Current Transformers
Current transformers (CT's) provide a simple, inexpensive and yet accurate means of
sensing current flow in power conductors. They are available in 3 basic configurations:
1. Ring Core CT's are available for measuring currents from 50 to 5000
amps, with windows (power conductor opening size) from 1" to 8"
diameter.
2. Split Core CT's are available for measuring currents from 100 to 5000
amps, with windows in varying sizes from 1" by 2" to 13" by 30". Split
core CT's have one end removable so that the load conductor or bus bar
does not have to be disconnected to install the CT.
3. Wound Primary CT's are designed to measure currents from 1 amp to
100 amps. Since the load current passes through primary windings in the
CT, screw terminals are provided for the load and secondary conductors.
Wound primary CT's are available in ratios from 2.5:5 to 100:5 (Models
189 and 190 are examples of wound primary CT's).
CT's used with watt transducers enable the owner to control demand as well as monitor
building and/or tenant power consumption. When CT's are used with Current
Transducers, the result is an excellent method of diagnosing the performance of fans,
pumps, chillers, etc. The Model 4CMA and 4CTV Current Transducers provide
alarms for each motor so the owner is warned immediately of any abnormal operating
condition. Low pump flows will be alarmed if the strainer is dirty or the coupling is
broken. Low fan flows will be alarmed if filters are dirty, belts are slipping, or dampers
(fire, smoke, etc.) are closed. High motor loads will alarm if bearings are dry or worn, or
belts are out of alignment.
CT's are designed to handle motor inrush currents, so no extra precaution is needed to
monitor motors.
Monitoring Multiple Loads With One Watt Transducer
There are two methods of monitoring multiple loads with one watt transducer. All loads
must be fed from the same service and the voltage must be sensed from one source.
1. The first method can be used to monitor up to 5 feeders with wide ranging
loads. The secondaries of the feeder CT's are connected to a Model 190
Summing Transformer. The output of the summing transformer is
connected to the input of a WT Series Watt Transducer. Typically the
CT ratios must be the same, but different ratios can be used with a
specially built summing transformer. Each summing transformer must be
connected to one phase only. It takes three summing transformers and
fifteen feeder CT's to monitor and totalize five three-phase loads.
When using summing transformers, add the primary CT currents to
calculate the kW and kWh outputs. For example, when summing five
1000:5 CT's use a CT ratio of 5000:5 to determine the outputs. When
using low amperage (200A) CT's with a summing transformer, be sure to
check the burden on the CT's as the summing transformer adds burden.
2. The second method is to parallel CT inputs at the transducer.
This method would require:
1. balanced loads,
2. same ratio CT's,
3. paralleling at transducer only,
4. grounding at transducer only,
5. burden capability to be reduced by the number of CT's (e.g., 3
CT's give 1/3 capability),
6. CT's to be oversized so the total secondary current does not
exceed the 5 amp rating, which reduces accuracy. Since this
method requires ideal conditions, it is generally better to use a
summing transformer.
CT Accuracy
A CT is most accurate at rated current with a low burden (load). Accuracy decreases
with increased burden (load) or low line current. In sizing CT's the conductor size and
distance is important. Improper sizing of current transformers or long secondary
conductor runs with undersized cable can result in poor accuracy.
Burden (load) Information On CT's
The external load (e.g., meters, transducers, etc.) applied to the secondary of a CT is
called the burden. The burden can be expressed in volt-amperes:
VA = I2
x Z
Z = Total CT secondary impedance
I = Secondary current
(Generally 1 or 5 amps)
Total burden is the sum of:
1. Device (transducer, meter, etc.) Burden - Furnished by the manufacturer.
2. Burden of Interconnecting Leads - can be calculated by using the above
formula. Use conductor resistance (total to the device and back) for Z (See
Power Equations for chart of impedance of wire sizes).
3. Internal Burden of CT Windings - This is so small that it can generally be
ignored.
Exact burden calculations are usually not necessary unless the CT ratio is below 200:5.
If necessary, see the section on burden calculations
The VA burden that a CT will handle varies with the ratio and physical size of the CT.
The burden capacity for each Model CT is specified on the data sheet. A small 50:5
Model 2RL will only handle 1 VA of burden capacity. A large 2000:5 Model 170RL
will handle a burden capacity of 100 VA.
As a rule of thumb, use a 1 amp input (WT-1) watt transducer for a 200 amp or less
feeder. The 5 amp (WT-5) transducer can be used for feeders less than 100 amps when
connected to wound primary CT's (Model 189).
Sizing CT's
On new construction, size the CT to handle about 80% of the circuit breaker capacity. If
the building is served by a 2000 amp breaker, use 1600 amp (2000 x 0.8) CT's.
For older buildings, the peak demand can generally be determined from the power
company or from past billings. In this case add 20 to 30% to the peak demand and size
the CT's for this load. If the peak demand was 500 kW, the peak current on a 480/3/60
system would be:
500,000 / (480 x 1.73 x 0.9 pf) = 669 amps
This assumes a 0.9 power factor. (Peak current would be higher with a lower power
factor.) Use CT's about 20% larger. 800:5 CT's would be a good selection.
For older buildings with no demand history, size the CT's the same as for new
construction. Where possible, use multi-tap CT's so that the ratio can be reduced if the
maximum load is much less than 80% of the breaker size.
CT's that are used to monitor motor loads can be sized from the nameplate full load
motor amps.
Selecting CT's
A "Selection Guide" is provided in this catalog to aid in selecting the type of CT for your
application. Non-standard ratios can be obtained by looping the conductor through the
window to add or subtract current flow. (See Example in Figure 2.)
The relationship of the ratio of primary and secondary turns is expressed in the following
formula:
Ka = (Kn ± Nsa) / Np
Ka = Actual transformation ratio
Kn = Nameplate transformation ratio
Transformation ratio = primary current / secondary current
Nsa = Number of secondary turns added or subtracted
(To Add - loop X1 lead through H1. To Subtract -
loop X1 opposite H1)
Np = Number of primary turns
•
3 Primary Loops + 2 Secondary Loops added
Example: An application requires a 20:5 CT ratio, but only a 50:5 CT is
available. Using the above formula it can be determined that by using 3 primary
loops and adding 2 secondary loops that a 20:5 actual ratio will be obtained.
Ka = (Kn ± Nsa) / Np
= (10 + 2) / 3
= 4
Actual CT Ratio = 20:5
Mounting CT's
CT's are generally located in the main breaker panel or in branch distribution panels
where space is always at a premium. Since CT's do not have to be installed 90 degrees to
the conductor run (the conductors can go through the CT at any angle) they are generally
held in place with plastic tie wraps. CT's with mounting feet are available if appearance is
important and there is enough room to accommodate this type of mounting arrangement.
Installing CT's
Window type CT's should be mounted with the H1 side of the
window towards the power source. The X1 secondary
terminal is the polarity terminal (Figure 3).The polarity marks
of a current transformer indicate that when a primary current
enters at the polarity mark (H1) of the primary, a current in
phase with the primary current and proportional to it in
magnitude will leave the polarity terminal of the secondary
(X1).
If a CT test switch is used, the switch must have a "make-before-break" contact pattern to
assure that the CT is not open-circuited during transition.
Normally CT's should not be installed on "Hot" services. The power should be
disconnected when the CT's are installed. Many times this is not possible because of
critical loads such as computers, laboratories, etc. that cannot be shut down. Split core
CT's should not be installed on "Hot" uninsulated bus bars under any conditions.
On existing cable installations where the monitoring point is not close to a cable end,
small ring core CT's can be shunt installed on #8 cable or smaller by using Hot Tap
insulation piercing connectors similar to those made by 3M. A parallel shunt through the
CT is connected to the power cable as shown in (Figure 4). Tape all bare ends.
Check your work before leaving the installation. Make sure all connections are tight and
the installation is neat.
Summary
CT's are inexpensive, accurate devices for monitoring current. If properly sized and
installed, they will give many years of trouble free service with no adjustments to make.
Call Kele for help with your specific applications.
CAUTION: Never open-circuit a CT secondary while the primary is energized.
High crest voltages may occur across the open secondary circuit. To avoid personal
injury or equipment damage, the secondary must always be short-circuited or
connected to a burden. NOTE: A buzzing transformer is an indication of an open
secondary.

More Related Content

DOC
Document org
PPT
CT design aspects - Nageswar-6
PPTX
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATION
PPTX
Effect of change in burden and power factor on CTs
PPTX
PWM Step-down Converter(NJM2309)
PDF
7SD52/53 Line Differential Protection Relay
PPT
Lecture 28 360 chapter 9_ power electronics inverters
PDF
Some Aspects on 3-Phase Bridge Inverter (180 Degree Mode)
Document org
CT design aspects - Nageswar-6
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATION
Effect of change in burden and power factor on CTs
PWM Step-down Converter(NJM2309)
7SD52/53 Line Differential Protection Relay
Lecture 28 360 chapter 9_ power electronics inverters
Some Aspects on 3-Phase Bridge Inverter (180 Degree Mode)

What's hot (20)

PPTX
Inverter
PPT
Power Electronics Chapter 7
PPT
Dead time pwm
PDF
pwm inverter
PDF
Sample calculation-for-differential-relays
PPTX
Harmonic comparisons of various PWM techniques for basic MLI
PDF
Transformer differential protection
PDF
Paper 33-FPGA Triggered Space Vector Modulated Voltage
PPSX
Electrical Basics-VBR
PPT
Inverter 2003
PPTX
Advanced techniques of PULSE WIDTH MODULATION.
PDF
Pullbox sizing
PPTX
CSI Manual
PPTX
A presentation on inverter by manoj
PPTX
Stability test of transformer
PPTX
Inverter (Industrial_C_06_mid)
PPTX
Single phase full bridge inverter
PDF
Space Vector Modulation with DC-Link Voltage Balancing Control for Three-Leve...
PDF
3 phase current source inverter
Inverter
Power Electronics Chapter 7
Dead time pwm
pwm inverter
Sample calculation-for-differential-relays
Harmonic comparisons of various PWM techniques for basic MLI
Transformer differential protection
Paper 33-FPGA Triggered Space Vector Modulated Voltage
Electrical Basics-VBR
Inverter 2003
Advanced techniques of PULSE WIDTH MODULATION.
Pullbox sizing
CSI Manual
A presentation on inverter by manoj
Stability test of transformer
Inverter (Industrial_C_06_mid)
Single phase full bridge inverter
Space Vector Modulation with DC-Link Voltage Balancing Control for Three-Leve...
3 phase current source inverter
Ad

Similar to Current transformers theory (20)

PPTX
Instrument transformer and his application.pptx
PPTX
Current_Transformer .......................
PPTX
CT & PT.pptx
PPTX
Electrical measurement & measuring instruments [emmi (nee-302) -unit-2]
PPTX
Factors to be considered while selecting CT
PPTX
CT and VT.pptx
PPTX
Ratio, Burden, and Admittance Testing
PPTX
current transformers.pptx
PDF
Introduction to Current Transformer (Substation)
PDF
Current transformer (ct)
PPT
Instrument transformer CT & PT
PPTX
Basic concept of Circuit breaker, Current transformer and potential transform...
PPTX
Ratio, Burden, Admittance Testing
PPTX
Current transformer AS ISTRUMINTATION EQUIPMENTS
PPTX
Chapter_4_Instrument_transformers_ff9a45ab_0efd_4f66_9085_8925fec18377.pptx
PPTX
CT Testing: Theory and Practice
PPTX
CT Testing: Theory and Practice
PPTX
Ppt of current transformer
PPTX
Current Transformer.pptx
PDF
TESCO Tuesday: Ratio, Burden and Admittance
Instrument transformer and his application.pptx
Current_Transformer .......................
CT & PT.pptx
Electrical measurement & measuring instruments [emmi (nee-302) -unit-2]
Factors to be considered while selecting CT
CT and VT.pptx
Ratio, Burden, and Admittance Testing
current transformers.pptx
Introduction to Current Transformer (Substation)
Current transformer (ct)
Instrument transformer CT & PT
Basic concept of Circuit breaker, Current transformer and potential transform...
Ratio, Burden, Admittance Testing
Current transformer AS ISTRUMINTATION EQUIPMENTS
Chapter_4_Instrument_transformers_ff9a45ab_0efd_4f66_9085_8925fec18377.pptx
CT Testing: Theory and Practice
CT Testing: Theory and Practice
Ppt of current transformer
Current Transformer.pptx
TESCO Tuesday: Ratio, Burden and Admittance
Ad

Recently uploaded (20)

PDF
Prof. Dr. KAYIHURA A. SILAS MUNYANEZA, PhD..pdf
PPTX
wireless networks, mobile computing.pptx
PPTX
CyberSecurity Mobile and Wireless Devices
PPTX
ai_satellite_crop_management_20250815030350.pptx
PDF
Implantable Drug Delivery System_NDDS_BPHARMACY__SEM VII_PCI .pdf
PDF
20250617 - IR - Global Guide for HR - 51 pages.pdf
PPTX
tack Data Structure with Array and Linked List Implementation, Push and Pop O...
PDF
Abrasive, erosive and cavitation wear.pdf
PPTX
Measurement Uncertainty and Measurement System analysis
PDF
First part_B-Image Processing - 1 of 2).pdf
PPTX
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
PPTX
Module 8- Technological and Communication Skills.pptx
PPTX
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
PDF
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
PPTX
Amdahl’s law is explained in the above power point presentations
PPTX
Chemical Technological Processes, Feasibility Study and Chemical Process Indu...
PPTX
Principal presentation for NAAC (1).pptx
PDF
August -2025_Top10 Read_Articles_ijait.pdf
PDF
Computer organization and architecuture Digital Notes....pdf
PPTX
"Array and Linked List in Data Structures with Types, Operations, Implementat...
Prof. Dr. KAYIHURA A. SILAS MUNYANEZA, PhD..pdf
wireless networks, mobile computing.pptx
CyberSecurity Mobile and Wireless Devices
ai_satellite_crop_management_20250815030350.pptx
Implantable Drug Delivery System_NDDS_BPHARMACY__SEM VII_PCI .pdf
20250617 - IR - Global Guide for HR - 51 pages.pdf
tack Data Structure with Array and Linked List Implementation, Push and Pop O...
Abrasive, erosive and cavitation wear.pdf
Measurement Uncertainty and Measurement System analysis
First part_B-Image Processing - 1 of 2).pdf
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
Module 8- Technological and Communication Skills.pptx
AUTOMOTIVE ENGINE MANAGEMENT (MECHATRONICS).pptx
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
Amdahl’s law is explained in the above power point presentations
Chemical Technological Processes, Feasibility Study and Chemical Process Indu...
Principal presentation for NAAC (1).pptx
August -2025_Top10 Read_Articles_ijait.pdf
Computer organization and architecuture Digital Notes....pdf
"Array and Linked List in Data Structures with Types, Operations, Implementat...

Current transformers theory

  • 1. Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide a simple, inexpensive and yet accurate means of sensing current flow in power conductors. They are available in 3 basic configurations: 1. Ring Core CT's are available for measuring currents from 50 to 5000 amps, with windows (power conductor opening size) from 1" to 8" diameter. 2. Split Core CT's are available for measuring currents from 100 to 5000 amps, with windows in varying sizes from 1" by 2" to 13" by 30". Split core CT's have one end removable so that the load conductor or bus bar does not have to be disconnected to install the CT. 3. Wound Primary CT's are designed to measure currents from 1 amp to 100 amps. Since the load current passes through primary windings in the CT, screw terminals are provided for the load and secondary conductors. Wound primary CT's are available in ratios from 2.5:5 to 100:5 (Models 189 and 190 are examples of wound primary CT's). CT's used with watt transducers enable the owner to control demand as well as monitor building and/or tenant power consumption. When CT's are used with Current Transducers, the result is an excellent method of diagnosing the performance of fans, pumps, chillers, etc. The Model 4CMA and 4CTV Current Transducers provide alarms for each motor so the owner is warned immediately of any abnormal operating condition. Low pump flows will be alarmed if the strainer is dirty or the coupling is broken. Low fan flows will be alarmed if filters are dirty, belts are slipping, or dampers (fire, smoke, etc.) are closed. High motor loads will alarm if bearings are dry or worn, or belts are out of alignment. CT's are designed to handle motor inrush currents, so no extra precaution is needed to monitor motors.
  • 2. Monitoring Multiple Loads With One Watt Transducer There are two methods of monitoring multiple loads with one watt transducer. All loads must be fed from the same service and the voltage must be sensed from one source. 1. The first method can be used to monitor up to 5 feeders with wide ranging loads. The secondaries of the feeder CT's are connected to a Model 190 Summing Transformer. The output of the summing transformer is connected to the input of a WT Series Watt Transducer. Typically the CT ratios must be the same, but different ratios can be used with a specially built summing transformer. Each summing transformer must be connected to one phase only. It takes three summing transformers and fifteen feeder CT's to monitor and totalize five three-phase loads. When using summing transformers, add the primary CT currents to calculate the kW and kWh outputs. For example, when summing five 1000:5 CT's use a CT ratio of 5000:5 to determine the outputs. When using low amperage (200A) CT's with a summing transformer, be sure to check the burden on the CT's as the summing transformer adds burden. 2. The second method is to parallel CT inputs at the transducer. This method would require: 1. balanced loads, 2. same ratio CT's, 3. paralleling at transducer only, 4. grounding at transducer only, 5. burden capability to be reduced by the number of CT's (e.g., 3 CT's give 1/3 capability), 6. CT's to be oversized so the total secondary current does not exceed the 5 amp rating, which reduces accuracy. Since this method requires ideal conditions, it is generally better to use a summing transformer. CT Accuracy A CT is most accurate at rated current with a low burden (load). Accuracy decreases with increased burden (load) or low line current. In sizing CT's the conductor size and distance is important. Improper sizing of current transformers or long secondary conductor runs with undersized cable can result in poor accuracy. Burden (load) Information On CT's
  • 3. The external load (e.g., meters, transducers, etc.) applied to the secondary of a CT is called the burden. The burden can be expressed in volt-amperes: VA = I2 x Z Z = Total CT secondary impedance I = Secondary current (Generally 1 or 5 amps) Total burden is the sum of: 1. Device (transducer, meter, etc.) Burden - Furnished by the manufacturer. 2. Burden of Interconnecting Leads - can be calculated by using the above formula. Use conductor resistance (total to the device and back) for Z (See Power Equations for chart of impedance of wire sizes). 3. Internal Burden of CT Windings - This is so small that it can generally be ignored. Exact burden calculations are usually not necessary unless the CT ratio is below 200:5. If necessary, see the section on burden calculations The VA burden that a CT will handle varies with the ratio and physical size of the CT. The burden capacity for each Model CT is specified on the data sheet. A small 50:5 Model 2RL will only handle 1 VA of burden capacity. A large 2000:5 Model 170RL will handle a burden capacity of 100 VA. As a rule of thumb, use a 1 amp input (WT-1) watt transducer for a 200 amp or less feeder. The 5 amp (WT-5) transducer can be used for feeders less than 100 amps when connected to wound primary CT's (Model 189). Sizing CT's On new construction, size the CT to handle about 80% of the circuit breaker capacity. If the building is served by a 2000 amp breaker, use 1600 amp (2000 x 0.8) CT's. For older buildings, the peak demand can generally be determined from the power company or from past billings. In this case add 20 to 30% to the peak demand and size the CT's for this load. If the peak demand was 500 kW, the peak current on a 480/3/60 system would be: 500,000 / (480 x 1.73 x 0.9 pf) = 669 amps This assumes a 0.9 power factor. (Peak current would be higher with a lower power factor.) Use CT's about 20% larger. 800:5 CT's would be a good selection.
  • 4. For older buildings with no demand history, size the CT's the same as for new construction. Where possible, use multi-tap CT's so that the ratio can be reduced if the maximum load is much less than 80% of the breaker size. CT's that are used to monitor motor loads can be sized from the nameplate full load motor amps. Selecting CT's A "Selection Guide" is provided in this catalog to aid in selecting the type of CT for your application. Non-standard ratios can be obtained by looping the conductor through the window to add or subtract current flow. (See Example in Figure 2.) The relationship of the ratio of primary and secondary turns is expressed in the following formula: Ka = (Kn ± Nsa) / Np Ka = Actual transformation ratio Kn = Nameplate transformation ratio Transformation ratio = primary current / secondary current Nsa = Number of secondary turns added or subtracted (To Add - loop X1 lead through H1. To Subtract - loop X1 opposite H1) Np = Number of primary turns • 3 Primary Loops + 2 Secondary Loops added Example: An application requires a 20:5 CT ratio, but only a 50:5 CT is available. Using the above formula it can be determined that by using 3 primary loops and adding 2 secondary loops that a 20:5 actual ratio will be obtained. Ka = (Kn ± Nsa) / Np = (10 + 2) / 3 = 4
  • 5. Actual CT Ratio = 20:5 Mounting CT's CT's are generally located in the main breaker panel or in branch distribution panels where space is always at a premium. Since CT's do not have to be installed 90 degrees to the conductor run (the conductors can go through the CT at any angle) they are generally held in place with plastic tie wraps. CT's with mounting feet are available if appearance is important and there is enough room to accommodate this type of mounting arrangement. Installing CT's Window type CT's should be mounted with the H1 side of the window towards the power source. The X1 secondary terminal is the polarity terminal (Figure 3).The polarity marks of a current transformer indicate that when a primary current enters at the polarity mark (H1) of the primary, a current in phase with the primary current and proportional to it in magnitude will leave the polarity terminal of the secondary (X1). If a CT test switch is used, the switch must have a "make-before-break" contact pattern to assure that the CT is not open-circuited during transition. Normally CT's should not be installed on "Hot" services. The power should be disconnected when the CT's are installed. Many times this is not possible because of critical loads such as computers, laboratories, etc. that cannot be shut down. Split core CT's should not be installed on "Hot" uninsulated bus bars under any conditions. On existing cable installations where the monitoring point is not close to a cable end, small ring core CT's can be shunt installed on #8 cable or smaller by using Hot Tap insulation piercing connectors similar to those made by 3M. A parallel shunt through the CT is connected to the power cable as shown in (Figure 4). Tape all bare ends. Check your work before leaving the installation. Make sure all connections are tight and the installation is neat.
  • 6. Summary CT's are inexpensive, accurate devices for monitoring current. If properly sized and installed, they will give many years of trouble free service with no adjustments to make. Call Kele for help with your specific applications. CAUTION: Never open-circuit a CT secondary while the primary is energized. High crest voltages may occur across the open secondary circuit. To avoid personal injury or equipment damage, the secondary must always be short-circuited or connected to a burden. NOTE: A buzzing transformer is an indication of an open secondary.