“ANALYSIS AND DESIGN OF MULTI-STOREYED LOAD BEARING
REINFORCED MASONRY STRUCTURE AND FRAMED RC
STRUCTURE”
Shashank B.S1
, S.Raghunath2
1
Assistant Professor, Civil Engineering, TOCE, shashankbsbhat.bs@gmail.com, Karnataka, India
2
Professor, Civil Engineering, BMSCE, raghunath.smrc@gmail.com, Karnataka, India
Abstract
Load bearing masonry structures in India are generally restricted to 3 or 4 storeys in height. This is mainly because of lack of
availability of good quality masonry unit and associated workmanship. Also, it is generally perceived that load bearing masonry
storey may perform in brittle manner under excessive lateral loads. However, with the advancement of availability of engineered
hollow concrete blocks which has a scope to introduce reinforcement, it is perhaps possible to design and eventually construct multi-
storeyed reinforced masonry building. In this paper an attempt has been made to analyse and design the structural components of a
multi-storeyed residential building using reinforced hollow concrete block masonry. (i) Residential occupancy in ground floor + 8
floors. The building is analysed and designed for all the load combination as per the codal provisions. Later the same building is
analysed and design by considering it as conventional RC framed structure system. The structural comparison of both of them has
been made. Based on the study it is found that the requirement of reinforcing steel and concrete is significantly lesser, when
compared to building designed as load bearing masonry system. It is also found that masonry prism strength of 7.5MPa with nominal
vertical reinforcement is adequate to withstand the combination of axial and lateral loads.
Keywords: Load bearing, hollow block, Reinforcement, Lateral strength, RC Frame
----------------------------------------------------------------------***------------------------------------------------------------------------
1. INTRODUCTION
There are a lot of arguments about the actuality of reinforced
masonry. Although bricks belong to the conventional and
traditional building materials, reinforced concrete frames are
favored in construction industry nowadays. In that case the
masonry is used purely as an infill wall. The load bearing
capacity of masonry is only significant for the design of some
storey constructions. On the other hand, it is possible to
dispense with RC frame and construct multi storied load
bearing masonry structures, when good quality blocks are used
in conjunction with reinforcement.
1.1 Reinforced Masonry
In India there has not been much progress in the construction
of tall load bearing masonry structures, mainly because of
poor quality of masonry workmanship and material such as
clay bricks that are manufactured even today having nominal
strength of only 7.0 to 10.0 MPa. However recently
mechanized brick plants are producing brick units of strength
17.5 to 24 MPa and therefore it is possible to construct 5 to 6
storied load bearing structures at costs less than those of RC
framed structures.
Reinforced masonry (RM) is more economical and structurally
efficient than framed RC structure
(a) If good quality blocks are produced
(b) If reinforcement is suitably introduced
(c) If the strength and elastic properties are known
In load bearing walls, when the plan length of openings
exceeds approximately one- half the total plan length of the
wall and lateral forces act on the walls whether in- plane or
out of plane, flexural tensile stresses generally become so
large that the walls must be designed as reinforced.
Reinforcement can also be used to increase shear resistance.
Fig-1 Reinforced masonry
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 180
2. STRUCTURAL DESIGN OF REINFORCED
MASONRY
Permissible Compressive Force: Compressive force in
reinforced masonry due to axial load shall not exceed that
given by following equation:
Po = (0.25fm'An+ 0.65Ast FS) Ks
Where,
An = Net area
Ast = Area of steel
Fs = Permissible steel tensile stress
Ks= Stress reduction factor as in Table 9 of IS: 1905-1987
The compressive force at the section from axial loads or from
the axial component of combined loads is calculated
separately as is limited to the permissible values. A coefficient
of 0.25 provides a factor of safety of about 4.0 against
crushing of masonry. The coefficient of 0.65 was determined
from tests on masonry.
Permissible Shear Stress for Reinforced masonry members
a) For Flexural members
i). Without Web Reinforcement
Fv = 0.083 fm but not greater than 0.25 MPa
ii). With Web Reinforcement
Fv = 0.25 fm but not greater than 0.75 MPa
b) For Walls
For reinforced masonry, the shear resistance is offered by both
masonry and reinforcement, however, their effect is not taken
additive in this document, like many other masonry codes.
This has basis in an experimental research by Priestley and
Bridgeman which concluded that the shear reinforcement in
masonry is effective in providing resistance when it is
designed to carry the full shear load. If calculated shear stress
exceeds the allowable shear stress for masonry, full shear load
has to be resisted by the reinforcement alone which is placed
parallel to the applied shear force direction. The amount of
shear reinforcement. Experiments have shown that shear
resistance of the reinforced shear walls are function of the
aspect ratio of the wall (i.e., ratio of height to length), besides
distribution of reinforcement and masonry strength. Shear
walls with lower aspect ratio have been provided with higher
allowable shear stress.
3. LOAD BEARING MASONRY ELEMENT-CASE
STUDY
The major objective of this Paper is to demonstrate a
comprehensive design procedure for multi-storied load
bearing masonry building. Typical residential building with
identical floor plans is amenable to be design as load bearing
structure. Avoiding provision of walls out of line with walls in
the underneath floors is crucial. Such a layout will ensure the
avoidance of beam. As a consequence of which excessive
point loads on load bearing walls can be avoided.
At this juncture that it is crucial to identify the load bearing
elements. Here it is provident to avoid considering walls of
significantly small cross section area as load bearing element
in this case study is identified with wall A to Z and A’ to K’
for axial load analysis and for the lateral load analysis it is
identified as 1 t0 54.It can be noticed that the walls for bath
room kitchens (which are lesser than 200mm thickness) is not
considered as load bearing masonry walls.
The process of design as already mentioned is carried out in 3
phases, viz,
a) Calculation of loads
b) Design for axial and eccentric loads
c) Design for flexure and shear
Fig -2: Plan of 1st Floor
3.1 Design of Wall Element Axial/Eccentric Loads
A building is basically subjected to two types of loads,
namely: a) Vertical loads on account of dead loads of
materials used in construction, plus live loads due to
occupancy; and b) Lateral loads due to wind and seismic
forces. While all walls in general can take vertical loads,
ability of a wall to take lateral loads depends on its disposition
in relation to the direction of lateral load. In general a
structural wall shall be designed to with stand axial
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 181
compression, stress due to eccentricity in plane shear and out
of plane building.
3.1.1 Design Loads
Loads to be taken into consideration for designing masonry
components of a structure are: a) Dead loads of walls,
columns, floors and roofs; b) Live loads of floors and roof c)
Wind loads on walls d) Seismic forces.
1. Dead loads shall be calculated on the basis of unit weights
taken in accordance with IS: 875-1 (1987).
2. Live loads of floors and roof shall be calculated on the basis
of unit weights taken in accordance with IS: 875-2 (1987).
3. Wind loads on walls calculated on the basis of IS: 875-3
(1987).
4. Seismic forces on walls is calculated by using IS 1893-2002
part 1.
Table -1: Sample Stress Calculation
W
al
ls
L Leff SR
Net
area
mm2
Loa
d kn
Stress
Devel
oped
MPa
Stres
s
allow
able
MPa
Fac
tor
A
3.6
5
2.9
7
11.
2
72817
657.
1
0.902 2.250
2.4
9
B
3.7
4
1.8
4
9.2
4
74662
997.
8
1.337 2.644
1.9
8
C
3.7
5
1.8
4
9.2
4
74916
107
6.
1.437 2.644
1.8
40
D
4.1
4
3.8
1
11.
2
82800
134
6.
1.626 2.250
1.3
8
E 4.7
4.3
9
11.
2
93878 877 0.935 2.250
2.4
0
F
3.2
7
3.8
1
11.
2
65316
1
991 1.517 2.250
1.4
8
G 4.1
3.4
0
11.
2
82000
0
142
9
1.743 2.250
1.2
9
3.2 Lateral Load Analysis and Design
A building is basically subjected to two types of loads,
namely: 1. vertical loads on account of dead loads of materials
used in construction, plus live loads due to occupancy; and 2.
Lateral loads due to wind and seismic forces. Lateral loads
from the wind or earthquakes are generally considered to act
in the direction of the principal axes of the building structure.
The distribution of lateral loads to various masonry wall
elements depends on the rigidities of the horizontal floor or
roof diaphragm and of the wall elements. If a diaphragm does
not undergo significant in-plane deformation with respect to
the supporting walls, it can be considered rigid and lateral
loads are distributed in various lateral load resisting wall
elements in proportion to their relative stiffness.
3.2.1 Distribution of Lateral Forces in the Piers of a
Masonry Wall
Masonry walls are often seen to be perforated to make
arrangement for windows and doors. The distribution of lateral
force in a masonry wall is dependent on the position of the
openings and the relative rigidity of the masonry piers created
due to the presence of the openings in the masonry wall. The
relative rigidity is dependent on the height by length ratio (h/L
Ratio) of the piers and the end conditions of those masonry
piers as the deflection of the masonry piers due to horizontal
loading changes due to the end condition of the piers. Here a
simple process is described which can be used to distribute the
lateral force in a wall which can be considered to be consist of
some piers with some specific arrangements.
In any kind of placing of opening the wall can be represented
as a horizontal and vertical combination of piers with their
respective end condition which will be used to find out their
rigidities. Where large openings occur, it is difficult to obtain
effective coupling of the wall segments or piers.
Lateral loads shall be distributed to the structure system in
accordance with member stiffness for rigid diaphragms or
tributary areas for flexible diaphragms and shall comply with
the following requirements 1. Flanges of intersecting walls
designed in accordance to IS 1905 draft section 4.2.2.5 shall
be included in stiffness determination. 2. Distribution of load
shall include the effect of diaphragm rigidity and of horizontal
torsion due to eccentricity of wind and seismic loads resulting
from non-uniform distribution of mass
3.2.2 Wind Load Analysis
The wind force calculated from these factors is assumed to act
as an equivalent uniformly distributed load on the building for
its full height. sometimes the wind velocity or the gust factor
is assumed variable with the height of the building ,so that the
intensity of the equivalent uniformly distributed load varies
accordingly in the united kingdom wind loads on buildings are
calculated from the provisions of the code of practice CP3
chapter V Part 2 1970 whilst masonry is strong in compression
it is very weak in tension thus engineering design for wind
loading may be needed not only for multi storey structures but
also for some single storey structures
Design Wind Speed (Vz) The basic wind speed (Vz) for any
site shall be obtained from and shall be modified to include the
following effects to get design wind velocity at any height
(Vz) for the chosen structure:
a) Risk level; b) Terrain roughness, height and size of
structure; and c) Local topography. d) It can be
mathematically expressed as follows: Vz= Vb kl k2 k3 Vb =
design wind speed at any height z in m/s; kl = probability
factor (risk coefficient) k2 = terrain, height and structure size
factor and k3 = topography factor
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 182
Table -2: Wind load
Total force = 1048 kN.
3.2.3 Sesmic Load Analysis
The primary objective of earthquake resistant design is to
prevent building collapse during earthquakes thus minimizing
the risk of death or injury to people in or around those
buildings. Because damaging earthquakes are rare, economics
dictate that damage to buildings is expected and acceptable
provided collapse is avoided.
Earthquake Resistant Design-The following steps may be
taken:
(a) Estimate fundamental time period Ta using empirical
expressions given in the Code IS: 1893-10 2002.
(b) Calculate the design horizontal Seismic coefficient Ah
The design horizontal coefficient Ah is given by
Ah =
𝑍𝐼
2𝑅
𝑆𝑎
𝑔
Take Z for the applicable seismic zone (IS: 1893 Cl.6.4.2),
Take I for the use importance of the building (IS: 1893 Table
2),
Take R for the lateral load resisting system adopted (IS: 1893
Table 7), and take Sa/g for the computed time period values
(c) Calculate the total horizontal shear (the base shear)
The design value of base shear VB
VB = Ah W
As per IS 1893 Cl.7.5.3.
(d) Seismic Moments and Forces in Frame Elements:
Calculate the seismic moments and axial forces in the
columns, shears and moments in the beams by using the
seismic weights on the floors/ (column beam joints) through
an appropriate computer software (having facility for using
floors as rigid diaphragm and torsional effects as per IS:
1893:2002).
Table -3: Seismic force on each floor
FLOORS HEIGHT m Qi kN
1 3 7
2 6 28
3 9 62
4 12 110
5 15 172
6 18 248
7 21 338
8 24 441
TOTAL 1406
3.4 Design for Shear
Members Subjected to Shear: Reinforced masonry walls
may be designed taking contribution of shear reinforcement.
Where contribution of shear reinforcement is considered in
resisting shear force the minimum area of shear reinforcement
in the direction of force shall be determined by the following:
Avmin = VS/FSd
V = total applied shear force
S = spacing of the shear reinforcement
d = distance from extreme compression fiber to centroid of
tension reinforcement
Fs = permissible stress in steel reinforcement
3.5 Location of the Center of Mass
Table -4: Centre of mass calculation
Par
t
B
m
D
m
ARE
A
m2
X AX Y AY
X’
m
Y’
m
a1
3.
4
1.
0
3.4 7.3 24.8
-
0.5
-1.7
7.
0
11.
7
a2 12
8.
4
101.3 6.0 607 4.2
425.
4
a3
4.
7
5.
4
25.7
11.
5
296
11.
0
284.
2
a4 12
8.
4
101.3 6.0 607
19.
5
197
5
Flo
or
Heigh
t
M
V
b
m
/s
k1 k2 k
3
Vz
N/m
2
AR
EA
m2
Pz
kN
kN
Wi
nd
for
ce
1 3 5
5
1.0
5
0.8
8
1 50.8
20
60 154
9
111
2 6 5
5
1.0
5
0.8
8
1 50.8
20
60 154
9
111
3 9 5
5
1.0
5
0.8
8
1 50.8
20
60 154
9
111
4 12 5
5
1.0
5
0.9
4
1 54.2
85
60 176
8
127
5 15 5
5
1.0
5
0.9
6
1 55.4
40
60 184
4
132
6 18 5
5
1.0
5
0.9
8
1 56.5
95
60 192
1
138
7 21 5
5
1.0
5
1.0 1 57.7
50
60 200
1
144
8 24 5
5
1.0
5
1.0
9
1 62.9
48
60 237
7
171
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 183
a5
3.
4
1.
0
3.4
7.3
2
24.8
22.
3
75.8
TOTAL 252
177
2
295
8
3.6 Location of the Center of Stiffness
Provision shall be made in all buildings for increase in shear
forces on the lateral force resisting elements resulting from the
horizontal torsional moment arising due between the centres
of mass. And centre of rigidity. The design forces calculated
as in IS 1893 Part 1 clause. 7.8.4.5 Are. To be applied at the
centre of mass appropriately displaced so as to cause design
eccentricity (IS 1893 Part 1 clause 7.9.2) between the
displaced centre of mass and centre of rigidity. However,
negative torsional shear shall be neglected.
Table -5: Center of Stiffness
3.7 Stress in Steel
Table -6: Stress in steel
PIER X Y KX KY KXY KYX
1 1.23 0.1 4.0E+07 6.9E+05 4.0E+06 8.5E+05
2 4.24 0.1 3.8E+05 1.1E+05 3.8E+04 4.7E+05
3 5.48 0.1 3.8E+05 1.1E+05 3.8E+04 6.0E+05
5 5.82 -0.5 5.9E+06 2.9E+05 -2.9E+06 1.7E+06
6 6.47 -1.2 5.9E+06 2.9E+05 -7.1E+06 1.9E+06
8 8.79 -1.2 2.7E+06 2.2E+05 -3.3E+06 1.9E+06
9 9.44 -0.5 2.7E+06 2.2E+05 -1.4E+06 2.1E+06
10 9.98 0.1 1.1E+06 8.2E+07 1.1E+05 8.2E+08
11 13.65 0.1 2.7E+05 4.7E+06 2.7E+04 6.4E+07
PIER NO
FC
MPa
NET COMPRESSION
MPa
TOTAL
MPa
STRESS IN STEEL
MPa
1 1.59 2.022 3.613 253.99
2 0.02 2.174 2.190 0.93
3 0.02 2.174 2.190 0.93
4 0.31 2.095 2.401 31.13
5 0.31 2.095 2.401 31.13
7 0.14 2.755 2.891 11.94
8 0.14 2.755 2.891 11.94
9 0.01 2.162 2.168 1.38
10 0.00 2.755 2.758 0.35
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 184
3.8 Allowable Shear Stress
Table -7: Allowable Shear Stress
3.8 Shear and Bending Force
Table -8: Shear and Bending Force
4. REINFORCEMENT DETAILING
From the design we came to know that the nominal
reinforcement is enough to ensure flexural stiffness of the
building. But to ensure shear force the web reinforcement has
to be provided at every bed joint.
Minimum Reinforcement Requirements
Vertical reinforcement of at least 100 mm2
in cross-sectional
area shall be provided at a maximum spacing of 3 m on centre
at critical sections:
a) Corners
b) Within 400 mm of each side of openings,
c) Within 200 mm of the end of the walls
Reinforcement around openings need not be provided for
opening smaller than 400 mm in either direction. The
masonry shall be uniformly reinforced in both horizontal and
vertical direction such that the sum of reinforcement area in
both directions shall be at least 0.2% of the gross cross-
sectional area of the wall and minimum reinforcement area in
each direction shall be not less than 0.07% of the gross cross-
sectional area of the wall. Reinforcement around openings
need not be provided for opening smaller than 400 mm in
either direction. Horizontal reinforcement shall consist of at
least two bars of 6 mm spaced not more than 400 mm; or bond
Pier
no
SHEAR
FORCE
d B
SHEAR
STRESS
BENDIG
MOMENT
ALLOWABLE
SHEAR STRESS
MAX ALLOWBLE
SHEAR STRESS
N/mm2
m m N/mm2
N/mm2
N/mm2
N/mm2
1 3.42E+01 2.35E+03 200 0.073 3.84E+01 0.47 0.22 0.17
2 7.13E-01 3.75E+02 200 0.010 8.02E-01 3.00 0.23 0.2
3 7.13E-01 3.75E+02 200 0.010 8.02E-01 3.00 0.23 0.2
4 9.31E+00 1.00E+03 200 0.047 1.05E+01 1.12 0.23 0.2
5 9.35E+00 1.00E+03 200 0.047 1.05E+01 1.12 0.23 0.2
6 4.73E+00 7.50E+02 200 0.032 5.32E+00 1.50 0.23 0.2
7 4.71E+00 7.50E+02 200 0.031 5.30E+00 1.50 0.23 0.2
8 2.07E+00 2.00E+02 3650 0.003 2.33E+00 5.62 0.23 0.2
9 5.20E-01 2.00E+02 915 0.003 5.85E-01 5.62 0.23 0.2
10 5.16E-01 2.00E+02 915 0.003 5.81E-01 5.62 0.23 0.2
PIER NO
Force in each pier Along X IN kN Along Y IN kN
Along X kN Along Y kN Shear force Bending force Shear force Bending force
1 7.49E+01 1.53E+00 3.11E+01 4.39E+01 1.51E+00 1.55E-02
2 7.09E-01 2.44E-01 6.84E-01 2.46E-02 2.42E-01 2.47E-03
3 7.09E-01 2.44E-01 6.84E-01 2.46E-02 2.42E-01 2.47E-03
5 1.11E+01 6.51E-01 8.83E+00 2.26E+00 6.44E-01 6.59E-03
6 1.11E+01 6.51E-01 8.83E+00 2.26E+00 6.44E-01 6.59E-03
8 5.14E+00 4.88E-01 4.49E+00 6.45E-01 4.83E-01 4.94E-03
9 5.14E+00 4.88E-01 4.49E+00 6.45E-01 4.83E-01 4.94E-03
10 2.01E+00 1.82E+02 1.99E+00 2.04E-02 4.12E+01 1.40E+02
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 185
beam reinforcement shall be provided of at least 100 mm2
in
cross-sectional area spaced not more than 3 m. Horizontal
reinforcement shall be provided at the bottom and top of wall
openings and shall extend at least 500 mm or 40 bar diameters
past the openings; continuously at structurally connected roof
and floor levels and within 400 mm of the top of the walls.
Fig-3 Reinforcement details
5. DESIGN OF RCC FRAME
The procedure for analysis and design of a given building will
depend on the type of building, its complexity, the number of
stories etc. First the architectural drawings of the building are
studied, structural system is finalized sizes of structural
members are decided and brought to the knowledge of the
concerned architect. The procedure for structural design will
involve some steps which will depend on the type of building
and also its complexity and the time available for structural
design. The principle objective of this project is to analyse and
design a multi-storeyed building [G +8 (3 dimensional frame)]
using STAAD.Pro. The design involves load calculations
manually and analysing the whole structure by STAAD Pro.
The design methods used in STAAD-Pro analysis are Limit
State Design conforming to Indian Standard Code of Practice
6. COMPARISION BETWEEN RHCBM AND RC
FRAMED STRUCTURE
Design parameter for the comparison purpose: 3 main
parameters of the building considered, viz steel concrete and
blocks. The slab quantities are almost same for the both type
of the building hence it is neglected in comparison. The total
quantities of steel and concrete of the RC framed building is
obtained directly from the Staad,Pro software.
Table -9: Comparison between Rhcbm and Rc Framed
Structure
7. CONCLUSIONS
7.1 Concluding Remarks
Multistoried load bearing masonry building in India is
emerging only recently. Indeed there are hardly any examples
of reinforced masonry system building, despite masonry
possessing good many advantages. In this project the analysis
and design of reinforced hollow concrete block masonry as a
load bearing member for G+8 storied residential apartments
has been presented comprehensively. The design itself has
been carried out for all the combination of load which includes
vertical and lateral loads. Nominal masonry strength of
7.5MPa has been chosen for the design. While the walls
designed for axial and eccentric loads as per IS 1907-1987 and
draft code of reinforced masonry, the lateral loads design have
been carried out as per the accepted structural analysis
principles.
Based on the analysis and design the following broad set of
conclusion can be drawn.
1) It was found that masonry strength of 7.5MPa with H1
grade mortar is sufficient for the vertical/eccentric loads for
almost all the walls. Only 2 out of 34 walls needed a nominal
vertical reinforcement.
2) It was noticed that for the typical building plan chosen in
Bangalore the earthquake loads are marginally higher than
winds for G+8 configurations. Hence the lateral load design of
wall based on critical combination of DL, LL and EL.
3). Since, the analysis and design calculations are quite
involved, a series of spread sheet were developed to identify
the crucial design parameter for each wall of the building. The
spread sheet includes:
MATERIAL RHCBM RC
FRAME
1 Steel 3 tones 30 tones
2 BLOCKS in number 40000 40000
3 CONCRETE only
for grout filling
45 m3
170m3
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 186
a) Design for axial and eccentric load for all the walls;
b) Obtaining lateral stiffness and relative stiffness of all the
walls;
c) Analysis and design for flexure and shear.
d) Analysis for all combination for axial and lateral loads.
e) Analysis for including the effect of torsion.
4) Based on the analysis and design it was found that lateral
load combination along shorter dimension of the building was
more critical. This is to be expected because of relatively
lesser lateral stiffness along this direction. However the
criticality depends on the configuration of load bearing wall. it
is suggested that as for as possible there has to adequate
amount of stiffness along the considered critical lateral load
direction.
5) It was found that the flexure stresses were within the
permissible limit and hence nominal reinforcement is
adequate.
6) The shear stress exceeded allowable stress limits for
significant numbers of wall. Therefore the design needed
provision of web reinforcement. This web reinforcement is
suggested at every bed joint of masonry element.
7) The same building was design as a conventional RC framed
structure. The analysis and design carried out by using
structural analysis software. By comparing the material
required for the both building approximately it is noticed that
the load bearing masonry structure is significantly more
economical than RC framed structure.
ACKNOWLEDGEMENTS
I would like to thank my mentor and guide Dr. Raghunath S,
Professor, Department of Civil Engineering, BMSCE,
Bengaluru, for his constant encouragement, guidance and
support, which enabled me to complete this project.
I would like to thank my Parents and friends for their
encouragement and support.
REFERENCES
[1]. Narendra Taly (2010), DESIGN OF REINFORCED
MASONRY STRUCTURE S, Second Edition New McGraw-
Hill New York, Professor Emeritus Department of Civil
Engineering California State University, Los Angeles.
[2]. A.W. Hendry (2004), “DESIGN OF MASONRY
STRUCTURES” Third edition of Load Bearing Brickwork,
Published by E & FN Spon, an imprint of Chapman & Hall,
2–6 Boundary Row, London SE1 8HN, UK .
[3]. MASONRY STRUCTURAL DESIGN FOR
BUILDINGS - DEPARTMENTS OF THE ARMY, THE
NAVY, AND THE AIR FORCE WASHINGTON, DC, 30
October 1992.
[4]. “REINFORCED MASONRY” Lecture notes of Dr. S
Raghunath, Professor, Department of Civil Engineering,
BMSCE, Bangalore.
[5]. EUROCODE 6: Design of masonry structures EN 1996-1-
1 General- Rules for reinforced and unreinforced masonry.
[6]. K.S. Nanjunda Rao, “STRUCTURAL MASONRY:
PROPERTIES AND BEHAVIOUR”, Department of Civil
Engineering, Indian Institute of Science, Bangalore.
[7]. IITK-GSDMA GUIDELINES for STRUCTURAL USE
of REINFORCED MASONRY, Dr. Durgesh C Rai
Department of Civil Engineering Indian Institute of
technology Kanpur.
[8]. Structural Use of Unreinforced Masonry by Dr. Durgesh
C. Rai, Department of Civil Engineering, Indian Institute of
Technology, Kanpur.
[9]. Structural Masonry Designers’ Manual- W. G. Curtin, G.
Shaw, J. K. Beck and W. A. Bray, Third Edition revised by
David Easterbrook Blackwell.
BIOGRAPHIES
Mr. Shashank B S studied at one of the esteemed
college BMSCE BANGALORE and working in
THE OXFORD College of Engineering
Bangalore as a Assistant Professor.
Dr. S. RAGHUNATH, Professor at the
BMSCE Bangalore in Department of Civil
Engineering with more than 25 year of
experience. Published about 30 papers in
National and International journals and
supervised more than 40 PG project works

More Related Content

PDF
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
PDF
Depremyonetmeligiing
DOCX
Project
PDF
seismic analysis of multistoryed building by ETABS
PDF
Analysis and Design of Commercial Building using ETABS
PDF
IRJET- Comparative Study on Analysis and Design of Regular Configuration of B...
PDF
Analysis and design of high rise building frame using staad pro
PDF
Wind Analysis and Design of G+11 Storied Building using STAAD-Pro
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
Depremyonetmeligiing
Project
seismic analysis of multistoryed building by ETABS
Analysis and Design of Commercial Building using ETABS
IRJET- Comparative Study on Analysis and Design of Regular Configuration of B...
Analysis and design of high rise building frame using staad pro
Wind Analysis and Design of G+11 Storied Building using STAAD-Pro

What's hot (20)

PDF
Design of G+8 RCC Training Institute & Hostel Block
PDF
IRJET- Design and Analysis of Residential Multistory Building (G+5) by using ...
PDF
Analysis and design of multi-storey building using staad.Pro
PPTX
Etabs BY Subash Pathak
PDF
Seismic Analysis and Design of Reinforced Concrete Multistory Building under ...
PDF
IRJET- Analysis and Design of Multi Storey Building Subjected to Seismic Load...
PDF
Analysis and Design of G+3 Residential Building using STRUDS
PDF
IRJET - Design and Analysis of a G+4 Commercial Building by using STAAD PRO
PPTX
Analysis and design of commercial building
PDF
PLANNING AND DESIGN OF G+3 RESIDENTIAL HOUSING COMPLEX (Share By Suman Sau)
PDF
IRJET- Planning, Analyzing and Design of High Rise Building using Etabs
PPTX
Hostel
PDF
IRJET- Design and Analysis of Residential Building
PDF
IRJET- Seismic Analysis of a Multi-Storey Building using Steel Braced Frames
PDF
Effect of Oblique Column and Viscous Damper on Podium Structure Using Etabs
PDF
Design and comparison of a residential building (g+10) for seismic forces usi...
PDF
IRJET- Comparative Study of High Rise Building Subjected to Seismic and Wind ...
PDF
Analysis, Design and Estimation of Basement +G+2 Residential Building
PDF
IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...
DOCX
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
Design of G+8 RCC Training Institute & Hostel Block
IRJET- Design and Analysis of Residential Multistory Building (G+5) by using ...
Analysis and design of multi-storey building using staad.Pro
Etabs BY Subash Pathak
Seismic Analysis and Design of Reinforced Concrete Multistory Building under ...
IRJET- Analysis and Design of Multi Storey Building Subjected to Seismic Load...
Analysis and Design of G+3 Residential Building using STRUDS
IRJET - Design and Analysis of a G+4 Commercial Building by using STAAD PRO
Analysis and design of commercial building
PLANNING AND DESIGN OF G+3 RESIDENTIAL HOUSING COMPLEX (Share By Suman Sau)
IRJET- Planning, Analyzing and Design of High Rise Building using Etabs
Hostel
IRJET- Design and Analysis of Residential Building
IRJET- Seismic Analysis of a Multi-Storey Building using Steel Braced Frames
Effect of Oblique Column and Viscous Damper on Podium Structure Using Etabs
Design and comparison of a residential building (g+10) for seismic forces usi...
IRJET- Comparative Study of High Rise Building Subjected to Seismic and Wind ...
Analysis, Design and Estimation of Basement +G+2 Residential Building
IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
Ad

Viewers also liked (20)

PPTX
Suspension
PPTX
Lecture2 classification of structures
PPTX
Building superstructure
PDF
STRUCTURAL FRAME
PPTX
CE 72.52 - Lecture 7 - Strut and Tie Models
PPTX
Load bearing elements part5
PPT
Columns and struts
PPT
TYPES OF FOUNDATION(PPT)
PPT
types of Foundations with animated sketches
PPTX
Types of construction
DOCX
Types of laods
PPTX
Report on rigid frame structures
PDF
Measurement of losses in direct torque controlled
PDF
A reduced complexity and an efficient channel
PDF
Automatic collision detection for an autonomous robot using proximity sensing...
PDF
An analysis of environmental impacts of various environmental aspects for ind...
PDF
Application of ibearugbulem’s model for optimizing granite concrete mix
PDF
A study of localized algorithm for self organized wireless sensor network and...
PDF
Review study on performance of seismically tested repaired shear walls
PDF
Tools description for product development process management in food industries
Suspension
Lecture2 classification of structures
Building superstructure
STRUCTURAL FRAME
CE 72.52 - Lecture 7 - Strut and Tie Models
Load bearing elements part5
Columns and struts
TYPES OF FOUNDATION(PPT)
types of Foundations with animated sketches
Types of construction
Types of laods
Report on rigid frame structures
Measurement of losses in direct torque controlled
A reduced complexity and an efficient channel
Automatic collision detection for an autonomous robot using proximity sensing...
An analysis of environmental impacts of various environmental aspects for ind...
Application of ibearugbulem’s model for optimizing granite concrete mix
A study of localized algorithm for self organized wireless sensor network and...
Review study on performance of seismically tested repaired shear walls
Tools description for product development process management in food industries
Ad

Similar to “Analysis and design of multi storeyed load bearing reinforced masonry structure and framed rc structure” (20)

PDF
Seismic evaluation of rc frame with brick masonry infill walls
PDF
Use of flat slabs in multi storey commercial building situated in high seismi...
DOCX
Behavior of plan irregularites using composite members by varying column spac...
DOCX
Behavior of plan irregularites using composite members by varying column spac...
PDF
Evaluation of Seismic Behaviour of RCC Building using Coupled Shear wall
PDF
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
PDF
Study of lateral load resisting systems of variable heights in all soil types...
PDF
Study of lateral load resisting systems of variable heights in all soil types...
PDF
seismic response of multi storey building equipped with steel bracing
PDF
Effect of modulus of masonry on initial lateral stiffness of infilled frames ...
PDF
Optimization of a multistorey building by optimum
PDF
“Static &dynamic analysis of multistory building using
PDF
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
PDF
Optimisation of earth quake response of tall building by using different fram...
PDF
IRJET- Post Peak Response of Reinforced Concrete Frames with and without in F...
PDF
IRJET- Study on Shear Wall and Bracing in Irregular Structure and Regular Str...
PDF
Seismic evelution of rc space frame with rectangular and equivalent square co...
PDF
Determination of period of vibration of buildings with open stilt floor and s...
PDF
IRJET- A Research on Comparing the Effect of Seismic Waves on Multistoried Bu...
PDF
Comparative Analysis of Cantilever Retaining Wall With And Without Column-Bea...
Seismic evaluation of rc frame with brick masonry infill walls
Use of flat slabs in multi storey commercial building situated in high seismi...
Behavior of plan irregularites using composite members by varying column spac...
Behavior of plan irregularites using composite members by varying column spac...
Evaluation of Seismic Behaviour of RCC Building using Coupled Shear wall
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
Study of lateral load resisting systems of variable heights in all soil types...
Study of lateral load resisting systems of variable heights in all soil types...
seismic response of multi storey building equipped with steel bracing
Effect of modulus of masonry on initial lateral stiffness of infilled frames ...
Optimization of a multistorey building by optimum
“Static &dynamic analysis of multistory building using
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Optimisation of earth quake response of tall building by using different fram...
IRJET- Post Peak Response of Reinforced Concrete Frames with and without in F...
IRJET- Study on Shear Wall and Bracing in Irregular Structure and Regular Str...
Seismic evelution of rc space frame with rectangular and equivalent square co...
Determination of period of vibration of buildings with open stilt floor and s...
IRJET- A Research on Comparing the Effect of Seismic Waves on Multistoried Bu...
Comparative Analysis of Cantilever Retaining Wall With And Without Column-Bea...

More from eSAT Publishing House (20)

PDF
Likely impacts of hudhud on the environment of visakhapatnam
PDF
Impact of flood disaster in a drought prone area – case study of alampur vill...
PDF
Hudhud cyclone – a severe disaster in visakhapatnam
PDF
Groundwater investigation using geophysical methods a case study of pydibhim...
PDF
Flood related disasters concerned to urban flooding in bangalore, india
PDF
Enhancing post disaster recovery by optimal infrastructure capacity building
PDF
Effect of lintel and lintel band on the global performance of reinforced conc...
PDF
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
PDF
Wind damage to buildings, infrastrucuture and landscape elements along the be...
PDF
Shear strength of rc deep beam panels – a review
PDF
Role of voluntary teams of professional engineers in dissater management – ex...
PDF
Risk analysis and environmental hazard management
PDF
Monitoring and assessment of air quality with reference to dust particles (pm...
PDF
Low cost wireless sensor networks and smartphone applications for disaster ma...
PDF
Coastal zones – seismic vulnerability an analysis from east coast of india
PDF
Can fracture mechanics predict damage due disaster of structures
PDF
Assessment of seismic susceptibility of rc buildings
PDF
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
PDF
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
PDF
Disaster recovery sustainable housing
Likely impacts of hudhud on the environment of visakhapatnam
Impact of flood disaster in a drought prone area – case study of alampur vill...
Hudhud cyclone – a severe disaster in visakhapatnam
Groundwater investigation using geophysical methods a case study of pydibhim...
Flood related disasters concerned to urban flooding in bangalore, india
Enhancing post disaster recovery by optimal infrastructure capacity building
Effect of lintel and lintel band on the global performance of reinforced conc...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Shear strength of rc deep beam panels – a review
Role of voluntary teams of professional engineers in dissater management – ex...
Risk analysis and environmental hazard management
Monitoring and assessment of air quality with reference to dust particles (pm...
Low cost wireless sensor networks and smartphone applications for disaster ma...
Coastal zones – seismic vulnerability an analysis from east coast of india
Can fracture mechanics predict damage due disaster of structures
Assessment of seismic susceptibility of rc buildings
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Disaster recovery sustainable housing

Recently uploaded (20)

PDF
Introduction to Power System StabilityPS
PDF
distributed database system" (DDBS) is often used to refer to both the distri...
PPTX
PRASUNET_20240614003_231416_0000[1].pptx
PPTX
ai_satellite_crop_management_20250815030350.pptx
PPTX
Software Engineering and software moduleing
PPTX
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
PPTX
A Brief Introduction to IoT- Smart Objects: The "Things" in IoT
PPTX
wireless networks, mobile computing.pptx
PDF
August 2025 - Top 10 Read Articles in Network Security & Its Applications
PDF
Unit I -OPERATING SYSTEMS_SRM_KATTANKULATHUR.pptx.pdf
DOC
T Pandian CV Madurai pandi kokkaf illaya
PDF
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
PDF
Computer organization and architecuture Digital Notes....pdf
PPTX
tack Data Structure with Array and Linked List Implementation, Push and Pop O...
PDF
Unit1 - AIML Chapter 1 concept and ethics
PDF
UEFA_Embodied_Carbon_Emissions_Football_Infrastructure.pdf
PPTX
ASME PCC-02 TRAINING -DESKTOP-NLE5HNP.pptx
PDF
Exploratory_Data_Analysis_Fundamentals.pdf
PDF
MLpara ingenieira CIVIL, meca Y AMBIENTAL
PPTX
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
Introduction to Power System StabilityPS
distributed database system" (DDBS) is often used to refer to both the distri...
PRASUNET_20240614003_231416_0000[1].pptx
ai_satellite_crop_management_20250815030350.pptx
Software Engineering and software moduleing
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
A Brief Introduction to IoT- Smart Objects: The "Things" in IoT
wireless networks, mobile computing.pptx
August 2025 - Top 10 Read Articles in Network Security & Its Applications
Unit I -OPERATING SYSTEMS_SRM_KATTANKULATHUR.pptx.pdf
T Pandian CV Madurai pandi kokkaf illaya
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
Computer organization and architecuture Digital Notes....pdf
tack Data Structure with Array and Linked List Implementation, Push and Pop O...
Unit1 - AIML Chapter 1 concept and ethics
UEFA_Embodied_Carbon_Emissions_Football_Infrastructure.pdf
ASME PCC-02 TRAINING -DESKTOP-NLE5HNP.pptx
Exploratory_Data_Analysis_Fundamentals.pdf
MLpara ingenieira CIVIL, meca Y AMBIENTAL
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx

“Analysis and design of multi storeyed load bearing reinforced masonry structure and framed rc structure”

  • 1. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 179 “ANALYSIS AND DESIGN OF MULTI-STOREYED LOAD BEARING REINFORCED MASONRY STRUCTURE AND FRAMED RC STRUCTURE” Shashank B.S1 , S.Raghunath2 1 Assistant Professor, Civil Engineering, TOCE, shashankbsbhat.bs@gmail.com, Karnataka, India 2 Professor, Civil Engineering, BMSCE, raghunath.smrc@gmail.com, Karnataka, India Abstract Load bearing masonry structures in India are generally restricted to 3 or 4 storeys in height. This is mainly because of lack of availability of good quality masonry unit and associated workmanship. Also, it is generally perceived that load bearing masonry storey may perform in brittle manner under excessive lateral loads. However, with the advancement of availability of engineered hollow concrete blocks which has a scope to introduce reinforcement, it is perhaps possible to design and eventually construct multi- storeyed reinforced masonry building. In this paper an attempt has been made to analyse and design the structural components of a multi-storeyed residential building using reinforced hollow concrete block masonry. (i) Residential occupancy in ground floor + 8 floors. The building is analysed and designed for all the load combination as per the codal provisions. Later the same building is analysed and design by considering it as conventional RC framed structure system. The structural comparison of both of them has been made. Based on the study it is found that the requirement of reinforcing steel and concrete is significantly lesser, when compared to building designed as load bearing masonry system. It is also found that masonry prism strength of 7.5MPa with nominal vertical reinforcement is adequate to withstand the combination of axial and lateral loads. Keywords: Load bearing, hollow block, Reinforcement, Lateral strength, RC Frame ----------------------------------------------------------------------***------------------------------------------------------------------------ 1. INTRODUCTION There are a lot of arguments about the actuality of reinforced masonry. Although bricks belong to the conventional and traditional building materials, reinforced concrete frames are favored in construction industry nowadays. In that case the masonry is used purely as an infill wall. The load bearing capacity of masonry is only significant for the design of some storey constructions. On the other hand, it is possible to dispense with RC frame and construct multi storied load bearing masonry structures, when good quality blocks are used in conjunction with reinforcement. 1.1 Reinforced Masonry In India there has not been much progress in the construction of tall load bearing masonry structures, mainly because of poor quality of masonry workmanship and material such as clay bricks that are manufactured even today having nominal strength of only 7.0 to 10.0 MPa. However recently mechanized brick plants are producing brick units of strength 17.5 to 24 MPa and therefore it is possible to construct 5 to 6 storied load bearing structures at costs less than those of RC framed structures. Reinforced masonry (RM) is more economical and structurally efficient than framed RC structure (a) If good quality blocks are produced (b) If reinforcement is suitably introduced (c) If the strength and elastic properties are known In load bearing walls, when the plan length of openings exceeds approximately one- half the total plan length of the wall and lateral forces act on the walls whether in- plane or out of plane, flexural tensile stresses generally become so large that the walls must be designed as reinforced. Reinforcement can also be used to increase shear resistance. Fig-1 Reinforced masonry
  • 2. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 180 2. STRUCTURAL DESIGN OF REINFORCED MASONRY Permissible Compressive Force: Compressive force in reinforced masonry due to axial load shall not exceed that given by following equation: Po = (0.25fm'An+ 0.65Ast FS) Ks Where, An = Net area Ast = Area of steel Fs = Permissible steel tensile stress Ks= Stress reduction factor as in Table 9 of IS: 1905-1987 The compressive force at the section from axial loads or from the axial component of combined loads is calculated separately as is limited to the permissible values. A coefficient of 0.25 provides a factor of safety of about 4.0 against crushing of masonry. The coefficient of 0.65 was determined from tests on masonry. Permissible Shear Stress for Reinforced masonry members a) For Flexural members i). Without Web Reinforcement Fv = 0.083 fm but not greater than 0.25 MPa ii). With Web Reinforcement Fv = 0.25 fm but not greater than 0.75 MPa b) For Walls For reinforced masonry, the shear resistance is offered by both masonry and reinforcement, however, their effect is not taken additive in this document, like many other masonry codes. This has basis in an experimental research by Priestley and Bridgeman which concluded that the shear reinforcement in masonry is effective in providing resistance when it is designed to carry the full shear load. If calculated shear stress exceeds the allowable shear stress for masonry, full shear load has to be resisted by the reinforcement alone which is placed parallel to the applied shear force direction. The amount of shear reinforcement. Experiments have shown that shear resistance of the reinforced shear walls are function of the aspect ratio of the wall (i.e., ratio of height to length), besides distribution of reinforcement and masonry strength. Shear walls with lower aspect ratio have been provided with higher allowable shear stress. 3. LOAD BEARING MASONRY ELEMENT-CASE STUDY The major objective of this Paper is to demonstrate a comprehensive design procedure for multi-storied load bearing masonry building. Typical residential building with identical floor plans is amenable to be design as load bearing structure. Avoiding provision of walls out of line with walls in the underneath floors is crucial. Such a layout will ensure the avoidance of beam. As a consequence of which excessive point loads on load bearing walls can be avoided. At this juncture that it is crucial to identify the load bearing elements. Here it is provident to avoid considering walls of significantly small cross section area as load bearing element in this case study is identified with wall A to Z and A’ to K’ for axial load analysis and for the lateral load analysis it is identified as 1 t0 54.It can be noticed that the walls for bath room kitchens (which are lesser than 200mm thickness) is not considered as load bearing masonry walls. The process of design as already mentioned is carried out in 3 phases, viz, a) Calculation of loads b) Design for axial and eccentric loads c) Design for flexure and shear Fig -2: Plan of 1st Floor 3.1 Design of Wall Element Axial/Eccentric Loads A building is basically subjected to two types of loads, namely: a) Vertical loads on account of dead loads of materials used in construction, plus live loads due to occupancy; and b) Lateral loads due to wind and seismic forces. While all walls in general can take vertical loads, ability of a wall to take lateral loads depends on its disposition in relation to the direction of lateral load. In general a structural wall shall be designed to with stand axial
  • 3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 181 compression, stress due to eccentricity in plane shear and out of plane building. 3.1.1 Design Loads Loads to be taken into consideration for designing masonry components of a structure are: a) Dead loads of walls, columns, floors and roofs; b) Live loads of floors and roof c) Wind loads on walls d) Seismic forces. 1. Dead loads shall be calculated on the basis of unit weights taken in accordance with IS: 875-1 (1987). 2. Live loads of floors and roof shall be calculated on the basis of unit weights taken in accordance with IS: 875-2 (1987). 3. Wind loads on walls calculated on the basis of IS: 875-3 (1987). 4. Seismic forces on walls is calculated by using IS 1893-2002 part 1. Table -1: Sample Stress Calculation W al ls L Leff SR Net area mm2 Loa d kn Stress Devel oped MPa Stres s allow able MPa Fac tor A 3.6 5 2.9 7 11. 2 72817 657. 1 0.902 2.250 2.4 9 B 3.7 4 1.8 4 9.2 4 74662 997. 8 1.337 2.644 1.9 8 C 3.7 5 1.8 4 9.2 4 74916 107 6. 1.437 2.644 1.8 40 D 4.1 4 3.8 1 11. 2 82800 134 6. 1.626 2.250 1.3 8 E 4.7 4.3 9 11. 2 93878 877 0.935 2.250 2.4 0 F 3.2 7 3.8 1 11. 2 65316 1 991 1.517 2.250 1.4 8 G 4.1 3.4 0 11. 2 82000 0 142 9 1.743 2.250 1.2 9 3.2 Lateral Load Analysis and Design A building is basically subjected to two types of loads, namely: 1. vertical loads on account of dead loads of materials used in construction, plus live loads due to occupancy; and 2. Lateral loads due to wind and seismic forces. Lateral loads from the wind or earthquakes are generally considered to act in the direction of the principal axes of the building structure. The distribution of lateral loads to various masonry wall elements depends on the rigidities of the horizontal floor or roof diaphragm and of the wall elements. If a diaphragm does not undergo significant in-plane deformation with respect to the supporting walls, it can be considered rigid and lateral loads are distributed in various lateral load resisting wall elements in proportion to their relative stiffness. 3.2.1 Distribution of Lateral Forces in the Piers of a Masonry Wall Masonry walls are often seen to be perforated to make arrangement for windows and doors. The distribution of lateral force in a masonry wall is dependent on the position of the openings and the relative rigidity of the masonry piers created due to the presence of the openings in the masonry wall. The relative rigidity is dependent on the height by length ratio (h/L Ratio) of the piers and the end conditions of those masonry piers as the deflection of the masonry piers due to horizontal loading changes due to the end condition of the piers. Here a simple process is described which can be used to distribute the lateral force in a wall which can be considered to be consist of some piers with some specific arrangements. In any kind of placing of opening the wall can be represented as a horizontal and vertical combination of piers with their respective end condition which will be used to find out their rigidities. Where large openings occur, it is difficult to obtain effective coupling of the wall segments or piers. Lateral loads shall be distributed to the structure system in accordance with member stiffness for rigid diaphragms or tributary areas for flexible diaphragms and shall comply with the following requirements 1. Flanges of intersecting walls designed in accordance to IS 1905 draft section 4.2.2.5 shall be included in stiffness determination. 2. Distribution of load shall include the effect of diaphragm rigidity and of horizontal torsion due to eccentricity of wind and seismic loads resulting from non-uniform distribution of mass 3.2.2 Wind Load Analysis The wind force calculated from these factors is assumed to act as an equivalent uniformly distributed load on the building for its full height. sometimes the wind velocity or the gust factor is assumed variable with the height of the building ,so that the intensity of the equivalent uniformly distributed load varies accordingly in the united kingdom wind loads on buildings are calculated from the provisions of the code of practice CP3 chapter V Part 2 1970 whilst masonry is strong in compression it is very weak in tension thus engineering design for wind loading may be needed not only for multi storey structures but also for some single storey structures Design Wind Speed (Vz) The basic wind speed (Vz) for any site shall be obtained from and shall be modified to include the following effects to get design wind velocity at any height (Vz) for the chosen structure: a) Risk level; b) Terrain roughness, height and size of structure; and c) Local topography. d) It can be mathematically expressed as follows: Vz= Vb kl k2 k3 Vb = design wind speed at any height z in m/s; kl = probability factor (risk coefficient) k2 = terrain, height and structure size factor and k3 = topography factor
  • 4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 182 Table -2: Wind load Total force = 1048 kN. 3.2.3 Sesmic Load Analysis The primary objective of earthquake resistant design is to prevent building collapse during earthquakes thus minimizing the risk of death or injury to people in or around those buildings. Because damaging earthquakes are rare, economics dictate that damage to buildings is expected and acceptable provided collapse is avoided. Earthquake Resistant Design-The following steps may be taken: (a) Estimate fundamental time period Ta using empirical expressions given in the Code IS: 1893-10 2002. (b) Calculate the design horizontal Seismic coefficient Ah The design horizontal coefficient Ah is given by Ah = 𝑍𝐼 2𝑅 𝑆𝑎 𝑔 Take Z for the applicable seismic zone (IS: 1893 Cl.6.4.2), Take I for the use importance of the building (IS: 1893 Table 2), Take R for the lateral load resisting system adopted (IS: 1893 Table 7), and take Sa/g for the computed time period values (c) Calculate the total horizontal shear (the base shear) The design value of base shear VB VB = Ah W As per IS 1893 Cl.7.5.3. (d) Seismic Moments and Forces in Frame Elements: Calculate the seismic moments and axial forces in the columns, shears and moments in the beams by using the seismic weights on the floors/ (column beam joints) through an appropriate computer software (having facility for using floors as rigid diaphragm and torsional effects as per IS: 1893:2002). Table -3: Seismic force on each floor FLOORS HEIGHT m Qi kN 1 3 7 2 6 28 3 9 62 4 12 110 5 15 172 6 18 248 7 21 338 8 24 441 TOTAL 1406 3.4 Design for Shear Members Subjected to Shear: Reinforced masonry walls may be designed taking contribution of shear reinforcement. Where contribution of shear reinforcement is considered in resisting shear force the minimum area of shear reinforcement in the direction of force shall be determined by the following: Avmin = VS/FSd V = total applied shear force S = spacing of the shear reinforcement d = distance from extreme compression fiber to centroid of tension reinforcement Fs = permissible stress in steel reinforcement 3.5 Location of the Center of Mass Table -4: Centre of mass calculation Par t B m D m ARE A m2 X AX Y AY X’ m Y’ m a1 3. 4 1. 0 3.4 7.3 24.8 - 0.5 -1.7 7. 0 11. 7 a2 12 8. 4 101.3 6.0 607 4.2 425. 4 a3 4. 7 5. 4 25.7 11. 5 296 11. 0 284. 2 a4 12 8. 4 101.3 6.0 607 19. 5 197 5 Flo or Heigh t M V b m /s k1 k2 k 3 Vz N/m 2 AR EA m2 Pz kN kN Wi nd for ce 1 3 5 5 1.0 5 0.8 8 1 50.8 20 60 154 9 111 2 6 5 5 1.0 5 0.8 8 1 50.8 20 60 154 9 111 3 9 5 5 1.0 5 0.8 8 1 50.8 20 60 154 9 111 4 12 5 5 1.0 5 0.9 4 1 54.2 85 60 176 8 127 5 15 5 5 1.0 5 0.9 6 1 55.4 40 60 184 4 132 6 18 5 5 1.0 5 0.9 8 1 56.5 95 60 192 1 138 7 21 5 5 1.0 5 1.0 1 57.7 50 60 200 1 144 8 24 5 5 1.0 5 1.0 9 1 62.9 48 60 237 7 171
  • 5. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 183 a5 3. 4 1. 0 3.4 7.3 2 24.8 22. 3 75.8 TOTAL 252 177 2 295 8 3.6 Location of the Center of Stiffness Provision shall be made in all buildings for increase in shear forces on the lateral force resisting elements resulting from the horizontal torsional moment arising due between the centres of mass. And centre of rigidity. The design forces calculated as in IS 1893 Part 1 clause. 7.8.4.5 Are. To be applied at the centre of mass appropriately displaced so as to cause design eccentricity (IS 1893 Part 1 clause 7.9.2) between the displaced centre of mass and centre of rigidity. However, negative torsional shear shall be neglected. Table -5: Center of Stiffness 3.7 Stress in Steel Table -6: Stress in steel PIER X Y KX KY KXY KYX 1 1.23 0.1 4.0E+07 6.9E+05 4.0E+06 8.5E+05 2 4.24 0.1 3.8E+05 1.1E+05 3.8E+04 4.7E+05 3 5.48 0.1 3.8E+05 1.1E+05 3.8E+04 6.0E+05 5 5.82 -0.5 5.9E+06 2.9E+05 -2.9E+06 1.7E+06 6 6.47 -1.2 5.9E+06 2.9E+05 -7.1E+06 1.9E+06 8 8.79 -1.2 2.7E+06 2.2E+05 -3.3E+06 1.9E+06 9 9.44 -0.5 2.7E+06 2.2E+05 -1.4E+06 2.1E+06 10 9.98 0.1 1.1E+06 8.2E+07 1.1E+05 8.2E+08 11 13.65 0.1 2.7E+05 4.7E+06 2.7E+04 6.4E+07 PIER NO FC MPa NET COMPRESSION MPa TOTAL MPa STRESS IN STEEL MPa 1 1.59 2.022 3.613 253.99 2 0.02 2.174 2.190 0.93 3 0.02 2.174 2.190 0.93 4 0.31 2.095 2.401 31.13 5 0.31 2.095 2.401 31.13 7 0.14 2.755 2.891 11.94 8 0.14 2.755 2.891 11.94 9 0.01 2.162 2.168 1.38 10 0.00 2.755 2.758 0.35
  • 6. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 184 3.8 Allowable Shear Stress Table -7: Allowable Shear Stress 3.8 Shear and Bending Force Table -8: Shear and Bending Force 4. REINFORCEMENT DETAILING From the design we came to know that the nominal reinforcement is enough to ensure flexural stiffness of the building. But to ensure shear force the web reinforcement has to be provided at every bed joint. Minimum Reinforcement Requirements Vertical reinforcement of at least 100 mm2 in cross-sectional area shall be provided at a maximum spacing of 3 m on centre at critical sections: a) Corners b) Within 400 mm of each side of openings, c) Within 200 mm of the end of the walls Reinforcement around openings need not be provided for opening smaller than 400 mm in either direction. The masonry shall be uniformly reinforced in both horizontal and vertical direction such that the sum of reinforcement area in both directions shall be at least 0.2% of the gross cross- sectional area of the wall and minimum reinforcement area in each direction shall be not less than 0.07% of the gross cross- sectional area of the wall. Reinforcement around openings need not be provided for opening smaller than 400 mm in either direction. Horizontal reinforcement shall consist of at least two bars of 6 mm spaced not more than 400 mm; or bond Pier no SHEAR FORCE d B SHEAR STRESS BENDIG MOMENT ALLOWABLE SHEAR STRESS MAX ALLOWBLE SHEAR STRESS N/mm2 m m N/mm2 N/mm2 N/mm2 N/mm2 1 3.42E+01 2.35E+03 200 0.073 3.84E+01 0.47 0.22 0.17 2 7.13E-01 3.75E+02 200 0.010 8.02E-01 3.00 0.23 0.2 3 7.13E-01 3.75E+02 200 0.010 8.02E-01 3.00 0.23 0.2 4 9.31E+00 1.00E+03 200 0.047 1.05E+01 1.12 0.23 0.2 5 9.35E+00 1.00E+03 200 0.047 1.05E+01 1.12 0.23 0.2 6 4.73E+00 7.50E+02 200 0.032 5.32E+00 1.50 0.23 0.2 7 4.71E+00 7.50E+02 200 0.031 5.30E+00 1.50 0.23 0.2 8 2.07E+00 2.00E+02 3650 0.003 2.33E+00 5.62 0.23 0.2 9 5.20E-01 2.00E+02 915 0.003 5.85E-01 5.62 0.23 0.2 10 5.16E-01 2.00E+02 915 0.003 5.81E-01 5.62 0.23 0.2 PIER NO Force in each pier Along X IN kN Along Y IN kN Along X kN Along Y kN Shear force Bending force Shear force Bending force 1 7.49E+01 1.53E+00 3.11E+01 4.39E+01 1.51E+00 1.55E-02 2 7.09E-01 2.44E-01 6.84E-01 2.46E-02 2.42E-01 2.47E-03 3 7.09E-01 2.44E-01 6.84E-01 2.46E-02 2.42E-01 2.47E-03 5 1.11E+01 6.51E-01 8.83E+00 2.26E+00 6.44E-01 6.59E-03 6 1.11E+01 6.51E-01 8.83E+00 2.26E+00 6.44E-01 6.59E-03 8 5.14E+00 4.88E-01 4.49E+00 6.45E-01 4.83E-01 4.94E-03 9 5.14E+00 4.88E-01 4.49E+00 6.45E-01 4.83E-01 4.94E-03 10 2.01E+00 1.82E+02 1.99E+00 2.04E-02 4.12E+01 1.40E+02
  • 7. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 185 beam reinforcement shall be provided of at least 100 mm2 in cross-sectional area spaced not more than 3 m. Horizontal reinforcement shall be provided at the bottom and top of wall openings and shall extend at least 500 mm or 40 bar diameters past the openings; continuously at structurally connected roof and floor levels and within 400 mm of the top of the walls. Fig-3 Reinforcement details 5. DESIGN OF RCC FRAME The procedure for analysis and design of a given building will depend on the type of building, its complexity, the number of stories etc. First the architectural drawings of the building are studied, structural system is finalized sizes of structural members are decided and brought to the knowledge of the concerned architect. The procedure for structural design will involve some steps which will depend on the type of building and also its complexity and the time available for structural design. The principle objective of this project is to analyse and design a multi-storeyed building [G +8 (3 dimensional frame)] using STAAD.Pro. The design involves load calculations manually and analysing the whole structure by STAAD Pro. The design methods used in STAAD-Pro analysis are Limit State Design conforming to Indian Standard Code of Practice 6. COMPARISION BETWEEN RHCBM AND RC FRAMED STRUCTURE Design parameter for the comparison purpose: 3 main parameters of the building considered, viz steel concrete and blocks. The slab quantities are almost same for the both type of the building hence it is neglected in comparison. The total quantities of steel and concrete of the RC framed building is obtained directly from the Staad,Pro software. Table -9: Comparison between Rhcbm and Rc Framed Structure 7. CONCLUSIONS 7.1 Concluding Remarks Multistoried load bearing masonry building in India is emerging only recently. Indeed there are hardly any examples of reinforced masonry system building, despite masonry possessing good many advantages. In this project the analysis and design of reinforced hollow concrete block masonry as a load bearing member for G+8 storied residential apartments has been presented comprehensively. The design itself has been carried out for all the combination of load which includes vertical and lateral loads. Nominal masonry strength of 7.5MPa has been chosen for the design. While the walls designed for axial and eccentric loads as per IS 1907-1987 and draft code of reinforced masonry, the lateral loads design have been carried out as per the accepted structural analysis principles. Based on the analysis and design the following broad set of conclusion can be drawn. 1) It was found that masonry strength of 7.5MPa with H1 grade mortar is sufficient for the vertical/eccentric loads for almost all the walls. Only 2 out of 34 walls needed a nominal vertical reinforcement. 2) It was noticed that for the typical building plan chosen in Bangalore the earthquake loads are marginally higher than winds for G+8 configurations. Hence the lateral load design of wall based on critical combination of DL, LL and EL. 3). Since, the analysis and design calculations are quite involved, a series of spread sheet were developed to identify the crucial design parameter for each wall of the building. The spread sheet includes: MATERIAL RHCBM RC FRAME 1 Steel 3 tones 30 tones 2 BLOCKS in number 40000 40000 3 CONCRETE only for grout filling 45 m3 170m3
  • 8. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 06 | May-2014 | RRDCE - 2014, Available @ http://www.ijret.org 186 a) Design for axial and eccentric load for all the walls; b) Obtaining lateral stiffness and relative stiffness of all the walls; c) Analysis and design for flexure and shear. d) Analysis for all combination for axial and lateral loads. e) Analysis for including the effect of torsion. 4) Based on the analysis and design it was found that lateral load combination along shorter dimension of the building was more critical. This is to be expected because of relatively lesser lateral stiffness along this direction. However the criticality depends on the configuration of load bearing wall. it is suggested that as for as possible there has to adequate amount of stiffness along the considered critical lateral load direction. 5) It was found that the flexure stresses were within the permissible limit and hence nominal reinforcement is adequate. 6) The shear stress exceeded allowable stress limits for significant numbers of wall. Therefore the design needed provision of web reinforcement. This web reinforcement is suggested at every bed joint of masonry element. 7) The same building was design as a conventional RC framed structure. The analysis and design carried out by using structural analysis software. By comparing the material required for the both building approximately it is noticed that the load bearing masonry structure is significantly more economical than RC framed structure. ACKNOWLEDGEMENTS I would like to thank my mentor and guide Dr. Raghunath S, Professor, Department of Civil Engineering, BMSCE, Bengaluru, for his constant encouragement, guidance and support, which enabled me to complete this project. I would like to thank my Parents and friends for their encouragement and support. REFERENCES [1]. Narendra Taly (2010), DESIGN OF REINFORCED MASONRY STRUCTURE S, Second Edition New McGraw- Hill New York, Professor Emeritus Department of Civil Engineering California State University, Los Angeles. [2]. A.W. Hendry (2004), “DESIGN OF MASONRY STRUCTURES” Third edition of Load Bearing Brickwork, Published by E & FN Spon, an imprint of Chapman & Hall, 2–6 Boundary Row, London SE1 8HN, UK . [3]. MASONRY STRUCTURAL DESIGN FOR BUILDINGS - DEPARTMENTS OF THE ARMY, THE NAVY, AND THE AIR FORCE WASHINGTON, DC, 30 October 1992. [4]. “REINFORCED MASONRY” Lecture notes of Dr. S Raghunath, Professor, Department of Civil Engineering, BMSCE, Bangalore. [5]. EUROCODE 6: Design of masonry structures EN 1996-1- 1 General- Rules for reinforced and unreinforced masonry. [6]. K.S. Nanjunda Rao, “STRUCTURAL MASONRY: PROPERTIES AND BEHAVIOUR”, Department of Civil Engineering, Indian Institute of Science, Bangalore. [7]. IITK-GSDMA GUIDELINES for STRUCTURAL USE of REINFORCED MASONRY, Dr. Durgesh C Rai Department of Civil Engineering Indian Institute of technology Kanpur. [8]. Structural Use of Unreinforced Masonry by Dr. Durgesh C. Rai, Department of Civil Engineering, Indian Institute of Technology, Kanpur. [9]. Structural Masonry Designers’ Manual- W. G. Curtin, G. Shaw, J. K. Beck and W. A. Bray, Third Edition revised by David Easterbrook Blackwell. BIOGRAPHIES Mr. Shashank B S studied at one of the esteemed college BMSCE BANGALORE and working in THE OXFORD College of Engineering Bangalore as a Assistant Professor. Dr. S. RAGHUNATH, Professor at the BMSCE Bangalore in Department of Civil Engineering with more than 25 year of experience. Published about 30 papers in National and International journals and supervised more than 40 PG project works