FIRE
Back - to - BasicsBack - to - Basics
Fire Alarm Seminar
FIRE
AgendaAgenda
What is a Fire Alarm System?n What is a Fire Alarm System?
n FA Circuits (Classes & Styles)
n Peripherals in Briefn Peripherals in Brief
n How to Wire a Building
n Voltage Drop Considerationsn Voltage Drop Considerations
n Old & Obsolete FA Panels and
Concepts
AC Systemsz AC Systems
z Series Signals
z Obsolete Panels
FIRE
What is a Fire AlarmWhat is a Fire AlarmWhat is a Fire Alarm
FIRE
What is a Fire Alarm System?What is a Fire Alarm System?
n The main purpose of a fire alarm system is to protect lifen The main purpose of a fire alarm system is to protect life
and property by giving early warning of a fire, so that the
occupants can evacuate and/or the Fire Department can
respond.respond.
n A system must be able to detect the initiation of a fire
condition, but also notify someone such as emergencycondition, but also notify someone such as emergency
personnel, the ocupants of the facility, or both.
FIRE
Fire Alarm System ComponentsFire Alarm System Components
n Fire Alarm Control Panel (FACP)n Fire Alarm Control Panel (FACP)
n Initiating Devices
n Notification Appliances
n Emergency Control
n Supplementary Equipmentn Supplementary Equipment
FIRE
Logic/Control
Fire Alarm Control Panel
User Interface
Program
IDCs
Power
NACs
AUX
Relays
Fire Alarm Control Panel
BATT
Program
Distribution
Hardware /
Software
Power
Supply
City
Ckt
Relays
Ckt
120 VAC
FIRE
Fire Alarm Control Panel ComponentsFire Alarm Control Panel Components
n Control Unitn Control Unit
n Initiating Device Circuits (IDCs)
n Notification Appliance Circuits (NACs)
n Auxiliary Circuits
n Power Supplyn Power Supply
FIRE
Fire Alarm Control Panel
Logic/Control
User Interface
Program
IDC
SLC
NACs
AUX
Relays
Fire Alarm Control Panel
PowerPrimary Program
Distribution
Hardware /
Software City
Ckt
Relays
BATT
Power
Supply
Primary
Secondary Ckt
120 VAC
FIRE
Initiating DevicesInitiating DevicesInitiating Devices
FIRE
NFPA Fire Alarm CircuitsNFPA Fire Alarm Circuits
n The National Fire Protection Association (NFPA)n The National Fire Protection Association (NFPA)
classifies circuit Types and dictate their Performance
FIRE
NFPA Circuit TypesNFPA Circuit Types
n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC)
z A circuit to which automatic or manual initiating
devices are connected where the signal received doesdevices are connected where the signal received does
not identify the individual device operated
z “Zone”
FIRE
Outputs
Notification Appliances
Inputs
Initiating Devices
Fire Alarm Control Panel
Logic/Control Notification Appliances
and Emergency Controls
Initiating Devices
SMK DET Bells/Horns
User Interface
Program
IDCs
Power
NACs
AUX
Relays
Fire Alarm Control Panel
F
I
Manual Station
StrobePULLPULLPULLPULL
Simplex
BATT
Program
Distribution
Hardware /
Software
Power
Supply
City
Ckt
Relays
I
R
EWaterflow
Smoke Control
WF
Ckt
Sprinkler
Tamper
Door Holders
Simplex
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE 9
ZONE 10
ZONE 11
ZONE 12
Fire Department
CRT/KBD or
PC Interface
Annunciators
Printer120 VAC
FIRE
Initiating DevicesInitiating Devices
n Manual Stationsn Manual Stations
n Automatic Fire Detectors
z Heat Detectors
PULLPULLPULLPULL
Simplex
z Heat Detectors
z Smoke Detectors
z Flame (UV/IR) Detectorsz Flame (UV/IR) Detectors
z Gas Detectors
n Water Flown Water Flow
n Supervisory Switches
z Sprinkler Valve Tamper
WF
z Sprinkler Valve Tamper
z Tank Water Level
FIRE
How They Work - Contact DevicesHow They Work - Contact Devices
Normal State
FIRE
How They Work - Contact DevicesHow They Work - Contact Devices
Normal State Alarm State
FIRE
How They Work - Current Limited DevicesHow They Work - Current Limited Devices
Normal State
Electronics
FIRE
How They Work - Current Limited DevicesHow They Work - Current Limited Devices
Normal State Alarm State
Electronics Electronics
FIRE
NFPA Fire Alarm CircuitsNFPA Fire Alarm Circuits
n Two basic circuit Classes existed prior to 1993n Two basic circuit Classes existed prior to 1993
z Class B - Non-redundant
z Class A - Redundantz Class A - Redundant
n In 1993 NFPA introduced circuit Styles in order to clarify
the difference in circuit operation made available by newthe difference in circuit operation made available by new
hardware and software
FIRE
NFPA Wiring StylesNFPA Wiring Styles
n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC)
z Class B (Style B)
PULL DOWNPULL DOWNPULL DOWNPULL DOWN
BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS
FIREFIREFIREFIRE FIREFIREFIREFIRE
PULL DOWNPULL DOWNPULL DOWNPULL DOWN
BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS
FIREFIREFIREFIRE FIREFIREFIREFIRE
PULL DOWNPULL DOWNPULL DOWNPULL DOWN
BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS
FIREFIREFIREFIRE FIREFIREFIREFIRE
Simplex
PULL DOWNPULL DOWNPULL DOWNPULL DOWN
Simplex
PULL DOWNPULL DOWNPULL DOWNPULL DOWN
Simplex
PULL DOWNPULL DOWNPULL DOWNPULL DOWN
FIRE
CLASS B (Style B)
Normal Operation
IDC Module
+
_
Typical Normally Open
Device
2ND FLOOR NORTH HALLWAY
NORMAL
FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER
NORMAL
ALARM
ACK
ALARM
ACK
SUPV
ACK
TBL
ACK
ALARM
SILENCE
SYSTEM
RESET
ALARM ALARM SUPERVISORY TROUBLE SILENCED
ON
ACK ACK ACK ACK SILENCE RESET
ACKNOWLEDGE
Class B (Style B)Class B (Style B)
Alarm (SHORT) Operation
IDC Module
+
_
1ST FLOOR ELECTRICAL CLOSET ROOM 102
SMOKE DETECTOR ALARM
2ND FLOOR NORTH HALLWAY
ALARM
FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER
SMOKE DETECTOR ALARMALARM
ALARM
ACK
ALARM
ACK
SUPV
ACK
TBL
ACK
ALARM
SILENCE
SYSTEM
RESET
ALARM ALARM SUPERVISORY TROUBLE SILENCED
ON
ACK ACK ACK ACK SILENCE RESET
ACKNOWLEDGE
Class B (Style B)Class B (Style B)
Trouble (OPEN) Condition
IDC Module
+
_
Class B (Style B)
Trouble (OPEN) ConditionTrouble (OPEN) Condition
IDC Module
+
_
This device can not operate
1ST FLOOR ELECTRICAL CLOSET ROOM 102
SMOKE DETECTOR ALARM
2ND FLOOR NORTH HALLWAY
TROUBLE
FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER
SMOKE DETECTOR ALARMTROUBLE
ALARM
ACK
ALARM
ACK
SUPV
ACK
TBL
ACK
ALARM
SILENCE
SYSTEM
RESET
ALARM ALARM SUPERVISORY TROUBLE SILENCED
ON
ACK ACK ACK ACK SILENCE RESET
ACKNOWLEDGE
FIRE
NFPA Wiring StylesNFPA Wiring Styles
n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC)
z Class A (Style D)
FIREFIREFIREFIRE FIREFIREFIREFIRE FIREFIREFIREFIRE FIREFIREFIREFIREFIREFIREFIREFIRE FIREFIREFIREFIRE
Simplex
PULL DOWNPULL DOWNPULL DOWNPULL DOWN
BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS
Simplex
PULL DOWNPULL DOWNPULL DOWNPULL DOWN
BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS
Simplex
PULL DOWNPULL DOWNPULL DOWNPULL DOWN
BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS
Simplex SimplexSimplex
FIRE
Class A (Style D)Class A (Style D)
Normal Operation
IDC Module
+
_
Class A (Style D)Class A (Style D)
Alarm (SHORT) Operation
IDC Module
++
__
Class A (Style D)Class A (Style D)
Trouble (OPEN) Condition
IDC Module
++
*
__
*
* Contacts Close on* Contacts Close on
Trouble Condition
Class A (Style D)Class A (Style D)
Trouble & Alarm Condition
IDC Module
++
*
__
*
* Contacts Close on* Contacts Close on
Trouble Condition
FIRE
NFPA Wiring StylesNFPA Wiring Styles
n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC)
z Class B (Style B)
Smoke Detectors - 4 wireSmoke Detectors - 4 wire
Relay Base
Class B (Style B)
Normal OperationNormal Operation
Resetable +
R
_
R
E
L
A
Y
Power Circuit
IDC Zone
_
IDC Zone
++
_
Zone Circuit
Form C Aux Contacts
Class B (Style B)
Trouble ConditionTrouble Condition
Resetable +
R
_
R
E
L
A
Y
IDC Zone
_
IDC Zone
++
_
FIRE
NFPA Wiring StylesNFPA Wiring Styles
n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC)
z Class B (Style B)
Smoke Detectors - 2 wire (Current Limited)
Class B (Style B)Class B (Style B)
Normal Operation
IDC ModuleIDC Module
+
_
Form A Aux ContactsMicro−Relay
Class B (Style B)Class B (Style B)
Alarm Condition
IDC ModuleIDC Module
+
_
FIRE
Current Limited (2-wire) LimitationsCurrent Limited (2-wire) Limitations
n Fire alarm panels are designed to work with specificn Fire alarm panels are designed to work with specific
types of 2-wire Detectors
n There is a limitation to the Quantity of detectorsn There is a limitation to the Quantity of detectors
which can be placed on a single circuit
n Only auxiliary output function can be guaranteed on
a single circuit
Only auxiliary output function can be guaranteed on
a single circuit
Smoke Detectors - 2 wire (Current Limited)
FIRE
NFPA Wiring StylesNFPA Wiring Styles
n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC)
z Class B (Style B)
Sprinkler
Combination Circuits
Sprinkler
Tamper
WF
FIRE
This would cause a trouble signal
Old School
Not Allowed
This would cause a trouble signal
Must be a Supervisory signal
+
_
WFWF
Class B (Style B)
Normal ConditionNormal Condition
IDC Module
WF
IDC Module
+
_
Class B (Style B)
Valve Tamper ConditionValve Tamper Condition
IDC Module
WF
IDC Module
+
_
1ST FLOOR ELECTRICAL CLOSET ROOM 102
SMOKE DETECTOR ALARM
MAIN RISER - EAST ENTRANCE
FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER
SMOKE DETECTOR ALARMSUPERVTAMPER
ALARM
ACK
ALARM
ACK
SUPV
ACK
TBL
ACK
ALARM
SILENCE
SYSTEM
RESET
ALARM ALARM SUPERVISORY TROUBLE SILENCED
ON
ACK ACK ACK ACK SILENCE RESET
ACKNOWLEDGE
Class B (Style B)
Waterflow ConditionWaterflow Condition
IDC Module
WF
IDC Module
+
_
1ST FLOOR ELECTRICAL CLOSET ROOM 102
SMOKE DETECTOR ALARM
MAIN RISER - EAST ENTRANCE
FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER
SMOKE DETECTOR ALARMALARMWATERFLOW
ALARM
ACK
ALARM
ACK
SUPV
ACK
TBL
ACK
ALARM
SILENCE
SYSTEM
RESET
ALARM ALARM SUPERVISORY TROUBLE SILENCED
ON
ACK ACK ACK ACK SILENCE RESET
ACKNOWLEDGE
FIRE
+ Tamper Supervisory
_
+
Waterflow Alarm
WF_
Waterflow Alarm
_
FIRE
Notification AppliancesNotification AppliancesNotification Appliances
FIRE
NFPA Circuit TypesNFPA Circuit Types
n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC)
z A circuit or path directly connected to a notification
appliance(s)appliance(s)
FIRE
Outputs
Notification Appliances
Inputs
Initiating Devices
Fire Alarm Control Panel
Logic/Control Notification Appliances
and Emergency Controls
Initiating Devices
SMK DET Bells/Horns
User Interface
Program
IDCs
Power
NACs
AUX
Relays
Fire Alarm Control Panel
PULLPULLPULLPULL
Simplex
Manual Station
Strobe
F
I
BATT
Program
Distribution
Hardware /
Software
Power
Supply
City
Ckt
Relays
WF
Waterflow
Smoke Control
I
R
E
Ckt
Sprinkler
Tamper
Door Holders
Simplex
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE 9
ZONE 10
ZONE 11
ZONE 12
Fire Department
CRT/KBD or
PC Interface
Annunciators
Printer120 VAC
FIRE
Notification Appliances
n Audibles
Notification Appliances
n Audibles
z Horns
z Bells/Chimes
Speakersz Speakers
n Visuals
Xenon Strobesz Xenon Strobes
y Non-synchronized
y Synchronized
n Combination Devices
n Firefighter’s Telephones
FIRE
How They Work - DC DevicesHow They Work - DC Devices
(Horns, Bells, Strobes, etc.)
-Normal State -
+
- +
-
-
-
+
CCCCathode- -
+ ++
+
+
-
AAAAnode
+ -
FIRE
How They Work - DC Devices (Horns,How They Work - DC Devices (Horns,
Bells, Strobes, etc.)
+-Normal State
Supervisory Mode
Monitor Mode
Activated State
Alarm Mode
+-
Monitor Mode
-+
FIRE
How They Work - AC Devices (Speakers)How They Work - AC Devices (Speakers)
-Normal State -
+
- Current
- CCCCathode
-
- 0.000.000.000.00
24 VDC24 VDC24 VDC24 VDC +
-
24 VDC24 VDC24 VDC24 VDC
0.000.000.000.00
++ AAAAnode
+ EOL
Value
+
Resistance
0.00
Value
Resistance
-
- CCCCathode
-
24 VDC24 VDC24 VDC24 VDC
++ AAAAnode
++
Alarm Mode =Alarm Mode =Alarm Mode =Alarm Mode = Remove DC monitoring and Output Signal (AC)
Back to Basics
--
24 VDC24 VDC24 VDC24 VDC
++
Audio SignalAudio SignalAudio SignalAudio SignalAudio SignalAudio SignalAudio SignalAudio Signal
FIRE
How They Work - AC Devices (Speakers)How They Work - AC Devices (Speakers)
--Normal State
+
FIRE
How They Work - AC Devices (Speakers)How They Work - AC Devices (Speakers)
-Normal State Activated State AC-
AC+
FIRE
NFPA Wiring StylesNFPA Wiring Styles
n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC)
z Class B (Style Y)
FIRE
Class B (Style Y)
Normal OperationNormal Operation
NAC Module
_
++
2ND FLOOR NORTH HALLWAY
NORMALSIGNALS
FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER
NORMALSIGNALS
ALARM
ACK
ALARM
ACK
SUPV
ACK
TBL
ACK
ALARM
SILENCE
SYSTEM
RESET
ALARM ALARM SUPERVISORY TROUBLE SILENCED
ON
ACK ACK ACK ACK SILENCE RESET
ACKNOWLEDGE
Class B (Style Y)
Alarm ConditionAlarm Condition
NAC Module
+
__
Class B (Style Y)
Trouble ConditionTrouble Condition
NAC Module
_
++
This device can not operate
1ST FLOOR ELECTRICAL CLOSET ROOM 102
SMOKE DETECTOR ALARM
2ND FLOOR NORTH HALLWAY
TROUBLESIGNALS
FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER
SMOKE DETECTOR ALARMTROUBLESIGNALS
ALARM
ACK
ALARM
ACK
SUPV
ACK
TBL
ACK
ALARM
SILENCE
SYSTEM
RESET
ALARM ALARM SUPERVISORY TROUBLE SILENCED
ON
ACK ACK ACK ACK SILENCE RESET
ACKNOWLEDGE
Class B (Style Y)
Alarm ConditionAlarm Condition
NAC Module
+
__
FIRE
NFPA Wiring StylesNFPA Wiring Styles
n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC)
z Class A (Style Z)
FIRE
Class A (Style Z)
Normal OperationNormal Operation
NAC Module
_
++
Class A (Style Z)
Alarm ConditionAlarm Condition
NAC Module
+
*
__
*
* Contacts Close on
Alarm Condition
Class A (Style Z)
Trouble ConditionTrouble Condition
NAC Module
_
++
Class A (Style Z)
Trouble & Alarm ConditionTrouble & Alarm Condition
NAC Module
+
*
__
*
* Contacts Close on
Alarm Condition
FIRE
Phone Circuit
+
Phone JackPhone JackPhone JackPhone Jack
5k EOL5k EOL5k EOL5k EOL
_
5k EOL5k EOL5k EOL5k EOL
300300300300
_
5k EOL = Normal5k EOL = Normal
300 = Phone plugged in
Open = Trouble
Short = TroubleShort = Trouble
GF = Trouble
FIRE
Signaling LinesSignaling LinesSignaling Lines
FIRE
NFPA Circuit TypesNFPA Circuit Types
n Signaling Line Circuits (SLC)n Signaling Line Circuits (SLC)
z A circuit or path between any combination of circuit
interfaces, control units, or transmitters over whichinterfaces, control units, or transmitters over which
multiple system input signals or output signals, or
both are carried
FIRE
NFPA Wiring StylesNFPA Wiring Styles
n Signaling Line Circuits (SLC)n Signaling Line Circuits (SLC)
z Class B (Style 4)
FIRE
Addressable Systems
Class B (Style 4)
Normal OperationAddressable SystemsNormal Operation
Control Panel Interrogation
101 102 103 104
101 What is your status?
FACP MemoryFACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Addressable Systems
Class B (Style 4)
Normal OperationAddressable SystemsNormal Operation
101 102 103 104
FACP Memory
101 Status: Normal
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Device Response
Addressable Systems
Class B (Style 4)
Normal OperationAddressable SystemsNormal Operation
Control Panel Interrogation
101 102 103 104
FACP Memory
102 What is your status?
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Addressable Systems
Class B (Style 4)
Normal OperationAddressable SystemsNormal Operation
101 102 103 104
FACP MemoryFACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
102 Status: Alarm
Device Response
Addressable Systems
Class B (Style 4)
Normal OperationAddressable SystemsNormal Operation
Control Panel Interrogation
101 102 103 104
FACP Memory
103 What is your status?
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Addressable Systems
Class B (Style 4)
Normal OperationAddressable SystemsNormal Operation
101 102 103 104
FACP Memory
103 Status: Trouble
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Device Response
Addressable Systems
Class B (Style 4)
Normal OperationAddressable SystemsNormal Operation
Control Panel Interrogation
101 102 103 104
FACP Memory
104 What is your status?
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Addressable Systems
Class B (Style 4)
Normal OperationAddressable SystemsNormal Operation
101 102 103 104
FACP MemoryFACP Memory
101 Normal
102 Alarm
103 Trouble
104 Normal
104 Status: Normal
Device Response
Addressable Systems
Class B (Style 4)
Trouble ConditionAddressable SystemsTrouble Condition
Control Panel Interrogation
101
101 What is your status?
FACP Memory
102 103 104
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Addressable Systems
Class B (Style 4)
Trouble ConditionAddressable SystemsTrouble Condition
101
FACP Memory
102 103 104
101 Status: Normal
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Device Response
Addressable Systems
Class B (Style 4)
Trouble ConditionAddressable SystemsTrouble Condition
Control Panel Interrogation
101
FACP Memory
102 103 104
102 What is your status?
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Addressable Systems
Class B (Style 4)
Trouble ConditionAddressable SystemsTrouble Condition
101
FACP Memory
102 103 104
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
102 Status: Alarm
Device Response
Addressable Systems
Class B (Style 4)
Trouble ConditionAddressable SystemsTrouble Condition
Control Panel Interrogation
101
FACP Memory
102 103 104
103 What is your status?
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Addressable Systems
Class B (Style 4)
Trouble ConditionAddressable SystemsTrouble Condition
101
FACP Memory
102 103 104
FACP Memory
101 Normal
102 Alarm
103 No Answer
104 Trouble
Device Response
Addressable Systems
Class B (Style 4)
Trouble ConditionAddressable SystemsTrouble Condition
Control Panel Interrogation
101
FACP Memory
102 103 104
104 What is your status?
FACP Memory
101 Normal
102 Alarm
103 No Answer
104 Trouble
Addressable Systems
Class B (Style 4)
Trouble ConditionAddressable SystemsTrouble Condition
101 102
FACP Memory
102 103 104
FACP Memory
101 Normal
102 Alarm
103 No Answer
104 No Answer
Device Response
FIRE
NFPA Wiring StylesNFPA Wiring Styles
n Signaling Line Circuits (SLC)n Signaling Line Circuits (SLC)
z Class A (Style 6)
FIRE
Addressable Systems
Class A (Style 6)
Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN
Control Panel Interrogation
101 102 103 104
101 What is your status?
FACP MemoryFACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Addressable Systems
Class A (Style 6)
Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN
101 102 103 104
FACP Memory
101 Status: Normal
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Device Response
Addressable Systems
Class A (Style 6)
Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN
Control Panel Interrogation
101 102 103 104
FACP Memory
102 What is your status?
FACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Addressable Systems
Class A (Style 6)
Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN
101 102 103 104
FACP MemoryFACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
102 Status: Alarm
Device Response
Addressable Systems
Class A (Style 6)
Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN
Control Panel Interrogation
101 102 103 104
FACP MemoryFACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
103 What is your status?
Addressable Systems
Class A (Style 6)
Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN
101 102 103 104
FACP MemoryFACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
Device Response
103 Status: Trouble
Addressable Systems
Class A (Style 6)
Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN
Control Panel Interrogation
101 102 103 104
FACP MemoryFACP Memory
101 Normal
102 Alarm
103 Trouble
104 Trouble
104 What is your status?
Addressable Systems
Class A (Style 6)
Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN
101 102 103 104
FACP MemoryFACP Memory
101 Normal
102 Alarm
103 Trouble
104 Normal
Device Response
104 Status: Normal
Addressable Systems
Class A (Style 6)
Trouble Condition - SHORTAddressable SystemsTrouble Condition - SHORT
101 102 103 104
FACP MemoryFACP Memory
101 No Answer
102 No Answer
103 No Answer
104 No Answer SLC FailureSLC Failure
Catastrophic FailureCatastrophic Failure
FIRE
FIRE
Style 7 (Class A) Network
Signalling Line Circuit, Normal Operation
FIRE
Token
Style 7 (Class A) Network
Signalling Line Circuit, Normal Operation
FIRE
Token
Style 7 (Class A) NetworkStyle 7 (Class A) Network
Signalling Line Circuit, Operation With a Single Short or
Open
FIRE
TokenToken
Token
Style 7 (Class A) Network
Signalling Line Circuit, Operation with Multiple Shorts
or Opens
MODULESMODULES
n MONITORn MONITOR
n RELAY
n SIGNAL
n MONITORn MONITOR
n Relay Module,n Relay Module,
z Control Module, Control ZAM
n Signaln Signal
Module
n Signaln Signal
FIRE
n MONITORn MONITOR
FIRE
n MONITORn MONITOR
n MONITORn MONITOR
FIRE
Addressable Devices - IAMAddressable Devices - IAM
n Individual Addressable Modulen Individual Addressable Module
z Addressable Station
z Addressable Basez Addressable Base
y Photo
y Ionization
y Heat
z Supervised IAM
y Monitors a single conventional contact devicey Monitors a single conventional contact device
z IAM Relay (ID Net only)
Obtains operating power from SLCn Obtains operating power from SLC
Supervised IAM
SLC
+
_
Typical Normally Open
Device
FIRE
Addressable Devices - ZAMAddressable Devices - ZAM
n Zone Addressable Modulen Zone Addressable Module
z Interfaces with a Zone of Conventional Devices
z Monitoring Devicesz Monitoring Devices
y Class B Monitor ZAM
y Class A Monitor ZAM
y 4-Wire Monitor ZAM
z Control Devices
y Unsupervised Control ZAMy Unsupervised Control ZAM
y Supervised Signal ZAM
n Obtains operating power from a separate sourcen Obtains operating power from a separate source
Class B Monitor ZAM
+
_
+
Operating
Power
SLC
_
+
_
Class A Monitor ZAM
+
_
+
Operating
Power
SLC
_
+
_
4-Wire Monitor ZAM
R
++ R
E
L
A
Y
Resetable
Power
_
+
_
+
Operating
Power
SLC
__
++
_
Control ZAM
+ Normally
_
+
Operating
Power
Normally
Open
Normally
Closed
SLC
_ Closed
1 Relay
Normally
Open
1 Relay
Open
Normally
Closed
Signal ZAM
+
_
+
Operating
Power
SLC
_
_
+
SIGNAL
Power
+
INTELLIGENT DEVICESINTELLIGENT DEVICES
MODULESMODULES
n MONITORn MONITOR
n RELAY
n SIGNAL
Single Input Contact Module
SIGA-CT1SIGA-CT1
n Four Assignable Personalities
z Alarm, Supervisory, Waterflow
(delayed latching retard),
MonitorMonitor
n 1-gang Mount
Dual Input Contact Module
SIGA-CT2SIGA-CT2
n Four Separate Assignable
Personalities to Each InputPersonalities to Each Input
z Alarm, Supervisory, Waterflow
(delayed latching retard),(delayed latching retard),
Monitor
n 1-gang Mountn 1-gang Mount
Monitor ModuleMonitor Module
SIGA-MM1
n Factory Pre-loaded Monitorn Factory Pre-loaded Monitor
Function
z Saves installation timez Saves installation time
n 1-gang Mount
Waterflow/Tamper ModuleWaterflow/Tamper Module
SIGA-WTMSIGA-WTM
n Factory Pre-loaded Waterflown Factory Pre-loaded Waterflow
(16 second delayed latching
retard) and Supervisory Input
z Saves installation time
n 1-gang Mountn 1-gang Mount
Single Circuit Control Module
SIGA-CC1SIGA-CC1
n Single Riser Select
n Switch Signal Riser
z 2 amps @ 24 Vdc
n Two Assignable
Personalities
z 2 amps @ 24 Vdc
z 50 watts @ 25 Vaudio
35 watts @ 70Vaudio
Personalities
n Switch Telphone Riser
z Built-in RING TONE
z 35 watts @ 70Vaudio
z Built-in RING TONE
generator for fire
phones
n 2-gang Mount
Dual Circuit Control ModuleDual Circuit Control Module
SIGA-CC2
Dual Riser Selectn Dual Riser Select
n Select Signal Risern Select Signal Riser
z 2 amps @ 24 Vdc
z 50 watts @ 25 Vaudioz 50 watts @ 25 Vaudio
z 35 watts @ 70Vaudio
n 2-gang Mount
Control RelayControl Relay
SIGA-CR
Form “C” NO or NC Contactn Form “C” NO or NC Contact
z 0.5 amps @ 220 Vac (non UL)
z 0.5 amps @ 120 Vac
z 2 amps (pilot duty) @ 24 Vdc
z 50 watts @ 25 Vaudio
z 35 watts @ 70 Vaudioz 35 watts @ 70 Vaudio
n 1-gang Mount
Universal Class A/B Module
15 Assignable Personalities15 Assignable Personalities
z Two Class B or one Class A
Initiating Device Circuits
SIGA-UM
Initiating Device Circuits
z One Class A or B Indicating
Appliance Circuit
z One Class A or B Smoke
Detector Circuit (2-wire verified
or non-verified)or non-verified)
z One Form “C” Dry Contact Relay
FIRE
Emergency ControlsEmergency ControlsEmergency Controls
FIRE
Outputs
Notification Appliances
Inputs
Initiating Devices
Fire Alarm Control Panel
Logic/Control Notification Appliances
and Emergency Controls
Initiating Devices
SMK DET Bells/Horns
User Interface
Program
IDCs
Power
NACs
AUX
Relays
Fire Alarm Control Panel
F
I
PULLPULLPULLPULL
Simplex
Manual Station
Strobe
BATT
Program
Distribution
Hardware /
Software
Power
Supply
City
Ckt
Relays
I
R
E
WF
Waterflow
Smoke Control
Ckt
Sprinkler
Tamper
Door Holders
Simplex
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE 9
ZONE 10
ZONE 11
ZONE 12
Fire Department
CRT/KBD or
PC Interface
Annunciators
Printer120 VAC
FIRE
Emergency Controls (Outputs)Emergency Controls (Outputs)
n Supervisedn Supervised
z City Connection
z UUKL Smoke Controlz UUKL Smoke Control
n Unsupervised
z Door Control (Holders & Locks)
z Smoke (Fan & Damper) Control
z Elevator Recall
z Emergency Lighting Control
FIRE
City ConnectionsCity ConnectionsCity Connections
Contact DACTContact DACT
FIRE
Conventional
Contact
Monitoring
DACTDACT
FIRE
Conventional
Contact
Monitoring
DACTDACT
FIRE
Conventional
Contact
Monitoring
DACTDACT
FIRE
Conventional
Contact
Monitoring
DACTDACT
FIRE
“ABC CORPORATION ALARM”“ABC CORPORATION ALARM”
Conventional
Contact
Monitoring
DACTDACT
FIRE
City ConnectionsCity ConnectionsCity Connections
Serial DACTSerial DACT
FIRE
SERIAL
DACT
FIRE
SERIAL
DACT
FIRE
SERIAL
DACT
FIRE
SERIAL
DACT
FIRE
“ABC CORPORATION
SMOKE DETECTOR ALARMSMOKE DETECTOR ALARM
THIRD FLOOR EAST STORAGE CLOSET”
SERIAL
DACT
FIRE
SupplementarySupplementarySupplementary
EquipmentEquipment
FIRE
Outputs
Notification Appliances
Inputs
Initiating Devices
Fire Alarm Control Panel
Logic/Control Notification Appliances
and Emergency Controls
Initiating Devices
SMK DET Bells/Horns
User Interface
Program
IDCs
Power
NACs
AUX
Relays
Fire Alarm Control Panel
F
I
PULLPULLPULLPULL
Simplex
Manual Station
Strobe
BATT
Program
Distribution
Hardware /
Software
Power
Supply
City
Ckt
Relays
I
R
E
WF
Waterflow
Smoke Control
Ckt
Sprinkler
Tamper
Door Holders
Fire Department
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE 9
ZONE 10
ZONE 11
ZONE 12
Simplex
CRT/KBD or
PC Interface
Annunciators
Printer120 VAC
FIRE
Supplementary Equipment - AnnunciatorsSupplementary Equipment - Annunciators
n Graphic or Directory Lamp Annunciators
ZONE 1 ZONE 5 ZONE 9
n Graphic or Directory Lamp Annunciators
n Computer Based Graphic Systems
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE 9
ZONE 10
ZONE 11
ZONE 12
n Text-based CRTs Simplex
n Text-based Printers
FIRE
Basic AnnunciatorsBasic Annunciators
n Hardwiredn Hardwired
z One Wire and Common per Point
ZONE 1 ZONE 5 ZONE 9
Simplex
ZONE 2
ZONE 3
ZONE 4
ZONE 6
ZONE 7
ZONE 8
ZONE 10
ZONE 11
ZONE 12
FIRE ALARM CONTROL
FIRE
Basic AnnunciatorsBasic Annunciators
n Serial Annunciatorn Serial Annunciator
z Twisted/Sheilded Wiring (Communications)
z Powerz Power
y 120 VAC
y 24 VDC
Simplex
ZONE 1 ZONE 5 ZONE 9
FIRE ALARM CONTROL
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE 9
ZONE 10
ZONE 11
ZONE 12
FIRE ALARM CONTROL
FIRE
Basic AnnunciatorsBasic Annunciators
n CRTs, Printers, PC Based Graphicsn CRTs, Printers, PC Based Graphics
z Twisted/Sheilded Wiring (Communications)
z Powerz Power
y 120 VAC
y 24 VDC
Simplex
FIRE ALARM CONTROL
120 VAC
FIRE ALARM CONTROL
FIRE
BasicBasicBasic
PeripherialsPeripherials
FIRE
Peripherals - Manual DevicesPeripherals - Manual Devices
n Manual Stationsn Manual Stations
z Conventional & Addressable
z Single or Double Actionz Single or Double Action
z Standard material - Lexan (Plastic)
y Limited choice of Metal models availabley Limited choice of Metal models available
n Valve Tamper
z Typically Supplied by Othersz Typically Supplied by Others
FIRE
Peripherals - Automatic DevicesPeripherals - Automatic Devices
n Smoke Detectorsn Smoke Detectors
z Photoelectric
z Ionizationz Ionization
z Beam
z Air Aspiration (VESDA)
z Ductz Duct
n Heat
Fixedz Fixed
z Rate-of-Rise
z Combinationz Combination
z Rate Compensated
FIRE
Peripherals - Automatic DevicesPeripherals - Automatic Devices
n Waterflown Waterflow
z Typically supplied by others
n Flame Detectors
FIRE
Peripherals - Audible AppliancesPeripherals - Audible Appliances
n Hornsn Horns
n Bells
n Chimes
n Speakers
z 25 VRMS
z 70 VRMS
FIRE
Peripherals - Visual AppliancesPeripherals - Visual Appliances
n XENONn XENON
y 15 cd
y 30 cd
y 110 cd
n Combined with Audible (AV)n Combined with Audible (AV)
n Synchronized Option
z Requires a “Sync Cube”z Requires a “Sync Cube”
FIRE
Miscellaneous DevicesMiscellaneous Devices
n Door Holdersn Door Holders
z Watch Voltage Requirements
y 24 volt units require Power Suppliesy 24 volt units require Power Supplies
n Relays
n Firefighter Phones
z Jacksz Jacks
z Emergency Phones in Cabinet
FIRE
How to Wire aHow to Wire aHow to Wire a
BuildingBuilding
IDC Module
+
IDC Module
+
_
Right
IDC Module
+
IDC Module
+
_
Wrong
IDC Module
+
IDC Module
+
_
Right
IDC Module
+
IDC Module
+
_
Right
NAC ModuleNAC Module
+
_
FIRE
PROPER WIRING TERMINATIONSPROPER WIRING TERMINATIONS
FOR HARDWIRED CIRCUITS
Conductors must be broken at each
device termination (Incoming &device termination (Incoming &
Outgoing conductors must not be
twisted together or left as a continuoustwisted together or left as a continuous
wire)
No T-Taps
FIRE
Pg. 72-99
Annex GAnnex G
FIRE
FIRE
ShieldingShielding
Most digital communication ckts require a twisted
shielded pair (TSP) of wires. Shielding usually
consist of a foil shield and a drain wire which is inconsist of a foil shield and a drain wire which is in
continuous contact with the foil. Shielding prevents
cross-talk between other circuits run next to the cable,cross-talk between other circuits run next to the cable,
shields against EMI or RFI noise or interference that
could be induced from the surroundings and helps tocould be induced from the surroundings and helps to
prevent the shielded circuit from emitting noise that
could interfere with other circuits.
FIRE
ShieldingShielding
1. When joints or connections are made, as little of the
cable as possible should be stripped back so that only a
small amount of the wiringwill be unshielded.small amount of the wiringwill be unshielded.
The shield must be continuous throughout the ckt. In2. The shield must be continuous throughout the ckt. In
other words, the drain(shield) wires must be tied together
with a good mechanical bond at every cable joint orwith a good mechanical bond at every cable joint or
splice.
FIRE
Shielding
1. The shield MUST be isolated from ground throughout
the ckt. Usually this is done with electrical tape but it may
be done with heat shrink. The shield is only tied to abe done with heat shrink. The shield is only tied to a
signal ground at one point (usually at the control panel).
This signal ground is sometimes earth ground and
sometimes 0V or system common.sometimes 0V or system common.
. Grounds at more than one point on the shield
can cause ground loops. This may create more
noise than having no shield at all.
FIRE
National Electrical Code (NEC)National Electrical Code (NEC)
n 1993 Editionn 1993 Edition
n Article 760 Fire Protective Signaling Circuits
z Scope & General 760-1 to 760-7
z Nonpower-Limited 760-11 to 760-18
z Power Limited 760-21 to 760-53
FIRE
Power Limited CircuitsPower Limited Circuits
n Operate between 20 VDC and 250 VDCn Operate between 20 VDC and 250 VDC
z Circuits are limited to 100 Volt-Amperes (VA)
n Power limiting is accomplished by use of proper power
source
A power limited source can be:n A power limited source can be:
z A circuit breaker or fuse if:
y The overcurrent device is not interchangeable with highery The overcurrent device is not interchangeable with higher
rated device
y The overcurrent device is located where the conductor to be
protected receives its supply
z An inherently limited power supply
y No output power is provided if the output is shorted
FIRE
Power Limited Control PanelsPower Limited Control Panels
n Circuit Marking (NEC 760-22):n Circuit Marking (NEC 760-22):
z The equipment shall be durably marked where plainly
visible to indicate each circuit that is a power-limited circuit.visible to indicate each circuit that is a power-limited circuit.
n If the circuits are not marked “Power Limited”, the system
must be considered Non-Power Limited.must be considered Non-Power Limited.
FIRE
Power Limited vs. Non-Power LimitedPower Limited vs. Non-Power Limited
(Exposed Wiring)
Power Limited Non-Power LimitedPower Limited
n Single conductors are allowed
(Table 760-51)
Non-Power Limited
n 2 conductors minimum
(760-17(c)(2)
n Minimum conductor size in
cable
z #26 AWG (Table 760-51)
n Minimum conductor size in
cable:
z #18AWGz #26 AWG (Table 760-51)
n FPLP Cable Installation
z Plenums
z #18AWG
n NPLFP Cable Installation
z Other spaces used forz Plenums
z DUCTs
z Other spaces used for
environmental air
z Other spaces used for
environmental air
n No cable substitutions are
allowedenvironmental air
n Cable substitutions are allowed
(Table 760-53)
allowed
FIRE
Fire Protective Signaling CablesFire Protective Signaling Cables
Non-power limited cablesn Non-power limited cables
z NEC 760 - 17(c) (4, 5, & 6)
n Power limited cables
z NEC 760 - 51(d, e, & f)
Power Non-Power
Application Limited Limited
General Use FPL NPLF
Riser (Vertical Runs) FPLR NPLFR
Plenum or DUCT [NEC 300-22(b)] FPLP Use conduit
Other spaces used to transport Environmental air [NEC 300-22(c)] FPLP NPLFP
FIRE
Wiring ConsiderationsWiring Considerations
Voltage Drop & DistancesVoltage Drop & Distances
FIRE
Wire Distance LimitationsWire Distance Limitations
n Initiating Device Circuits:#14 = 3.07 / 1000 Feetn Initiating Device Circuits:
z 8 Zone Monitor modules - Class B (Style B)
y 10,000 feet or 50 ohms, whichever comes first
#14 = 3.07 / 1000 Feet
50 / 3.07 = 16.3
16.3 x 1000 = 16300y 10,000 feet or 50 ohms, whichever comes first
y 2-wire smoke detector circuits: 50 ohms max. line resistance
y Dry contact only circuits: 800 ohms max. line resistance
8 Zone Monitor Modules - Class A (Style D)
16.3 x 1000 = 16300
16300 / 2 = 8150 Ckt Length
z 8 Zone Monitor Modules - Class A (Style D)
y 10,000 feet from module and back to the module or 50 ohms,
whichever comes first (5,000 feet to furthest device)
FIRE
Wire Distance LimitationsWire Distance Limitations
n Monitor Zone Addressable Module (ZAM)n Monitor Zone Addressable Module (ZAM)
z Class B (Style B)
y 2,000 feet or 10 ohms, whichever comes firsty 2,000 feet or 10 ohms, whichever comes first
z Class A (Style D)
y 2,000 feet or 10 ohms, whichever comes first, from ZAM
terminals and back to the ZAM terminalsterminals and back to the ZAM terminals
y 2000 feet from module and back to the module or 10 ohms,
whichever comes first (1,000 feet to furthest device)
n Wire Guage
z 18 AWG minimumz 18 AWG minimum
z 12 AWG maximum
FIRE
Wire Distance LimitationsWire Distance Limitations
n MAPNET & IDNetn MAPNET & IDNet
z Class B (Style 4)
y 10,000 feet maximum of all wire runs including:y 10,000 feet maximum of all wire runs including:
y All T-taps
y Parallel runs
y For each continuous run:y For each continuous run:
y 2,500 feet for up to 250 IDNet devices
y 2,500 feet for up to 128 MAPNET devices
3,000 feet for up to 96 MAPNET devicesy 3,000 feet for up to 96 MAPNET devices
y 4,000 feet for up to 64 MAPNET devices
y When run exceeds 2,500 feet twisted shielded wiring is
required.required.
FIRE
Wire Distance LimitationsWire Distance Limitations
n MAPNETn MAPNET
z Class A (Style 6)
y No T-tapping is allowedy No T-tapping is allowed
y For each continuous run from FACP and back:
y 2,500 feet for up to 128 MAPNET devices
y 1250 feet to furthest devicey 1250 feet to furthest device
y 3,000 feet for up to 96 MAPNET devices
y 1500 feet to furthest device
4,000 feet for up to 64 MAPNET devicesy 4,000 feet for up to 64 MAPNET devices
y 2000 feet to furthest device
y When run exceeds 2,500 feet twisted shielded wiring is
required.required.
FIRE
Wire Distance LimitationsWire Distance Limitations
n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC)
z Audibles & Visuals
MaximumMaximum
Circuit Line Maximum distance (feet)
Current Resistance (2 conductor cable)
(amps) (Ω) 18AWG 16AWG 14AWG 12AWG
0.250 10.8 845 1340 2138 3400
0.500 5.4 420 670 1065 1700
0.750 3.6 280 445 710 1130
1.000 2.7 210 335 530 8501.000 2.7 210 335 530 850
1.250 2.16 165 265 425 680
1.500 1.8 140 220 350 565
1.750 1.54 120 190 300 480
2.000 1.35 105 165 265 4252.000 1.35 105 165 265 425
FIRE
Wire Distance LimitationsWire Distance Limitations
n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC)
z Speakers
z 25 VRMSz 25 VRMS
Maximum Distance (feet)
25VRMS POWER (Twisted Pair Wire)25VRMS POWER (Twisted Pair Wire)
APPLIED 18AWG 16AWG 14AWG 12AWG
50W 400 680 1021 1624
40W 505 804 1279 2033
30W 673 1070 1704 2707
20W 1011 1608 2558 4067
10W 2024 3219 5120 8140
FIRE
Wire Distance LimitationsWire Distance Limitations
n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC)
z Speakers
z 70 VRMSz 70 VRMS
Maximum Distance (feet)
70VRMS POWER (Twisted Pair Wire)
APPLIED 18AWG 16AWG 14AWG 12AWG
100W 1620 2577 4098 6500100W 1620 2577 4098 6500
80W 2020 3212 5108 8121
70W 2317 3685 5860 9318
60W 2700 4276 6800 10860
50W 3241 5154 8197 1300050W 3241 5154 8197 13000
40W 4040 6424 10216 16243
30W 5379 8553 13602 21721
20W 8065 12823 20394 32424
10W 16000 25000 40000 6480010W 16000 25000 40000 64800
FIRE
FIRE
Old StuffOld StuffOld Stuff
FIRE
Series Notification Circuits (AC)Series Notification Circuits (AC)
n Works like inexpensive Christmas lights…n Works like inexpensive Christmas lights…
One fails, they all fail
z 120 VACz 120 VAC
y Horns, Bells, Chimes
z 300+ Volt Audio
y Speakers
n All devices must be replaced when
upgrading system
All devices must be replaced when
upgrading system
FIRE
Series Notification Circuits (AC)Series Notification Circuits (AC)
(Normal Condition)
120
VACVAC
NEUT
Trouble Monitor
Circuit
FIRE
Series Notification Circuits (AC)Series Notification Circuits (AC)
(Normal Condition)
120
VACVAC
NEUT
Trouble Monitor
Circuit
Series AC
NAC ModuleNAC Module
Right
NAC ModuleNAC Module
+
_
Need Additional Wiring
FIRE
4246/4247 AC FACP4246/4247 AC FACP
FIRE
4246/4247 AC FACP4246/4247 AC FACP
n Introduced ??????n Introduced ??????
n All Peripherals operate on 120 VAC
z No Standby Batteries
n ONE IDCn ONE IDC
n 2- Series Wired NACs
z Built in groups of 2z Built in groups of 2
n Boxes not compatible with and current
panelspanels
FIRE
4208 Hardwired FACP4208 Hardwired FACP
n Introduced in early 1970sn Introduced in early 1970s
n First Multi-zone FACP
n Not Programmable
n MOST features duplicated in 4XXX series panels
z Watch for AC Series NACs
n Boxes not compatible with and current panels
FIRE
4207 Hardwired FACP4207 Hardwired FACP
n Introduced in 1974n Introduced in 1974
n Transistor based replacment for the 4208
n Not Programmable
n MOST features duplicated in 4XXX series panels
z Watch for AC Series NACs
n Boxes not compatible with and current panels
FIRE
2001 Hardwired FACP2001 Hardwired FACP
FIRE
2001 Hardwired FACP2001 Hardwired FACP
n Introduced in late 1978n Introduced in late 1978
z Workhorse FACP for 15 yrs!
n Modular-based replacement of 4207
n Sometimes packaged with 2100 & 2120 Multiplexn Sometimes packaged with 2100 & 2120 Multiplex
Systems
n Not Programmable
n MOST features duplicated in 4XXX series panels
z Watch for AC Series NACs
n 2, 4, & 6 unit Boxes not compatible with 4XXX series
panels

More Related Content

PPT
fire detection and alarm system
PPT
1 Fire safety design principles
PPTX
Fundamentals of Fire Alarm System
PPTX
السلامة.pptx
PPTX
Fire alarm system and common types of detectors
PPT
Much many little few
PPT
BS 9999 Fire Engineering
PPTX
HZOP-HAZID Presentation by Tony
fire detection and alarm system
1 Fire safety design principles
Fundamentals of Fire Alarm System
السلامة.pptx
Fire alarm system and common types of detectors
Much many little few
BS 9999 Fire Engineering
HZOP-HAZID Presentation by Tony

What's hot (20)

PDF
Fire Alarm System, BMS
PPTX
Fire detection and alarm system
PPTX
Fire Detection and Alarm Systems
PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
PPT
Fire alarm systems
PDF
Fire alarm systems
PDF
Water spray system
PPTX
Fire alarm system Research
PDF
Fundamental training on Fire Detection & Alarm System
PDF
Basic fire alarm training (1)
PPTX
Building lightning protection for Metro Railway
PPT
Intro to basic fire alarm technology
PPT
Carbon dioxide fire suppression
PPTX
Clean Agent & Inert Gas Fire Suppression
PPTX
Functioning of a Fire alarm panel
PPTX
Fire alarm , detection and suppression system
PDF
Introductory training on fire water pumping system
PPTX
FIRE ALARM SYSTEM
PPTX
Fire Protection System - Automatic Fire Detectors
PPTX
Fire fighting
Fire Alarm System, BMS
Fire detection and alarm system
Fire Detection and Alarm Systems
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
Fire alarm systems
Fire alarm systems
Water spray system
Fire alarm system Research
Fundamental training on Fire Detection & Alarm System
Basic fire alarm training (1)
Building lightning protection for Metro Railway
Intro to basic fire alarm technology
Carbon dioxide fire suppression
Clean Agent & Inert Gas Fire Suppression
Functioning of a Fire alarm panel
Fire alarm , detection and suppression system
Introductory training on fire water pumping system
FIRE ALARM SYSTEM
Fire Protection System - Automatic Fire Detectors
Fire fighting
Ad

Viewers also liked (16)

PPT
Fire alarm
PPTX
Fire Alarm, Smoke Detector and Automatic Sprinkle System
PPT
PPT
Fire detection & alarm system
PPT
Chapter 07
PPT
Basic Fire Alarm Systems
PPT
Fire alarm system
PPTX
Somke detector project presentation
PDF
PDF
Forex Autopilot
PDF
Fire alarm using thermistor
PDF
Mini 2 zones Conventional Fire Alarm Control Panel
PPT
Chapter 08
PDF
FIRE DETECTION SENSOR
DOCX
Dissertation report 2_3
PDF
Access control-installation
Fire alarm
Fire Alarm, Smoke Detector and Automatic Sprinkle System
Fire detection & alarm system
Chapter 07
Basic Fire Alarm Systems
Fire alarm system
Somke detector project presentation
Forex Autopilot
Fire alarm using thermistor
Mini 2 zones Conventional Fire Alarm Control Panel
Chapter 08
FIRE DETECTION SENSOR
Dissertation report 2_3
Access control-installation
Ad

Similar to Back to Basics (20)

PDF
main_complete catalogue_en
PDF
Product solution_compressed.pdf
PDF
Dn 6724
PDF
Edwards Signaling EGCFVMH Installation Manual
PPS
Apt 3rd Edition Presentation
 
PDF
Edwards Signaling CS405-7A-T Installation Manual
PDF
Bussmann By Eaton - Surge Protection Devices Catalogue
PDF
Edwards Signaling LKC-1 Data Sheet
PPTX
THREE PHASE TRANSMISSION LINE FAULT DETECTION.pptx
PDF
NCM-W_Manual.pdf
PDF
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
PDF
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
PDF
Edwards Signaling G4WA-S7VMC Data Sheet
PDF
Power amplifier (1)
PPTX
FIRE DETECTION AND ALARM SYSTEM_FUNCTIONALITY.pptx
PDF
Horn with Strobe 49AV-WRF.pdf
PDF
Surge Protection
PPT
NFS2-640
main_complete catalogue_en
Product solution_compressed.pdf
Dn 6724
Edwards Signaling EGCFVMH Installation Manual
Apt 3rd Edition Presentation
 
Edwards Signaling CS405-7A-T Installation Manual
Bussmann By Eaton - Surge Protection Devices Catalogue
Edwards Signaling LKC-1 Data Sheet
THREE PHASE TRANSMISSION LINE FAULT DETECTION.pptx
NCM-W_Manual.pdf
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Edwards Signaling G4WA-S7VMC Data Sheet
Power amplifier (1)
FIRE DETECTION AND ALARM SYSTEM_FUNCTIONALITY.pptx
Horn with Strobe 49AV-WRF.pdf
Surge Protection
NFS2-640

More from michaeljmack (20)

PDF
Auburn, NY - 200 Years of History 1793-1993
PDF
Auburn High School, Auburn, NY, 1982 Yearbook
PDF
Auburn High School, Auburn, NY, 1980 Yearbook
PDF
Diesel Particulate Filters Control Systems
PDF
Understanding Arc Flash
PDF
Siemens MV GIS Switchgear
PDF
Fundamentals of transformer inrush
PDF
Building information modeling
PDF
15 years of experience stator ground fault protection
PPT
Emergency, Legally Required and Optional Standby Systems
PDF
Lighting Control Solutions for Daylit Spaces
PDF
COPS: An Arresting Look at NEC Article 708
PDF
Seismic Compliance of Electrical Distribution
PDF
Generator Set Transient Performance
PDF
Modeling of a digital protective relay in a RT Digital Simulator
PDF
Facts on Grid Friendly Wind Plants
PDF
Power Plant Horror Stories
PDF
Blackout Avoidance & Undervoltage Load Shedding
PDF
Transformer Fundamentals
PDF
Arc Flash
Auburn, NY - 200 Years of History 1793-1993
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
Diesel Particulate Filters Control Systems
Understanding Arc Flash
Siemens MV GIS Switchgear
Fundamentals of transformer inrush
Building information modeling
15 years of experience stator ground fault protection
Emergency, Legally Required and Optional Standby Systems
Lighting Control Solutions for Daylit Spaces
COPS: An Arresting Look at NEC Article 708
Seismic Compliance of Electrical Distribution
Generator Set Transient Performance
Modeling of a digital protective relay in a RT Digital Simulator
Facts on Grid Friendly Wind Plants
Power Plant Horror Stories
Blackout Avoidance & Undervoltage Load Shedding
Transformer Fundamentals
Arc Flash

Recently uploaded (20)

PPTX
introduction to high performance computing
PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
Nature of X-rays, X- Ray Equipment, Fluoroscopy
PPTX
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
PDF
737-MAX_SRG.pdf student reference guides
PPTX
Artificial Intelligence
PDF
Soil Improvement Techniques Note - Rabbi
PPT
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
PDF
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
PPT
introduction to datamining and warehousing
PPTX
Safety Seminar civil to be ensured for safe working.
PPTX
UNIT - 3 Total quality Management .pptx
PDF
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
Exploratory_Data_Analysis_Fundamentals.pdf
PDF
Analyzing Impact of Pakistan Economic Corridor on Import and Export in Pakist...
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PDF
Visual Aids for Exploratory Data Analysis.pdf
PDF
Integrating Fractal Dimension and Time Series Analysis for Optimized Hyperspe...
introduction to high performance computing
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Nature of X-rays, X- Ray Equipment, Fluoroscopy
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
737-MAX_SRG.pdf student reference guides
Artificial Intelligence
Soil Improvement Techniques Note - Rabbi
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
introduction to datamining and warehousing
Safety Seminar civil to be ensured for safe working.
UNIT - 3 Total quality Management .pptx
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
R24 SURVEYING LAB MANUAL for civil enggi
Exploratory_Data_Analysis_Fundamentals.pdf
Analyzing Impact of Pakistan Economic Corridor on Import and Export in Pakist...
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
Visual Aids for Exploratory Data Analysis.pdf
Integrating Fractal Dimension and Time Series Analysis for Optimized Hyperspe...

Back to Basics

  • 1. FIRE Back - to - BasicsBack - to - Basics Fire Alarm Seminar
  • 2. FIRE AgendaAgenda What is a Fire Alarm System?n What is a Fire Alarm System? n FA Circuits (Classes & Styles) n Peripherals in Briefn Peripherals in Brief n How to Wire a Building n Voltage Drop Considerationsn Voltage Drop Considerations n Old & Obsolete FA Panels and Concepts AC Systemsz AC Systems z Series Signals z Obsolete Panels
  • 3. FIRE What is a Fire AlarmWhat is a Fire AlarmWhat is a Fire Alarm
  • 4. FIRE What is a Fire Alarm System?What is a Fire Alarm System? n The main purpose of a fire alarm system is to protect lifen The main purpose of a fire alarm system is to protect life and property by giving early warning of a fire, so that the occupants can evacuate and/or the Fire Department can respond.respond. n A system must be able to detect the initiation of a fire condition, but also notify someone such as emergencycondition, but also notify someone such as emergency personnel, the ocupants of the facility, or both.
  • 5. FIRE Fire Alarm System ComponentsFire Alarm System Components n Fire Alarm Control Panel (FACP)n Fire Alarm Control Panel (FACP) n Initiating Devices n Notification Appliances n Emergency Control n Supplementary Equipmentn Supplementary Equipment
  • 6. FIRE Logic/Control Fire Alarm Control Panel User Interface Program IDCs Power NACs AUX Relays Fire Alarm Control Panel BATT Program Distribution Hardware / Software Power Supply City Ckt Relays Ckt 120 VAC
  • 7. FIRE Fire Alarm Control Panel ComponentsFire Alarm Control Panel Components n Control Unitn Control Unit n Initiating Device Circuits (IDCs) n Notification Appliance Circuits (NACs) n Auxiliary Circuits n Power Supplyn Power Supply
  • 8. FIRE Fire Alarm Control Panel Logic/Control User Interface Program IDC SLC NACs AUX Relays Fire Alarm Control Panel PowerPrimary Program Distribution Hardware / Software City Ckt Relays BATT Power Supply Primary Secondary Ckt 120 VAC
  • 10. FIRE NFPA Fire Alarm CircuitsNFPA Fire Alarm Circuits n The National Fire Protection Association (NFPA)n The National Fire Protection Association (NFPA) classifies circuit Types and dictate their Performance
  • 11. FIRE NFPA Circuit TypesNFPA Circuit Types n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC) z A circuit to which automatic or manual initiating devices are connected where the signal received doesdevices are connected where the signal received does not identify the individual device operated z “Zone”
  • 12. FIRE Outputs Notification Appliances Inputs Initiating Devices Fire Alarm Control Panel Logic/Control Notification Appliances and Emergency Controls Initiating Devices SMK DET Bells/Horns User Interface Program IDCs Power NACs AUX Relays Fire Alarm Control Panel F I Manual Station StrobePULLPULLPULLPULL Simplex BATT Program Distribution Hardware / Software Power Supply City Ckt Relays I R EWaterflow Smoke Control WF Ckt Sprinkler Tamper Door Holders Simplex ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9 ZONE 10 ZONE 11 ZONE 12 Fire Department CRT/KBD or PC Interface Annunciators Printer120 VAC
  • 13. FIRE Initiating DevicesInitiating Devices n Manual Stationsn Manual Stations n Automatic Fire Detectors z Heat Detectors PULLPULLPULLPULL Simplex z Heat Detectors z Smoke Detectors z Flame (UV/IR) Detectorsz Flame (UV/IR) Detectors z Gas Detectors n Water Flown Water Flow n Supervisory Switches z Sprinkler Valve Tamper WF z Sprinkler Valve Tamper z Tank Water Level
  • 14. FIRE How They Work - Contact DevicesHow They Work - Contact Devices Normal State
  • 15. FIRE How They Work - Contact DevicesHow They Work - Contact Devices Normal State Alarm State
  • 16. FIRE How They Work - Current Limited DevicesHow They Work - Current Limited Devices Normal State Electronics
  • 17. FIRE How They Work - Current Limited DevicesHow They Work - Current Limited Devices Normal State Alarm State Electronics Electronics
  • 18. FIRE NFPA Fire Alarm CircuitsNFPA Fire Alarm Circuits n Two basic circuit Classes existed prior to 1993n Two basic circuit Classes existed prior to 1993 z Class B - Non-redundant z Class A - Redundantz Class A - Redundant n In 1993 NFPA introduced circuit Styles in order to clarify the difference in circuit operation made available by newthe difference in circuit operation made available by new hardware and software
  • 19. FIRE NFPA Wiring StylesNFPA Wiring Styles n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC) z Class B (Style B) PULL DOWNPULL DOWNPULL DOWNPULL DOWN BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS FIREFIREFIREFIRE FIREFIREFIREFIRE PULL DOWNPULL DOWNPULL DOWNPULL DOWN BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS FIREFIREFIREFIRE FIREFIREFIREFIRE PULL DOWNPULL DOWNPULL DOWNPULL DOWN BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS FIREFIREFIREFIRE FIREFIREFIREFIRE Simplex PULL DOWNPULL DOWNPULL DOWNPULL DOWN Simplex PULL DOWNPULL DOWNPULL DOWNPULL DOWN Simplex PULL DOWNPULL DOWNPULL DOWNPULL DOWN
  • 20. FIRE
  • 21. CLASS B (Style B) Normal Operation IDC Module + _ Typical Normally Open Device
  • 22. 2ND FLOOR NORTH HALLWAY NORMAL FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER NORMAL ALARM ACK ALARM ACK SUPV ACK TBL ACK ALARM SILENCE SYSTEM RESET ALARM ALARM SUPERVISORY TROUBLE SILENCED ON ACK ACK ACK ACK SILENCE RESET ACKNOWLEDGE
  • 23. Class B (Style B)Class B (Style B) Alarm (SHORT) Operation IDC Module + _
  • 24. 1ST FLOOR ELECTRICAL CLOSET ROOM 102 SMOKE DETECTOR ALARM 2ND FLOOR NORTH HALLWAY ALARM FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER SMOKE DETECTOR ALARMALARM ALARM ACK ALARM ACK SUPV ACK TBL ACK ALARM SILENCE SYSTEM RESET ALARM ALARM SUPERVISORY TROUBLE SILENCED ON ACK ACK ACK ACK SILENCE RESET ACKNOWLEDGE
  • 25. Class B (Style B)Class B (Style B) Trouble (OPEN) Condition IDC Module + _
  • 26. Class B (Style B) Trouble (OPEN) ConditionTrouble (OPEN) Condition IDC Module + _ This device can not operate
  • 27. 1ST FLOOR ELECTRICAL CLOSET ROOM 102 SMOKE DETECTOR ALARM 2ND FLOOR NORTH HALLWAY TROUBLE FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER SMOKE DETECTOR ALARMTROUBLE ALARM ACK ALARM ACK SUPV ACK TBL ACK ALARM SILENCE SYSTEM RESET ALARM ALARM SUPERVISORY TROUBLE SILENCED ON ACK ACK ACK ACK SILENCE RESET ACKNOWLEDGE
  • 28. FIRE NFPA Wiring StylesNFPA Wiring Styles n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC) z Class A (Style D) FIREFIREFIREFIRE FIREFIREFIREFIRE FIREFIREFIREFIRE FIREFIREFIREFIREFIREFIREFIREFIRE FIREFIREFIREFIRE Simplex PULL DOWNPULL DOWNPULL DOWNPULL DOWN BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS Simplex PULL DOWNPULL DOWNPULL DOWNPULL DOWN BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS Simplex PULL DOWNPULL DOWNPULL DOWNPULL DOWN BREAK GLASSBREAK GLASSBREAK GLASSBREAK GLASS Simplex SimplexSimplex
  • 29. FIRE
  • 30. Class A (Style D)Class A (Style D) Normal Operation IDC Module + _
  • 31. Class A (Style D)Class A (Style D) Alarm (SHORT) Operation IDC Module ++ __
  • 32. Class A (Style D)Class A (Style D) Trouble (OPEN) Condition IDC Module ++ * __ * * Contacts Close on* Contacts Close on Trouble Condition
  • 33. Class A (Style D)Class A (Style D) Trouble & Alarm Condition IDC Module ++ * __ * * Contacts Close on* Contacts Close on Trouble Condition
  • 34. FIRE NFPA Wiring StylesNFPA Wiring Styles n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC) z Class B (Style B) Smoke Detectors - 4 wireSmoke Detectors - 4 wire Relay Base
  • 35. Class B (Style B) Normal OperationNormal Operation Resetable + R _ R E L A Y Power Circuit IDC Zone _ IDC Zone ++ _ Zone Circuit Form C Aux Contacts
  • 36. Class B (Style B) Trouble ConditionTrouble Condition Resetable + R _ R E L A Y IDC Zone _ IDC Zone ++ _
  • 37. FIRE NFPA Wiring StylesNFPA Wiring Styles n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC) z Class B (Style B) Smoke Detectors - 2 wire (Current Limited)
  • 38. Class B (Style B)Class B (Style B) Normal Operation IDC ModuleIDC Module + _ Form A Aux ContactsMicro−Relay
  • 39. Class B (Style B)Class B (Style B) Alarm Condition IDC ModuleIDC Module + _
  • 40. FIRE Current Limited (2-wire) LimitationsCurrent Limited (2-wire) Limitations n Fire alarm panels are designed to work with specificn Fire alarm panels are designed to work with specific types of 2-wire Detectors n There is a limitation to the Quantity of detectorsn There is a limitation to the Quantity of detectors which can be placed on a single circuit n Only auxiliary output function can be guaranteed on a single circuit Only auxiliary output function can be guaranteed on a single circuit Smoke Detectors - 2 wire (Current Limited)
  • 41. FIRE NFPA Wiring StylesNFPA Wiring Styles n Initiating Device Circuits (IDC)n Initiating Device Circuits (IDC) z Class B (Style B) Sprinkler Combination Circuits Sprinkler Tamper WF
  • 42. FIRE This would cause a trouble signal Old School Not Allowed This would cause a trouble signal Must be a Supervisory signal + _ WFWF
  • 43. Class B (Style B) Normal ConditionNormal Condition IDC Module WF IDC Module + _
  • 44. Class B (Style B) Valve Tamper ConditionValve Tamper Condition IDC Module WF IDC Module + _
  • 45. 1ST FLOOR ELECTRICAL CLOSET ROOM 102 SMOKE DETECTOR ALARM MAIN RISER - EAST ENTRANCE FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER SMOKE DETECTOR ALARMSUPERVTAMPER ALARM ACK ALARM ACK SUPV ACK TBL ACK ALARM SILENCE SYSTEM RESET ALARM ALARM SUPERVISORY TROUBLE SILENCED ON ACK ACK ACK ACK SILENCE RESET ACKNOWLEDGE
  • 46. Class B (Style B) Waterflow ConditionWaterflow Condition IDC Module WF IDC Module + _
  • 47. 1ST FLOOR ELECTRICAL CLOSET ROOM 102 SMOKE DETECTOR ALARM MAIN RISER - EAST ENTRANCE FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER SMOKE DETECTOR ALARMALARMWATERFLOW ALARM ACK ALARM ACK SUPV ACK TBL ACK ALARM SILENCE SYSTEM RESET ALARM ALARM SUPERVISORY TROUBLE SILENCED ON ACK ACK ACK ACK SILENCE RESET ACKNOWLEDGE
  • 48. FIRE + Tamper Supervisory _ + Waterflow Alarm WF_ Waterflow Alarm _
  • 50. FIRE NFPA Circuit TypesNFPA Circuit Types n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC) z A circuit or path directly connected to a notification appliance(s)appliance(s)
  • 51. FIRE Outputs Notification Appliances Inputs Initiating Devices Fire Alarm Control Panel Logic/Control Notification Appliances and Emergency Controls Initiating Devices SMK DET Bells/Horns User Interface Program IDCs Power NACs AUX Relays Fire Alarm Control Panel PULLPULLPULLPULL Simplex Manual Station Strobe F I BATT Program Distribution Hardware / Software Power Supply City Ckt Relays WF Waterflow Smoke Control I R E Ckt Sprinkler Tamper Door Holders Simplex ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9 ZONE 10 ZONE 11 ZONE 12 Fire Department CRT/KBD or PC Interface Annunciators Printer120 VAC
  • 52. FIRE Notification Appliances n Audibles Notification Appliances n Audibles z Horns z Bells/Chimes Speakersz Speakers n Visuals Xenon Strobesz Xenon Strobes y Non-synchronized y Synchronized n Combination Devices n Firefighter’s Telephones
  • 53. FIRE How They Work - DC DevicesHow They Work - DC Devices (Horns, Bells, Strobes, etc.) -Normal State - +
  • 54. - + - - - + CCCCathode- - + ++ + + - AAAAnode + -
  • 55. FIRE How They Work - DC Devices (Horns,How They Work - DC Devices (Horns, Bells, Strobes, etc.) +-Normal State Supervisory Mode Monitor Mode Activated State Alarm Mode +- Monitor Mode -+
  • 56. FIRE How They Work - AC Devices (Speakers)How They Work - AC Devices (Speakers) -Normal State - +
  • 57. - Current - CCCCathode - - 0.000.000.000.00 24 VDC24 VDC24 VDC24 VDC + - 24 VDC24 VDC24 VDC24 VDC 0.000.000.000.00 ++ AAAAnode + EOL Value + Resistance 0.00 Value Resistance
  • 58. - - CCCCathode - 24 VDC24 VDC24 VDC24 VDC ++ AAAAnode ++ Alarm Mode =Alarm Mode =Alarm Mode =Alarm Mode = Remove DC monitoring and Output Signal (AC)
  • 60. -- 24 VDC24 VDC24 VDC24 VDC ++
  • 61. Audio SignalAudio SignalAudio SignalAudio SignalAudio SignalAudio SignalAudio SignalAudio Signal
  • 62. FIRE How They Work - AC Devices (Speakers)How They Work - AC Devices (Speakers) --Normal State +
  • 63. FIRE How They Work - AC Devices (Speakers)How They Work - AC Devices (Speakers) -Normal State Activated State AC- AC+
  • 64. FIRE NFPA Wiring StylesNFPA Wiring Styles n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC) z Class B (Style Y)
  • 65. FIRE
  • 66. Class B (Style Y) Normal OperationNormal Operation NAC Module _ ++
  • 67. 2ND FLOOR NORTH HALLWAY NORMALSIGNALS FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER NORMALSIGNALS ALARM ACK ALARM ACK SUPV ACK TBL ACK ALARM SILENCE SYSTEM RESET ALARM ALARM SUPERVISORY TROUBLE SILENCED ON ACK ACK ACK ACK SILENCE RESET ACKNOWLEDGE
  • 68. Class B (Style Y) Alarm ConditionAlarm Condition NAC Module + __
  • 69. Class B (Style Y) Trouble ConditionTrouble Condition NAC Module _ ++ This device can not operate
  • 70. 1ST FLOOR ELECTRICAL CLOSET ROOM 102 SMOKE DETECTOR ALARM 2ND FLOOR NORTH HALLWAY TROUBLESIGNALS FIRE PRIORITY 2 SYSTEM SYSTEM ALARM POWER SMOKE DETECTOR ALARMTROUBLESIGNALS ALARM ACK ALARM ACK SUPV ACK TBL ACK ALARM SILENCE SYSTEM RESET ALARM ALARM SUPERVISORY TROUBLE SILENCED ON ACK ACK ACK ACK SILENCE RESET ACKNOWLEDGE
  • 71. Class B (Style Y) Alarm ConditionAlarm Condition NAC Module + __
  • 72. FIRE NFPA Wiring StylesNFPA Wiring Styles n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC) z Class A (Style Z)
  • 73. FIRE
  • 74. Class A (Style Z) Normal OperationNormal Operation NAC Module _ ++
  • 75. Class A (Style Z) Alarm ConditionAlarm Condition NAC Module + * __ * * Contacts Close on Alarm Condition
  • 76. Class A (Style Z) Trouble ConditionTrouble Condition NAC Module _ ++
  • 77. Class A (Style Z) Trouble & Alarm ConditionTrouble & Alarm Condition NAC Module + * __ * * Contacts Close on Alarm Condition
  • 78. FIRE Phone Circuit + Phone JackPhone JackPhone JackPhone Jack 5k EOL5k EOL5k EOL5k EOL _ 5k EOL5k EOL5k EOL5k EOL 300300300300 _ 5k EOL = Normal5k EOL = Normal 300 = Phone plugged in Open = Trouble Short = TroubleShort = Trouble GF = Trouble
  • 80. FIRE NFPA Circuit TypesNFPA Circuit Types n Signaling Line Circuits (SLC)n Signaling Line Circuits (SLC) z A circuit or path between any combination of circuit interfaces, control units, or transmitters over whichinterfaces, control units, or transmitters over which multiple system input signals or output signals, or both are carried
  • 81. FIRE NFPA Wiring StylesNFPA Wiring Styles n Signaling Line Circuits (SLC)n Signaling Line Circuits (SLC) z Class B (Style 4)
  • 82. FIRE
  • 83. Addressable Systems Class B (Style 4) Normal OperationAddressable SystemsNormal Operation Control Panel Interrogation 101 102 103 104 101 What is your status? FACP MemoryFACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble
  • 84. Addressable Systems Class B (Style 4) Normal OperationAddressable SystemsNormal Operation 101 102 103 104 FACP Memory 101 Status: Normal FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble Device Response
  • 85. Addressable Systems Class B (Style 4) Normal OperationAddressable SystemsNormal Operation Control Panel Interrogation 101 102 103 104 FACP Memory 102 What is your status? FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble
  • 86. Addressable Systems Class B (Style 4) Normal OperationAddressable SystemsNormal Operation 101 102 103 104 FACP MemoryFACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble 102 Status: Alarm Device Response
  • 87. Addressable Systems Class B (Style 4) Normal OperationAddressable SystemsNormal Operation Control Panel Interrogation 101 102 103 104 FACP Memory 103 What is your status? FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble
  • 88. Addressable Systems Class B (Style 4) Normal OperationAddressable SystemsNormal Operation 101 102 103 104 FACP Memory 103 Status: Trouble FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble Device Response
  • 89. Addressable Systems Class B (Style 4) Normal OperationAddressable SystemsNormal Operation Control Panel Interrogation 101 102 103 104 FACP Memory 104 What is your status? FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble
  • 90. Addressable Systems Class B (Style 4) Normal OperationAddressable SystemsNormal Operation 101 102 103 104 FACP MemoryFACP Memory 101 Normal 102 Alarm 103 Trouble 104 Normal 104 Status: Normal Device Response
  • 91. Addressable Systems Class B (Style 4) Trouble ConditionAddressable SystemsTrouble Condition Control Panel Interrogation 101 101 What is your status? FACP Memory 102 103 104 FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble
  • 92. Addressable Systems Class B (Style 4) Trouble ConditionAddressable SystemsTrouble Condition 101 FACP Memory 102 103 104 101 Status: Normal FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble Device Response
  • 93. Addressable Systems Class B (Style 4) Trouble ConditionAddressable SystemsTrouble Condition Control Panel Interrogation 101 FACP Memory 102 103 104 102 What is your status? FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble
  • 94. Addressable Systems Class B (Style 4) Trouble ConditionAddressable SystemsTrouble Condition 101 FACP Memory 102 103 104 FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble 102 Status: Alarm Device Response
  • 95. Addressable Systems Class B (Style 4) Trouble ConditionAddressable SystemsTrouble Condition Control Panel Interrogation 101 FACP Memory 102 103 104 103 What is your status? FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble
  • 96. Addressable Systems Class B (Style 4) Trouble ConditionAddressable SystemsTrouble Condition 101 FACP Memory 102 103 104 FACP Memory 101 Normal 102 Alarm 103 No Answer 104 Trouble Device Response
  • 97. Addressable Systems Class B (Style 4) Trouble ConditionAddressable SystemsTrouble Condition Control Panel Interrogation 101 FACP Memory 102 103 104 104 What is your status? FACP Memory 101 Normal 102 Alarm 103 No Answer 104 Trouble
  • 98. Addressable Systems Class B (Style 4) Trouble ConditionAddressable SystemsTrouble Condition 101 102 FACP Memory 102 103 104 FACP Memory 101 Normal 102 Alarm 103 No Answer 104 No Answer Device Response
  • 99. FIRE NFPA Wiring StylesNFPA Wiring Styles n Signaling Line Circuits (SLC)n Signaling Line Circuits (SLC) z Class A (Style 6)
  • 100. FIRE
  • 101. Addressable Systems Class A (Style 6) Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN Control Panel Interrogation 101 102 103 104 101 What is your status? FACP MemoryFACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble
  • 102. Addressable Systems Class A (Style 6) Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN 101 102 103 104 FACP Memory 101 Status: Normal FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble Device Response
  • 103. Addressable Systems Class A (Style 6) Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN Control Panel Interrogation 101 102 103 104 FACP Memory 102 What is your status? FACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble
  • 104. Addressable Systems Class A (Style 6) Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN 101 102 103 104 FACP MemoryFACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble 102 Status: Alarm Device Response
  • 105. Addressable Systems Class A (Style 6) Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN Control Panel Interrogation 101 102 103 104 FACP MemoryFACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble 103 What is your status?
  • 106. Addressable Systems Class A (Style 6) Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN 101 102 103 104 FACP MemoryFACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble Device Response 103 Status: Trouble
  • 107. Addressable Systems Class A (Style 6) Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN Control Panel Interrogation 101 102 103 104 FACP MemoryFACP Memory 101 Normal 102 Alarm 103 Trouble 104 Trouble 104 What is your status?
  • 108. Addressable Systems Class A (Style 6) Trouble Condition - OPENAddressable SystemsTrouble Condition - OPEN 101 102 103 104 FACP MemoryFACP Memory 101 Normal 102 Alarm 103 Trouble 104 Normal Device Response 104 Status: Normal
  • 109. Addressable Systems Class A (Style 6) Trouble Condition - SHORTAddressable SystemsTrouble Condition - SHORT 101 102 103 104 FACP MemoryFACP Memory 101 No Answer 102 No Answer 103 No Answer 104 No Answer SLC FailureSLC Failure Catastrophic FailureCatastrophic Failure
  • 110. FIRE
  • 111. FIRE Style 7 (Class A) Network Signalling Line Circuit, Normal Operation
  • 112. FIRE Token Style 7 (Class A) Network Signalling Line Circuit, Normal Operation
  • 113. FIRE Token Style 7 (Class A) NetworkStyle 7 (Class A) Network Signalling Line Circuit, Operation With a Single Short or Open
  • 114. FIRE TokenToken Token Style 7 (Class A) Network Signalling Line Circuit, Operation with Multiple Shorts or Opens
  • 117. n Relay Module,n Relay Module, z Control Module, Control ZAM
  • 120. FIRE
  • 124. FIRE Addressable Devices - IAMAddressable Devices - IAM n Individual Addressable Modulen Individual Addressable Module z Addressable Station z Addressable Basez Addressable Base y Photo y Ionization y Heat z Supervised IAM y Monitors a single conventional contact devicey Monitors a single conventional contact device z IAM Relay (ID Net only) Obtains operating power from SLCn Obtains operating power from SLC
  • 126. FIRE Addressable Devices - ZAMAddressable Devices - ZAM n Zone Addressable Modulen Zone Addressable Module z Interfaces with a Zone of Conventional Devices z Monitoring Devicesz Monitoring Devices y Class B Monitor ZAM y Class A Monitor ZAM y 4-Wire Monitor ZAM z Control Devices y Unsupervised Control ZAMy Unsupervised Control ZAM y Supervised Signal ZAM n Obtains operating power from a separate sourcen Obtains operating power from a separate source
  • 127. Class B Monitor ZAM + _ + Operating Power SLC _ + _
  • 128. Class A Monitor ZAM + _ + Operating Power SLC _ + _
  • 129. 4-Wire Monitor ZAM R ++ R E L A Y Resetable Power _ + _ + Operating Power SLC __ ++ _
  • 130. Control ZAM + Normally _ + Operating Power Normally Open Normally Closed SLC _ Closed 1 Relay Normally Open 1 Relay Open Normally Closed
  • 134. Single Input Contact Module SIGA-CT1SIGA-CT1 n Four Assignable Personalities z Alarm, Supervisory, Waterflow (delayed latching retard), MonitorMonitor n 1-gang Mount
  • 135. Dual Input Contact Module SIGA-CT2SIGA-CT2 n Four Separate Assignable Personalities to Each InputPersonalities to Each Input z Alarm, Supervisory, Waterflow (delayed latching retard),(delayed latching retard), Monitor n 1-gang Mountn 1-gang Mount
  • 136. Monitor ModuleMonitor Module SIGA-MM1 n Factory Pre-loaded Monitorn Factory Pre-loaded Monitor Function z Saves installation timez Saves installation time n 1-gang Mount
  • 137. Waterflow/Tamper ModuleWaterflow/Tamper Module SIGA-WTMSIGA-WTM n Factory Pre-loaded Waterflown Factory Pre-loaded Waterflow (16 second delayed latching retard) and Supervisory Input z Saves installation time n 1-gang Mountn 1-gang Mount
  • 138. Single Circuit Control Module SIGA-CC1SIGA-CC1 n Single Riser Select n Switch Signal Riser z 2 amps @ 24 Vdc n Two Assignable Personalities z 2 amps @ 24 Vdc z 50 watts @ 25 Vaudio 35 watts @ 70Vaudio Personalities n Switch Telphone Riser z Built-in RING TONE z 35 watts @ 70Vaudio z Built-in RING TONE generator for fire phones n 2-gang Mount
  • 139. Dual Circuit Control ModuleDual Circuit Control Module SIGA-CC2 Dual Riser Selectn Dual Riser Select n Select Signal Risern Select Signal Riser z 2 amps @ 24 Vdc z 50 watts @ 25 Vaudioz 50 watts @ 25 Vaudio z 35 watts @ 70Vaudio n 2-gang Mount
  • 140. Control RelayControl Relay SIGA-CR Form “C” NO or NC Contactn Form “C” NO or NC Contact z 0.5 amps @ 220 Vac (non UL) z 0.5 amps @ 120 Vac z 2 amps (pilot duty) @ 24 Vdc z 50 watts @ 25 Vaudio z 35 watts @ 70 Vaudioz 35 watts @ 70 Vaudio n 1-gang Mount
  • 141. Universal Class A/B Module 15 Assignable Personalities15 Assignable Personalities z Two Class B or one Class A Initiating Device Circuits SIGA-UM Initiating Device Circuits z One Class A or B Indicating Appliance Circuit z One Class A or B Smoke Detector Circuit (2-wire verified or non-verified)or non-verified) z One Form “C” Dry Contact Relay
  • 143. FIRE Outputs Notification Appliances Inputs Initiating Devices Fire Alarm Control Panel Logic/Control Notification Appliances and Emergency Controls Initiating Devices SMK DET Bells/Horns User Interface Program IDCs Power NACs AUX Relays Fire Alarm Control Panel F I PULLPULLPULLPULL Simplex Manual Station Strobe BATT Program Distribution Hardware / Software Power Supply City Ckt Relays I R E WF Waterflow Smoke Control Ckt Sprinkler Tamper Door Holders Simplex ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9 ZONE 10 ZONE 11 ZONE 12 Fire Department CRT/KBD or PC Interface Annunciators Printer120 VAC
  • 144. FIRE Emergency Controls (Outputs)Emergency Controls (Outputs) n Supervisedn Supervised z City Connection z UUKL Smoke Controlz UUKL Smoke Control n Unsupervised z Door Control (Holders & Locks) z Smoke (Fan & Damper) Control z Elevator Recall z Emergency Lighting Control
  • 145. FIRE City ConnectionsCity ConnectionsCity Connections Contact DACTContact DACT
  • 150. FIRE “ABC CORPORATION ALARM”“ABC CORPORATION ALARM” Conventional Contact Monitoring DACTDACT
  • 151. FIRE City ConnectionsCity ConnectionsCity Connections Serial DACTSerial DACT
  • 156. FIRE “ABC CORPORATION SMOKE DETECTOR ALARMSMOKE DETECTOR ALARM THIRD FLOOR EAST STORAGE CLOSET” SERIAL DACT
  • 158. FIRE Outputs Notification Appliances Inputs Initiating Devices Fire Alarm Control Panel Logic/Control Notification Appliances and Emergency Controls Initiating Devices SMK DET Bells/Horns User Interface Program IDCs Power NACs AUX Relays Fire Alarm Control Panel F I PULLPULLPULLPULL Simplex Manual Station Strobe BATT Program Distribution Hardware / Software Power Supply City Ckt Relays I R E WF Waterflow Smoke Control Ckt Sprinkler Tamper Door Holders Fire Department ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9 ZONE 10 ZONE 11 ZONE 12 Simplex CRT/KBD or PC Interface Annunciators Printer120 VAC
  • 159. FIRE Supplementary Equipment - AnnunciatorsSupplementary Equipment - Annunciators n Graphic or Directory Lamp Annunciators ZONE 1 ZONE 5 ZONE 9 n Graphic or Directory Lamp Annunciators n Computer Based Graphic Systems ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9 ZONE 10 ZONE 11 ZONE 12 n Text-based CRTs Simplex n Text-based Printers
  • 160. FIRE Basic AnnunciatorsBasic Annunciators n Hardwiredn Hardwired z One Wire and Common per Point ZONE 1 ZONE 5 ZONE 9 Simplex ZONE 2 ZONE 3 ZONE 4 ZONE 6 ZONE 7 ZONE 8 ZONE 10 ZONE 11 ZONE 12 FIRE ALARM CONTROL
  • 161. FIRE Basic AnnunciatorsBasic Annunciators n Serial Annunciatorn Serial Annunciator z Twisted/Sheilded Wiring (Communications) z Powerz Power y 120 VAC y 24 VDC Simplex ZONE 1 ZONE 5 ZONE 9 FIRE ALARM CONTROL ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9 ZONE 10 ZONE 11 ZONE 12 FIRE ALARM CONTROL
  • 162. FIRE Basic AnnunciatorsBasic Annunciators n CRTs, Printers, PC Based Graphicsn CRTs, Printers, PC Based Graphics z Twisted/Sheilded Wiring (Communications) z Powerz Power y 120 VAC y 24 VDC Simplex FIRE ALARM CONTROL 120 VAC FIRE ALARM CONTROL
  • 164. FIRE Peripherals - Manual DevicesPeripherals - Manual Devices n Manual Stationsn Manual Stations z Conventional & Addressable z Single or Double Actionz Single or Double Action z Standard material - Lexan (Plastic) y Limited choice of Metal models availabley Limited choice of Metal models available n Valve Tamper z Typically Supplied by Othersz Typically Supplied by Others
  • 165. FIRE Peripherals - Automatic DevicesPeripherals - Automatic Devices n Smoke Detectorsn Smoke Detectors z Photoelectric z Ionizationz Ionization z Beam z Air Aspiration (VESDA) z Ductz Duct n Heat Fixedz Fixed z Rate-of-Rise z Combinationz Combination z Rate Compensated
  • 166. FIRE Peripherals - Automatic DevicesPeripherals - Automatic Devices n Waterflown Waterflow z Typically supplied by others n Flame Detectors
  • 167. FIRE Peripherals - Audible AppliancesPeripherals - Audible Appliances n Hornsn Horns n Bells n Chimes n Speakers z 25 VRMS z 70 VRMS
  • 168. FIRE Peripherals - Visual AppliancesPeripherals - Visual Appliances n XENONn XENON y 15 cd y 30 cd y 110 cd n Combined with Audible (AV)n Combined with Audible (AV) n Synchronized Option z Requires a “Sync Cube”z Requires a “Sync Cube”
  • 169. FIRE Miscellaneous DevicesMiscellaneous Devices n Door Holdersn Door Holders z Watch Voltage Requirements y 24 volt units require Power Suppliesy 24 volt units require Power Supplies n Relays n Firefighter Phones z Jacksz Jacks z Emergency Phones in Cabinet
  • 170. FIRE How to Wire aHow to Wire aHow to Wire a BuildingBuilding
  • 176. FIRE PROPER WIRING TERMINATIONSPROPER WIRING TERMINATIONS FOR HARDWIRED CIRCUITS Conductors must be broken at each device termination (Incoming &device termination (Incoming & Outgoing conductors must not be twisted together or left as a continuoustwisted together or left as a continuous wire) No T-Taps
  • 178. FIRE
  • 179. FIRE ShieldingShielding Most digital communication ckts require a twisted shielded pair (TSP) of wires. Shielding usually consist of a foil shield and a drain wire which is inconsist of a foil shield and a drain wire which is in continuous contact with the foil. Shielding prevents cross-talk between other circuits run next to the cable,cross-talk between other circuits run next to the cable, shields against EMI or RFI noise or interference that could be induced from the surroundings and helps tocould be induced from the surroundings and helps to prevent the shielded circuit from emitting noise that could interfere with other circuits.
  • 180. FIRE ShieldingShielding 1. When joints or connections are made, as little of the cable as possible should be stripped back so that only a small amount of the wiringwill be unshielded.small amount of the wiringwill be unshielded. The shield must be continuous throughout the ckt. In2. The shield must be continuous throughout the ckt. In other words, the drain(shield) wires must be tied together with a good mechanical bond at every cable joint orwith a good mechanical bond at every cable joint or splice.
  • 181. FIRE Shielding 1. The shield MUST be isolated from ground throughout the ckt. Usually this is done with electrical tape but it may be done with heat shrink. The shield is only tied to abe done with heat shrink. The shield is only tied to a signal ground at one point (usually at the control panel). This signal ground is sometimes earth ground and sometimes 0V or system common.sometimes 0V or system common. . Grounds at more than one point on the shield can cause ground loops. This may create more noise than having no shield at all.
  • 182. FIRE National Electrical Code (NEC)National Electrical Code (NEC) n 1993 Editionn 1993 Edition n Article 760 Fire Protective Signaling Circuits z Scope & General 760-1 to 760-7 z Nonpower-Limited 760-11 to 760-18 z Power Limited 760-21 to 760-53
  • 183. FIRE Power Limited CircuitsPower Limited Circuits n Operate between 20 VDC and 250 VDCn Operate between 20 VDC and 250 VDC z Circuits are limited to 100 Volt-Amperes (VA) n Power limiting is accomplished by use of proper power source A power limited source can be:n A power limited source can be: z A circuit breaker or fuse if: y The overcurrent device is not interchangeable with highery The overcurrent device is not interchangeable with higher rated device y The overcurrent device is located where the conductor to be protected receives its supply z An inherently limited power supply y No output power is provided if the output is shorted
  • 184. FIRE Power Limited Control PanelsPower Limited Control Panels n Circuit Marking (NEC 760-22):n Circuit Marking (NEC 760-22): z The equipment shall be durably marked where plainly visible to indicate each circuit that is a power-limited circuit.visible to indicate each circuit that is a power-limited circuit. n If the circuits are not marked “Power Limited”, the system must be considered Non-Power Limited.must be considered Non-Power Limited.
  • 185. FIRE Power Limited vs. Non-Power LimitedPower Limited vs. Non-Power Limited (Exposed Wiring) Power Limited Non-Power LimitedPower Limited n Single conductors are allowed (Table 760-51) Non-Power Limited n 2 conductors minimum (760-17(c)(2) n Minimum conductor size in cable z #26 AWG (Table 760-51) n Minimum conductor size in cable: z #18AWGz #26 AWG (Table 760-51) n FPLP Cable Installation z Plenums z #18AWG n NPLFP Cable Installation z Other spaces used forz Plenums z DUCTs z Other spaces used for environmental air z Other spaces used for environmental air n No cable substitutions are allowedenvironmental air n Cable substitutions are allowed (Table 760-53) allowed
  • 186. FIRE Fire Protective Signaling CablesFire Protective Signaling Cables Non-power limited cablesn Non-power limited cables z NEC 760 - 17(c) (4, 5, & 6) n Power limited cables z NEC 760 - 51(d, e, & f) Power Non-Power Application Limited Limited General Use FPL NPLF Riser (Vertical Runs) FPLR NPLFR Plenum or DUCT [NEC 300-22(b)] FPLP Use conduit Other spaces used to transport Environmental air [NEC 300-22(c)] FPLP NPLFP
  • 187. FIRE Wiring ConsiderationsWiring Considerations Voltage Drop & DistancesVoltage Drop & Distances
  • 188. FIRE Wire Distance LimitationsWire Distance Limitations n Initiating Device Circuits:#14 = 3.07 / 1000 Feetn Initiating Device Circuits: z 8 Zone Monitor modules - Class B (Style B) y 10,000 feet or 50 ohms, whichever comes first #14 = 3.07 / 1000 Feet 50 / 3.07 = 16.3 16.3 x 1000 = 16300y 10,000 feet or 50 ohms, whichever comes first y 2-wire smoke detector circuits: 50 ohms max. line resistance y Dry contact only circuits: 800 ohms max. line resistance 8 Zone Monitor Modules - Class A (Style D) 16.3 x 1000 = 16300 16300 / 2 = 8150 Ckt Length z 8 Zone Monitor Modules - Class A (Style D) y 10,000 feet from module and back to the module or 50 ohms, whichever comes first (5,000 feet to furthest device)
  • 189. FIRE Wire Distance LimitationsWire Distance Limitations n Monitor Zone Addressable Module (ZAM)n Monitor Zone Addressable Module (ZAM) z Class B (Style B) y 2,000 feet or 10 ohms, whichever comes firsty 2,000 feet or 10 ohms, whichever comes first z Class A (Style D) y 2,000 feet or 10 ohms, whichever comes first, from ZAM terminals and back to the ZAM terminalsterminals and back to the ZAM terminals y 2000 feet from module and back to the module or 10 ohms, whichever comes first (1,000 feet to furthest device) n Wire Guage z 18 AWG minimumz 18 AWG minimum z 12 AWG maximum
  • 190. FIRE Wire Distance LimitationsWire Distance Limitations n MAPNET & IDNetn MAPNET & IDNet z Class B (Style 4) y 10,000 feet maximum of all wire runs including:y 10,000 feet maximum of all wire runs including: y All T-taps y Parallel runs y For each continuous run:y For each continuous run: y 2,500 feet for up to 250 IDNet devices y 2,500 feet for up to 128 MAPNET devices 3,000 feet for up to 96 MAPNET devicesy 3,000 feet for up to 96 MAPNET devices y 4,000 feet for up to 64 MAPNET devices y When run exceeds 2,500 feet twisted shielded wiring is required.required.
  • 191. FIRE Wire Distance LimitationsWire Distance Limitations n MAPNETn MAPNET z Class A (Style 6) y No T-tapping is allowedy No T-tapping is allowed y For each continuous run from FACP and back: y 2,500 feet for up to 128 MAPNET devices y 1250 feet to furthest devicey 1250 feet to furthest device y 3,000 feet for up to 96 MAPNET devices y 1500 feet to furthest device 4,000 feet for up to 64 MAPNET devicesy 4,000 feet for up to 64 MAPNET devices y 2000 feet to furthest device y When run exceeds 2,500 feet twisted shielded wiring is required.required.
  • 192. FIRE Wire Distance LimitationsWire Distance Limitations n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC) z Audibles & Visuals MaximumMaximum Circuit Line Maximum distance (feet) Current Resistance (2 conductor cable) (amps) (Ω) 18AWG 16AWG 14AWG 12AWG 0.250 10.8 845 1340 2138 3400 0.500 5.4 420 670 1065 1700 0.750 3.6 280 445 710 1130 1.000 2.7 210 335 530 8501.000 2.7 210 335 530 850 1.250 2.16 165 265 425 680 1.500 1.8 140 220 350 565 1.750 1.54 120 190 300 480 2.000 1.35 105 165 265 4252.000 1.35 105 165 265 425
  • 193. FIRE Wire Distance LimitationsWire Distance Limitations n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC) z Speakers z 25 VRMSz 25 VRMS Maximum Distance (feet) 25VRMS POWER (Twisted Pair Wire)25VRMS POWER (Twisted Pair Wire) APPLIED 18AWG 16AWG 14AWG 12AWG 50W 400 680 1021 1624 40W 505 804 1279 2033 30W 673 1070 1704 2707 20W 1011 1608 2558 4067 10W 2024 3219 5120 8140
  • 194. FIRE Wire Distance LimitationsWire Distance Limitations n Notification Appliance Circuits (NAC)n Notification Appliance Circuits (NAC) z Speakers z 70 VRMSz 70 VRMS Maximum Distance (feet) 70VRMS POWER (Twisted Pair Wire) APPLIED 18AWG 16AWG 14AWG 12AWG 100W 1620 2577 4098 6500100W 1620 2577 4098 6500 80W 2020 3212 5108 8121 70W 2317 3685 5860 9318 60W 2700 4276 6800 10860 50W 3241 5154 8197 1300050W 3241 5154 8197 13000 40W 4040 6424 10216 16243 30W 5379 8553 13602 21721 20W 8065 12823 20394 32424 10W 16000 25000 40000 6480010W 16000 25000 40000 64800
  • 195. FIRE
  • 197. FIRE Series Notification Circuits (AC)Series Notification Circuits (AC) n Works like inexpensive Christmas lights…n Works like inexpensive Christmas lights… One fails, they all fail z 120 VACz 120 VAC y Horns, Bells, Chimes z 300+ Volt Audio y Speakers n All devices must be replaced when upgrading system All devices must be replaced when upgrading system
  • 198. FIRE Series Notification Circuits (AC)Series Notification Circuits (AC) (Normal Condition) 120 VACVAC NEUT Trouble Monitor Circuit
  • 199. FIRE Series Notification Circuits (AC)Series Notification Circuits (AC) (Normal Condition) 120 VACVAC NEUT Trouble Monitor Circuit
  • 203. FIRE 4246/4247 AC FACP4246/4247 AC FACP n Introduced ??????n Introduced ?????? n All Peripherals operate on 120 VAC z No Standby Batteries n ONE IDCn ONE IDC n 2- Series Wired NACs z Built in groups of 2z Built in groups of 2 n Boxes not compatible with and current panelspanels
  • 204. FIRE 4208 Hardwired FACP4208 Hardwired FACP n Introduced in early 1970sn Introduced in early 1970s n First Multi-zone FACP n Not Programmable n MOST features duplicated in 4XXX series panels z Watch for AC Series NACs n Boxes not compatible with and current panels
  • 205. FIRE 4207 Hardwired FACP4207 Hardwired FACP n Introduced in 1974n Introduced in 1974 n Transistor based replacment for the 4208 n Not Programmable n MOST features duplicated in 4XXX series panels z Watch for AC Series NACs n Boxes not compatible with and current panels
  • 206. FIRE 2001 Hardwired FACP2001 Hardwired FACP
  • 207. FIRE 2001 Hardwired FACP2001 Hardwired FACP n Introduced in late 1978n Introduced in late 1978 z Workhorse FACP for 15 yrs! n Modular-based replacement of 4207 n Sometimes packaged with 2100 & 2120 Multiplexn Sometimes packaged with 2100 & 2120 Multiplex Systems n Not Programmable n MOST features duplicated in 4XXX series panels z Watch for AC Series NACs n 2, 4, & 6 unit Boxes not compatible with 4XXX series panels