Current transformers (CTs) are tested for correct ratio and functionality at rated burdens. Ratio testing involves measuring the primary and secondary currents to calculate the ratio. Burden testing applies varying levels of burden to the secondary loop to ensure the CT maintains accuracy within 0.3% up to 0.5 ohms of burden, as specified by ANSI standards. Admittance testing uses an audio frequency signal to measure the "health" of the secondary loop. CTs can become magnetized over time and may need to be demagnetized by slowly increasing and decreasing the secondary resistance to saturate and remove residual magnetism.