CAPACITIVE VOLTAGE
TRANSFORMER
BOGHANI KAUSHAL B.
(130760109002)
CAPACITIVE VOLTAGE
TRANSFORMER
oA capacitor voltage transformer (CVT or CCVT), is a transformer used in power
systems to step down extra high voltage signals and provide a low voltage signal, for
metering or operating a protective relay.
INTRODUCTION
oCapacitor Voltage Transformers (CVT), are used for voltage metering and
protection in high voltage network systems.
oThey transform the high voltage into low voltage adequate to be processed in
measuring and protection instruments secondary equipment, such as relays and
recorders).
oA Voltage Transformer (VT) isolates the measuring instruments from the high
voltage of the monitored circuit. VTs are commonly used for metering and protection
in the electrical power industry.
oA voltage transformer comprising a capacitor divider unit and an electromagnetic
unit so designed and interconnected that the secondary voltage of the
electromagnetic unit is substantially proportional to and in phase with the primary
voltage applied to the capacitor divider unit.
WORKING
oIn its most basic form, the device consists of three parts: two capacitors across
which the transmission line signal is split, an inductive element to tune the device to
the line frequency, and a voltage transformer to isolate and further step down the
voltage for metering devices or protective relay.
oThe tuning of the divider to the line frequency makes the overall division ratio less
sensitive to changes in the burden of the connected metering or protection devices.
o The device has at least four terminals: a terminal for connection to the high voltage
signal, a ground terminal, and two secondary terminals which connect to the
instrumentation or protective relay.
oIn practice, capacitor C1 is often constructed as a stack of smaller capacitors
connected in series.
o This provides a large voltage drop across C1 and a relatively small voltage drop
across C2. As the majority of the voltage drop is on C1, this reduces the required
insulation level of the voltage transformer.
oThe voltage across the larger capacitance C2 will be V2 = V*C1/(C1+C2)
oThis makes CVTs more economical than the wound voltage transformers under high
voltage (over 100kV), as the latter one requires more winding and materials.
APPLICATION
oThe CVT is also useful in communication systems. CVTs in combination with wave
traps are used for filtering high-frequency communication signals from power
frequency. This forms a carrier communication network throughout the transmission
network.
oVoltage Measuring: They accurately transform transmission voltages down to
useable levels for revenue metering, protection and control purposes
oInsulation: They guarantee the insulation between HV network and LV circuits
ensuring safety condition to control room operators
oHF Transmissions: They can be used for Power Line Carrier (PLC) coupling
oTransient Recovery Voltage: When installed in close proximity to HV/EHV Circuit
Breakers, CVT’s own High Capacitance enhance C/B short line fault / TRV
performance
Difference between CVT and PT
CVT PT
where as CVT is capacitive voltage transformer
consisting of stack of series connected capacitor the
voltage across the capacitor is used to measure the
voltage. It also serves the purpose of power line carrier
communication.
Potential Transformer is Inductive step down transformer
used for measurement of voltage and protection.
CVT is rated for extremely high voltage levels above
230KV.
while PT's aren't designed for such large values. upto
12KV
CVT's offer the advantage that the voltage divider
capacitor, being itself relatively smaller and lighter,
configuration makes the transformer's iron core much
smaller in size, and hence more economical, versus what
it would be if a pure magnetic transformer would be used.
Core loss is too much high and so it is less economical
Also the CVT's can be tuned to the fundamental
frequency of the line, and the capacitance prevents the
inductive "fire-back" of the coils in the transformer when
a breaker trips.
PT's can't provide such advantage.
WHAT IS SATURATION IN
CURRENT
TRANSFORMER?oThe term saturation of the CT can be defined as a condition in which the CT is no
longer able to reproduce the secondary current in proportion to its primary current .
oThe basic principle on which the CT reproduces the secondary current is based on the
well known Transformer principle where current flowing through the primary winding
produces a flux in the core of the transformer which is normally proportional to the
current in the primary.
o This flux is the basic reason for the current in the Secondary winding . Now if the core
is not able to reproduce a flux in proportion to the primary current , then the secondary
current will not be in proportion to the primary current and hence the measurement of
the current become wrong .
oThe phenomena of the CT core unable to produce the flux in proportion to the primary
current is called saturation of CT or CT core.
REASON OF
SATURATION IN CT.
o With constant VA applied in the CT secondary circuit the CT goes to saturation if the
primary current is increased beyond the designed value.
oWith constant current in the primary and if the burden is increased beyond the
designed value , still we will find the same phenomena of CT saturation.
oThe amount of the DC component available in the primary fault current etc.
EFFECT OF SATURATION ON
METERING AND PROTECTIVE
CURRENT TRANSFORMER
oOnce the CT is saturated then it will not be able to reproduce the secondary current in
proportion to its primary current and hence the relays connected to this CT circuit
may malfunction indiscriminately and trips the circuit without coordination with other
relays in the network or it may completely fail to operate for a fault both the condition
to be avoided.
oThis will give wrong readings.
oDue to this huge loss to cost will take place.
REMEDIES
oIt is the duty of the protection design engineer to do a CT sizing
calculation so that , the CT will not saturate for the worst case through
fault . There are number of factors to be considered before a CT is
designed for protection purposes which included the maximum
symmetrical and asymmetrical short circuit current and the system X/R
ratio.
oThe symmetrical and asymmetrical short circuit current can be calculated
by doing a short circuit study on the system under consideration . For
small systems manual calculation of the short circuit study is possible .
However for large systems the application of software are generally
required , otherwise the calculation become more tedious
Capacitive voltage transformer (1)

More Related Content

PPTX
PPTX
Process plant equipment and their operations in petrochemical industry
PPT
Circuit breaker
PPTX
Contact Process
PDF
Internet Governance
PPTX
fire alarm system
PPTX
Multi terminal dc systems (mtdc)
PPTX
Basics of electrical control panel
Process plant equipment and their operations in petrochemical industry
Circuit breaker
Contact Process
Internet Governance
fire alarm system
Multi terminal dc systems (mtdc)
Basics of electrical control panel

What's hot (20)

PPTX
Directional relay & Differential relay.pptx
PDF
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
PPSX
Switch yard & Protection
PPTX
HVDC System
PPT
Switchyard
PPTX
Classification of transmission lines
PPT
ABCB(air blast circuit breaker)
PPTX
Ppt of current transformer
PPTX
HVDC & FACTS
PPT
Measurement of hvac (High Voltage Engineering )
PPTX
presentation on substation layout and BUS bar arrangement.
PPTX
Chapter1 breakdown in gases
PDF
chapter-2 Breakdown in Gases (part-1)
PPTX
BREAKDOWN IN GASES
PDF
Chapter 06 - Generation of High Direct Current Voltages
PPTX
INTERLINE FLOW CONTROLLER
ODP
Transformers protection, an introduction
PPTX
Generator and Transformer Protection (PART 1)
PPTX
Insulation coordination
PPTX
**Lightning Arrester Presentation**
Directional relay & Differential relay.pptx
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
Switch yard & Protection
HVDC System
Switchyard
Classification of transmission lines
ABCB(air blast circuit breaker)
Ppt of current transformer
HVDC & FACTS
Measurement of hvac (High Voltage Engineering )
presentation on substation layout and BUS bar arrangement.
Chapter1 breakdown in gases
chapter-2 Breakdown in Gases (part-1)
BREAKDOWN IN GASES
Chapter 06 - Generation of High Direct Current Voltages
INTERLINE FLOW CONTROLLER
Transformers protection, an introduction
Generator and Transformer Protection (PART 1)
Insulation coordination
**Lightning Arrester Presentation**
Ad

Similar to Capacitive voltage transformer (1) (20)

PPT
Electrical Protection systems Circuit breakers
PPTX
Factors to be considered while selecting CT
PDF
Current transformers theory
PDF
Current transformer (ct)
PPTX
Electrical measurement & measuring instruments [emmi (nee-302) -unit-2]
PPTX
Lecture (11.11.22).pptx
PPTX
Apparatus Protection Using Relays for Engineering Students
PPTX
Instrument transformer and his application.pptx
DOCX
Report On Industrial Tour At Khulshi Grid Sub-Station
PPTX
CT & PT.pptx
PPTX
Current_Transformer .......................
PDF
C0212014018
DOCX
Seminar Report on 220 KV Grid Sub Station on Bundi
PPTX
Uttar pradesh power corporation limited
PDF
Knee-Point Voltage Determination for Current Transformer Functional Identific...
PDF
A DAPTIVE S UPPLY V OLTAGE M ANAGEMENT F OR L OW P OWER L OGIC C IRCU...
PDF
grid sub-station training Report
PPT
Power System Protection lectures22_6.ppt
PDF
475393259-Training-On-Current-Transformer.pdf
PDF
Get 8402
Electrical Protection systems Circuit breakers
Factors to be considered while selecting CT
Current transformers theory
Current transformer (ct)
Electrical measurement & measuring instruments [emmi (nee-302) -unit-2]
Lecture (11.11.22).pptx
Apparatus Protection Using Relays for Engineering Students
Instrument transformer and his application.pptx
Report On Industrial Tour At Khulshi Grid Sub-Station
CT & PT.pptx
Current_Transformer .......................
C0212014018
Seminar Report on 220 KV Grid Sub Station on Bundi
Uttar pradesh power corporation limited
Knee-Point Voltage Determination for Current Transformer Functional Identific...
A DAPTIVE S UPPLY V OLTAGE M ANAGEMENT F OR L OW P OWER L OGIC C IRCU...
grid sub-station training Report
Power System Protection lectures22_6.ppt
475393259-Training-On-Current-Transformer.pdf
Get 8402
Ad

Recently uploaded (20)

PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPT
A5_DistSysCh1.ppt_INTRODUCTION TO DISTRIBUTED SYSTEMS
PDF
Integrating Fractal Dimension and Time Series Analysis for Optimized Hyperspe...
PDF
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
PDF
PPT on Performance Review to get promotions
PPTX
Safety Seminar civil to be ensured for safe working.
PDF
86236642-Electric-Loco-Shed.pdf jfkduklg
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PDF
Exploratory_Data_Analysis_Fundamentals.pdf
PPTX
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
PPT
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
PDF
Visual Aids for Exploratory Data Analysis.pdf
PDF
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
PDF
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
PDF
SMART SIGNAL TIMING FOR URBAN INTERSECTIONS USING REAL-TIME VEHICLE DETECTI...
PPT
Total quality management ppt for engineering students
PPTX
Current and future trends in Computer Vision.pptx
PPT
Occupational Health and Safety Management System
PDF
Analyzing Impact of Pakistan Economic Corridor on Import and Export in Pakist...
Automation-in-Manufacturing-Chapter-Introduction.pdf
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
A5_DistSysCh1.ppt_INTRODUCTION TO DISTRIBUTED SYSTEMS
Integrating Fractal Dimension and Time Series Analysis for Optimized Hyperspe...
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
PPT on Performance Review to get promotions
Safety Seminar civil to be ensured for safe working.
86236642-Electric-Loco-Shed.pdf jfkduklg
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
Exploratory_Data_Analysis_Fundamentals.pdf
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
Visual Aids for Exploratory Data Analysis.pdf
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
SMART SIGNAL TIMING FOR URBAN INTERSECTIONS USING REAL-TIME VEHICLE DETECTI...
Total quality management ppt for engineering students
Current and future trends in Computer Vision.pptx
Occupational Health and Safety Management System
Analyzing Impact of Pakistan Economic Corridor on Import and Export in Pakist...

Capacitive voltage transformer (1)

  • 2. CAPACITIVE VOLTAGE TRANSFORMER oA capacitor voltage transformer (CVT or CCVT), is a transformer used in power systems to step down extra high voltage signals and provide a low voltage signal, for metering or operating a protective relay.
  • 3. INTRODUCTION oCapacitor Voltage Transformers (CVT), are used for voltage metering and protection in high voltage network systems. oThey transform the high voltage into low voltage adequate to be processed in measuring and protection instruments secondary equipment, such as relays and recorders). oA Voltage Transformer (VT) isolates the measuring instruments from the high voltage of the monitored circuit. VTs are commonly used for metering and protection in the electrical power industry. oA voltage transformer comprising a capacitor divider unit and an electromagnetic unit so designed and interconnected that the secondary voltage of the electromagnetic unit is substantially proportional to and in phase with the primary voltage applied to the capacitor divider unit.
  • 4. WORKING oIn its most basic form, the device consists of three parts: two capacitors across which the transmission line signal is split, an inductive element to tune the device to the line frequency, and a voltage transformer to isolate and further step down the voltage for metering devices or protective relay. oThe tuning of the divider to the line frequency makes the overall division ratio less sensitive to changes in the burden of the connected metering or protection devices. o The device has at least four terminals: a terminal for connection to the high voltage signal, a ground terminal, and two secondary terminals which connect to the instrumentation or protective relay.
  • 5. oIn practice, capacitor C1 is often constructed as a stack of smaller capacitors connected in series. o This provides a large voltage drop across C1 and a relatively small voltage drop across C2. As the majority of the voltage drop is on C1, this reduces the required insulation level of the voltage transformer. oThe voltage across the larger capacitance C2 will be V2 = V*C1/(C1+C2) oThis makes CVTs more economical than the wound voltage transformers under high voltage (over 100kV), as the latter one requires more winding and materials.
  • 6. APPLICATION oThe CVT is also useful in communication systems. CVTs in combination with wave traps are used for filtering high-frequency communication signals from power frequency. This forms a carrier communication network throughout the transmission network. oVoltage Measuring: They accurately transform transmission voltages down to useable levels for revenue metering, protection and control purposes oInsulation: They guarantee the insulation between HV network and LV circuits ensuring safety condition to control room operators oHF Transmissions: They can be used for Power Line Carrier (PLC) coupling oTransient Recovery Voltage: When installed in close proximity to HV/EHV Circuit Breakers, CVT’s own High Capacitance enhance C/B short line fault / TRV performance
  • 7. Difference between CVT and PT CVT PT where as CVT is capacitive voltage transformer consisting of stack of series connected capacitor the voltage across the capacitor is used to measure the voltage. It also serves the purpose of power line carrier communication. Potential Transformer is Inductive step down transformer used for measurement of voltage and protection. CVT is rated for extremely high voltage levels above 230KV. while PT's aren't designed for such large values. upto 12KV CVT's offer the advantage that the voltage divider capacitor, being itself relatively smaller and lighter, configuration makes the transformer's iron core much smaller in size, and hence more economical, versus what it would be if a pure magnetic transformer would be used. Core loss is too much high and so it is less economical Also the CVT's can be tuned to the fundamental frequency of the line, and the capacitance prevents the inductive "fire-back" of the coils in the transformer when a breaker trips. PT's can't provide such advantage.
  • 8. WHAT IS SATURATION IN CURRENT TRANSFORMER?oThe term saturation of the CT can be defined as a condition in which the CT is no longer able to reproduce the secondary current in proportion to its primary current . oThe basic principle on which the CT reproduces the secondary current is based on the well known Transformer principle where current flowing through the primary winding produces a flux in the core of the transformer which is normally proportional to the current in the primary. o This flux is the basic reason for the current in the Secondary winding . Now if the core is not able to reproduce a flux in proportion to the primary current , then the secondary current will not be in proportion to the primary current and hence the measurement of the current become wrong . oThe phenomena of the CT core unable to produce the flux in proportion to the primary current is called saturation of CT or CT core.
  • 9. REASON OF SATURATION IN CT. o With constant VA applied in the CT secondary circuit the CT goes to saturation if the primary current is increased beyond the designed value. oWith constant current in the primary and if the burden is increased beyond the designed value , still we will find the same phenomena of CT saturation. oThe amount of the DC component available in the primary fault current etc.
  • 10. EFFECT OF SATURATION ON METERING AND PROTECTIVE CURRENT TRANSFORMER oOnce the CT is saturated then it will not be able to reproduce the secondary current in proportion to its primary current and hence the relays connected to this CT circuit may malfunction indiscriminately and trips the circuit without coordination with other relays in the network or it may completely fail to operate for a fault both the condition to be avoided. oThis will give wrong readings. oDue to this huge loss to cost will take place.
  • 11. REMEDIES oIt is the duty of the protection design engineer to do a CT sizing calculation so that , the CT will not saturate for the worst case through fault . There are number of factors to be considered before a CT is designed for protection purposes which included the maximum symmetrical and asymmetrical short circuit current and the system X/R ratio. oThe symmetrical and asymmetrical short circuit current can be calculated by doing a short circuit study on the system under consideration . For small systems manual calculation of the short circuit study is possible . However for large systems the application of software are generally required , otherwise the calculation become more tedious