IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE)
e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 2 Ver. I (Mar. – Apr. 2016), PP 13-17
www.iosrjournals.org
DOI: 10.9790/1676-1102011317 www.iosrjournals.org 13 | Page
Automatic Load Frequency Control of Two Area Power System
Using Proportional Integral Derivative Tuning Through Internal
Model Control
Aibangbee J. O
(D Department of Electrical and Computer Engineering, BELLs University of Technology, Ota, Ogun State-
Nigeria.
Abstract: The main purpose of operating Load Frequency Control (LFC) is to keep uniformly the frequency
changes during the load changes. In this paper, Automatic Load Frequency control of two area power systems
using Proportional Integral Derivative (PID) tuning through internal model control (IMC) technique. Two main
objectives of LFC are to maintain the real frequency and the desired power output in the interconnected power
system and, to control the change in tie line power between control areas. The PID-IMC controller have the
ability to provide high adaption for changing conditions and the ability for making quick decisions. The
controller are used to improve the dynamic response as well as to reduce or eliminate the steady-state error. It
is much faster, applicable under different nonlinearities and give better stability response as compared to the
conventional integral Load Frequency controllers for a two area power system.
Keywords: Proportional Integral Derivative, Load Frequency Control, internal model control, Tie-line,
Twoarea power systemso
I. Introduction
The main purpose of operating the load frequency control is to keep uniformly the frequency changes
during the load changes. During the power system operation rotor angle, frequency and active power are the
main parameters to change [1]. The interconnection of more than one control areas through tie lines is call
power systems. Generating plants in a control area always vary their speed together for maintenance of
frequency and the relative power angles to the predefined values in both static and dynamic conditions. When
there is any sudden load change occurs in a control area of an interconnected power system there will be
frequency deviation as well as tie line power deviation. Two main objective of Load Frequency Control (LFC)
are, to maintain the real frequency and the desired power output in the interconnected power system and, to
control the change in tie line power between control areas [2]. When there is a small change in load power in a
single area power system operating at set value of frequency it creates mismatch in power both for generation
and demand. Nowadays there are more complex power systems which required operation in less structured and
uncertain environment. Similarly innovative and improved control is required for economic, secure and stable
operation. The conventional Proportional Integral (PI) controller [3,4] has the following drawback a) Inherent
nonlinearity of different power system components; b) There is continuous load changes occurrence during
daily cycle, this changes the operating point accordingly and c) very slow in operation [5]. In this paper, a
proposed advance control techniques having the ability to provide high adaption for changing conditions and the
ability for making quick decisions is the Proportional Integral Derivative (PID) controller. The PID controller is
used to improve the dynamic response as well as to reduce or eliminate the steady-state error [6]
Two Area Power Systems
A two area system consists of two single area systems, connected through a power line called tie-line.
Figure 1 shows a two area power system where each area supplies to its own area and the power flow between
the areas are allowed by the tie line. For two area power system, the individual areas are strong, the tie line
which connects the two area is weak and a single frequency is characterized throughout. A block diagram model
of two area power system with integral controller is shown in Figure 2. The block diagram model contained two
control inputs named u1 and u2. The block diagram representing a two area power system model is having two
control areas connected to each other through a line having its own dynamics (block 7) called tie line. From the
figure it is clearly seen that the control areas are made-up with three block each with an integral controller
block. The three blocks are namely governor block, turbine block, and the power system block which is actually
the load block.
Automatic Load Frequency Control Of Two Area Power System Using Proportional Integral Derivative..
DOI: 10.9790/1676-1102011317 www.iosrjournals.org 14 | Page
Figure1: Two area interconnected power system
Model of a Two Area Thermal Non-Reheat Power System
Both areas consist of four blocks each and another one block represents the tie line power. Therefore
total 9 blocks are present for the whole system [7,8].
The control input equations can be written as below:
For area 1 (at block 8)
= ( ) ( ) (1)
For area 2 (at block 9)
= ( ) ( ) (2)
Where ACE1 and ACE2 are the Area Control Errors of area-1 and area-2 respectively. KT is the integral gain
for both the areas.
Figure 2: Two area thermal (non-reheat) power system with integral controller
II. Materials And Methods
Tuning of PID controllers proposed for LFC via Internal model control (IMC) considering the
simplicity of their execution [8,9,10,11] in load frequency controller PID tuning method for two area power
system.
A. Design of Internal model control (IMC)
An internal model control (IMC) method is adapted for load frequency controller design. In Process
control IMC is a very popular controller [7]. Figure 3 show the IMC structure where the plant to be controlled is
‗P‘, and the plant model is ‗Ṗ‘.
Figure 3: IMC structure
IMC design procedure is given in equation 3 as
Ṗ (s) = PM (s) PA (s) (3)
Automatic Load Frequency Control Of Two Area Power System Using Proportional Integral Derivative..
DOI: 10.9790/1676-1102011317 www.iosrjournals.org 15 | Page
Where PM (s) invertible minimum phase in part, and PA (s) is the no minimum phase part with unity
magnitude.
Design an IMC controller
Q(s) = PM
-1
(s) (4)
Where 𝜆 = the tuning parameter,
= the desired set point response and
r = the degree of PM (s).
It is shown that the IMC controller gives very good tracking performance but not satisfying the
disturbance rejection performance some times. So a secondary controller Qd is included to optimize the
disturbance rejection performance.
The designed disturbance rejecting IMC controller is given as
= (5)
Where 𝜆d is the disturbance rejection tuning parameter, 'm‘ is the number of poles Ṕ(s).
The feedback controller K is equals to
K = (6)
Here K is considered as the PID controller.
Direct implementation of IMC controller needs higher order transfer function knowledge if the model Ṗ
is of higher order, as discussed in LFC of power system. So the IMC structure is transformed to a PID control
structure.
Figure 4: IMC equivalent conventional feedback configuration
The standard technique of tuning the PID parameters from IMC controllers is to expand the controller
block K shown in Figure 4 in to Maclaurin series. The first three terms coefficients of the Maclaurin series are
the parameters of the PID controller.
B. Load Frequency Control PID Design
The tuning of PID controller is to improve the performance of the load frequency control of power
system as represented by the single area model shown in figure 5.
Figure 5: Linear model of a single area power system
So the control law u K(s) f,
Where K(s) = (7)
Practically PID controller is implemented to reduce the noise effect. So K(s) can be written as K(s) =
where N is called the filter constant.
Automatic Load Frequency Control Of Two Area Power System Using Proportional Integral Derivative..
DOI: 10.9790/1676-1102011317 www.iosrjournals.org 16 | Page
III. Analysis And Results
The performance of IMC-PID controller are shown in figures 6 to 8. The responses shown are in form
of dynamic responses of each area frequencies and the power of tie line, for the two area power system model.
Results of IMC-PID Controller for LFC of Two Area Power System
Figures 6, 7, and 8 are showing the dynamic responses of deviation in frequency for both the areas ( f1,
f2 ) and the power deviation in tie line ( tie( ) for a power system having two control areas with
thermal non-reheat turbines. The figures show the performances of a PID controller for LFC of power system,
tuned via IMC. Figures shows that the responses are stable with very less overshoot and less settling time. So
PID - IMC controller is a powerful controller which gives better stability for LFC of a two area power system.
Figure 6: change in frequency V/S time in area-1 for 0.01 step load change in area-1
Figure 7: change in frequency V/S time in area-2 for 0.01 step load change in area-1
The figures show that the IMC-PID controller gives better response than the conventional integral
controller for LFC of power system.
Figure 8: change in tie line power V/S time for 0.01 step load change in area-1
IV. Conclusions
Model of a two area interconnected power system has been developed with different area
characteristics for optimal and conventional control strategies. The control equations have successfully been
derived in continuous time for a two area power system. The model developed has been examined for the
stability before and after the application of state feedback control.
An IMC-PID controller is designed for LFC of the proposed power system via Internal Model Control
(IMC) and its results are compared with conventional integral Load Frequency Controller for a two area power
system. So PID controller is designed on the basis of IMC controller and applied for LFC of a two area power
system and well stabilized responses are obtained.
References
[1] S. Sivanagaraju, G. Sreenivasan. Power System Operation and Control, 2008.
[2] Jawat, T. and Fadel, A, B. ―Adaptive Fuzzy Gain Scheduling for load frequency control‖ IEEE Trans. On PAS, vol,14, No1
February1999.
Automatic Load Frequency Control Of Two Area Power System Using Proportional Integral Derivative..
DOI: 10.9790/1676-1102011317 www.iosrjournals.org 17 | Page
[3] N. Cohn, ‗Some aspects of tie-line bias control on interconnected power systems,‘ Amer. Inst. Elect. Eng. Trans., Vol. 75, pp. 1415-
1436, Feb. 1957.
[4] B. Oni, H. Graham, and L. Walker, ‗nonlinear tie-line bias control of Interconnected power systems,‘ IEEE Trans. Power App.Syst.,
vol. PAS-100 no. 5 pp. 2350–2356.
[5] E. C. Tacker, T. W. Reddoch, O. T. Pan, and T. D. Linton, ‗Automatic generation Control of electric energy systems—A simulation
study,‘ IEEE Trans. Syst. Man Cybern., vol. SMC-3, no. 4, pp. 403–5, Jul. 1973.
[6] A. Khodabakhshian and M. Edrisi, ―A new robust PID load frequency controller,‖ Control Eng. Pract., vol. 16, no. 9, pp. 1069–
1080, 2008.
[7] M. Morari and E. Zafiriou, Robust Process Control. Englewood Cliffs, NJ: Prentice- Hall, 1989.
[8] Niranjan et al. ―load frequency control of power system,‖ 2013.
[9] J. Talaq and F. Al-Basri, ―Adaptive fuzzy gain scheduling for load frequency control,‖ IEEE Trans. Power Syst., vol. 14, no. 1,
pp. 145–150, Feb. 1999.
[10] M. F. Hossain, T. Takahashi, M. G. Rabbani, M. R. I. Sheikh, and M. Anower, ―Fuzzy proportional integral controller for an AGC
in a single area power system,‖ in Proc. 4th
Int. Conf. Electrical and Computer Engineering (ICECE), Dhaka, Bangladesh, pp. 120–
123, Dec. 2006.
[11] Y. H. Moon, H. S. Ryu, J. G. Lee, and S. Kim, ―Power system load frequency control using noise-tolerable PID feedback,‖ in Proc.
IEEE Int. Symp. Industrial Electronics (ISIE), vol. 3, pp. 1714–1718, Jun. 2001.
[12] A. Khodabakhshian and N. Golbon, ―Unified PID design for load frequency control,‖ in Proc. 2004 IEEE Int. Conf. Control
Applications (CCA), Taipei, Taiwan, pp. 1627–1632,Sep. 2004.

More Related Content

PDF
IRJET- Load Frequency Control of a Wind Integrated Power System using Convent...
PDF
Parallel control structure scheme for load frequency controller design using ...
PDF
Current control of grid-connected inverter using integral sliding mode contro...
PDF
Ijetr011915
PDF
IRJET- Load Frequency Control of a Renewable Source Integrated Four Area ...
PDF
Performance evaluation-of-hybrid-intelligent-controllers-in-load-frequency-co...
PDF
Differential game approach for the analysis of two area load frequency control
PDF
LOAD FREQUENCY CONTROL IN TWO AREA NETWORK INCLUDING DG
IRJET- Load Frequency Control of a Wind Integrated Power System using Convent...
Parallel control structure scheme for load frequency controller design using ...
Current control of grid-connected inverter using integral sliding mode contro...
Ijetr011915
IRJET- Load Frequency Control of a Renewable Source Integrated Four Area ...
Performance evaluation-of-hybrid-intelligent-controllers-in-load-frequency-co...
Differential game approach for the analysis of two area load frequency control
LOAD FREQUENCY CONTROL IN TWO AREA NETWORK INCLUDING DG

What's hot (20)

PDF
Load Frequency Control of Multi Area System using Integral-Fuzzy Controller
PDF
Stability analysis of photovoltaic system under grid faults
PDF
IRJET- Design and Implementation of PWM Rectifier with Power Factor Control
PDF
Fractional Order PID Controlled Interleaved Boost converter Fed Shunt Active ...
PDF
Digital Implementation of Paralleling DC_DC conv
PDF
Starting of induction motor fed with stand-alone DFIG
PDF
A1103030111
PDF
Fi34989995
PDF
NARMA-L2 Controller for Five-Area Load Frequency Control
PDF
Ijartes v2-i4-001
PPTX
V fuzzy logic implementation for induction motor control
PDF
Aa4103156160
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PDF
IRJET- Vector Control of Three Phase Induction Motor
PDF
Power System Stability Enhancement Using FLC and MPC for STATCOM
PDF
A hybrid approach for ipfc location and parameters optimization for congestio...
PDF
Cuckoo Search Optimization Algorithm based Load Frequency Control of Intercon...
PDF
Solar energy based impedance-source inverter for grid system
PDF
FUZZY LOGIC CONTROL DESIGN FOR ELECTRICAL MACHINES
PDF
Fractional PID controlled cascaded flyback switched mode power supply with en...
Load Frequency Control of Multi Area System using Integral-Fuzzy Controller
Stability analysis of photovoltaic system under grid faults
IRJET- Design and Implementation of PWM Rectifier with Power Factor Control
Fractional Order PID Controlled Interleaved Boost converter Fed Shunt Active ...
Digital Implementation of Paralleling DC_DC conv
Starting of induction motor fed with stand-alone DFIG
A1103030111
Fi34989995
NARMA-L2 Controller for Five-Area Load Frequency Control
Ijartes v2-i4-001
V fuzzy logic implementation for induction motor control
Aa4103156160
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IRJET- Vector Control of Three Phase Induction Motor
Power System Stability Enhancement Using FLC and MPC for STATCOM
A hybrid approach for ipfc location and parameters optimization for congestio...
Cuckoo Search Optimization Algorithm based Load Frequency Control of Intercon...
Solar energy based impedance-source inverter for grid system
FUZZY LOGIC CONTROL DESIGN FOR ELECTRICAL MACHINES
Fractional PID controlled cascaded flyback switched mode power supply with en...
Ad

Viewers also liked (20)

PDF
Q01061117126
PDF
L010218691
PDF
D017311724
PDF
Periodic Table Gets Crowded In Year 2011.
PDF
On The Origin of Electromagnetic Waves from Lightning Discharges
PDF
G011124753
PDF
A0730103
PDF
L0947075
PDF
Longitudinal Skeleton Dimensionality Characteristics of Nigerian Junior Male ...
PDF
Comparative Study on Selected Physical Fitness Components among the Physical ...
PDF
L012117482
PDF
H1803025360
PDF
B012460814
PDF
N0123298103
PDF
A017540106
PDF
C018211723
PDF
Vehicle Obstacles Avoidance Using Vehicle- To Infrastructure Communication
PDF
D017232729
PDF
E017363243
PDF
A017160104
Q01061117126
L010218691
D017311724
Periodic Table Gets Crowded In Year 2011.
On The Origin of Electromagnetic Waves from Lightning Discharges
G011124753
A0730103
L0947075
Longitudinal Skeleton Dimensionality Characteristics of Nigerian Junior Male ...
Comparative Study on Selected Physical Fitness Components among the Physical ...
L012117482
H1803025360
B012460814
N0123298103
A017540106
C018211723
Vehicle Obstacles Avoidance Using Vehicle- To Infrastructure Communication
D017232729
E017363243
A017160104
Ad

Similar to C1102011317 (20)

PDF
A New Control Method for the Multi-Area LFC System Based on Port-Hamiltonian ...
PDF
Study of PID Controllers to Load Frequency Control Systems with Various Turbi...
PDF
Design Fuzzy-PI Based Controller for Load Frequency Control of Thermal - Ther...
PDF
Bc35306309
PPTX
MINOR_PROJECT_GROUP_indira gandhi _16.pptx
PDF
G010525868
PDF
A new approach for Tuning of PID Load Frequency Controller of an Interconnect...
DOCX
Optimized coordinated economic dispatch and automatic generation control for ...
PDF
Automatic Load Frequency Control ppt.pdf
PPTX
Presentation1
PDF
Non-integer IMC Based PID Design for Load Frequency Control of Power System t...
PDF
V044145150
PDF
Comparative Analysis of Different Controllers in Two–Area Hydrothermal Power ...
PDF
IRJET- A New Load Frequency Control Method of Multi-Area Power System Via the...
PPTX
Use of the Genetic Algorithm-Based Fuzzy Logic.pptx
PDF
IRJET- Load Frequency Control of an Interconnected Power System using Grey Wo...
PPTX
LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...
PDF
C0333017026
PDF
J010346786
PDF
Load Frequency Control in Three Area Power System using Fuzzy Logic Controller
A New Control Method for the Multi-Area LFC System Based on Port-Hamiltonian ...
Study of PID Controllers to Load Frequency Control Systems with Various Turbi...
Design Fuzzy-PI Based Controller for Load Frequency Control of Thermal - Ther...
Bc35306309
MINOR_PROJECT_GROUP_indira gandhi _16.pptx
G010525868
A new approach for Tuning of PID Load Frequency Controller of an Interconnect...
Optimized coordinated economic dispatch and automatic generation control for ...
Automatic Load Frequency Control ppt.pdf
Presentation1
Non-integer IMC Based PID Design for Load Frequency Control of Power System t...
V044145150
Comparative Analysis of Different Controllers in Two–Area Hydrothermal Power ...
IRJET- A New Load Frequency Control Method of Multi-Area Power System Via the...
Use of the Genetic Algorithm-Based Fuzzy Logic.pptx
IRJET- Load Frequency Control of an Interconnected Power System using Grey Wo...
LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...
C0333017026
J010346786
Load Frequency Control in Three Area Power System using Fuzzy Logic Controller

More from IOSR Journals (20)

PDF
A011140104
PDF
M0111397100
PDF
L011138596
PDF
K011138084
PDF
J011137479
PDF
I011136673
PDF
G011134454
PDF
H011135565
PDF
F011134043
PDF
E011133639
PDF
D011132635
PDF
C011131925
PDF
B011130918
PDF
A011130108
PDF
I011125160
PDF
H011124050
PDF
G011123539
PDF
F011123134
PDF
E011122530
PDF
D011121524
A011140104
M0111397100
L011138596
K011138084
J011137479
I011136673
G011134454
H011135565
F011134043
E011133639
D011132635
C011131925
B011130918
A011130108
I011125160
H011124050
G011123539
F011123134
E011122530
D011121524

Recently uploaded (20)

PPTX
TechTalks-8-2019-Service-Management-ITIL-Refresh-ITIL-4-Framework-Supports-Ou...
PDF
NewMind AI Weekly Chronicles - August'25-Week II
PDF
Building Integrated photovoltaic BIPV_UPV.pdf
PDF
Enhancing emotion recognition model for a student engagement use case through...
PDF
From MVP to Full-Scale Product A Startup’s Software Journey.pdf
PDF
1 - Historical Antecedents, Social Consideration.pdf
PDF
gpt5_lecture_notes_comprehensive_20250812015547.pdf
PDF
ENT215_Completing-a-large-scale-migration-and-modernization-with-AWS.pdf
PDF
Microsoft Solutions Partner Drive Digital Transformation with D365.pdf
PDF
Transform Your ITIL® 4 & ITSM Strategy with AI in 2025.pdf
PDF
Assigned Numbers - 2025 - Bluetooth® Document
PPTX
Tartificialntelligence_presentation.pptx
PDF
Profit Center Accounting in SAP S/4HANA, S4F28 Col11
PDF
A novel scalable deep ensemble learning framework for big data classification...
PPTX
Group 1 Presentation -Planning and Decision Making .pptx
PPTX
Digital-Transformation-Roadmap-for-Companies.pptx
PDF
MIND Revenue Release Quarter 2 2025 Press Release
PDF
August Patch Tuesday
PPTX
1. Introduction to Computer Programming.pptx
PDF
Encapsulation_ Review paper, used for researhc scholars
TechTalks-8-2019-Service-Management-ITIL-Refresh-ITIL-4-Framework-Supports-Ou...
NewMind AI Weekly Chronicles - August'25-Week II
Building Integrated photovoltaic BIPV_UPV.pdf
Enhancing emotion recognition model for a student engagement use case through...
From MVP to Full-Scale Product A Startup’s Software Journey.pdf
1 - Historical Antecedents, Social Consideration.pdf
gpt5_lecture_notes_comprehensive_20250812015547.pdf
ENT215_Completing-a-large-scale-migration-and-modernization-with-AWS.pdf
Microsoft Solutions Partner Drive Digital Transformation with D365.pdf
Transform Your ITIL® 4 & ITSM Strategy with AI in 2025.pdf
Assigned Numbers - 2025 - Bluetooth® Document
Tartificialntelligence_presentation.pptx
Profit Center Accounting in SAP S/4HANA, S4F28 Col11
A novel scalable deep ensemble learning framework for big data classification...
Group 1 Presentation -Planning and Decision Making .pptx
Digital-Transformation-Roadmap-for-Companies.pptx
MIND Revenue Release Quarter 2 2025 Press Release
August Patch Tuesday
1. Introduction to Computer Programming.pptx
Encapsulation_ Review paper, used for researhc scholars

C1102011317

  • 1. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 2 Ver. I (Mar. – Apr. 2016), PP 13-17 www.iosrjournals.org DOI: 10.9790/1676-1102011317 www.iosrjournals.org 13 | Page Automatic Load Frequency Control of Two Area Power System Using Proportional Integral Derivative Tuning Through Internal Model Control Aibangbee J. O (D Department of Electrical and Computer Engineering, BELLs University of Technology, Ota, Ogun State- Nigeria. Abstract: The main purpose of operating Load Frequency Control (LFC) is to keep uniformly the frequency changes during the load changes. In this paper, Automatic Load Frequency control of two area power systems using Proportional Integral Derivative (PID) tuning through internal model control (IMC) technique. Two main objectives of LFC are to maintain the real frequency and the desired power output in the interconnected power system and, to control the change in tie line power between control areas. The PID-IMC controller have the ability to provide high adaption for changing conditions and the ability for making quick decisions. The controller are used to improve the dynamic response as well as to reduce or eliminate the steady-state error. It is much faster, applicable under different nonlinearities and give better stability response as compared to the conventional integral Load Frequency controllers for a two area power system. Keywords: Proportional Integral Derivative, Load Frequency Control, internal model control, Tie-line, Twoarea power systemso I. Introduction The main purpose of operating the load frequency control is to keep uniformly the frequency changes during the load changes. During the power system operation rotor angle, frequency and active power are the main parameters to change [1]. The interconnection of more than one control areas through tie lines is call power systems. Generating plants in a control area always vary their speed together for maintenance of frequency and the relative power angles to the predefined values in both static and dynamic conditions. When there is any sudden load change occurs in a control area of an interconnected power system there will be frequency deviation as well as tie line power deviation. Two main objective of Load Frequency Control (LFC) are, to maintain the real frequency and the desired power output in the interconnected power system and, to control the change in tie line power between control areas [2]. When there is a small change in load power in a single area power system operating at set value of frequency it creates mismatch in power both for generation and demand. Nowadays there are more complex power systems which required operation in less structured and uncertain environment. Similarly innovative and improved control is required for economic, secure and stable operation. The conventional Proportional Integral (PI) controller [3,4] has the following drawback a) Inherent nonlinearity of different power system components; b) There is continuous load changes occurrence during daily cycle, this changes the operating point accordingly and c) very slow in operation [5]. In this paper, a proposed advance control techniques having the ability to provide high adaption for changing conditions and the ability for making quick decisions is the Proportional Integral Derivative (PID) controller. The PID controller is used to improve the dynamic response as well as to reduce or eliminate the steady-state error [6] Two Area Power Systems A two area system consists of two single area systems, connected through a power line called tie-line. Figure 1 shows a two area power system where each area supplies to its own area and the power flow between the areas are allowed by the tie line. For two area power system, the individual areas are strong, the tie line which connects the two area is weak and a single frequency is characterized throughout. A block diagram model of two area power system with integral controller is shown in Figure 2. The block diagram model contained two control inputs named u1 and u2. The block diagram representing a two area power system model is having two control areas connected to each other through a line having its own dynamics (block 7) called tie line. From the figure it is clearly seen that the control areas are made-up with three block each with an integral controller block. The three blocks are namely governor block, turbine block, and the power system block which is actually the load block.
  • 2. Automatic Load Frequency Control Of Two Area Power System Using Proportional Integral Derivative.. DOI: 10.9790/1676-1102011317 www.iosrjournals.org 14 | Page Figure1: Two area interconnected power system Model of a Two Area Thermal Non-Reheat Power System Both areas consist of four blocks each and another one block represents the tie line power. Therefore total 9 blocks are present for the whole system [7,8]. The control input equations can be written as below: For area 1 (at block 8) = ( ) ( ) (1) For area 2 (at block 9) = ( ) ( ) (2) Where ACE1 and ACE2 are the Area Control Errors of area-1 and area-2 respectively. KT is the integral gain for both the areas. Figure 2: Two area thermal (non-reheat) power system with integral controller II. Materials And Methods Tuning of PID controllers proposed for LFC via Internal model control (IMC) considering the simplicity of their execution [8,9,10,11] in load frequency controller PID tuning method for two area power system. A. Design of Internal model control (IMC) An internal model control (IMC) method is adapted for load frequency controller design. In Process control IMC is a very popular controller [7]. Figure 3 show the IMC structure where the plant to be controlled is ‗P‘, and the plant model is ‗Ṗ‘. Figure 3: IMC structure IMC design procedure is given in equation 3 as Ṗ (s) = PM (s) PA (s) (3)
  • 3. Automatic Load Frequency Control Of Two Area Power System Using Proportional Integral Derivative.. DOI: 10.9790/1676-1102011317 www.iosrjournals.org 15 | Page Where PM (s) invertible minimum phase in part, and PA (s) is the no minimum phase part with unity magnitude. Design an IMC controller Q(s) = PM -1 (s) (4) Where 𝜆 = the tuning parameter, = the desired set point response and r = the degree of PM (s). It is shown that the IMC controller gives very good tracking performance but not satisfying the disturbance rejection performance some times. So a secondary controller Qd is included to optimize the disturbance rejection performance. The designed disturbance rejecting IMC controller is given as = (5) Where 𝜆d is the disturbance rejection tuning parameter, 'm‘ is the number of poles Ṕ(s). The feedback controller K is equals to K = (6) Here K is considered as the PID controller. Direct implementation of IMC controller needs higher order transfer function knowledge if the model Ṗ is of higher order, as discussed in LFC of power system. So the IMC structure is transformed to a PID control structure. Figure 4: IMC equivalent conventional feedback configuration The standard technique of tuning the PID parameters from IMC controllers is to expand the controller block K shown in Figure 4 in to Maclaurin series. The first three terms coefficients of the Maclaurin series are the parameters of the PID controller. B. Load Frequency Control PID Design The tuning of PID controller is to improve the performance of the load frequency control of power system as represented by the single area model shown in figure 5. Figure 5: Linear model of a single area power system So the control law u K(s) f, Where K(s) = (7) Practically PID controller is implemented to reduce the noise effect. So K(s) can be written as K(s) = where N is called the filter constant.
  • 4. Automatic Load Frequency Control Of Two Area Power System Using Proportional Integral Derivative.. DOI: 10.9790/1676-1102011317 www.iosrjournals.org 16 | Page III. Analysis And Results The performance of IMC-PID controller are shown in figures 6 to 8. The responses shown are in form of dynamic responses of each area frequencies and the power of tie line, for the two area power system model. Results of IMC-PID Controller for LFC of Two Area Power System Figures 6, 7, and 8 are showing the dynamic responses of deviation in frequency for both the areas ( f1, f2 ) and the power deviation in tie line ( tie( ) for a power system having two control areas with thermal non-reheat turbines. The figures show the performances of a PID controller for LFC of power system, tuned via IMC. Figures shows that the responses are stable with very less overshoot and less settling time. So PID - IMC controller is a powerful controller which gives better stability for LFC of a two area power system. Figure 6: change in frequency V/S time in area-1 for 0.01 step load change in area-1 Figure 7: change in frequency V/S time in area-2 for 0.01 step load change in area-1 The figures show that the IMC-PID controller gives better response than the conventional integral controller for LFC of power system. Figure 8: change in tie line power V/S time for 0.01 step load change in area-1 IV. Conclusions Model of a two area interconnected power system has been developed with different area characteristics for optimal and conventional control strategies. The control equations have successfully been derived in continuous time for a two area power system. The model developed has been examined for the stability before and after the application of state feedback control. An IMC-PID controller is designed for LFC of the proposed power system via Internal Model Control (IMC) and its results are compared with conventional integral Load Frequency Controller for a two area power system. So PID controller is designed on the basis of IMC controller and applied for LFC of a two area power system and well stabilized responses are obtained. References [1] S. Sivanagaraju, G. Sreenivasan. Power System Operation and Control, 2008. [2] Jawat, T. and Fadel, A, B. ―Adaptive Fuzzy Gain Scheduling for load frequency control‖ IEEE Trans. On PAS, vol,14, No1 February1999.
  • 5. Automatic Load Frequency Control Of Two Area Power System Using Proportional Integral Derivative.. DOI: 10.9790/1676-1102011317 www.iosrjournals.org 17 | Page [3] N. Cohn, ‗Some aspects of tie-line bias control on interconnected power systems,‘ Amer. Inst. Elect. Eng. Trans., Vol. 75, pp. 1415- 1436, Feb. 1957. [4] B. Oni, H. Graham, and L. Walker, ‗nonlinear tie-line bias control of Interconnected power systems,‘ IEEE Trans. Power App.Syst., vol. PAS-100 no. 5 pp. 2350–2356. [5] E. C. Tacker, T. W. Reddoch, O. T. Pan, and T. D. Linton, ‗Automatic generation Control of electric energy systems—A simulation study,‘ IEEE Trans. Syst. Man Cybern., vol. SMC-3, no. 4, pp. 403–5, Jul. 1973. [6] A. Khodabakhshian and M. Edrisi, ―A new robust PID load frequency controller,‖ Control Eng. Pract., vol. 16, no. 9, pp. 1069– 1080, 2008. [7] M. Morari and E. Zafiriou, Robust Process Control. Englewood Cliffs, NJ: Prentice- Hall, 1989. [8] Niranjan et al. ―load frequency control of power system,‖ 2013. [9] J. Talaq and F. Al-Basri, ―Adaptive fuzzy gain scheduling for load frequency control,‖ IEEE Trans. Power Syst., vol. 14, no. 1, pp. 145–150, Feb. 1999. [10] M. F. Hossain, T. Takahashi, M. G. Rabbani, M. R. I. Sheikh, and M. Anower, ―Fuzzy proportional integral controller for an AGC in a single area power system,‖ in Proc. 4th Int. Conf. Electrical and Computer Engineering (ICECE), Dhaka, Bangladesh, pp. 120– 123, Dec. 2006. [11] Y. H. Moon, H. S. Ryu, J. G. Lee, and S. Kim, ―Power system load frequency control using noise-tolerable PID feedback,‖ in Proc. IEEE Int. Symp. Industrial Electronics (ISIE), vol. 3, pp. 1714–1718, Jun. 2001. [12] A. Khodabakhshian and N. Golbon, ―Unified PID design for load frequency control,‖ in Proc. 2004 IEEE Int. Conf. Control Applications (CCA), Taipei, Taiwan, pp. 1627–1632,Sep. 2004.