-3-functions_to_docs_08
Fire basics 1-2-the_nec_11
Fire basics 1-1-fundamentals
Fiber optics 2-7
Fiber optics 2-6
Fiber optics 2-5

Recently uploaded (20)

PPTX
additive manufacturing of ss316l using mig welding
PPTX
Welding lecture in detail for understanding
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PDF
composite construction of structures.pdf
PPTX
web development for engineering and engineering
PPT
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PDF
Digital Logic Computer Design lecture notes
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PPTX
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PPTX
Construction Project Organization Group 2.pptx
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
additive manufacturing of ss316l using mig welding
Welding lecture in detail for understanding
R24 SURVEYING LAB MANUAL for civil enggi
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
composite construction of structures.pdf
web development for engineering and engineering
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Digital Logic Computer Design lecture notes
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Automation-in-Manufacturing-Chapter-Introduction.pdf
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
Model Code of Practice - Construction Work - 21102022 .pdf
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
CYBER-CRIMES AND SECURITY A guide to understanding
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
Construction Project Organization Group 2.pptx
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx

Access control basics-7

  • 1. INSTALLATIONINSTALLATION SYSTEM INSTALLATION. Installation personnel will be supervised by persons who are qualified and experienced in the installation, inspection, and testing of electronic premises security systems. Qualified personnel will include, but not be limited to, the following: (1) Equipment manufacturer trained and certified personnel
  • 2. INSTALLATIONINSTALLATION SYSTEM INSTALLATION. (2) Personnel licensed or certified by federal, state, or local authority (3) Personnel certified by an accreditation program acceptable to the AHJ (4) Trained and qualified personnel employed by an organization listed by a national testing laboratory for the servicing of electronic premises security systems
  • 3. INSTALLATIONINSTALLATION POWER SUPPLIES Code Conformance. All power supplies will be installed in conformity with the requirements of NFPA 70, National Electrical Code, for such equipment and with the requirements indicated in this subsection. INSTALLATION Unless otherwise permitted by the manufacturer, control units, power supplies, and batteries will be mounted in the vertical, upright position.
  • 4. INSTALLATIONINSTALLATION INSTALLATION Manual Resetting. All equipment requiring manual resetting to maintain normal operation will have an indication to the user that the device has not been restored to normal. Equipment Location. Equipment will be installed in locations where conditions do not exceed the voltage, temperature, and humidity limits specified below or unless listed for the application.
  • 5. INSTALLATIONINSTALLATION INSTALLATION Voltage, Temperature, and Humidity Variation. Equipment shall be designed so that it is capable of performing its intended functions under the following conditions: (1) At 85 percent and at 110 percent of the nameplate primary (main) and secondary (standby) input voltage(s) (2) At ambient temperatures of 0°C (32°F) and 49°C (120°F) (3) At a relative humidity of 85 percent and an ambient temperature of 30°C (86°F)
  • 6. INSTALLATIONINSTALLATION INSTALLATION Damp, Wet, or Exterior Environments. Equipment intended for use in damp, wet, or exterior environments shall be listed for its use. Interconnecting Control Units. Control units, sub-controls, and devices that are used to interconnect the control unit to protection devices will be located within the area being protected by the system.
  • 7. INSTALLATIONINSTALLATION INSTALLATION Damp, Wet, or Exterior Environments cont. If the enclosures for such equipment are not located in such an area, the enclosures will be protected by one of the following methods: (1) Continuously under the notice of assigned security personnel (2) Located in an area that is accessible only to authorized personnel (3) Supervised to annunciate tampering Control units and sub-controls will be readily accessible to service personnel.
  • 8. INSTALLATIONINSTALLATION INSTALLATION Protection. To reduce the possibility of damage by induced transients, circuits and equipment will be protected in accordance with the requirements of NFPA 70, National Electrical Code, Article 800.
  • 9. INSTALLATIONINSTALLATION WIRING. General. The installation of all wiring, cable, and equipment will be performed in a workman-like manner in accordance with NFPA 70, National Electrical Code, and specifically with Article 725 or 800, where applicable. Optical fiber cables will be protected against mechanical injury in accordance with NFPA 70, National Electrical Code, Article 770.
  • 10. INSTALLATIONINSTALLATION WIRING. General cont. A conductor will be spliced or joined with a mechanical splicing device listed for this purpose. Unless specifically allowed by the manufacturer’s wiring specifications, low voltage electronic premises security system wiring will be spaced at least 5.08 cm (2 in.) from conductors of any light and power circuits, unless one of the circuits is in metal raceway.
  • 11. INSTALLATIONINSTALLATION WIRING. General cont. Electronic premises security system wiring and cables will be of the appropriate gauge, strands, insulation, and electrical properties as specified by the equipment manufacturer. Termination. Connections of conductors to terminal parts will ensure a good connection without damaging the conductors and be made by means of pressure connectors, wire binding screws, or splices to flexible leads.
  • 12. INSTALLATIONINSTALLATION WIRING. Termination cont. Conductors will be connected to devices and to fittings so that tension is not transmitted to joints or terminals. Wires and cables will not be placed in such a manner as to prevent access to equipment. Terminals for more than one conductor will be identified and intended for the purpose.
  • 13. INSTALLATIONINSTALLATION WIRING. Termination cont. Conductors will be of the same size and composition. Terminals will be marked or colored coded where necessary to indicate the proper connections. All raceway connections to junction boxes and at all open ends of raceway or flexible raceway will be protected from abrasion and fixed in position in accordance with NFPA 70, National Electrical Code, Articles 725 and 800.
  • 14. INSTALLATIONINSTALLATION WIRING. Circuit Identification. Circuit identification will be within the control panel and enclosures used for wiring connections. Circuit identification will be at all field terminations. The circuit identification will not be visible to the public. Strain Relief. Strain relief will be provided for wiring leaving control panels and junction boxes not utilizing raceway.
  • 15. INSTALLATIONINSTALLATION WIRING. Service Loop Metallic Conductors. A minimum 15.24 cm (6 in.) service loop will be at control panels and enclosures used for wiring terminations. A minimum 15.24 cm (6 in.) service loop will be at field terminations. All service loops will be mechanically protected.
  • 16. INSTALLATIONINSTALLATION WIRING. Service Loop Optical Fiber Cable. A service loop will be at control panels and enclosures used for terminations. The radius of the service loop will meet the manufacturer’s specifications. If no manufacturer’s specifications exist, the radius will not be less than 10 times the cable diameter. Service loops will be mechanically protected.
  • 17. INSTALLATIONINSTALLATION WIRING. Routing of Cables. When determining a logical pattern for laying out the low-voltage cables always begin with the manufacturer’s recommendation for the maximum number of stations on a single cable run. The pattern should also take into account the physical layout of the rooms along with the ease of trouble-shooting the system cabling. For example, a 'T' shaped floor might tend itself to three runs; (one for each log of the "T') or, if there are a large number of stations in these corridors, six runs (one for each side of each leg).
  • 18. INSTALLATIONINSTALLATION WIRING. Splicing of interconnections. NEC recommends using butt splices or equivalent crimp-style connectors for splicing the low-voltage wires. Electric tape and wire nuts are not recommended. Each manufacturer will specify a preferred splicing method.
  • 19. INSTALLATIONINSTALLATION WIRING. Building-to-Building Wiring. Special care must be taken in running low-voltage wiring between buildings because its location is subject to potentially large transients and its length may result in large voltage drops. In addition, proper consid-eration of ground water leakage should be taken. Wiring shall conform to NFPA 70 725.57 Installation of Circuit Conductors Extending Beyond One Building.
  • 20. INSTALLATIONINSTALLATION WIRING. Building-to-Building Wiring. Where Class 2 or Class 3 circuit conductors extend beyond one building and are run so as to be subject to accidental contact with electric light or power conductors operating over 300 volts to ground, or are exposed to lightning on inter- building circuits on the same premises, the requirements of the following shall also apply:
  • 21. INSTALLATIONINSTALLATION WIRING. Building-to-Building Wiring. (1) Sections 800.10, 800.12, 800.13, 800.31, 800.32, 800.33, and 800.40 for other than coaxial conductors (2) Sections 820.10, 820.33, and 820.40 for coaxial conductors Transient Protection. All building-to- building wiring should be run in an underground conduit system. Any wiring in an above-ground conduit system must have transient protectors (as specified by the manufacturer).
  • 22. INSTALLATIONINSTALLATION WIRING. Signal Loss. The length of wiring between buildings may contribute to signal losses (voltage drops) or signal deg-radation (accumulated wire capacitance). Always follow the manufacturers' guidelines regarding the length of such runs.
  • 23. INSTALLATIONINSTALLATION GROUNDING. All grounding will be in accordance with NFPA 70, National Electrical Code, Articles 250 and 800. Additional grounding will be in accordance with manufacturer’s requirements. All other circuits will test free of grounds.
  • 24. INSTALLATIONINSTALLATION ZONING & ANNUNCIATION. General. All required annunciation means will be readily accessible to responding personnel and shall be located as required by the AHJ to facilitate an efficient response to the event. Visible Zone Indication. When required, the location of an operated initiating device will be visibly indicated by building, floor, or other approved subdivision by annunciation, printout, or other approved means.
  • 25. INSTALLATIONINSTALLATION ZONING & ANNUNCIATION. Visible Zone Indication cont. When required, the visible indication will not be canceled by the operation of an audible alarm silencing means. If all locations in alarm are not displayed simultaneously, visual indication will show that other locations are in alarm.
  • 26. INSTALLATIONINSTALLATION ZONING & ANNUNCIATION. Testing. All electronic premises security systems will be maintained and tested in accordance with NFPA 731 Standard for the Installation of Electronic Premises Security Systems Chapter 9.
  • 27. INSTALLATIONINSTALLATION ZONING & ANNUNCIATION. Voltage Drop. Normally, 1-16 rooms will be on a power riser. The voltage drop should be tested on each power cable as follows: a. Take the measurement at the splice point of the last splice box on the riser. b. Attach the voltmeter leads across the positive and negative power wires (as specified by the manufacturer).
  • 28. INSTALLATIONINSTALLATION ZONING & ANNUNCIATION. Voltage Drop. c. Load the system by placing enough calls to represent 20% of the riser's calling capacity. d. The voltage measured should be within the specified input range for the station in the room. A reading that is too low indicates the need for additional or higher-gauge power wires.
  • 29. INSTALLATIONINSTALLATION ZONING & ANNUNCIATION. Software Control. Where required, all software provided with an electronic premises security system shall be listed for use with the equipment on which it is installed. A record of installed software version numbers will be maintained at the location of the electronic premises security system.
  • 30. INSTALLATIONINSTALLATION ZONING & ANNUNCIATION. Software Control. All software will be protected from unauthorized changes. All changes will be tested in accordance with NFPA 731 Standard for the Installation of Electronic Premises Security Systems Chapter 9.